Louvre Screening & Ventilation. Architectural Solutions - Louvre
|
|
|
- Millicent Golden
- 10 years ago
- Views:
Transcription
1 Louvre Screening & Ventilation Architectural Solutions - Louvre
2 Introduction Front cover image One London Wall, London. Colt provided an elliptical plant room louvre screen for this prestigious commercial office development designed by Foster & Partners.The Main Contractor was Sir Robert McAlpine. C-Plex,West Bromwich. Trapezoidal 2UL louvre panels. INTRODUCTION Louvre systems are popular with designers for many applications in industrial and commercial buildings. Their purpose can be to control light entry, to provide ventilation whilst maintaining rain defence, to provide screening, or a combination of these. They can also be provided simply for aesthetic impact. This brochure describes Colt s range of screening, ventilation and rain defence louvre systems, as well as acoustic louvres. FEATURES & BENEFITS Aesthetically pleasing. Colt louvre systems have a distinctive sharp louvre profile. Reduced energy costs. Colt louvre systems are highly aerodynamically efficient. This reduced air resistance allows the plant and the aperture to be smaller thereby saving running costs. Enhanced performance. Colt louvre systems are both aerodynamically efficient and have a remarkably high resistance to weather. Proven performance. All Colt louvre systems have been tested to EN 13030:2001. Easy to install. Colt louvre systems can be either be delivered to site preassembled or as a kit of parts. A wide range. Colt louvre systems are available in various shapes, configurations, materials, finishes and coatings to meet the requirements of almost any project. Louvres can be extruded or rollformed; polyester powder painted, precoated or anodised, perforated, or stucco embossed. Besides aluminium and stainless steel profiles, there are all manner of glass, textile, wood, terracotta clay and translucent acrylic louvres available depending upon aesthetic and energetic requirements. There are also a wide range of accessories, including single skin or insulated blanking panels, acoustic modules, guards and meshes, doors and turrets. Upgradeable louvre. Colt can upgrade live areas to double or triple bank configurations at a later stage than the installation. Please see page 7 for more details. Design input provided by Colt. Colt louvre systems can be uniquely configured to provide the solution to your needs. Software programs are freely available to assist with this. It s easy to size a panel according to a maximum pressure drop, or to specify the appropriate louvre bank configuration based on a set flow rate and maximum pressure drop. With Colt louvre systems, the possibilities are endless. 2
3 COLT LOUVRE SYSTEMS Colt offers two generic types of louvre systems: Screening Louvre: Single Bank Universal roll formed Louvre and exruded E Series ESC Louvre. Ventilation and Rain Defence Louvre: Double and Triple Bank Universal roll formed Louvre, and E Series ERD, a Single Bank extruded rain defence Louvre. Portway School, Bristol Pre-assembled 3UL louvre turrets on top of natural vent shafts. 1UL Shallow 1UL Deep ESC 2UL Shallow 2UL Deep ERD 3UL Shallow 3UL Deep 3
4 Technical Standards INTRODUCTION Specifying louvre is always a compromise, and requires some judgement to take into account the particular needs of each application. At one end of the scale for example a car park may require maximum ventilation but little protection from rain penetration. Alternatively, a plant room containing special machinery or electrical equipment may still need high levels of ventilation but with maximum protection from water entry. The ideal design solution is to produce a louvre system that offers the best RAIN DEFENCE and AERODYNAMIC PERFORMANCE. Unfortunately this seems to be unachievable. But nothing matches the overall performance standards set by the Colt Universal Louvre range. BACKGROUND There has been a problem for many years in quantifying the performance of louvre systems due to the competing test standards and lack of application guidance for designers. The European Standard EN 13030:2001 Ventilation for buildings Terminals Performance testing of louvres subjected to simulated rain helps by providing a useful classification method. However, the responsibility for recommending classifications for particular applications still remains with the designer or specifier. This guide is therefore intended to assist designers and specifiers to select the most appropriate louvre performance classification to suit each specific application. CONSIDERATIONS Site location and exposure Severity of local (site) weather conditions Location and exposure of louvres on building Airflow rate and direction through louvre Maximum acceptable pressure drop Degree and depth of water penetration acceptable Special solutions for sloping applications EN 13030:2001 AND EQUIVALENT STANDARDS British manufacturers of louvre systems in conjunction with HEVAC and BSRIA developed a test and classification method to help designers differentiate between alternative louvre systems to suit specific applications. The HEVAC standard formed the basis for the European standard EN 13030, which is technically identical. BS EN13030 Test Results Rain Defence Effectiveness Rain Defence Actual Rain Entry Rate Classification (1.0 = 100%) Effectiveness (%) (litres/hr/m 2 louvre) Class A % % 0.75 Class B % % 3.75 Class C % % 15.0 Class D below % % % 37.5 To help put the performance classifications into perspective the table above shows how effectiveness relates to actual rain entry under standard test conditions, which are representative of bad Northern European weather.the effectiveness classification should be specified for the design air inlet velocity through the louvre since it is velocity dependent. Class Class 1 Aerodynamic Performance Coeficient 0.40 and above Class to Class to Class 4 below 0.20 A high coefficient means low resistance and high airflow performance. 4
5 APPLICATIONS The test environment in the standard, at 13m/s (30mph) wind speed and 75mm/h (3 inches/h) for a period of 30 to 60 minutes, is intended to represent bad Northern European weather conditions. Two performance classifications are provided, one for rain defence and one for aerodynamic performance. However it is worth noting that this test is based on louvre panels of only 1m x 1m in size. Whilst being very useful in allowing direct performance comparisons for louvres with different designs, it cannot accurately replicate the need for water collection and drainage needed where large louvre panels are installed. Unlike other louvre types, Colt 2UL and 3UL panels have efficient drainage paths into their hollow section mullions, which in practice further increases their rain defence effectiveness. The principles of EN are replicated in the USA under the AMCA Standard 500-L, Laboratory Methods of Testing Louvers for Rating, and in Australia / New Zealand in AS/NZS 4740:2000: Natural ventilators - Classification and performance. Recommendations for the selection of rain defence louvres, based on actual design inlet air velocities (for exhaust louvres take a velocity of 0 m/s, representing the worst case with the exhaust system switched off): Class A Where excellent rain defence is required and core velocities are above 1m/s and up to 3.5m/s. Solution 3 UL No appreciable water penetration Class A Where excellent rain defence is required and core velocities are up to 1m/s. Solution 2 UL No appreciable water penetration Class B Where good rain defence is required and core velocities are between 1m/s and 2.2m/s. Solution 2 UL Some water entry but limited depth of penetration Class B Where good rain defence is required and core velocities are up to 1.5m/s. Solution E Series ERD Some water entry Class C Where reasonably good rain defence is of benefit and core velocities are between 2.2m/s and 3.5m/s. Solution 2 UL Significant water entry but limited depth of penetration Class C Where reasonably good rain defence is of benefit and core velocities are between 1.5m/s and 2.3m/s. Solution E Series ERD Some water entry Class D Where maximum airflow is required but rain defence is not considered important. Solution 1 UL Only limited protection from wind driven rain Class D Where maximum airflow is required but rain defence is not considered important. Solution E Series ESC Only limited protection from wind driven rain CLASSIFICATIONS FOR COLT LOUVRE SYSTEMS 3 UL (Triple Bank) Class A3 up to 3.5m/s 2 UL (Double Bank) Class A2 up to 1.0 m/s Class B2 from 1.0m/s to 2.2 m/s Class C2 from 2.2m/s to 3.5 m/s ERD (Single Bank) Class A2 at 0m/s Class B2 up to 1.5 m/s Class C2 from 1.5m/s to 2.3 m/s Class D2 from 2.3m/s to 3.5 m/s 1 UL (Single Bank) Class D1 all velocities ESC (Single Bank) Class D1 all velocities Performance specifications should always include the design air inlet (core) velocity. 5
6 Screening Louvre INTRODUCTION The principal objective of screening louvre is to obstruct line of sight from normal vantage points by virtue of its design or orientation. Generally each run of louvre will have a continuous appearance unbroken by framing so as to blend in with the building, but it also can be made to provide contrast so as to provide an architectural feature. Whilst the screening application is certainly the simplest from a performance perspective, it is arguably the most demanding from the viewpoint of aesthetics and configuration. Colt Universal Louvre 1UL and E Series ESC Louvre allow maximum airflow with minimum resistance and are ideal for screening areas such as plant rooms and car parks. DESIGN CONSIDERATIONS What building elements do I want to hide? Do I want the louvre to blend with the surrounding building structure? Do I want the louvre to be a feature on my building? What effect do I want to create? What material and finish do I need? Do I need to maximise the light entry through the louvre system? Should louvre blades be inverted? COLT SCREENING LOUVRE Colt offers two choices of screening louvre: a single bank 50mm or 100mm pitch roll-formed Universal Louvre 1UL, and a single bank 50mm pitch extruded E Series ESC Louvre. Universal Louvre - 1UL E Series ESC Sanyo, Hong Kong. Louvre doors. UCL, London. Louvre doors to loading bay. 6
7 Experian, Nottingham. UPGRADEABLE LOUVRE Establishing the louvre material, colour and louvre blade arrangement is relatively straightforward. However when it comes to rain defence performance this can present problems relating to an appropriate specification, particularly at the stage in a project before full ventilation design requirements have been established. If a basic louvre is specified, there is a risk that water penetration may occur resulting in later problems on a completed project, often with only limited and / or expensive solutions being available. Alternatively, if the need for high performance rain defence louvre is accepted, often requiring double or triple bank configurations, it may be difficult to determine the location and areas of functional louvre required at an early enough stage. This can result in large areas of double or triple bank louvre being installed but subsequently blanked off. Clearly this can add unnecessary cost. Colt has developed a design solution for Universal Louvre. This allows a basic installation of single bank louvres, which can be blanked off as part of an initial installation, but with the capability to be upgraded at any later date, to suit either final design requirements or later modifications and use requirements. This solution allows complete design flexibility at optimum cost. Project Orange/Gerber, Bridgewater. 1UL & 2UL louvre panels for screening and ventilation. 7
8 Screening Louvre - 1UL SINGLE BANK UNIVERSAL LOUVRE Its consistent appearance and installation flexibility makes the Single Bank Universal Louvre ideal for screening and cladding applications. Single Bank Universal Louvre, 1UL (one louvre deep) is an aerodynamically shaped louvre and has two standard louvre profiles: Shallow (50mm pitch) and Deep (100mm pitch) 1UL also has two arrangements: Horizontal Vertical Both arrangements can be inverted for roof screens, which is important when wishing to hide items which are high up, such as the lift plant on high rise apartments. FINISHING OPTIONS There are three standard material options for the principal components: Aluminium Mild Steel Stainless Steel (50mm pitch only) There are many decorative finish options, including: Mill Finish Stoved Polyester Powder Paint Anodised Perforated, Stucco and Pre-Coated Louvres are also available on request for larger applications. The applied finishes can be supplied in two coverage levels: Total (all principal components) Partial (louvres and frames only) OPTIONAL EXTRAS There are a large selection of optional accessories such as: Mitred Corners Blanking Panels (Single Skin or Insulated) Special Shapes Acoustic Modules Guards (Bird / Insect* / Security) Doors Turrets * Insect mesh will result in reduced airflow and additional resistance. Perforated louvre allows additional daylight into this partially underground car park. Arup Fitzrovia, London. 2UL rain defence screens for plant rooms. 8
9 William Harvey Hospital, Ashford. 1UL/SH inverted louvre panels. PERFORMANCE SPECIFICATION A multi purpose louvre system shall be provided to achieve minimum resistance to airflow, with louvre blades to be aerodynamically shaped with no sharp edges or protrusions, to ensure the highest efficiency airflow performance. Airflow The following minimum aerodynamic coefficients shall be achieved when the louvre panel is tested to EN 13030: Air Inlet Air Extract The above aerodynamic coefficients shall be established as a result of full scale wind tunnel tests. Rain Defence Single bank louvres are ideally applied in sheltered locations or where rain penetration may be acceptable. The louvre system will achieve Class D1 when tested at all velocities to EN 13030:2001. PRODUCT SPECIFICATION Colt Single Bank Universal Louvre type 1UL having louvre blades at 50mm pitch (shallow section) or 100mm pitch (deep section). Construction throughout shall be from high quality corrosion resistant aluminium alloy type 3005 (Colterra) or 3105 to BS Louvre blades shall not be drilled but shall be clipped and not rivetted or screwed to structural supporting mullions. Thus allowing for expansion and contraction along their length without distortion and to provide a continuous external appearance if required. Mullions shall be concealed at 1250mm maximum centres and their points of support along their length shall be in accordance with prevailing site wind pressures (as calculated and specified by a structural engineer) in accordance with BS 6399 part 2. Manufactured from 2mm sheet so that associated support steelwork is reduced to a minimum. Cill and frames shall contain all peripheral fixings and be manufactured from 1.6mm sheet. PERFORMANCE SUMMARY High airflow properties Moderate rain defence properties (subject to location and exposure) Equally suited to applications requiring architectural screening or cladding, Colt Single Bank Louvre is ideal where a high airflow is required and where rain defence is not of primary importance. 9
10 Screening Louvre - 1UL Performance Data Dimensions Note: All dimensions are given as internal, external dimensions will vary depending upon material thickness 167 Shallow section Deep section Pitch Pitch Mullion Centres (M) Maximum Unsupported MullionLength Pressure Drop (pa) INLET Wind Load (N/m ) Face Velocity (m/s) 10
11 Assembly Side Frame Top Frame Cill Louvre Blade (Shallow) Mullion Intermediate supporting steelwork External Corner Internal Corner WIND SPEED CONDITIONS 1.0 UL Effectiveness under 13m/s 1 UL effectiveness wind speed conditions under 13m/s wind speed conditions 75mm/hr rainfall Effectiveness Inlet Ventilation (m/s) 11
12 Screening Louvre - E Series ESC SINGLE BANK E SERIES LOUVRE The E Series is the latest addition to the Colt Universal Louvre range. It is an extruded aluminium, Single Bank Louvre System available in a 75mm pitch configuration. E Series type ESC offers an alternative solution to screening and cladding applications. It is recommended that E Series type ESC should not be installed in exposed locations where rain penetration may not be acceptable. FINISHING OPTIONS Standard material options for the principal components: Aluminium There are many decorative finish options, including: Mill Finish Stoved Polyester Powder Paint Anodised Perforated, Stucco and Pre-Coated Louvres are not available, please see Universal Louvre. The applied finishes can be supplied in two coverage levels: Total (all principal components) Partial (louvres and frames only) OPTIONAL EXTRAS There are a large selection of optional accessories such as: Mitred Corners Blanking Panels (Single Skin or Insulated) Special Shapes Acoustic Modules Guards (Bird / Insect* / Security) Doors Turrets * Insect mesh will result in reduced airflow and additional resistance. Wales Millenium Centre, Cardiff. Rough cut wooden 1UL/DH louvres. Evelina s Childrens Hospital, London. Plant room louvres and doors.. 12
13 PERFORMANCE SPECIFICATION A simple, clean extruded louvre with sharp, crisp edges to give a continuous appearance. Airflow The following minimum aerodynamic coefficients shall be achieved when the louvre panels is tested to EN 13030:2001: Air Inlet Air Extract The above aerodynamic coefficients shall be established as a result of full scale wind tunnel tests. Rain Defence Single bank louvres should only be applied in sheltered locations or where rain penetration may be acceptable. The louvre system will achieve Class D1 when tested at all velocities to EN 13030:2001. PRODUCT SPECIFICATION Colt Single Bank E Series Louvre type ESC having louvre blades at 75mm pitch. Construction throughout shall be from high quality corrosion resistant aluminium alloy. Louvre blades shall not be drilled but clipped and not rivetted or screwed to structural supporting mullions. Thus allowing for expansion and contraction along their length without distortion and to provide a continuous external appearance if required. Mullions shall be concealed at 1250mm maximum centres and their points of support along their length shall be in accordance with prevailing site wind pressures (as calculated and specified by a structural engineer) in accordance with BS 6399 part 2. Manufactured from 2mm sheet so that associated support steelwork is reduced to a minimum. Cill and frames shall contain all peripheral fixings and be manufactured from 1.6mm sheet. C-Plex,West Bromich. Trapezoidal 2UL louvre panels. 13
14 Screening Louvre - E Series ESC Dimensions Note: All dimensions are given as internal, external dimensions will vary depending upon material thickness Non flanged frame Flanged frame Mullion Centres (M) Maximum Unsupported MullionLength Pressure Drop (pa) INLET Wind Load (N/m ) Face Velocity (m/s) 14
15 Assembly Top Frame Saddle False Louvre Half Mullion Internal Mitre Mullion Top Frame ESC Louvre Saddle Corner Cill Cill False Louvre ESC MITRED CORNERS Corners are tack welded from the inside to produce a clean external appearance
16 Ventilation & Rain Defence Louvre INTRODUCTION The principal objective of ventilation and rain defence louvre is to allow the passage of air, whilst providing a measure of protection against the rain. If your louvre has a functional role to play, your selection will need further consideration. Specifying performance has not been helped by conflicting technical information given by louvre manufacturers which quotes percentage free areas measured in different ways, namely as resistance to airflow and aerodynamic coefficients alternatively. For a true comparison of performance the aerodynamic coefficient and the degree of rain defence effectiveness are the only sensible measures. These have been included as part of the EN test standard, which includes a simple classification system. DESIGN CONSIDERATIONS How much air needs to flow through the louvre It is worth considering that the actual area of louvre system being installed to meet the performance requirements, might result in more ventilation than is actually needed. Some areas may even need to be blanked off. However, this should not stop you from clearly specifying your ventilation requirements. Whether you are specifying a louvre system for natural or forced ventilation, you need to know the resistance to airflow caused by the louvre system for a given flowrate. How much rain defence is required UPGRADEABLE LOUVRE Please see page 7. RAIN DEFENCE & PERFORMANCE Colt offer three choices of performance louvre, a double bank roll formed louvre: Universal Louvre - 2UL a triple bank roll formed louvre: Universal Louvre - 3UL and an extruded, 75mm pitch single bank louvre: E Series ERD Indoor Recreation Centre, Ma On Shan, Hong Kong. Universal Louvre for plant room ventilation and for controllable air inlet for the smoke extraction system. 16
17 Mass Transit Railway Corporation (MTRC), Hong Kong. Side vents fitted externally with Colt Universal Louvre in line with surrounding Colt Louvre panels. HOW COLT UNIVERSAL LOUVRE 2UL & 3UL WORKS 1 Air and rain enters between the louvre blades. 2 Water is transferred to the second louvre where it is collected Water is transferred along the blades and into the hollow vertical mullion thus preventing re-entrainment, draining the collected water onto the cill. 1 RAIN DISPERSION AIR FLOW Clarks Shoes, Somerset. Universal Louvre for screening in both painted and pre-coated finishes. 17
18 Ventilation & Rain Defence Louvre - 2UL DOUBLE BANK UNIVERSAL LOUVRE Double Bank Universal Louvre is ideal for applications requiring ventilation with a good degree of rain defence. Double Bank Universal Louvre, 2UL (two louvres deep) and has two front louvre profiles: Shallow (50mm pitch) Deep (100mm pitch) 2UL also has two arrangements: Horizontal and Vertical Both arrangements can be inverted. FINISHING OPTIONS There are three standard material options for the principal components: Aluminium Mild Steel Stainless Steel (50mm pitch only) There are many decorative finish options, including: Mill Finish Stoved Polyester Powder Paint Anodised Perforated, Stucco and Pre-Coated louvres (normally applied to front louvres blades and frames only) are also available on request. The applied finishes can be supplied in two coverage levels: Total (all principal components) Partial (louvres and frames only) OPTIONAL EXTRAS There are a large selection of optional accessories such as: Mitred Corners Blanking Panels (Single Skin or Insulated) Special Shapes Acoustic Modules Guards (Bird / Insect* / Security) Doors Turrets * Insect mesh will result in reduced airflow and additional resistance. Crawley College, Crawley. ERD louvre panels on the plant room, and Solarfin solar shading panels. Xscape, Milton Keynes, UK. 2000m 2 of Universal Louvre including both Colt Single Bank and Double Bank Universal rain defence louvre. 18
19 Piccadilly Station, Manchester. A combination of single and double bank louvres, depending on the specific airflow and rain defence requirements. PERFORMANCE SPECIFICATION A multi purpose louvre system shall be provided to achieve minimum resistance to airflow, with louvre blades to be aerodynamically shaped with no sharp edges or protrusions, to ensure the highest efficiency airflow performance. Airflow The following minimum aerodynamic coefficients shall be achieved when the louvre panel is tested to EN 13030:2001: Air Inlet Air Extract Rain defence The louvre system will achieve the following weathering classification when the louvre panel is tested to EN 13030:2001: Class A2 - up to 1m/s suction velocity Class B2 - up to 2.2m/s suction velocity Class C2 - up to 3.0m/s suction velocity Class D2 - up to 3.5m/s suction velocity The louvre system shall be drained internally through hollow section vertical mullions which shall discharge water onto the cill. The louvre system shall be capable of combining both double bank functional louvre and single bank aesthetic louvre with rear blanking panels on the same elevation without variation in external profile. PRODUCT SPECIFICATION Colt Double Bank Universal Louvre type 2UL having louvre blades at 50mm pitch (shallow section) or 100mm pitch (deep section, front louvre only). Construction throughout shall be from high quality corrosion resistant aluminium alloy type 3005 (Colterra) or 3105 to BS Front louvre blades shall not be drilled but clipped and not rivetted or screwed to structural supporting mullions allowing for expansion and contraction along their length without distortion and to provide a continuous external appearance if required. Mullions shall be concealed at 1250mm maximum centres and their points of support along their length shall be in accordance with prevailing site wind pressures (as calculated and specified by a structural engineer) in accordance with BS 6399 part 2. Manufactured from 2mm sheet so that associated support steelwork is reduced to a minimum. Cill and frames shall contain all peripheral fixings and be manufactured from 1.6mm sheet. PERFORMANCE SUMMARY Good airflow properties Good rain defence properties Equally suited to applications requiring architectural screening or cladding with ventilation and a good degree of rain defence. Piccadilly Station, Manchester. 19
20 Ventilation & Rain Defence Louvre - 2UL Dimensions Note: All dimensions are given as internal, external dimensions will vary depending upon material thickness Shallow section Deep section Pitch Pitch Mullion Centres (M) Maximum Unsupported MullionLength Pressure Drop (pa) INLET Wind Load (N/m ) Face Velocity (m/s) 20
21 Assembly Top Frame Secondary Steel Support Cill External Corner Mullion Front Louvre Blade (Shallow) Internal Corner WIND SPEED CONDITIONS UL UL Effectiveness effectiveness under under 13m/s 13m/s wind speed conditions wind speed conditions 75mm/hr rainfall Effectiveness Inlet Ventilation (m/s) 21
22 Ventilation & Rain Defence Louvre - 3UL TRIPLE BANK UNIVERSAL LOUVRE Its consistent appearance and installation flexibility makes the Triple Bank Universal Louvre ideal for screening and cladding applications requiring ventilation with maximum rain defence. Triple Bank Universal Louvre, 3UL (three louvres deep) has two front louvre profiles: Shallow (50mm pitch) and Deep (100mm pitch) Front louvre only 3UL also has two arrangements: Horizontal andvertical FINISHING OPTIONS There are three standard material options for the principal components: Aluminium Mild Steel and Stainless Steel (50mm pitch only) There are many decorative finish options, including: Mill Finish Stoved Polyester Powder Paint and Anodised Perforated, Stucco and Pre-Coated louvres (normally applied to front louvres blades and frames only) are also available on request. The applied finishes can be supplied in two coverage levels: Total (all principal components) Partial (louvres and frames only) OPTIONAL EXTRAS There are a large selection of optional accessories such as: Mitred Corners Blanking Panels (Single Skin or Insulated) Special Shapes Acoustic Modules Guards (Bird / Insect* / Security) Doors Turrets * Insect mesh will result in reduced airflow and additional resistance. Western Harbour Tunnel, Hong Kong. Triple bank facetted circular louvre installed to handle the high air volumes required and to provide maximum rain protection even in typhoon conditions. Indoor Recreation Centre, Ma On Shan, Hong Kong. Universal Louvre for plant room ventilation and for controllable air inlet for the smoke extraction system. 22
23 The Light, Leeds. Single bank 1UL louvre upgraded to 3UL for live areas. PERFORMANCE SPECIFICATION PRODUCT SPECIFICATION PERFORMANCE SUMMARY A multi purpose louvre system shall be provided to achieve minimum resistance to airflow, with louvre blades to be aerodynamically shaped with no sharp edges or protrusions, to ensure the highest efficiency airflow performance. Airflow The following minimum aerodynamic coefficients shall be achieved when the louvre panel is tested to EN 13030:2001: Air Inlet Air Extract Rain defence The louvre system will achieve the following weathering classification when the louvre panel is tested to EN 13030:2001: Class A3 - up to 3.5m/s suction velocity The louvre system shall be drained internally through hollow section vertical mullions which shall discharge water onto the cill. The louvre system shall be capable of combining both double bank functional louvre and single bank aesthetic louvre with rear blanking panels on the same elevation without variation in external profile. Colt Triple Bank Universal Louvre type 3UL having louvre blades at 50mm pitch (shallow section) or 100mm pitch (deep section, front louvres only). Construction throughout shall be from high quality corrosion resistant aluminium alloy type 3005 (Colterra) or 3105 to BS Front louvre blades shall not be drilled but clipped and not rivetted or screwed to structural supporting mullions allowing for expansion and contraction along their length without distortion and to provide a continuous external appearance if required. Mullions shall be concealed at 1250mm maximum centres and their points of support along their length shall be in accordance with prevailing site wind pressures (as calculated and specified by a structural engineer) in accordance with BS 6399 part 2. Manufactured from 2mm sheet such that associated support steelwork is reduced to a minimum. Cill and frames shall contain all peripheral fixings and be manufactured from 1.6mm sheet. Good airflow properties Excellent rain defence properties Suited to applications requiring architectural screening or cladding with excellent rain defence protection even with high air intake velocities. Turbine Surface Technologies, Nottingham, UK. Customer comment: Colt was the only company capable of handling a combined package of natural extract ventilation, solar shading louvre and screening & ventilation louvre. 23
24 Ventilation & Rain Defence Louvre - 3UL Dimensions Note: All dimensions are given as internal, external dimensions will vary depending upon material thickness Shallow section Deep section Pitch Pitch Mullion Centres (M) MAX Maximum Unsupported MullionLength Wind Load (N/m ) Pressure Drop (pa) INLET Face Velocity (m/s)
25 Assembly Frame Mullion External Corner Mullion Drain Outlet Inner Louvre Outer Louvre (Shallow) WIND SPEED CONDITIONS Effectiveness UL Effectiveness under 313m/s UL effectiveness wind speed conditions under 13m/s wind speed conditions 75mm/hr rainfall Inlet Ventilation (m/s) 25
26 Ventilation & Rain Defence Louvre - E Series ERD SINGLE BANK E SERIES ERD LOUVRE E Series type ERD is an extruded aluminium, single bank louvre system available in a 75mm pitch configuration. E Series type ERD offers a competitive solution to screening and cladding applications which require a good degree of rain defence. Kowloon Canton Railway Corporation, Hong Kong. Colt inverted Universal Louvre is used extensively for this new underground station to provide high volume airflow with rain defence for plant rooms, entrances, vent shafts and external decoration. FINISHING OPTIONS Standard material for all principal components: Aluminium There are many decorative finish options, including: Mill Finish Stoved Polyester Powder Paint Anodised Perforated, Stucco and Pre-Coated louvres are not available, please see Universal Louvre. The applied finishes can be supplied in two coverage levels: Total (all principal components) Partial (louvres and frames only) OPTIONAL EXTRAS There are a large selection of optional accessories such as: Mitred Corners Blanking Panels (Single Skin or Insulated) Special Shapes Acoustic Modules Guards (Bird / Insect* / Security) Doors Turrets * Insect mesh will result in reduced airflow and additional resistance. ERD rain defence louvre to plantroom enclosures. 26
27 National Physical Laboratory,Teddington. 1UL/SH panels with upgradeable 2UL/SH panel sections. PERFORMANCE SPECIFICATION A simple, clean extruded louvre with sharp, crisp edges to give a continuous appearance. Airflow The following minimum aerodynamic coefficients shall be achieved when the louvre panel is tested to EN 13030:2001: Air Inlet Air Extract Rain defence The louvre system will achieve the following weathering classification when the louvre panel is tested to EN 13030:2001: Class A2 - up to 0m/s suction velocity Class B2 - up to 1.5m/s suction velocity Class C2 - up to 2.0m/s suction velocity Class D2 - up to 3.5m/s suction velocity PRODUCT SPECIFICATION Colt Single Bank E Series Louvre type ERD having louvre blades at 75mm pitch, shallow section only. Construction throughout shall be from high quality corrosion resistant aluminium alloy. Louvre blades shall not be drilled but clipped and not rivetted or screwed to structural supporting mullions allowing for expansion and contraction along their length without distortion and to provide a continuous external appearance if required. Mullions shall be concealed at 1250mm maximum centres and their points of support along their length shall be in accordance with prevailing site wind pressures (as calculated and specified by a structural engineer) in accordance with BS 6399 part 2. Manufactured from 2mm sheet such that associated support steelwork is reduced to a minimum. Cill and frames shall contain all peripheral fixings and be manufactured from 1.6mm sheet. 27
28 Ventilation & Rain Defence - E Series ERD Dimensions Note: All dimensions are given as internal, external dimensions will vary depending upon material thickness Non flanged frame Flanged frame Mullion Centres (M) Maximum Unsupported MullionLength Pressure Drop (pa) INLET Wind Load (N/m ) Face Velocity (m/s) 28
29 Wales Millenium Centre, Cardiff. Addenbrookes Car Park, Cambridge. Bexley Business Academy, Bexley. Eastbourne Terrace, London. Evelina s Childrens Hospital, London. Crawley College, Crawley. Burj Al Arab, Jumeirah Beach, Dubai. 29
30 Acoustic Louvre INTRODUCTION As part of the Colt Universal Louvre range, Colt can provide acoustic louvre panels for mounting behind the louvre. Plant room openings, cooling towers, condenser plant etc., will produce sound pressure levels which may exceed existing or required noise criteria at prescribed distances from the building. Colt is able to provide attenuation for the Colt Universal Louvre System that will meet the most stringent criteria. If a single bank of elements does not provide the required noise control, a double bank may be specified. As an alternative, duct silencers may be selected to give the desired noise reduction. To ensure the most economic solution, noise control must be considered at the earliest possible design stage. Retrofit installations can be significantly more expensive. If in doubt, please contact Colt International. 30 ACOUSTIC RANGE There are two acoustic louvre models: Type R Optimum acoustic performance with normal pressure drop. Type LP Normal acoustic performance with minimum pressure drop. MATERIAL The outer casing shall be of no less than 1.2mm galvanised mild steel sheet. The acoustic louvre blades shall be of aerofoil configuration formed from 0.7mm perforated galvanised mild steel sheet on the inner surface and 0.7mm galvanised mild steel sheet externally. Modules Acoustic louvre banks over 1220mm wide and/or 3660mm high will normally be supplied as two or more modules for site assembly. Infill The infill shall be in organic mineral wool or glass fibre of 47kg/m 3 density and packed under not less than 5% compression to eliminate voids due to settlement. The infill shall be inert, as well as vermin, rot and moisture proof. Type R
31 PERFORMANCE Dimension X * Acoustic Performance Aerodynamic Performance Transmission Loss db Type LP Type R Static Pressure Drop (Pa) Type R Type LP k 2k 4k 8k Octave Band Hz Face Velocity (m/s) ACOUSTIC PERFORMANCE Octave Band Centre Frequency, Hz k 6 2k 7 4k 8 8k Model R Model LP AERODYNAMIC PERFORMANCE Acoustic Louvre Model Aerodynamic Coefficient (cv) Pressure Loss ( ) Model R Model LP DIMENSIONS Vertical section through Colt E Series ESC 75 pitch louvre panel with acoustic module into brickwork opening. Acoustic Louvre Model Model R Module Width (mm) 610, 914 or 1219 Module Height (mm) 305 to 3653 in 305mm increments * Dimension X is a minimum of 300mm or greater depending on the acoustic performance requirements. Model LP 610, 914 or to 3556 in 356mm increments 31
32 C a TERMINOLOGY COLT SERVICE Weather Louvre A device intended to allow the passage of inlet or exhaust air while minimising the ingress of rain (HEVAC). Acoustic Louvre Specially designed louvres to reduce the transmission of noise to or from a building or enclosure and may be used in conjunction with other weather louvres (HEVAC). Free Area The minimum area through which air can pass. Determined by multiplying the sum of the minimum distance between intermediate blades, top blade, head and bottom blade and cill by the minimum distance between jambs (AMCA). In performance terms Free Area is a wholly meaningless measure. People feel better in Colt conditions t l o 1 9 I 3 n 1 t e - r n 2 a t 0 i o n 6 0 l Measured Free Area A term used to indicate the open area between frame members with the louvre blades removed and used with the aerodynamic co-efficient (Cv) to calculate the aerodynamic free area and thus the pressure drop through a louvre. This is now sometimes referred to as the core area. Aerodynamic Area The product of measured free area and the aerodynamic coefficient. Equal to the total area of a theoretically perfect opening. This value is used for the calculation of the pressure drop. Architectural Solutions Climate Control Smoke Control Service and Maintenance Part of the Colt Group of companies, Colt Service offers a comprehensive range of maintenance packages incorporating the maintenance and repair of all building services equipment including non Colt products. Colt Service provide a 24 hour, 365 day emergency cover as standard. MAINTENANCE Colt Louvre Systems are designed to be virtually maintenance free, although regular cleaning of the louvres with a mild detergent is recommended. For obvious reasons, abrasive cleaning agents and wire brushes must not be used. Colt International Limited New Lane Havant Hampshire PO9 2LY Tel +44(0) Fax +44(0) [email protected] Subject to modification. Publication number PD 45: 04/06 Colt and the Colt logo are registered trademarks of Colt International Licensing Limited. Colt International Licensing Limited 2006.
Installation Detailed installation instructions are provided which should be strictly followed.
Specification System 6 The Metal Technology Thermally-Broken Vertical Slide Window has been designed in such a way that its'attractive and clean lines will enhance all types of residential and commercial
People work better in Colt conditions Colt Climate Control products and services
People work better in Colt conditions Colt Climate Control products and services People work better in Colt Conditions - Colt climate control systems COLT CONDITIONS We harness the natural elements to
Fire Resistant Systems
Fire Resistant Systems A R C H I T E C T U R A L A L U M I N I U M G L A Z I N G S Y S T E M S Fire Resistant Systems Introduction Kawneer are pleased to introduce two new comprehensive Fire Resistant
Confort 26. Sliding Systems. Sapa Building System
Confort 26 Sliding Systems Sapa Building System Confort 26 is Sapa s thermally insulated sliding system for windows and doors. Available as two- and three-rail solution. Among its features, there are
RPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
Incorporating V2.3. Product spec >>> > Series ECG - Egg Crate Grilles. > Series ECG45-45 Egg Crate Grilles
Incorporating V2.3 Product spec >>> > Series ECG - Egg Crate Grilles > Series ECG45-45 Egg Crate Grilles Grilles Egg crate Recommended for: Wall, ceiling & duct Extract Overview Industry standard extract
Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 [email protected]
CARDOK CARLIFT Fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built to measure, all dimensions can
HVAC air curtains. Type InduAir
Air Conditioning Cooling Heating Ventilation HVAC air curtains Type InduAir The Energy Saving air curtain for Industrial Applications InduAir The solid, self-supporting housing of the energy saving air
Peninsula Place, Greenwich, London
Concepts Products Service Peninsula Place, Greenwich, London 1 Project Report Peninsula Place, Greenwich, London Designed as one of the most sustainable commercial buildings in the UK, with a BREEAM rating
Roof Curbs, Extensions and Equipment Supports
Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....
Insulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW
Insulated Roof & Wall Panels Trapezoidal Insulated Roof Panels KS1000 RW Overview Kingspan roof panel systems present a superior system compared to conventional multi-part site assembled systems. They
Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments
Cannon T4 Modular Data Centres For Outside Deployment & Challenging Environments A high performance, full specification Data Centre, up to Tier 4* resilience, instantly deployable A highly secure Data
Plaisance 50. Windows and doors. Sapa Building System
Plaisance 50 Windows and doors Sapa Building System Plaisance 50 is a non-thermally broken system for aluminium windows and doors with a building depth. The system offers a wide range of inward and outward
CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED
CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.
Weather Resistant Louvres
L---e Weather Resistant Louvres Type WSL Untreated aluminium Contents Application Realisation Safety instructions Contents Application Realisation Safety instructions Dimensions Sizes Installation Accessories
INDEX. Chapter8. air master. Perforated Ceiling Diffusers
Chapter8 INDEX A. Perforated ceiling diffuser 1. Perforated ceiling diffuser with plenum box..: APCD+P...8.1. Perforated ceiling diffuser with damper....: APCD...8. Standard sizes...8. Fixing details...8.
TFSR & TFSK Roof Fans
Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans TFSR & TFSK Roof Fans With swing-out function 2 I TFSR/TFSK TFSR & TFSK Roof
Optiffuser. High-performance, high bandwidth lightweight 1D diffuser.
Optiffuser High-performance, high bandwidth lightweight 1D diffuser. General product information The Optiffuser comes in packs of four panels. Two positives and two negatives (see page 5) per package.
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
Unbeatable energy efficient glass curtain wall system
Unbeatable energy efficient glass curtain wall system CONTENT Introduction 1 System 2 World Class Engineering 4 Unit Selection 5 Energy Efficiency & Comfort 10 Maximised Installation Efficiency 12 Aesthetics
Plaisance 24. Sliding Systems. Sapa Building System
Plaisance 24 Sliding Systems Sapa Building System Plaisance 24 is Sapa s noninsulated sliding system for windows and doors. Available as one-, two-, three- and fourrail solution. Among its features, there
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide
Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape
ModuSec Secure and efficient IT room solutions Turnkey Modular Construction Fast clean build to any size or shape Room in room Standalone external build Transportable Modusec SR Options Modusec SR Options
Grilles & Diffusers Series LFP Incorporating
Grilles & Diffusers Incorporating Series LFP Produce a stable linear throw, creating an area of clean air with minimal diffusion Perfect for areas like clean rooms and operating theatres Tile replacer
AMF Line; wall absorbers Wall mounted acoustic designs PERFORMANCE CEILINGS. M ore s c op e f or i n n ovat i on MADE IN GERMANY
PERFORMANCE CEILINGS M ore s c op e f or i n n ovat i on AMF Line; wall absorbers Wall mounted acoustic designs MADE IN GERMANY 138568_Prospekt Wandabsorber_GB int.indd 1 Acoustic elements on the wall
Glass partitions SFB 3074
Glass partitions SFB 3074 Our facade system SFB 3074 is innovative in its design. We have made a great effort to obtain an energy effective system. The future requirements regarding the economical use
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow
1.2.1 1.1.8 PRODUCTBLADEN GT ROCKPANEL STRUCTURE
1..1 1.1.8 PRODUCTBLADEN SHEETS GT page 1 to 6 Rockpanel Structure is a very durable panel with a lightly textured finish, specially developed for use in cladding, fascia, soffit applications. The basic
Window Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
AIR CONDITIONING PRODUCTS COMPANY
Quality Products Fixed Louvers AIR CONDITIONING PRODUCTS COMPANY all Shutter Backdraft Damper Ceiling Shutter Motorized Damper Fixed Louver Ga le Shutter Drainable Louver Supply Damper Fiberglass Shutter
Installation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
BACKGROUND VENTILATION SOLUTIONS FOR DOMESTIC BUILDINGS
CI/SfB (57) Uniclass L753 October 2015 BACKGROUND VENTILATION SOLUTIONS FOR DOMESTIC BUILDINGS... PRODUCT RANGE AND OVERVIEW..................................................................................
BLADE S-MAX Cabinet for Blade Server
Cabinet for Blade Server 1 2 Overview Material specification Corner verticals: 1.5 mm steel End frames: 1.5 mm steel Panel mounts: 2.0 mm steel Panel mount supports: 1.5 mm steel Side panels, door and
Rockwool Cladding Roll
Rockwool Cladding Roll High performance industrial insulation has been specifically developed for use in lightweight cladding applications to commercial or industrial framed buildings. Cladding Roll U/F
SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES
SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES 4121 N.W. 37 th Street, Lincoln, NE 68524 Telephone (402) 470-2627 Fax (404) 470-2410 www.gtexhaust.com
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
I-Line - Snap-On Feature
Oct 2012 I-Line - Snap-On Feature DATA SHEET Snap-On features - Guaranteed truelines every time Bailey I-Line Snap-On is an architectural cladding feature offering creative possibilities for architects
Solar Mounting System
Xiamen Antai New Energy Tech.Co., Ltd Installation Manual Antai Rail Solar Mounting System (Flat Roof Solution) Version 1.1 Office Add: 508#, North Tower, Guangxia Building Huli Torch Hi-tech Zone, Xiamen,
CADB and CADT-D / DI / DC Series
HEAT RECOVERY UNITS CADB and CADT-D / DI / DC Series NEW The CADB, CADT heat recovery range consists of: - Self-supporting casing with extruded aluminium profile structure and beige plastic coated galvanised
Avantis 75. Windows & Doors. Sapa Building System
Avantis 75 Windows & Doors Sapa Building System Avantis 75 is a thermally broken three-chamber window and door system, which sets the highest standards of thermal insulation and stability. Avantis 75
Installation Window Building In Details
Installation Window Building In Details INSTALLATION Photo courtesy of Rowe Aluminium DATE: NOVEMBER 2009 REPLACES: AUGUST 2003 INSTALLATION Installation Replaces: Scale: NOT TO SCALE Vantage snap-on couplers
ORAY PREFABRICATED GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS
GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS ~GSM SHELTER CONTAINERS ARE PROCUDED ACCORDING TO THE DEMANDED SIZE.~ (W x L x H) Page1 GENERAL FEAUTURES Environmental Conditions : Maximum outdoor temperature
Ubiflex. Non-lead flashing system
Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof
Climasys Thermal Management System. Schneider Electric Universal Enclosures 2009
Climasys Thermal Management System Schneider Electric Universal Enclosures 2009 Schneider Electric Universal Enclosures The specialist in sealed equipment What is the mission of Schneider Electric Universal
UDSA - UDSBD unit heater
APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the
Tel: 0800 975 4933 Sales: [email protected] STORAGE CABINETS. PREMIERSHIELD anti-bacterial powder coating system. quality products made in the UK
Tel: 0800 975 4933 Sales: [email protected] STORAGE PREMIERSHIELD anti-bacterial powder coating system quality products made in the UK MEDIUM DUTY : 88 SERIES PREMIER BDU DESK UNITS: 88 SERIES Of welded
Laminar Flow Panel. Type LFP 2/2.4/B/2. Telephone +44(0) 1842 754545 Telefax +44(0) 1842 763051 e-mail [email protected] www.troxuk.co.
2/2./B/2 Laminar Flow Panel Type LFP TROX UK Ltd Caxton Way Thetford Norfolk IP2 3SQ Telephone +(0) 182 7555 Telefax +(0) 182 763051 e-mail [email protected] www.troxuk.co.uk Contents Description Description
WTW SWANTM. Linear slot air diffusers of wall-to-wall design for ceilings
SWANTM WTW Linear slot air diffusers of wall-to-wall design for ceilings Quick facts Wall-to-wall installation Diffuser face of light aluminium design 2, 3 or slots Horizontal/vertical air distribution
GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY
GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY July 2008 1.0 SCOPE These guidelines describe the way in which air conditioning units shall be installed or replaced
The WANZ Guide to Window Installation
The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check
SERVER ROOM CABINET INSTALLATION CONCEPTS
SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the
Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery
Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6
Hoesch Matrix System individuell. ThyssenKrupp Steel Europe Thinking the future of steel
Hoesch Matrix System individuell ThyssenKrupp Steel Europe Thinking the future of steel 2 3 Steel in perfect shape and precision Steel the material of contemporary architecture. Throughout the production
CDW Systems Ltd Contemporary Doors & Windows
CDW Systems Ltd Contemporary Doors & Windows The comprehensive product overview A complete specification guide to CDW Systems range of Aluminium windows, doors and curtain walling for commercial and residential
19 DYNAmax Free Standing Server C A B I N E T s
9 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server Cabinets FAMILY W=600mm and W=800mm DYNAmax Series Free Standing Server Cabinets DYNAmax series Servering Enclosures, provide
Colonnade Security Pipe
Description: Round & Square downpipe formed from extruded 6060 T4 aluminium in various sizes (Ø83mm, Ø108mm, 83x83 mm & 108x108mm*) & supplied with a complete range of accessories i.e. Offsets, bends,
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM. Product. Scope. Appraisal No. 573 [2013]
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM This Appraisal replaces BRANZ Appraisal No. 573 (2007). Amended 05 February 2016. BRANZ Appraisals Technical Assessments of products for building and construction.
TARIFF CODE and updates standard
TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of
Series 456 Commercial Awning Window
Commercial Awning Window COMMERCIAL SERIES Photo courtesy of Hanlon Windows Australia DATE: MAY 2013 REPLACES: MARCH 2008 COMMERCIAL SERIES KEY FEATURES/PERFORMANCE CHARACTERISTICS Scale: not to scale
Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
ACOUSTICS. Axiom Canopy Clouds Absorption Data Sabines (average 500, 1k, 2k, 4k Hz) ACOUSTICS TESTING DATA Sound Absorption in Sabines
ACOUSTICS ACOUSTICS TESTING DATA Sound Absorption in Sabines SABINE DEFINITION A Sabine is a measure of the sound absorption provided by a material when installed within an architectural space. The number
Series 602 MAGNUM Sliding Window DESIGNER SERIES
Series 602 DESIGNER SERIES DATE: NOVEMBER 2009 REPLACES: AUGUST 2003 DESIGNER SERIES Series 602 KEY EATURES / PERORMANCE CHARACTERISTICS Scale: NOT TO SCALE Designed to complement our existing high quality
Premium flat 167 Twinson (P 9576) (formerly O-Wall) Technical file. Roofline & Cladding. Cladding premium. www.deceuninck.com
Premium flat 167 Twinson (P 9576) (formerly O-Wall) Technical file Cladding premium Roofline & Cladding www.deceuninck.com 01/02/2012 23/03/2011 V 1.1: Update chapter Length: replace colour 65 by 66. 16/01/2012
sound reduction systems for commercial, educational and industrial environments
sound reduction systems for commercial, educational and industrial environments Tel: +44 ()14 3874 Fax: +44 ()14 38957 E-mail: [email protected] Web: www.soundreduction.co.uk soundblocker Acoustic
When considering Roof drainage design the following should be taken into account:
Roof Drainage Design The primary objective of a gutter or spouting system is to remove water from the roof catchment area and channel that water to the ground drainage. Water ingress can have detrimental
Elegant ECM. ELEGANT ECM air conditioners allow. The range is made up of 12 models: Ceiling Air Conditioner
Elegant ECM Ceiling Air Conditioner ELEGANT ECM air conditioners allow to heat and cool very economically small and medium areas, like shops, show rooms, workshops, supermarkets. The range is made up of
Airline. small air handlers and extract fan units. VES Airline part of a complete range of innovative, flexible products from the HVAC experts
Lo w p r o f i l e small air handlers and extract fan units Duties to 0.55m 3 /sec Available with the Electroline fitted control panel Ceiling void friendly - unit heights from 190mm to 350mm Airline VES
information information
Technicalinformation Technicalinformation technicalinformation SYSTEM 40C GENERAL GROPERTIES 1 Glazing: from 4 to 22 mm 2 E.P.D.M. Sealing Gasket 3 Efficent drainage of the vent section 4 Efficent chamber
All Weather Hall. Efficient, multipurpose & quick to build
All Weather Hall Efficient, multipurpose & quick to build ALL WEATHER HALL www.deboer.com www.deboer.com ALL WEATHER HALL A flexible solution for a multitude of needs All Weather halls from De Boer provide
Profiles in stock Standard catalogue. Discover the possibilities with aluminium profiles from Sapa
Profiles in stock Standard catalogue Discover the possibilities with aluminium from Sapa You can create your own profile or you can choose from a wide selection of standard. Delivery: 1 2 weeks for standard
Laminar Flow Cabinets and Workstations
VERTICAL AND HORIZONTAL HEPA FILTERED SYSTEMS FOR PROCESS OR OPERATOR PROTECTION Laminar Flow Cabinets and Workstations For procedures requiring protection from particulate contamination and for aseptic
Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes
Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,
19 DYNAmax Free Standing Server C A B I N E T s
9 DYNAmax Free Standing Server C A B I N E T s 9 DYNAmax Free Standing Server Cabinets FAMILY W=mm and W=800mm DYNAmax Series Free Standing Server Cabinets DYNAmax series Servering Enclosures, provide
Product Data Sheet ROCKPANEL Rockclad
Product Data Sheet ROCKPANEL Rockclad Durable - Xtreme - FS-Xtra United Kingdom 1 Product description ROCKPANEL boards are prefabricated compressed mineral wool boards with synthetic binders. The surface
Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01
Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal
LAMINAR FLOW CABINETS
LAMINAR FLOW CABINETS Vertical Laminar Flow Cabinets VLF 550 VLF650 VLF1000 VLF1200 VLF 1500 VLF1800 Monmouth Scientific's brand new range of Vertical laminar Flow (VLF) cabinets is available in six different
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
IMPACT DAMAGE RESISTANT WALL SYSTEMS
IMPACT DAMAGE RESISTANT WALL SYSTEMS CONTENTS Introduction 2 Advantages 2 2 Material Specifications 2 Design Considerations 3 Framing 5 Plasterboard Installation 5 Health, Safety & Warranty 6 Contact Details
Installation Instructions
Installation Instructions READ BEFORE INSTALLING UNIT For Low Profile Window Air Conditioner INSTALLATION WARNINGS AND CAUTION Carefully read the installation manual before beginning. Follow each step
Quality Building Products for over 50 Years
Light Commercial Quality Building Products for over 50 Years Harvey Building Products is a leading manufacturer and distributor of high quality building products. We manufacture a complete line of superior
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
MAJESTIC. OUTDOOR / INDOOR WOOD FIREPLACES Model: ODSR36A OWNERS INSTALLATION & OPERATING INSTRUCTIONS. KEEP THESE INSTRUCTIONS FOR FUTURE REFERANCE.
MAJESTIC OUTDOOR / INDOOR WOOD FIREPLACES Model: ODSR36A OWNERS INSTALLATION & OPERATING INSTRUCTIONS. KEEP THESE INSTRUCTIONS FOR FUTURE REFERANCE. CONTENTS Part 1: Safety Information Part 2: Installation
Miami-Dade Qualified Drainable Blade Louvered Penthouse
Application and Design is a gravity intake or exhaust louvered penthouse. Model incorporates high performance horizontal drainable style blades. Meets the performance requirements established by the Florida
!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035
Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí
MacroFlo Opening Types User Guide <Virtual Environment> 6.0
MacroFlo Opening Types User Guide 6.0 Page 1 of 18 Contents 1. Introduction...4 2. What Are Opening Types?...5 3. MacroFlo Opening Types Manager Interface...5 3.1. Add... 5 3.2. Reference
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
MagTek A. Aluminium Manual Attack Resistant Doors
MagTek A Aluminium Manual Attack Resistant Doors MANUAL ATTACK-RESISTANCE Gunnebo s manual attack resistant doors have been designed to satisfy the ever increasing need to protect people, property and
MODEL HSR-007 Direct Drive Rolling Steel
MODEL HSR-007 Direct Drive Rolling Steel 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: [email protected] Model HSR-007
Guide to Safety Edge Systems
Guide to Safety Edge Systems Tel: 0845 054 5070 [email protected] Guide to Safety Edges All new automatic gate & door systems installed in the UK should comply to BS-EN13241-1 & EN-138491-1 harmonised
SERIES L. Fineline & Broadline. Linear Strip Grilles GRILLES 12
Fineline & Broadline PUBLICATION Strip GRILLES JUNE 0 Features - Fineline or Broadline Appearances. - 6 Different Frame Options. - 0, or 0 Angles. - Single Units or Continuous Runs. - Multiple Fixing Options.
Confort 160. Sliding Systems. Sapa Building System
Confort 160 Sliding Systems Sapa Building System Confort 160 is a high performance thermally insulated sliding window system, with a user-friendly slide action. The system, which has an attractive aesthetic
PHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:
PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV
FIRE RATED GLAZING System Guide
SYSTEM GUIDE Issue date: 05-05-2015 Expiry date: 31-12-2016 System Guide Introduction Pyropanel Developments are specialists in fire rated glazing solutions, and our systems are designed for easy installation
PLASTIC VOLUME CONTROL DAMPERS OVERVIEW TYPE: GGB
OVERVIEW TYPE: GGB All composite construction Rigid extruded upvc aerofoil blade section Integral blade seals for low leakage operation Individual blades driven via reinforced styrene gear wheels in maintenance
STEEL BUILDINGS IN EUROPE. Single-Storey Steel Buildings Part 8: Building Envelope
STEEL BUILDINGS IN EUROPE Single-Storey Steel Buildings Part 8: Building Envelope Single-Storey Steel Buildings Part 8: Building Envelope 2 - ii Part 8: Building Envelope emissions
