Closed-Loop Ground-Coupled Heat Pump Systems
|
|
|
- Scott Harris
- 9 years ago
- Views:
Transcription
1 The following article was published in ASHRAE Journal, September Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. Closed-Loop Ground-Coupled Heat Pump Systems By Michel A. Bernier, Ph.D, Member ASHRAE Closed-loop ground-coupled heat pump systems offer several advantages over conventional HVAC systems. For instance, they collect renewable ground heat or recuperate building heat rejection that accumulated in the ground during the cooling season. Furthermore, because of their relatively high coefficient of performance (COP) in both heating and cooling they are, as noted by the U.S. Department of Energy and the U.S. Environmental Protection Agency, among the most energy-efficient and environment-friendly heating and cooling systems. Finally, they emit less greenhouse gas than conventional HVAC systems given the power generation mix found in most jurisdictions.
2 ... some design engineers are still reluctant to specify these systems [because they] do not fully understand the relatively complex phenomena occurring in the borehole and in the ground at peak conditions and during long periods of time. The type of system under consideration is presented in Figure 1. This closed-loop system represents one of the most popular configurations. A heat transfer fluid is pumped through a series of vertical boreholes, where heat is collected (rejected) with a corresponding fluid temperature increase (decrease). Borehole depth is project dependent, but is usually in the 50 m 150 m (165ft 495 ft) range. As shown in the cross section, boreholes are usually filled with a grout to facilitate heat transfer from the fluid to the ground and to protect groundwater aquifers as required by some state regulations. Fluid then returns to the building, where heat pumps either collect (reject) heat in the fluid loop, thereby decreasing (increasing) the fluid temperature. At any given time, some heat pumps may operate in heating mode while others might be in cooling mode. Thus, it is possible to transfer energy from one section of the building to the other via the fluid loop. Finally, in some situations it is advantageous to design so-called hybrid systems where a supplementary heat rejecter or extractor is added to reduce the length of the ground heat exchanger. Despite the environmental advantages, some design engineers are still reluctant to specify these systems. Two main reasons exist for this. First, the capital and maintenance costs of these systems often are perceived to be higher than conventional systems. In reality, cost data on installed systems 1,2,3 do not totally support this assertion. Furthermore, some cost containment options, such as hybrid systems, can reduce the length (and cost) of the ground heat exchanger. The second reason, which is the main focus of this article, is that some designers do not fully understand the relatively complex phenomena occurring in the borehole and in the ground at peak conditions and during long periods of time. Performance Data on Heat Pumps Before discussing the design of the ground heat exchanger, it is important to review performance data on heat pumps. The coefficient of performance (COP) and capacity of heat pumps depend on several parameters such as fluid flow rate and temperatures on the source and load sides. The COP is defined as the ratio of useful energy (either in cooling or heating) to the power input to the unit (used to run the compressor and the fan). Note that the cooling COP is used here instead of the usual EER values (cooling COP = EER/3.41) to make a direct comparison between cooling and heating COP. Also, note that pumping power usually is not included in the COP values provided by manufacturers. Figure 2 presents values of COP in heating and cooling for 10 commercially available 10.5 kw (3 ton) water-to-air extended range heat pumps. As shown in Figure 2, heat pumps are not created equal and significant differences exist among manufacturers. Also, some heat pumps operate over a wider temperature range than others. It is also important to note the strong dependency of the COP on the inlet fluid temperature. In cooling, the inlet fluid temperature should be as low as possible to reduce heat pump energy consumption. While in heating mode the inlet fluid temperature should be as high as possible. In other words, the temperature lift across the heat pump, i.e., the difference between the source and load temperatures (i.e., T in,hp T Load in Figure 1) should be minimized. One way to minimize the lift is to increase the length of the ground heat exchanger so that T in,hp tends towards the undisturbed ground temperature, T g. However, oversized ground heat exchangers are not economically feasible. So, the design engineer must find the right compromise between the length of the ground heat exchanger that will give an acceptable T in,hp to reduce heat pump energy consumption as much as possible. In some cases, this may imply the use of a hybrid system to reduce peak ground loads and the length of the ground heat exchanger. Ground Heat Exchanger Length Determining the required length of a vertical geothermal heat exchanger is not a trivial task and should not be undertaken lightly. Back of the envelope calculations usually lead to either conservative, uneconomical systems or to undersized ground About the Author Michel A. Bernier, Ph.D., is a professor in the département de génie mécanique at École Polytechnique de Montréal in Montréal. S e p t e m b e r A S H R A E J o u r n a l 1 3
3 heat exchangers with potential operational problems linked to out-of-range inlet temperatures to the heat pumps. Software to determine the length is a must and, in some cases, simulation tools are required to ascertain the impact of advanced systems such as hybrid designs. Ground heat exchangers usually are designed for the worst conditions by considering that the ground heat exchanger needs to handle three consecutive thermal pulses of various magnitude and duration. 4 The magnitude corresponds to the yearly average ground load (q y ), the highest monthly ground load (q m ), and the peak hourly load (q h ). The corresponding durations are usually 20 years, one month, and six hours. The required borehole length to exchange heat at these conditions is given by: q y R 20y + q m R 1m + q h R 6h L = T w (T g + T p ) where L is the total borehole length required. The values of R 20y, R 1m, and R 6h represent effective ground thermal resistances for 20 years, one month, and six hours thermal pulses. The borehole wall temperature is represented by T w (Figure 1). Borehole thermal interference between adjacent boreholes is accounted for by introducing a temperature penalty, T p. This article does not address borehole thermal interference. For a more detailed discussion on this subject, the reader is referred to the book by Kavanaugh and Rafferty. 5 The effective ground thermal resistances depend mainly on ground thermal conductivity and, to a lesser extent, on borehole diameter and ground thermal diffusivity. Table 1 presents some typical values for three different ground thermal conductivities. 5 As shown, the effective ground thermal resistances decrease with an increase in the ground thermal conductivity (k ground ). The variations of R 20y, R 1m and R 6h are almost proportional to the variation of 1/ k ground. For example, when k ground varies from 1.2 to 3.1 W/m K, a reduction of 1/ k ground of 60% from to 0.323, the values of R 20, R 1m and R 6h are also reduced by about 60%. Thus, in this particular example, an increase in ground thermal conductivity from 1.2 to 3.1 W/m K would translate, according to Equation 1, into a 60% reduction in the required length of the heat exchanger. This significant impact of ground thermal conductivity is somewhat mitigated by the borehole thermal resistance and borehole interference. Nonetheless, this shows the importance of knowing as precisely as possible the ground thermal conductivity. This is why many engineers perform a ground thermal conductivity test prior to their design. The cost of such a test varies from one region to the other (from $2,500 to $7,500 excluding the borehole itself). It usually pays for itself by avoiding oversized (or undersized) loops. For more details on the impact of thermal conductivity error on the length of the ground heat exchanger, the readers are referred to the article by Bernier 6 and the Outside the Loop newsletter. 7 The temperature difference in the borehole, i.e., between the mean fluid temperature, T m (= (T in,hp +T out,hp )/2) and T w, is given by: 1 Optional Supplementary Heat Rejector (Hybrid System) T g T out, HP Other Heat Pumps T in,hp To Other Boreholes Grout Borehole Pipe A A A A Water-to-Air Heat Pump Figure 1: Closed-loop ground-coupled heat pump system. COP F 60 F 80 F 100 F 120 F 20 F 40 F 60 F 80 F Cooling 0 C 10 C 20 C 30 C 40 C 50 C Inlet Fluid Temp. COP T W Heating 10 C 0 C 10 C 20 C 30 C Inlet Fluid Temp. Figure 2: COP values in heating and cooling for 10 commercially available 10.5 kw (3 ton) water-to-air extended range heat pumps for standard entering air conditions and a nominal water flow rate of 0.57 L/s (9 gpm). (T m T w ) = q h R b L The value of R b is the effective borehole thermal resistance. It depends on borehole diameter, pipe diameter, separating distance between pipes, grout thermal conductivity, pipe thermal conductivity, and fluid flow rate. Table 2 presents some typical values of R b for two commonly used configurations and two grout thermal conductivities. These values of R b were obtained by assuming turbulent flow. At peak load, laminar flow is undesirable in a borehole as it increases borehole thermal resistance. However, when the load on the loop is small, laminar flow can be acceptable. In this situation R b will be high but q h will be low, resulting in acceptable temperature differences in the borehole (Equation 2). Configuration B is usually assumed to prevail when pipes are freely inserted in a borehole. In configuration C, mechanical spacers are required (usually every 3 m [10 ft] or so) to spread the pipes so that they are nearer to the ground. It is advantageous to have the smallest effective borehole thermal resistance in order to have the smallest temperature difference in the borehole. As shown in Table 2, this can be accomplished by increasing grout thermal conductivity and/or pipe spacing. In some regions, high thermal conductivity grouts have become the norm. As for mechanical spacers, some installers do not like to use them because tube insertion can become difficult. T load A S H R A E J o u r n a l a s h r a e. o r g S e p t e m b e r
4 Hourly Building Loads, kw ,000 4,000 6,000 8,000 Hour of the Year Figure 3: Hourly building loads for the example building. 4e + 5 2e + 5 Combining Equations 1 and 2, one gives Equation 3, the design length equation: q h R b + q y R 10y + q m R 1m + q h R 6h L = T m (T g + T p ) 3 Although different in appearance, this equation is basically the same as the one contained in the 2003 ASHRAE Handbook HVAC Systems and Equipment. 4 The design length should 0 2e + 5 4e + 5 Hourly Building Loads, Btu/h Annual CO 2 Emissions, kg CO Québec Vermont Canada Avg. Natural Gas Power Plant Emissions, kg CO 2 per MWh of Electricity Produced Figure 4: Annual CO 2 emissions as a function of CO 2 emitted per MWh of electricity produced for the example building. Lines a and b correspond to Cases 1 and 2, respectively ( Table 3). Lines c and d are for a system with a gas boiler (η = 80%) and a chiller with a COP of 4 and 5, respectively. be calculated with the worst conditions in cooling and in heating. The maximum of these two lengths is the required borehole length. A number of commercially available software products have implemented Equation 3 or an equivalent form. However, Equation 3 has its limits, especially when hybrid systems are used. USA Avg. Georgia Alberta Coal Power Plant North Dakota a c d b Advertisement formerly in this space. S e p t e m b e r A S H R A E J o u r n a l 1 5
5 In these cases, multiyear hourly simulation tools are required to model the complex interaction between the ground heat exchanger, the heat pumps and the supplementary fluid heater or cooler and determine the optimum length. Moreover, the simulation lead to a more precise evaluation of heat pump energy consumption. Example In this section, the required length of a ground heat exchanger is determined for a given building and four design options. A life-cycle cost analysis of each option and an estimate of their CO 2 emissions are also provided. The building used is this example is part of the TESS library of TRNSYS. 8 It has an area of 1486 m 2 (16,000 ft 2 ), and it is assumed to be located in Atlanta. As shown in Equation 3, the correct determination of the ground heat exchanger length depends on precise evaluations of ground loads, which depend on the building loads and heat pump COP. Peak hourly and monthly ground loads, q h and q m, and the yearly average power rejection/collection in the ground, q a, need to be evaluated. Particular attention should be given to peak loads as, in most cases, more than 70% of the ground heat exchanger length will be required to handle the peak load. In this article, building loads are evaluated hourly using the TRNSYS simulation package. 9 Alternatively, designers who do not have access to simulation programs may evaluate peak cooling/heating loads using available load calculation software and calculate monthly and yearly loads using tabulated values of equivalent full load hours of operation (see table 9, page in the 2003 ASHRAE Handbook). The hourly cooling and heating loads for the example building are shown in Figure 3. The peak building cooling load is 111 kw (31.6 tons). The building is assumed to be equipped with fifteen 10.5 kw (3 ton) extended range heat pumps. The total annual building heating and cooling loads are MJ ( Btu) and MJ ( Btu), respectively. Boreholes have a 150 mm (6 in.) diameter and include two 1 in. (25 mm) HDPE SDR-9 pipes (which can withstand a hydrostatic pressure of 140 m [450 ft] of water). The borehole-to-borehole distance is set to 8 m (26 ft). A wet shale ground composition is assumed (see Table 1 for corresponding resistance values) and the undisturbed ground temperature is 15 C (59 F). The ground heat exchanger is sized according to Equation 3. Considering that the cooling loads are much greater than the heating loads, the ground heat exchanger length is determined based on the cooling loads. It is assumed that the maximum acceptable inlet fluid temperature to the heat pump is 38 C (100 F). Finally, TRNSYS simulations are used to evaluate heat pump energy consumption every hour over 20 years of operation. Table 4 presents Ground Type k ground R 20y R 1m R 6h Ground Thermal m K/W m K/W m K/W Conductivity ( F ft h/btu) ( F ft h/btu) ( F ft h/btu) W/m K (Btu/h ft F) Clay Wet Shale Limestone (0.69) (0.62) (0.50) (0.25) (1.1) (0.40) (0.32) (0.18) (1.8) (0.24) (0.20) (0.12) Table 1: Typical effective ground thermal resistances. (Calculated for a bore diameter of 150 mm [6 in.].) Borehole Diameter 150 mm (6 in.) 150 mm (6 in.) Pipe Nominal Diameter Table 2: Typical equivalent borehole thermal resistances for two pipe spacing and two grout thermal conductivities. 1 6 A S H R A E J o u r n a l a s h r a e. o r g S e p t e m b e r B 1 in. (25 mm) DR-9 1 in. (25 mm) DR-9 Center-to-Center Pipe Distance 8.3 cm (3.3 in.) 11.7 cm (4.6 in.) R b, Equivalent Borehole Thermal Resistance, m K/W ( F ft h/btu) Regular Grout Thermal Conductivity W/m K (0.40 Btu/h ft F) (0.34) (0.25) Thermally Enhanced Grout Thermal Conductivity W/m K (1.2 Btu/h ft F) (0.17) (0.15) results obtained for four design options. The length determination results will be examined first followed by an analysis of energy consumption, life-cycle costs and CO 2 emissions. Length Case 1 uses low-efficiency heat pumps (bottom performance curve in Figure 2) and a B configuration borehole with a low thermal conductivity grout. The resulting total borehole length is 3165 m (10,400 ft) with 25 boreholes (5 5 configuration) each with a depth of m (416 ft). It is assumed that the proper pipe thickness has been selected to resist the hydrostatic pressure resulting from the use of such a relatively deep borehole. The annual thermal imbalance, q y, is relatively high at 21.4 kw ( Btu/h), which leads to a relatively high borehole thermal interference with a resulting temperature penalty of 7.9 K (14.2 F). The temperature difference between the mean fluid temperature in the borehole and the borehole wall, T m T w, is also high at 9.3 K (16.7 F) due mainly to the use of a low thermal conductivity grout. Case 2 is similar to Case 1 except that high-efficiency heat pumps are used (top curve on Figure 2). The use of high-efficiency heat pumps diminishes the peak ground load, from kw ( Btu/h) to kw ( Btu/h), and the annual thermal imbalance, from 21.4 kw ( Btu/h) C
6 Case 1 Case 2 Case 3 Case 4 Length Determination Type of Heat Pump (Low or High Efficiency) Low High High High Borehole Thermal Resistance 0.20 m K/W 0.20 m K/W 0.09 m K/W 0.09 m K/W Hybrid System No No No Yes 1 Peak Ground Load (q h ) kw kw kw kw Annual Thermal Imbalance (q y ) 21.4 kw 19.9 kw 19.9 kw 15.1 kw Borefield Configuration Borehole Thermal Interference (T p ) 7.9 C 7.7 C 8.8 C 5.7 C Temperature Difference In Borehole (T m T w ) Table 3: Results for the example building for four design options. 9.3 K 9.3 K 5.4 K 5.9 K Total Ground Heat Exchanger Length 3165 m 2980 m 2280 m 1500 m Annual Energy Consumption Average Annual Cooling COP Average Annual Heating COP Heat Pumps kwh kwh kwh kwh Fluid Cooler 420 kwh Cost Analysis Boreholes 2 $103,812 $97,777 $82,190 $54,120 Heat Pumps 3 $36,000 $49,500 $49,500 $49,500 Fluid Cooler 4 $10,500 Total First Costs $139,812 $147,277 $131,690 $114,120 First Year Energy Cost 5 $3,820 $2,755 $2,780 $3,005 Present Value of 20 Years of Operation 6 $50,904 $36,728 $37,068 $40,075 Present Value of Total Costs $190,716 $184,005 $168,758 $154, ton fluid cooler 2. $32.80/m ($10/ft) for Cases 1 and 2 and $36.60/m ($11/ft) for Cases 3 and 4 3. $2,400 and $3,300 for low- and high-efficiency heat pumps, respectively 4. $350/ton 5. Energy costs of $0.08/kWh are assumed 6. Assuming an electricity escalation rate of 3% and a discount rate of 7% to 19.9 kw ( Btu/h). Both of these factors contribute in reducing the required length down to 2980 m (9,770 ft). The borehole thermal resistance has been lowered in Case 3 by using a high thermal conductivity grout and spreading the pipes against the borehole wall. This reduces (T m T w ) significantly, and consequently the required length, which is reduced to 2280 m (7,480 ft), a 23% drop when compared to Case 2. In Case 4, the ground heat exchanger length has been reduced to 1500 m (4,920 ft). With a shorter length, the ground heat exchanger only can transfer the required amount of heat at peak conditions by raising the mean fluid temperature. However, the resulting inlet temperature to the heat pumps at peak loads is higher than the upper temperature limits of the heat pumps. To alleviate this problem, a 105 kw (30 ton) closed-circuit fluid cooler is used in the fluid loop (positioned as indicated in Figure 1). It operates to maintain the inlet fluid temperature to the heat pumps at 38 C (100 C) at peak conditions. The tower fan and pump require 3.38 kw (4.5 hp). As shown in Table 4, the use of the fluid cooler reduces both the peak ground load (down to kw [ Btu/h]) and the annual thermal imbalance (down to 15.1 kw [ Btu/h]). Annual Energy Consumption As expected, the average annual COP for the low efficiency heat pumps (Case 1) are lower than the other three cases, while the COP for Cases 2 and 3 are very similar. With the hybrid system, the ground temperatures, and consequently the inlet fluid temperature to the heat pumps, are higher than for Cases 2 and 3 on average. Consequently, the cooling COP for Case 4 differs from the ones observed for Cases 2 and 3 even though the same high-efficiency heat pumps are used. In terms of annual energy consumption, the low efficiency heat pumps (Case 1) consume about 30% more energy than the S e p t e m b e r A S H R A E J o u r n a l 1 7
7 other three cases. Cases 2 and 3 have similar energy consumption while the hybrid system consumes about 10% more energy than Cases 2 and 3. The fluid cooler of the hybrid system operates an average of 125 hours per year with an average annual energy consumption of 420 kwh. Cost Analysis A life-cycle cost analysis is presented in Table 3. National average borehole costs are assumed to prevail. These costs are equal to $32.80/m ($10/ft) for the low thermal conductivity grout (Cases 1 and 2) and $36.60/m ($11/ft) for the high thermal conductivity grout (Cases 3 and 4). These numbers were obtained by adjusting for inflation the data obtained by Cane et al. in who reported average borehole costs of $29/m ($8.84/ft) for nine installations and on an analysis reported in a newsletter 10 on grout costs. Heat pump costs, $2,400 and $3,300 for low- and highefficiency heat pumps, are based on prices provided by a leading heat pump manufacturer. The fluid cooler cost is assumed to be $10,500 based on a unit cost of $99.50 per kw ($350 per ton) reported by Yavuzturk and Spitler. 11 The cost of electricity is assumed to be $0.08/kWh. Finally, the present value of 20 years of operation is based on a fuel escalation rate of 3%, in line with the predicted 2.7% average annual inflation rate 12 and a discount rate of 7%. Results show that Case 4 has the lowest life-cycle cost followed by Case 3. The main difference between these two cases has to do with borehole costs, which differ by $28,070. This difference is greater than the capital cost Region of the fluid cooler estimated at $10,500. Case 2 has the lowest energy consumption followed closely by Case 3. The present value of 20 years of operation of low-efficiency heat pumps (Case 1) is much higher than the three other cases that use high-efficiency heat pumps. As with any cost analysis, its accuracy depends on the assumptions used. For example, if borehole costs are lower and electricity costs are higher than the ones assumed here, then the hybrid system might not be the lowest cost system. CO 2 Emissions The total amount of CO 2 emitted by a cooling/heating apparatus is often evaluated as the sum of the direct (equivalent CO 2 emissions linked to refrigerant leakage) and indirect (equivalent CO 2 emissions due to the energy consumption of the apparatus) effects. 13 In what follows, only the indirect effect is considered as in most cases it is the most important. The CO 2 emissions of the closed-loop ground-coupled heat pump system considered previously will be compared with a system that uses a gas boiler to provide heat and a conventional chiller for cooling. Thus, in the former case, only electricity is used for heating and cooling while in the latter case electricity is used for cooling and natural gas for heating. In the case of natural gas, the amount of CO 2 emitted is taken as 1891 g of CO 2 per m 3 ( lb of CO 2 per ft 3 ) of natural gas or g CO 2 per MJ ( lb of CO 2 per kwh). For electricity, as indicated in Table 4, the amount of CO 2 emitted per MWh of electricity varies significantly from one region to the other depending on the fuel mix used in power plants for that region. Regions that rely on hydroelectricity, such as in the province of Québec (Canada), have low CO 2 emissions. Coal-based production regions, such as in North Dakota, present high CO 2 emissions. Figure 4 presents the amount of CO 2 emitted by these two systems for the example building used earlier. The x-axis is the amount of CO 2 emitted per CO 2 Emissions, kg/mwh (lb/mwh) MWh of electricity produced. Canada Values given in Table 4 are represented as vertical lines on the graph. The y-axis is the total amount of CO 2 emitted to heat and cool the example building. USA In the case of the geothermal system, Cases 1 and 2 are considered (represented by Lines a and b on Figure 4). For the gas boiler-chiller system, a gas boiler efficiency of 80% is assumed, and two chiller s COP (4 and 5) are considered (they are represented by Lines c and d in Figure 4). As mentioned earlier, the example building is located in Atlanta. In that region, the lowest CO 2 emissions are obtained with high efficiency heat pumps with 21,100 kg (46,500) of annual CO 2 emissions. The system with the gas boiler and low efficiency chiller has the highest CO 2 emissions at 30,000 kg (66,140 lb) per year. Figure 4 also presents a number of interesting results particularly when lines intersect each other. For example, Lines a and d intersect at 360 kg (800 lb) of CO 2 emissions per MWh of electricity produced. Thus, if the example building was located in a region with CO 2 emissions higher than this value, then the low-efficiency heat pumps will emit more CO 2 than the gas boiler and high-efficiency chiller system. A similar behaviour occurs when Lines a and c intersect at 730 kg (1610 lb) of CO 2 per MWh of electricity produced. In that case the low-efficiency heat pumps emit more CO 2 than the gas boiler and the low-efficiency chiller system. The last observation regarding Figure 4 has to do with Line b, which is always lower than the other three. This indicates that the operation of high-efficiency heat pumps leads to the Québec 9 (19.8) Alberta 910 (2,002) National Average 422 (928) Vermont 26 (56.9) North Dakota 1085 (2,393) Georgia 642 (1,414) National Average 631 (1,388) Power Plants By Fuel Type Natural Gas 503 (1,107) Coal 960 (2,112) Table 4: Representative CO 2 emissions from electricity production in some North American regions. Sources: egrid/pdfs/state.pdf and A S H R A E J o u r n a l a s h r a e. o r g S e p t e m b e r
8 least amount of annual CO 2 emissions even in regions that rely on coal for electricity production. Thus, high-efficiency heat pumps offer a clear environmental advantage in this example. Conclusions This article reviewed the process involved in calculating the required length of a closed-loop vertical ground heat exchanger linked to geothermal heat pumps. As shown in Equation 3, the determination of the required length relies on an accurate determination of a number of parameters. First, ground loads should be determined as precisely as possible including the annual thermal imbalance in the ground. Second, ground conditions should be known. Without knowledge of ground thermal conductivity and ground temperature, a proper evaluation of ground heat transfer cannot be made. Third, the effective borehole thermal resistance should be determined (Table 2). In the second part of this article a design example in a cooling-dominated climate (Atlanta) is given, and four design options are considered (see results in Table 3). A number of conclusions can be drawn from this example. First, the use of high-efficiency heat pumps decreases peak ground loads and the annual thermal imbalance both of which contribute in reducing the length of the ground heat exchanger. Second, using a high thermal conductivity grout reduces the ground heat exchanger length significantly (a drop of 23% in this particular case). Finally, the use of a hybrid system with a supplementary closed-circuit fluid cooler is examined. Its use reduces the required length and the corresponding cost of the ground heat exchanger to the point where this option has the lowest life-cycle cost. In terms of CO 2 emissions, it is shown that, for the example building, the use of high-efficiency heat pumps leads to the lowest CO 2 emissions not only in Atlanta, where the example building is located, but even in jurisdictions that rely on coal for electricity production. References 1. Cane, et al Operating Experiences with Commercial Ground-Source Heat Pump Systems, Atlanta: ASHRAE. 2. Cane, D., Garnet, J.M Update on maintenance and service costs of commercial building ground-source heat pump systems. ASHRAE Transactions 106(1): Martin, M,A., Madgett, M.G., Hughes, P.J Comparing maintenance costs of geothermal heat pump systems with other HVAC systems: preventive maintenance actions and total maintenance costs. ASHRAE Transactions 106(1): ASHRAE Handbook Applications, Chap Kavanaugh, S.P., Rafferty, K Ground-Source Heat Pumps Design of Geothermal System for Commercial and Institutional Buildings. Atlanta: ASHRAE. 6. Bernier, M Uncertainty in the design length calculation for vertical ground heat exchangers. ASHRAE Transactions. 108(1): Impact of conductivity error on design results. Outside the Loop: A Newsletter for Geothermal Heat Pump Designers and Installers. 2(3). oit.edu/otl/otl02-03.pdf. 8. TESS TESS Libraries Version 2.02, Reference Manuals (13 Volumes). Thermal Energy Systems Specialists. tess-inc.com. 9. SEL TRNSYS 16 A Transient System Simulation Program Documentation Set (9 Volumes). Version Solar Energy Laboratory, University of Wisconsin-Madison. Madison, Wis. me.wisc.edu/trnsys Grout thermal conductivity bigger is not always better. Outside the Loop: A Newsletter for Geothermal Heat Pump Designers and Installers. 3(2). otl03-02.pdf. 11. Yavuzturk, C., Spitler, J.D Comparative study of operating and control strategies for hybrid ground-source heat pump systems using a short time step simulation model. ASHRAE Transactions 106(2): EIA Annual Energy Outlook 2006 with Projection to eia.doe.gov/oiaf/aeo/economic.html. 13. Sand, J.R., Fischer, S.K., Baxter V.D Comparison of TEWI for fluorocarbon alternative refrigerants and technologies in residential heat pumps and air-conditioners. ASHRAE Transactions 105(1): Advertisement formerly in this space. S e p t e m b e r A S H R A E J o u r n a l 1 9
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems ASHRAE TRP-1384 Scott P. Hackel Under the supervision of Professors Greg Nellis and Sanford Klein and the University of Wisconsin
Basic Design Considerations for Geothermal Heat Pump Systems
Basic Design Considerations for Geothermal Heat Pump Systems 2005 Tri-Service Infrastructure Systems Conference and Exhibition Gary Phetteplace US Army Engineer Research and Development Center Cold Regions
OPTIMIZATION OF HYBRID GEOTHERMAL HEAT PUMP SYSTEMS
1 OPTIMIZATION OF HYBRID GEOTHERMAL HEAT PUMP SYSTEMS Scott Hackel, Graduate Research Assistant; Gregory Nellis, Professor; Sanford Klein, Professor; all from the University of Wisconsin Solar Energy Lab,
Optimization of a Hybrid Ground Source Heat Pump using the Response Surface Method
Optimization of a Hybrid Ground Source Heat Pump using the Response Surface Method Honghee Park 1, Wonuk Kim 1, Joo Seoung Lee 1 and Yongchan Kim 2* 1 Graduate School of Division of Mechanical Engineering,
A FEASIBILITY STUDY OF A MULTI-SOURCE HYBRID DISTRICT GEOTHERMAL HEAT PUMP SYSTEM
A FEASIBILITY STUDY OF A MULTI-SOURCE HYBRID DISTRICT GEOTHERMAL HEAT PUMP SYSTEM Andrew Chiasson, Geo-Heat Center, Klamath Falls, OR INTRODUCTION Accurate calculation of transient subsurface heat transfer
FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE
FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE February 2006 FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO,
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Renewable Heat Pumps. A guide for the technically minded
Renewable Heat Pumps A guide for the technically minded How do heat pumps work? A heat pump is an environmental energy technology that extracts heat from low temperature sources (air, water, ground), upgrades
Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E.
Ground Source Heat Pumps The Fundamentals Southington, Connecticut 860 628 4622 John F. Sima III P.E. Winter/Spring 2010 Ground Source Heat Pumps The Fundamentals TOPICS: Heat Pump Terminology Basic Physics
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
Geothermal Heat Pump Systems
Geothermal Heat Pump Systems GeoExchange Technology Curtis J. Klaassen, P.E. Iowa Energy Center Energy Resource Station Geothermal Heat Pump Technology Introduction What is Geothermal Energy? Geothermal
ADVANTAGES OF USING THE HYBRID GEOTHERMAL OPTION
ADVANTAGES OF USING THE HYBRID GEOTHERMAL OPTION J. B. Singh, PE* Gustav Foster, Jr. PE** *J and P Engineers, P.A. 14 Kory Drive Kendall Park, NJ 08824 USA phone: 732-940-7994 fax: 732-940-5528 **Conectiv
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
Geothermal Heat Pump Systems: From Basics to Hybrids
Geothermal Heat Pump Systems: From Basics to Hybrids January 17, 2013 Scott Hackel Energy Center of Wisconsin www.ecw.org/hybrid Today s discussion The basics of geothermal The hybrid approach, our recent
Hybrid Geothermal Heat Pumps for Beachfront Hotel
The following article was published in ASHRAE Journal, September 2006. Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center
GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center Heat pumps are used where geothermal water or ground temperatures are only slightly above normal, generally 50 to 90 o F. Conventional
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL
ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL Jevgeni Fadejev, Jarek Kurnitski Faculty of Civil Engineering, Tallinn University of Technology, Tallinn, Estonia [email protected];
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
DESIGN OF CLOSED-LOOP GEOTHERMAL HEAT EXCHANGERS IN THE U.S.
Chapter 2.4 DESIGN OF CLOSED-LOOP GEOTHERMAL HEAT EXCHANGERS IN THE U.S. Edited by John W. Lund Geo-Heat Center E-mail: [email protected] INTRODUCTION and some western European countries. The size of individual
Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa
OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a
Geothermal Heat Pumps in Agricultural Applications
Geothermal Heat Pumps in Agricultural Applications Oregon Geothermal Working Group Meeting May 17, 2006 Alternative Farming Center, Johnson County, Tennessee Andrew Chiasson Geo-Heat Center Oregon Institute
Evaporative Cooling System for Aquacultural Production 1
Fact Sheet EES-100 March 1993 Evaporative Cooling System for Aquacultural Production 1 C. D. Baird, R. A. Bucklin, C. A. Watson and F. A. Chapman 2 INTRODUCTION Florida aquaculture sales totaled $54 million
Hybrid geothermal systems: less is more
Hybrid geothermal systems: less is more Lessons learned, impacts and tools IGSHPA Conference 2014 Scott Hackel Energy Center of Wisconsin www.ecw.org/hybrid Today s discussion The basics of the hybrid
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
Designing coaxial ground heat exchangers with a thermally enhanced outer pipe
Raymond et al. Geothermal Energy (2015) 3:7 DOI 10.1186/s40517-015-0027-3 RESEARCH ARTICLE Open Access Designing coaxial ground heat exchangers with a thermally enhanced outer pipe Jasmin Raymond 1*, Serge
Saving Heating Costs In Warehouses
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 12, December 2005). This article may not
Ground Source Heat Pumps versus High Efficiency Natural Gas Furnaces in Alberta
Ground Source Heat Pumps versus High Efficiency Natural Gas Furnaces in Alberta Jerry Shaw Ph D, P Ag February 2, 2003 Ground Source Heat Pumps (GSHPs) have been used for heating and cooling buildings
Case Study. Southwestern Manitoba town simplifies ice-making while reducing costs. Miami, Manitoba Hockey Arena and Community Hall
Case Study Earth Energy Systems Volume 1, Issue 4 April 2000 Southwestern Manitoba town simplifies ice-making while reducing costs Miami, Manitoba Hockey Arena and Community Hall Phased approach spreads
GSHP Design Recommendations- Residential & Light Commercial
GSHP Design Recommendations- Residential & Light Commercial These residential closed- loop ground source heat pump (a.k.a geothermal or groundcoupled heat pumps) design guidelines were developed in conjunction
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?
GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? Richard C. Niess 1 Gilbert & Associates / Apogee Interactive, Inc., Gloucester Point, Virginia 23062 Phone & Fax (804) 642 0400 ABSTRACT
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact
Three-years operation experience of a ground source heat pump system in Northern Greece
Energy and Buildings 39 (2007) 328 334 www.elsevier.com/locate/enbuild Three-years operation experience of a ground source heat pump system in Northern Greece A. Michopoulos, D. Bozis, P. Kikidis, K. Papakostas,
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
Low GWP Replacements for R404A in Commercial Refrigeration Applications
Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, [email protected] Abstract
Comparison of Natural Gas, Electricity, & GeoExchange Systems in a Saskatchewan Building Study Performed in Cooperation with Canadian GeoExchange
Comparison of Natural Gas, Electricity, & GeoExchange Systems in a Saskatchewan Building Study Performed in Cooperation with Canadian GeoExchange Coalition, Saskatchewan Industry and Resources, Office
Daikin Altherma hybrid heat pump. The natural combination
Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient
Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements
Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements Stuart Self 1, Marc Rosen 1, and Bale Reddy 1 1 University of Ontario Institute of Technology, Oshawa, Ontario Abstract
Hybrid Ground-Source Heat Pump Installations:
PREPARED BY Energy Center of Wisconsin with the assistance of The University of Wisconsin Solar Energy Laboratory Hybrid Ground-Source Heat Pump Installations: Experiences, Improvements and Tools June
GEOTHERMAL HEATING AND COOLING INTRODUCTION
GEOTHERMAL HEATING AND COOLING INTRODUCTION Geothermal Heating and Cooling Systems provide space conditioning -- heating, cooling, and humidity control. They may also provide water heating -- either to
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Contents. 1 Introduction systems and applications 3 1.1 Types of system 3 1.2 Applications 4 1.3 Potential benefits 4. 2 General design 6
Contents 1 Introduction systems and applications 3 1.1 Types of system 3 1.2 Applications 4 1.3 Potential benefits 4 2 General design 6 3 Ground heat exchanger 7 3.1 Types of ground heat exchanger 7 3.2
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard
Wet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device
Project No TREN/FP7EN/218952 ALONE small scale solar cooling device Collaborative Project Small or Medium-scale Focused Research Project DELIVERABLE D5.2 Start date of the project: October 2008, Duration:
THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS Michaël Kummert 1, William Dempster 1, and Ken McLean
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Application Guide AG 31-008. Geothermal Heat Pump. Design Manual. 2002 McQuay International
Application Guide AG 31-008 Geothermal Heat Pump Design Manual 2002 McQuay International Table of Contents Introduction...3 Why are Geothermal Heat Pumps So Effective?...3 Other Benefits...5 Loop Design
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses
Lisa Meline, P.E. Meline Engineering Corp. [email protected] Office: 916.366.3458 Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses Session C: Institutional Applications
HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers
HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
Rules of Thumb Energy Efficiency in Buildings
Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split
A heat pump system with a latent heat storage utilizing seawater installed in an aquarium
Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics
The natural ombination
The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,
The function of a power station is to deliver
CHAPTER CHAPTER 3 Variable Load on Power Stations 3.1 Structure of Electric Power System 3.2 Variable Load on Power Station 3.3 Load Curves 3.4 Important Terms and Factors 3.5 Units Generated per Annum
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT
Thermal Coupling Of Cooling and Heating Systems
This article was published in ASHRAE Journal, February 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
This presentation is posted for public use. ACEEE does not endorse any product or service.
This presentation is posted for public use. ACEEE does not endorse any product or service. ACEEE accepts no responsibility for any facts or claims this presentation may contain. SOLAR Solar Water Heating
The next generation of geothermal systems for school buildings
The following article was published in ASHRAE Journal, August 2007. Copyright 2007 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
A Feasibility of Geothermal Cooling in Middle East
A Feasibility of Geothermal Cooling in Middle East ASAD SALEM & HAFIZ ELSIR MIRGHANI HASHIM Department of Mechanical Engineering Rochester Institute of Technology Rochester Institute of Technology, Dubai
How a Ground Source Heat Pump Works for a School or College
How a Ground Source Heat Pump Works for a School or College Vertical System Image courtesy of Climate Master 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy
Commercial Earth Energy Systems:
Commercial Earth Energy Systems: A buyer s Guide Natural Resources Canada Ressources naturelles Canada Commercial Earth Energy Systems Buyer s Guide B Preface This publication is distributed for informational
Tim Facius Baltimore Aircoil
Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of
Calculating System Flow Requirements
Calculating System Flow Requirements To select a pump, we need to know the flow rate (the amount of fluid to be pumped) and the system resistance or head. In the U.S., flow rates are given in gallons per
EnergyPro Building Energy Analysis. Assisted Living Building
EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings Version 2006.1 AUSTRALIAN BUILDING CODES BOARD JANUARY 2006 TABLE OF CONTENTS Foreword 1. Scope 2. Purpose and context
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland
Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland Jaroslaw
Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
Climate Action Plan and Ground Source Heat Pump GHG
Climate Action Plan and Ground Source Heat Pump GHG Emission Study Preliminary Results October, 17 th Aspen, CO Jeff Lyng, Renewable Energy Program Manager The Mission of the Governor s Energy Office is
HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE
HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE Satish Joshi Managing Director CONTENTS 1. INTRODUCTION, APPLICATIONS 2. TECHNOLOGY, PROJECTS DONE, COST COMPARISION 3. HEAT PUMPS IN THE RENEWABLES DIRECTIVE,
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting