INDEX MITSUBISHI HEAVY INDUSTRIES - VRF SERVICE MANUAL MAINTENANCE DATA 2 ERROR CODES 2 PCB INDOOR UNITS 11 PCB OUTDOOR UNITS 19
|
|
|
- Phillip Manning
- 10 years ago
- Views:
Transcription
1 SERVICE MANUAL KX4 2-pipe VRF Systems KXR4 3-pipe VRF Systems
2
3 MITSUBISHI HEAVY INDUSTRIES - VRF SERVICE MANUAL INDEX MAINTENANCE DATA 2 ERROR CODES 2 PCB INDOOR UNITS 11 PCB OUTDOOR UNITS 19 ERROR DISPLAY OUTDOOR UNIT 21 OPERATIAL DATA CHECK WIRED CTROLLER 22 REMOTE CTROL WIRED 39 - SETTING FUNCTIS 40 MAINTENANCE SCHEDULE 41 MAINTENANCE CHECKLIST 42
4 1 MAINTENANCE DATA (1) Before starting troubleshooting (a) Confirmation of the error code on the remote controller (by pressing the inspection switch) and the inspection display and normal display lamps on PCBs (Printed circuit board) of indoor/outldoor units The microcomputer detects errors on electrical components, which include the microcomputer itself, errors on the power supply line and errors (overload, etc.) on the refrigerant circuit and the location of trouble is displayed (with the commbination of error symbols of remote controller, normal (green) and inspection (red) display LED on PCBs of indoor/outdoor units). When any error occurs, check first the inspection display. It will guide you to trouble point and assist you to complete the repair work quickly. Error code of the remote controller is recorded on microcomputer after the trouble has been reset automatically so that, if you press the inspection switch of remote controller, the error code and the number of unit in trouble are displayed for 10sec.. The inspection display lamp on the indoor/outdoor unit PCB keeps flashing (glowing) even after the trouble was reset automatically. Inspection lamp on the indoor unit PCB is turned off if the remote controller is reset. 1) Inspection/normal: List of power display Section Display Section Display Contents of display Remote controller Power supply display Error code LCD LCD At power : Displays always the return air temperature and Center/Remote. At error : Displays E1 ~ E63 or blank depending on the kings of error. Inspection display Red-LED At error : Flash continuously (indicates the occurence of error). Indoor/outdoor unit Normal display Error display Green-LED2 Red-LED1 At power (normal) : Flash continuously. At error : Off or continuous glowing or irregular illumination. At error : Flash 1 ~ 3 times/5 sec for indoor unit depending on the kinds of error, continuous flash, irregular illumination or off. At error : Flash 1 ~ 6 times/10 sec for outdoor unit depending on the kinds of error, continuous flash, irregular illumination or off. Normaly display Green-LED At power (normal) : Flash continuously. At error : Off or continuous glowing or irregular illumination. Invertes Error display Red-LED 1 time flashes: Current cut (power transistor over-current) Short-circuited compressor wiring Trouble on inverter PCB Trouble on power transistor Compressor motor neutral line disconnected. 2 time flashes: Power transistor overheat Fastening of the power transistor to the heat dissipation fins (tighten the screws, apply silicone) is insufficient. Power transistor is defective. 3 time flashes: Compressor rotor lock Compressor breakdown Inverter board breakdown 4 time flashes: Compressor starting is defective. Compressor breakdown Inverter board breakdown Power transistor breakdown Lights up : Transmission error between inverter and outdoor unit Connectors CN11 or CN12 is disconnected or beoken wire between connectors Error on outdoor control PCB Error on inverter PCB - 3 -
5 2) Check Indicator Table Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote controller eroor code, indoor/outdoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp). Remote controller error code LED Green Red LED Green Red Cause Normal Power, T phase wiring is open, power source failure No-indication *3 time flash Remote controller wires X and Y are reversely connected. *For wire breaking at power, the LED is. Remote controller wire is open. (X wire breaking : A beep is produced and no indication is made. Z wire breaking : No beep and no indication) The remote controller wires Y and Z are reversely connected. The remote controller wires are connected to A and B on the terminal block. The indoor/outdoor signal wire are connected in loop form. The indoor unit microcomputer runs away. E1 Stay or Lights continuously Stay or Lights continuously PCB fault *3 time flash Remote control wire breakage (signal) *For wire breaking at power, the LED is. E2 1 time flash No. duplication at indoor unit addressing. More than 49 indoor unit are connected E3 2 time flash 2 time flash power supply (detected only during operation) The corresponding outdoor unit address No. is not found. (Detected only during operation) E5 E6 E7 E9 E10 E11 E12 E16 (1) E28 Note (1) In the case of FDT112, 140 or FDK22~56 type. 2 time flash 2 time flash 2 time flash 2 time flash 1 time flash 1 time flash 1 time flash Irregular illumination Irregular illumination or Lights continuously or Lights continuously 1 time flash 1 time flash power (Detected only during operation) Indoor / outdoor transmission error. Wire A and B swapping after power. Outdoor power unit failure (when the indoor power supply is different from the outdoor one). microcomputer failure heat exchanger thermistor failure return air thermistor failure The float SW operates (with FS only). Drain up kit wiring fault. When multi-unit control by remote controller is performed, the number of units is over (more than 17 units). Two remote controller are provided for one controller is perfirmed. Addresses setting for plural remote controllers Addresses No. combination error or addressing is performed with the following combinations. Outdoor No, 0~47 48, 49 Defect of fan motor. Remote controller thermistor failure Indoor No, 48, 49 0~47
6 Models FDCA224HKXRE4, 280HKXRE4, 335HKXRE4-5 - Remote controller error code E30 E31 E32 E36 E37 E38 E39 E40 E41 E42 E43 E45 E46 E48 E49 E53 E54 E59 E60 E63 LED LED Green Red Green Red 1 time flash 1 time flash Outdoor LED 7-Segment E30 Unmatched indoor/outdoor connection Cause 1 time flash E32 L3-phase wiring is open phase or reversal phose E31 Duplication outdoor unit address No. address setting error. 1 time flash 1 time flash E36-1 E37-1 Discharge temperature (Tho-D1) abnormality. heat exchanger thermistor (Tho-R1) failure 2 time flash E37-2 heat exchanger thermistor (Tho-R2) failure 3 time flash E37-3 heat exchanger thermistor (Tho-R3) failure 4 time flash E37-4 heat exchanger thermistor (Tho-R4) failure 5 time flash E37-5 heat exchanger thermistor (Tho-SC) failure 6 time flash E37-6 heat exchanger thermistor (Tho-H) failure 1 time flash 1 time flash 1 time flash E38 E39-1 E40 Outdoor air temperature thermistor (Tho-A) failure Discharge temperature thermistor (Tho-D1) failure High pressure (63H1-1) error 1 time flash 1 time flash 1 time flash 1 time flash E41-1 E42-1 E43 E45-1 Power transistor (CM1) overheat Abnormal current cut of compressor (CM1) The number of connectable units is exceeded. Transmission error between inverter and outdoor unit control PCB (CM1) 1 time flash E48-1 Abnormalities in an outdoor fan motor FM01 2 time flash E48-2 Abnormalities in an outdoor fan motor FM02 1 time flash E49 Low pressure error (PSL) 1 time flash E53 Suction pipe temperature thermistor (Tho-S) failure 1 time flash E54-1 Low pressure sensor (PSL) disconnection/output error 2 time flash E54-2 High pressure sensor (PSH) disconnection/output error 1 time flash E59-1 Compressor startup error (CM1) 1 time flash E60-1 Compressor loader position detection error (CM1) 1 time flash E63 Emergency stop of indoor unit Automatic address setting and remote controller address setting coexists in the same network.
7 Models FDCA335HKXRE4-K, 400HKXRE4, 450HKXRE4 Remote controller error code E30 E31 E32 E36 E37 LED LED Green Red Green Red 1 time flash 1 time flash Outdoor LED 7-Segment E30 Unmatched indoor/outdoor connection Cause 1 time flash E32 L3-phase wiring is open phase or reversal phose E31 Duplication outdoor unit address No. address setting error. 1 time flash E36-1 Discharge temperature (Tho-D1) abnormality. 2 time flash E36-2 Discharge temperature (Tho-D2) abnormality. 1 time flash E37-1 heat exchanger thermistor (Tho-R1) failure 2 time flash E37-2 heat exchanger thermistor (Tho-R2) failure 3 time flash E37-3 heat exchanger thermistor (Tho-R3) failure 4 time flash E37-4 heat exchanger thermistor (Tho-R4) failure 5 time flash E37-5 heat exchanger thermistor (Tho-SC) failure 6 time flash E37-6 heat exchanger thermistor (Tho-H) failure E38 E39 E40 E41 E42 E43 E45 E46 E48 E49 E51 E53 E54 E59 E60 E61 E63 1 time flash E38 Outdoor air temperature thermistor (Tho-A) failure 1 time flash E39-1 Discharge temperature thermistor (Tho-D1) failure 2 time flash E39-2 Discharge temperature thermistor (Tho-D2) failure 1 time flash E40 High pressure (63H1-1, 2) error 1 time flash E41-1 Power transistor (CM1) overheat 2 time flash E41-2 Power transistor (CM2) overheat 1 time flash E42-1 Abnormal current cut of compressor (CM1) 2 time flash E42-2 Abnormal current cut of compressor (CM2) 1 time flash E43 The number of connectable units is exceeded. 1 time flash E45-1 Transmission error between inverter and outdoor unit control PCB (CM1) 2 time flash E45-2 Transmission error between inverter and outdoor unit control PCB (CM2) 1 time flash E48-1 Abnormalities in an outdoor fan motor FM01 2 time flash E48-2 Abnormalities in an outdoor fan motor FM02 1 time flash E49 Low pressure error (PSL) 1 time flash E51-1 Power transistor overheating (CM1) (15 minute continuation) 2 time flash E51-2 Power transistor overheating (CM2) (15 minute continuation) 1 time flash E53 Suction pipe temperature thermistor (Tho-S) failure 1 time flash E54-1 Low pressure sensor (PSL) disconnection/output error 2 time flash E54-2 High pressure sensor (PSH) disconnection/output error 1 time flash E59-1 Compressor startup error (CM1) 2 time flash E59-2 Compressor startup error (CM2) 1 time flash E60-1 Compressor loader position detection error (CM1) 2 time flash E60-2 Compressor loader position detection error (CM2) 1 time flash E61 Communication error between outdoor unit master unit and slave units. 1 time flash E63 Emergency stop of indoor unit Automatic address setting and remote controller address setting coexists in the same network.
8 3) Display sequence of error, inspection display lamp a) One kind error Display corresponding to the error is shown. b) More than one errors. Section Error code of remote controller Inspection LED (red) of indoor unit PCB Inspection LED (red) of outdoor unit PCB Display section Displays the error of higher priority (When plural errors are persisting) Displays the present errors. (When a new error has occurred after the former error was reset.) c) Timing of error detection side. Error detail Transmission error of remote controller indoor unit CPU is out of control Transmission error between indoor/outdoor units Broken wire of heat exchanger thermistor Broken wire of indoor unit return air thermistor Drain error (float switch motion) Error detail Discharge temperature abnormality Broken wire of heat exchanger thermister Broken wire of outdoor temperature thermistor Broken wire of discharge thermistor High pressure cut Power transistor overheat Current cut side. Excessive number of indoor and outdoor units Transmission error between inverter and outdoor unit PCB Broken wire of low pressures sensor Broken wire of high pressures sensor Error code Error code Timing of error detection When the transmission error continuously for 2 min. Resetting was performed at the rate of 1 time per second. An abnormal stop occured 32-sec time flash. A check was made once every 20 second. An abnormal stop occured 7 time running. After a compressor command, this failure was detected for 5 second in the period of 2 minutes to 2 minutes and 20 seconds. This failure was detected continuously for 5 seconds. At all times from 31 seconds after power. Timing of error detection A stop occurs when this abnormality occurs for 2 seconds running at 130 C. After a stop for 3 minutes, an recovery is automatically made. An abnormal stop occurs when this abnormality occurs 2 times for 60 minutes. (The abnormal state is held for 45 minutes.) This failure is detected when it occurs for 5 seconds running in the period of 2 minutes to 2 minutes and 20 seconds with the compressor. An abnormal stop occurs when this failure occurs 3 times for 40 minutes. This failure is detected when it occurs for 5 seconds running in the period of 10 minutes to 10 minutes and 20 seconds with the compressor. An abnormal stop occurs when this failure occurs 3 times for 40 minutes. An abnormal stop occurs when this abnormality occurs 5 times for 60 minutes. Stops at 110ºC or higher, recovers automatically at 90 C or lower, abnormal stop if this occurs 5 times in 60 minutes. An abnormal stop occurs when this abnormality occurs 4 times for 15 minutes. This error is detected when the number of connectable units is set over the specified value at remote control addressing. With a delay of 3 minutes, a recovery is automatically made. An abnormal stop occurs when this errors occurs 4 times for 15 minutes. This failure is detected when it occurs for 5 seconds running in the period of 2 minutes to 2 minutes and 20 seconds with the compressor. An abnormal stop occurs when this failure occurs 3 times for 40 minutes
9 d) Recording and reset of error Error display Memory Reset Error code Saves in memory the mode (1) of higher priority inspection lamp (red) inspection lamp (red) Cannot save in memory Saves in memory the mode (1) of higher priority Stop the unit operation by pressing the / switch of remote controller. Operation can be started again if the error has been reset. (2) Notes (1) Priority is in the order of E1 >... > E10 >... > 63. Notes (2) Reset is disabled for 45min. at the error of outdoor unit or compressor overcurrent or the discharge gas temperature error. e) Reset of error code in memory (when the error has been reset.) : Press the Timer switch and the Stop switch while the Inspection switch of wired remote controller is held down or detach the power supply connector (CnW2) of indoor unit PCB and connect again or turn the power. : Detach the power supply connector (CNA2) of outdoor unit PCB and connect again or turn the power supply or turn on and off the SW3-1. 4) Indications with 7-segement indicator Refer to page 166, 202. (2) Procedures of trouble diagnosis When any error occurs, inspect in following sequence. Detailed explanation on each step is given later in this text. Error Power supply check (indoor/outdoor unit) Check of inspection display [Indoor/outdoor unit PCB, remote controller or Indication board] or repair of defective parts Test run/adjustment Check of unit controller Check of inspection display [Indoor/outdoor unit PCB, remote controller or Indication board] - 8 -
10 (a) Diagnosis by the power supply reset When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc. Check at the indoor unit side. Error Is any errror code display? Check the error code displayed / switch Does the error code disappear? Microcomputer out of control Turn off the wiring breaker (power supply) and back on again 1min.later. (Power supply reset) / switch Does start operation with display of cooling degree: Hi, thermostat: 23 C? Power supply line error See page 321 Does the error repeat Cause is acccidental (noise, etc.) and the unit is normal. Check of error code Errors due to external noise, etc. Error code may be displayed or the error may not be displayed normally even if the controller is normal because of external noise source(1) or joined or parallel arrangement of power cables and singal wires. It is because the wire of remote controller, wired remote controller signal wires for multiple units or the network signal wires may be influenced by external noises whitch are judged as signals by the microcomputer whitch reacts mistakenly. When there is any noise source, it is necessary to the shield wire for the remote controller and signal wires. Note (1) High frequency medical machine, rectifier motor application device, thyristor, broadcast transmission tower, power transmission line, power line of electric train, automatic door motor, elevator (voltage drop), wireless telephone, high voltage power distribution line, computer, personal computer and their cables. These do not necessarily always cause problems but they can be a source of electrical noise
11 (2) Reference Effect of noise When noises inturude into remote controller. Abnormal or irregular display such as the flashing of irrelevant display (lamp) (for example, LEDs of cooling and heating illuminated simultaneously or the like) is observed even if the remote controller is not operated or the remote or the remote controller and, as the result, the operation of units may be disabled or similar abnormal phenomenons are observed. When noises intruded into the microcomputer of printed circuit board; State of operation becomes abnormal such as the units perform irregular operation while the remote controller is not operated, the operation cannot be stopped with the remote controller, etc. Electro magnetic noise prevention (example) Cover the entire surface of control box or the inside of unit cover with the cover foil or cover the entire unit with a wire net. Interisified shielding of control section Signal wire Insert in a steel pipe shield. Use the shield or twist pair wires Remote controller wire Put in a steel case Remote controller (indoor unit) l1 Outdoor unit Make a positive ground Separate from cutting machine as far as possible. This is very effective because the effect of noise is inverse proportion to 1.5 times of distance. Beware of noises transmitted via air. (indoor unit) l2 Shut off electrically the noise source or put it in a shield room. Cutting machine welder High frequency Power cable Distribution board Unless it has a sufficient current capacity, mini split current drops momentarily at the start/stop of cutting machine. A void supply from the same distribution board to prevent troubles by the power source propagation. Install the line filter at the power supply of cuting machine of mini split (Positive grounding is necessary.) (b) Error diagnosis procedures at the indoor unit side To diagnose the error, measure the voltage (AC,DC), resistance, etc. at each connector around the printed circuit board of indoor unit PCB on the inspection display or the operation state of unit (no operation of comressor or blower, no switching of 4-way valve, etc.). If any defective parts are discovered, replace with the assembly of parts as shown below. (i) Unit of replacement parts releated to indoor unit printed circuit board ( Electric components on and around the microcomputer) printed circuit board, thermistor (Return air, heat exchanger), remote controller switch, limit switch, transformer, fuse Note (1) Judges the troubles on the parts of driving power circuit or cooling cycle with the ordinary check method
12 (ii) Parts layout on the indoor unit printed circuit board The control board in the following figure shows for the FDT type. Power source PCB (CNW8) Address switch (SW1~4) For power source PCB (only 112~160) (CNW9) Fan motor (90~160) Connector (CNT) C CNT CNM2 CNW8 C13 IC9 CNY PC5 L1 C58 C3 IC2 CNI C12 CNW9 C2 C1 IC3 PC3 CNM3 52X6 52X1 52X2 52X3 SW1 C4 X1 SW2 SW3 CNQ SW4 Fan motor (22~80) IC12 J8 J10 J11 J12 CNG C5 SW10 CNH CNN1 CNN2 CNF CNR 52X4 SW X8-2 SW5 CNE J1 J2 J3 J4 SW7 C41 J1 J2 J3 J SW9 KN1 TVS1 IC8 IC11 CNK1 CNV Model select switch (SW6) F2 F1 CNK1 J1~J4 (SW7) DIP switch (SW9) 52X7 Z2D Z3D Z4D Z5D L2 C23 TM1 52X8-1 CNB C11 CNW7 PC2 PC1 D2 R17 IC7 R16 For power source PCB (CNW7) ZD1 CNJ CNZ CND CNA Remote controller Louver motor Heat exchanger thermistor Return air thermistor (Thi-R1 Thi-A) Heat exchanger thermistor (Thi-R2) J10~J11 (SW10) DIP switch (SW5) Function of jumper wires Name Function With Filter sign: Valid J1 (SW7-1) None (1) Filter sign: Invalid With Normal operation operable J2 (SW7-2) None (1) Operation permission prohibited With Heating thermostat : Intermittenet operation With None Heating thermostat : Lo operation J3 (SW7-3) J4 (SW7-4) (1) Heating thermostat : Stop None (1) With None (1) Heating thermostat : - With Remote controller air flow: 3 speed With None Remote controller air flow: 1 speed J10 (SW10-2) J11 (SW10-3) (1) Remote controller air flow: 2 speed None (1) With None (1) Remote controller air flow: - Note (1) None means that jumper wire is not provided on the PCB or the connection is cut procedure of indoor unit micrcomputer printed circuit board Microcomputer printed circuit board can replaced with following procedure. 1) Confirm the parts numbers. (Refer to the following parts layout drawing for the location of parts number.) Parts No. PJA505A137ZG PJA505A137ZF PJA505A139ZH FDTA28~90 FDTA112, 140 FDE Model select switch (SW6) Model Switch SW6-1 SW6-2 SW6-3 SW6-4 Model Parts No. PJA505A138ZC PJA505A138ZD PHA505A022ZB Function of DIP switches (SW5, 9) Switch Function Test run of condensate pump motor SW5-1 Normal Input Reverse Invalid SW5-3 signal Run stop Emergency stop signal: Invalid SW5-4 Emergency stop signal: Valid Louver stop: Louver Range SW9-3 Louver stop: Normal Fan control: UH, H, M SW9-4 Fan control: H, M, L Note (1) All under load condition. Model FDQM, FDUM, FDTW, FDR, FDFL, FDFU, FDUR FDTQ, FDTS, FDKA71 FDKA22~56 (iii) Check method when the error code is displayed Remote controller or Indication board: Inspection LED, error code PCB: ( inspcetion display), ( CPU. normal display ) PCB: ( inspcetion display), ( CPU. normal display ) (iv) Check procedure depending on indication lamps (For the indoor unit) The next page error diagnosis is applicable to cases where only 1 unit is installed in a network unless stated otherwise but the check method is same even if there are multiple units on the network. Except the network occupation state due to out of control indoor unit CPU, the error display indicates the state of respective units. Check each unit specified by the error display as explained on next page
13 1 No display LCD display : No display [Polarity determination trouble] When the LCD display (Center/Remote, temperature display, etc.) of remote controller flashes, it means the polarity on the unit is not yet determined. Polarity determination is completed within a few seconds after the power on. If it is not completed in time, CPU out of cotnrol, etc. is suspected. Remote controller LCD display: WAIT Inside control board LED: Flashes continuously. Power supply reset Notes (1) When CPU of one unit goes out of control, it occuping the transmission section of the network, so the transmission of other units are not done and the polarity of the whole network will not be determined. (2) The unit which has its indoor and green LED keeps flashing (or no lighting) is the one with a defective indoor unit PCB. (3) If it becomes normal after replacing the PCB. it can be considered that the PCB. is defective (defective network transmission circuit). Is it more than 10 sec. after power on? Is the remote controller LCD nomal (1) (Center or Remote only display) If yes, it is a malfunction by electrical noise 1 unit only on network Defective indoor unit PCB (3) Multiple units on network Defective indoor unit PCB on some units (2) (3)
14 2 No display LCD display : No display [Power supply line error] Red LED Green LED Stays Stays Power supply checked between L1 ~ N or L, N No power supply, wiring error of power line Repair Indoor/outdoor unit transfomer CNW2 (indoor). CNA2 (outdoor). Is AC 15V checked between (red)(red) and AC 10V between(red) (red) or AC16.5V between (blue) (blue)? Blown fuse (indoor unit:3.15a, outdoor unit:3.15a) Defective transfomer Broken power cables of inside or outside of unit Repair Power supply reset Unit is normal (Malfunction by noisse) Is it normalized Defective remote controller PCB 3 time flash Flash of green LED means CPU is normal. Remote controller wiring connect check (Red White Black) OK Correction (1) Approximately 10 ~ 11 V between X and Z. Power supply reset Normal? Remote controller wire disconnection? Remote controller defective Note (1) Z is GND. Remote controller wire is removed Maltifunction by accidental noise Remeasure between X~Z. 10~11V. indoor unit PCB Remote controller wire short circuit? Remote controller defective 3 [Communication error between remote controller~] Indoor and outdoor unit (1) Note (1) With the separate power supplies for indoor/outdoor units, the outdoor unit green LED may flash in some cases. Is the remote controller covering multiple units? Is the power on all indoor units? Defectve indoor unit PCB Power supply reset Power supply Is it normalized Unit is normal. (Malfunction by accidental noise) Defectve indoor unit PCB
15 *3 times flash * Lamp if remote controller wire is broken at power. Voltage between X and Z approximately 10~11 V? remote controller Remote controller wire is removed Voltage fluctuates between 5~11 V between Y and Z. Power supply Is the resistance between Y~Z on the remote controller approximately 10kΩ? remote controller Voltage fluctuates between 5~10 V between Y and Z indoors. Voltage fluctuates between 5~10 V between CNB Y and Z. Remote controller wire disconnection Terminal block CNB harness is defective. Resistance is approximately 10kΩ between indoor Y~Z. Remote controller wire short circuit indoor unit resets every 4 minutes. Power supply reset Power supply reset After the green LED lights up once, it begins flashing again continuously. The louver moves once in the close direction. Normal? remote controller Noise? Normal? Noise indoor unit PCB or Lights continuously or Lights continuously Power supply reset Is it normalized? Unit is normal. (Runaway of indoor unit CPU due to noise, etc. Transient trouble) Defective indoor unit PCB Replace. (Defective CPU)
16 4 [Duplicated indoor unit No. or More than 49 indoor unit are connected.] 1 time flash Is the indoor unit No. duplicated or More than 49 indoor unit are connected? Defective indoor unit PCB (defective unit number circuit) (2) Correction of unit No. setting (1) Notes (1) When correcting the unit number, check again the pairing of indoor/ outdoor units (same Number assigned to coupled units) is correct. (2) If it is normalized by changing PCB, judge the unit number input circuit is defective. 5 [Defective indoor unit heat exchanger thermistor] 1 time flash Return air thermistor (Th1-A) heat exchanger thermistor (Th1-R1, R2, R3) Resistance temperature characteristics Defective indoor unit PCB (Defective indoor unit heat exchanger themistor input circuit) 15 Is the indoor unit heat exchanger thermistor connector connection OK? Correction Are characteristics of indoor unit heat exchanger thermistor OK or is there any broken wire? Defective indoor unit heat exchanger themistor Display condition If a temperature of 40ºC or lower is detected by the thermistor continuously for 5 seconds. Resistance (kω) kΩ at 25 C Temperature ( C) Note (1) 22.5 kω at -6 C 6 [Detective Return air thermistor] 1 time flash Is the return air thermistor connector connection OK? Is the return air thermistor characteristics OK or is there a broken wire? Defective indoor unit PCB (Defective return air thermistor input circuit) Correction Defective return air thermistor Note (1) Characteristics as per the above graph. Display Condition If a temperature of 20ºC or lower is detected by the thermistor continuously for 5 seconds
17 7 [Drain trouble] 1 time flash Abnormal data check in remote controller Is there any overflow? DC 12 V at both terminals of CNI? indoor unit PCB Float switch check Drain motor from remote controller. Drain motor operation AC 220/240V at both terminals of CNR? indoor unit PCB Is drain piping unclogged? Is the slop OK? Correction Drain motor check of motor wiring Drain motor check 8 [Control of 1 remote controller VS multiple units Excessive number of units (more than 17 units) ] Are more than 17 units connected to a remote controller? Defective indoor unit PCB Reduce to 16 units or less 9 [Addresses setting for plural remote controllers] Aren, t plural indoor units connected to one remote controller and isn, t it in the remote controller address condition? The remote controller is defective. Connect each remote controller separately. or use the remote controller with manual address setting
18 10 [Address No. combination eroor or addressing is preformed with the following combinations.] 1 time flash Are unit number set for see following? (1) Unit number correction Defective indoor unit PCB (defective unit number input circuit) Note (1) address No. 00 ~ 47 48, 49 address No. 48, ~ [ fan motor abnormal] 1 time flash S Only case of FDT112, 114 type Abnormal data check with remote controller After check reset, fan runs on weak. Fan? CNM1 (Red White) DC280V? White is GND. indoor unit PCB Was it reproduced? Check the circumstances. CNW9 1 ~ 3 DC15V? (1) DC 15V between CNW9-3 and CNM2 4? 3 is GND. Note (1) CNW9-3 is GND. Secondary side of transformer (red-red) 15V or more transformer indoor unit PCB When the motor is turning, does the voltage at CNM2 2 fluctuate between 0 ~ 15 V? indoor unit PCB Does the fan motor turn smoothly by hand? Detective fan motor (2) Is the voltage at CNM2 3 DC 1V or higher? Note (2) CNW9-3 is GND. indoor unit PCB Display conditions If an indoor unit fan motor s speed is detected to be less than 200 rpm continuously for 30 seconds, the fan motor stops for 2 seconds. After 2 seconds, it starts again, but this occurs 4 times within a period of 1 hour
19 S Only case of FDK22~56 type Abnormal data check with remote controller After check reset, fan runs on weak. Fan? Is the 3 (black) is GND. voltage DC 280 between CNM 1 and 3 (red black)? 3 (black) is GND. Is the voltage DC 15 V between CNM 4 and 3 (white black)? Does the fan motor turn smoothly by hand? Replace the indoor unit s board. Is the voltage on the transformer secondary side (brown brown) AC 17 V or higher? Replace the transformer. Detective fan motor Check the circumstances. Was it reproduced? (1) When the motor is turning, does the voltage at CNM 6 (blue) fluctuate between 0 ~ 15 V? Note (1) CNM 3 (black) is GND. indoor unit PCB Is the (2) voltage at CNM 5 (yellow) DC 1V or higher? Note (2) CNM 3 (black) is GND. indoor unit PCB Display conditions If an indoor unit fan motor s speed is detected to be less than 200 rpm continuously for 30 seconds, the fan motor stops for 2 seconds. After 2 seconds, it starts again, but this occurs 4 times within a period of 1 hour. 12 [Directive remote controller thermistor.] Is the remote controller thermistor connector connection OK? Are characteristics of remote controller thermistor OK or is there any broken wire? Detectivie remote controller PCB (Detective remote thermistor input circuit) Correction Detective remote controller thermistor Resistance-temperature characteristic of remote controller thermister Temperrature( C) Resistance value (kω) Temperrature( C) Resistance value (kω) Temperrature( C) Resistance value (kω) Temperrature( C) Resistance value (kω)
20 (c) Error diagnosis procedures at the outdoor unit side At the error diagnosis related to the outdoor unit, check at first the error code of remote controller and the illumination patterns of norma 1 and inspection display lamps in the same manner as the case of indoor unit. Then estimate the outline, the cause and the location of error based on the pattern and proceed to the inspcetion and repair. Since the self diagnosis function by means of the microcomputers of indoor/outdoor units provide the judgement of error of microcomputers them selves irregularity power supply line, overload, etc. caused by the installation space, inadequate volume of refrigerant etc., the location and cause of trouble will be discovered without difficulty. In addition, the display lamps error code of indoor/outdoor unit is kept flashing, (except when the power supply is iterrupted) after the irregularity is automatically recovered to give irregularity information to the service presonnel. If any mode of higher priority than the error retained in memory occurs after the reset of error, it is switched to that mode and saved in the memory. (i) parts assembly related to the outdoor unit PCB PCB, outdoor unit inverter PCB, power transistor module, diode module, capacitor, reactor, noise filter, thermistor, (heat exchanger, discharge pipe, outdoor temperature etc.), fuse, transformer, etc. (ii) Parts layout on the outdoor unit PCB 7-segement indicator LED3 (green) LED2 (green) PCB power supply connector (Secondary side) number address setting switch (SW:Order or 10) number address setting switch (SW:Order or 1) SW5 SW3 SW4 CNP2 CNF1 CND CNP1 CNC1 CNU1 CNJ CNF2 CNY CNI3 CNZ1 CNH CNV2 CNC2 CNB4 CNB3CNB2 CNB1 7SEG1 7SEG2 SW9 SW8 J13 J15 SW7 J14 SW1 SW2 J12 SW5 CNE CNG4 CNG3 CNG2 CNXG1CNS2 CNS1 CNI1 CNL2 CNX2 CNX1 CNL1 SW10 LED3 LED2 LED1 SW3 SW4 CNA2 CNQ3 CNW1 CNQ5 CNW2 CNQ4 CNQ2 CNQ1 CNK CNA3 CNA1 CNM1 CNM2 X01 X02 X03 X04 X05 X06 X07 X08 X09 X10 X11 X15 X16 X17 X18 X19 X20 X21 X22 X12 X13 X14 X23 CNDC2 CNDC1 CNFM3 CNFM3 CNFM1 CNN4 CNN3 CNN2 Function of DIP switch Name SW3-1 SW3-2 SW3-3 SW3-7 SW3-8 SW5-1 SW5-2 SW5-3 CNN10 CNN9 CNR2 CNR1 Function Inspection LED reset Normal Backup operation-with Backup operation-none Renewal Normal Forced cooling/heating Normal Test mode Normal Test run operatopm Normal Test run operation Cooling Test run operation - Heating Pump down Normal LED1 (red) SW4-1 SW4-2 SW4-3 SW4-4 CNN1 CNN8 CNN7 CNN6 CNN1 CNN5 PCB power supply connector (Primary side) Models FDCA224HKXRE4 FDCA280HKXRE4 FDCA335HKXRE4 FDCA335HKXRE4-K FDCA400HKXRE4 FDCA450HKXRE4 Function of jumper wire Name Function With External input level J13 None (1) External input pulse With Defrosting temp. - Strengthening J14 None (1) Defrosting temp. - Normal With Defrosting time - Cold weather region J15 None (1) Defrosting time - Normal Note (1) "None" means that jumper wire is not provided on the PCB or the connection is cut. Name SW4-6 SW4-5 _ SW4-7 Function Demando change (Compressor capabilicy) 0% Demando change (Compressor capabilicy) 40% Demando change (Compressor capabilicy) 60% Demando change (Compressor capabilicy) 80% Address setup of master/slave unit-slave Address setup of master/slave unit-master
21 procedure of outdoor unit control printed circuit board. Micromputer printed circuit board can replaced with following procedure. 1) Confirm the parts numbers. (Refer to the following parts layout drawing for the location of parts number.) Parts No. PCB505A042RC PCB505A042RF Model FDCA224HKXRE4, 280HKXRE4, 335HKXRE4 FDCA335HKXRE4-K, 400HKXRE4, FDCA450HKXRE4 (iii) Parts layout on the outdoor unit inverter PCB procedure of outdoor unit inverter printed circuit board Inverter printed circuit board can replaced with following procedure. 1) Confirm the parts numbers. (Refer to the following parts layout drawing for the location of parts number.) Parts No. PCB505A044ZA PCB505A044ZB Model FDCA224HKXRE4, 280HKXRE4, 335HKXRE4 FDCA335HKXRE4-K, 400HKXRE4, 450HKXRE4 Model FDCA224HKXRE4, 280HKXRE4, 335HKXRE4 SW1 SW2 LED1 LED2 SW1,2 (It is besides SW2-1 () entirely) TB1 Model FDCA335HKXRE4-K, 400HKXRE4, 450HKXRE4 SW1,2 (It is besides SW2-1 () entirely)
22 Check points of inverter outdoor unit Check with power at the points marked with. This figure applies to the FDCA224HKXRE4, 280HKXRE4, 335HKXRE4. The FDCA335HKXRE4-K, 400HKXRE4 and 450HKXRE4 have 2 inverter related systems. Check of power supply Check the power supply on L1, L2 and L3 of terminal block TB. (It is normal if AC 380/415V is detected.) L1 L2 L3 N Signal wire TB1 RD WH BL BK Fuse Check: There should be continuity. F (3.15A) 52C1 Noise filter check: There should be continuity, and there should be no short circuit between phases. Ri Si Ti Noise filiter Resistance R1-1 or R2-1 check: Resistance is measured (15Ω) Ro So To Diode module check: There should be no short circuit, open circuit or destruction. AC1 AC2 R5 R1-1 R Diode module AC3-6 G K DC reactor continuity check: 30 mω or higher but less than 100 mω Capacitor check: Check for abnormality in appearance such as damage, swell, etc. RD DC380~415V BK CM Thermistor resistance (kω)[t 80 C] > = Power transistor thermistor temperature, resistance characteristics check T< 80 C Temperature [T] ( C) T >80 C (kω)[t 80 C] Thermistor resistance > = TB2 Transformer 1 Control P.C.B CNDCW1 FMO1 FMO2 CNDCW2 BK RD A B CNX1 CNA1 CNA2 CNDC1 CNW1 LED1 LED2 LED3 Red Green Green CNDC2 RD CNM1 CNI3 CNZ1 CNT1 CNT2 CNP1 BL CNI CNI2 CNR LED2 LED1 Green Red LED2 (Green) It is normal if it flashes at each 0.5-second. P2 P3 N2 Inverter P.C.B Power transistor thermistor RD WH BL P N U V W Power transistor module F4 (250V 3A) Power transistor module check: Is there any short circuit, open circuit or damage? (See page 345 for the check procedure.) Fuse Check: There should be continuity. If defective, replace the inverter board. C1 C2 EEV P.C.B CNI3 CNZ1 CNT1 CNT2 CNEEV1 CNEEV2 CNEEV3 RD BR BL OR EEV H1 Y WH RD BR BL OR EEV H2 Y WH RD BR BL OR EEV SC Y WH Communication cheched at the CN11 will show the following values. Connecter Voltage 1 12V 2 Swings between 8~12 V CNI 3 (analog tester) 4 Swings between 4 ~ 5 V (analog tester) LED2 (Green) check: If it flashes, the microcomputer operates normaly. If it is off, Check LED2 of the inverter board and the CNI1 connector. The control board s power supply is supplied from the inverter board. Note (1) The operating frequency, etc. is displayed by the 7-segment display in accordance with the setting of SW8, 9. (See page 166, 202) LED1 (Red) Check 1 time flashes: Current cut (power transistor over-current) Short-circuited compressor wiring Trouble on inverter PCB Trouble on power transistor Compressor motor neutral line disconnected. 2 time flashes: Power transistor overheat Fastening of the power transistor to the heat dissipation fins (tighten the screws, apply silicone) is insufficient. Power transistor is defective. 3 time flashes: 4 time flashes: Lights up: Compressor rotor lock Compressor breakdown Inverter board breakdown Compressor starting is defective. Compressor breakdown Inverter board breakdown Power transistor breakdown Transmission error between inverter and outdoor unit Connectors CN11 or CN12 is disconnected or broken wire between connectors Error on outdoor control PCB Error on inverter PCB
23 (iv) Check procedure depending on indication lamps (For the outdoor unit) 1 [Error on the outdoor unit signal line] (Detected during operation only) 2 time flash Power supply check between L1 ~ N or terminal block Is there AC 10V checked between CNA2 (red) ~ (red) and AC 16.5V between (blue) ~(blue) of outdoor unit transfomer? Blown fuse (3.15A) Defective transformer Replcement Briken power supply wire in the unit Repair Power not supplied. Power supply wiring error Repair. Power supply reset Unit is normal Is it Nomalized? Defective outdoor unit PCB Is the paining of Indoor/outdoor units OK? Is the connection of network signal wires good? With power, disconnect the network signal line and measure the resistance across terminals A and B. (1) Change of unit number setting Note (1) No outdoor unit corresponding to the indoor unit. Repair the door connection, broken wire of network signal wires. Is the resistance approximately 9.1KΩ? Replace the outdoor PCB. Super-lynk protection fuse is blown Is normal status restored after recovery? Is the resistance approximately 9.1KΩ? Change the connector connection to the spare circuit Normal [Error on the outdoor unit signal line] (Detection at the power on) or Lights continuously Power supply reset Its it normalized? Unit is normal. (Malfunction by noise) Irregular illumination Defective outdoor unit PCB (Defective network communication circuit)
24 2 [ signal line error, power supply error] 2 time flash (1) Did turn off the power of outdoor unit during operatioon? Power supply Blown fuse? Broken or loose wire at L1, L2 or N Phase? Was not there the power failure? Note (1) This case is limited to the separate power supplies to indoor/outdoor units. (Combination of (indoor unit) red LED 2 time flash and (outdoor unit) green LED stays off means that the power supply to the outdoor unit has been interrupted during operation.) or Irregular illumination Power supply reset Is it normalized Malfunction due to noise, etc. (Out of control CPU of outdoor unit due to noise during power on) Defective outdoor unit PCB (Defective network communication circuit) (1) Signal wire poor connection at outdoor unit? Repair (2) Signal wire poor contact between indoor/outdoor unit? Repair Power supply reset Is it normalized Unit is normal. (Malfunction by accidental noise) Notes (1) Check for poor connection (looseness, misconnection) at outdoor unit terminal block and droken signal wires between outdoor units. (2) Check the poor connection or broken signal wires between indoor/outdoor units. Defective outdoor unit PCB (Defective network communication circuit)
25 3 [Connection error indoor and outdoor unit] 7-segment display : 1 time flash Connection of indoor and outdoor unit OK? Repair Defective outdoor unit PCB 4 7-segment display : [Duplicated unit No. of outdoor units] 1 time flash Is the unit No. duplicated on outdoor units? Correction Defective outdoor unit PCB (Defective unit No. read circuit) 5 [Antiphase on power supply or open 52C L3 phase (primary side) on power supply] 7-segment display : 1 time flash Is there antiphase on power supply? Correction Note (1) Wrong wire connection of the antiphase detection circuit is suspected occured during replacement of the outdoor unit PCB. work should be performed carefully. (1) Is L3 phase open at primary side? Correction Is antiphase detection circuit wired properly? Defective outdoor unit PCB (Defective antiphase detection circuit) Replace Correction
26 6 [Discharge temperature error] 7-segment display : 1 time flash (1) Note (1): Single flashing ofoutdoor unit LED indicates Tho-D1 and double flashing indicates Tho-D2. Is the discharge pipe thermistror characteristics normal? Discharge pipe thermistor replacement Is the unit normalized Discharge pipe temperature error? (At cooling/heating operation) Discharge pipe temperature normal? Is the abnormal temperature detection (actual measurement) correct? Defective outdoor unit PCB Check the unit side. Insufficient refrigerant Charge the refrigerant (measure) Is it the oveload operation? Check the unit side. Is the filter clogged? Is the heat exchanger dirty or clogged? Is the installation space of indoor/outdoor unit adequate? Is there any short circuit air flow for indoor/outdoor units? If the discharge pipe temperature (Tho-D1, 2) exceeds the set value the capacity of the compressor are controlled to restrict the rise in the discharge pipe temperature. Compressor control Retention Reset 110 C 120 C Discharge pipe temp. Compressor capacity is reduced at 5 seconds Display conditions If the discharge pipe temperature becomes 130 C or higher for 2 seconds, the compressor stops. If it drops to 90 C or lower, the compressor restarts, but, if this operation occurs 2 times within 60 minutes. Abnormal temperature detection Error stop Operable 90 C 130 C Discharge pipe temp. Thermistor resistance (kω)[t < 80 C] Temperature-resistance characteristics of discharge pipe thermistor (ThO-D1, 2) T< 80 C T> 80 C Temperature [T] ( C) Thermistor resistance (kω)[t > 80 C]
27 9 [Defective outdoor unit heat exchanger and sub-cooling coil thermistor] 7-segment display : 1 time flash (1) Note (1) Tho-R1 flashes 1 time, Tho-R2 flashes 2 times, Tho-R3 flashes 3 times, Tho-R4 flashes 4 times, Tho-SC flashes 5 times, Tho-H flashes 6 times. Is the outdoor unit heat exchanger and sub-cooling coil themistor connector OK? Are the outdoor unit heat exchanger and sub-cooling coil themistor characteristics OK, is there any broken wire? Defective outdoor unit PCB (Defective outdoor unit heat exchanger and sub-cooling coil themistor input circuit) heat exchanger themistor (ThO-R1~R4), sub-cooling coil (ThO-SC, H) Resistance temperature characteristics Repair Defective outdoor unit heat exchanger and sub-cooling coil thermistor 15 Display conditions If the temperature sensed by the thermistor is 50 C or lower continuously for 5 seconds between 2 minutes and 2 minutes 20 seconds after the compressor goes, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected 3 times in 40 minutes. Resistance(kΩ) kΩ at 25 C Temperature ( C) 10 [Defective outdoor temperature thermistor] 7-segment display : 1 time flash Is the outdoor air temperature thermistor connector connection OK? Repair Is the outdoor temperature thermistor characteristics OK, is there no broken wire? Defective outdoor temperature thermistor 400 Defective outdoor unit PCB (Defective outdoor temperature thermistor input circuit) Temperature-resistance characteristics of outdoor temperature thermistor (ThO-A) 40 Display Conditions If the temperature detected by the thermistor is 30 C or lower continuously for 5 seconds between 2 minutes and 2 minutes 20 seconds after the compressor goes, the compressor stops. After a 3 minute delay, the compressor restarts. If this condition is detected 3 times within 40 minutes. Thermistor resistance (kω)[t 0 C] T 0 C T 0 C Temperature [T]( C) Thermistor resistance (kω)[t 0 C]
28 11 [Defective discharge pipe thermistor] 7-segment display : 1 time flash (1) Note (1) Single flashing of outdoor unit LED indicates Tho-D1 and double flashing indicates Tho-D2. Is the discharge pipe thermistor connector connection OK? Are the discharge pipe thermistor characteristics OK, is there no broken wire? Defective outdoor unit PCB (Defective discharge pipe thermistor input circuit) Repair Defective discharge pipe thermistor Display conditions If the temperature sensed by the thermistor is 3 C or lower continuously for 5 seconds between 10 minutes and 10 minutes 20 seconds after the compressor goes, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected 3 times in 40 minutes. Thermistor resistance (kω)[t < 80 C] Temperature-resistance characteristics of discharge pipe thermistor (ThO-D1, 2) T< 80 C T > 80 C Temperature [T] ( C) Thermistor resistance (kω)[t > 80 C] 12 [63H1-1,2, motion] 7-segment display : 1 time flash At 63H1-1,2 operation Did 63H-1, 2, operate? Defective outdoor unit PCB (Defective 63H1-1,2, input circuit) 1. During cooling Is the outdoor unit fan motor operating? Is there no short circuit air circulation for thr outdoor unit? Is there sufficient space for air inlet & outlet? 2. During heating Is the gas side service valve fully opened? Is the indoor unit heat exchanger thermistor detached from the detector case? Is the filter clogged? 3. During colling/heating Is the refrigerant overcharge? Display conditions If the 63H1-1,2 goes (open), the compressor stops. After a 3 minute delay, the compressor restarts. If this condition is detected 5 times within 60 minutes, or if the (open) state continues for 60 minutes without interruption. Abnormal pressure detection Compressor stop Compressor operating High pressure (MPa)
29 13 [Power transistor overheating] 7-segment display : 1 time flash (1) Note (1) Single flashing of outdoor unit LED indicates power transistor (CM1) overheat and double flashing indicates power transistor (CM2) overheat. If the compressor s stopped state continues for about 10 minutes, abnormal reset is possible. inverter PCB Is the indoor unit s installation space proper? Correction Does the outdoor unit fan rotate? Replace either the fan motor or control board. Are the power transistor thermistor characteristics OK is there any broken wire? power transistor thermistor Is the power transistor thermistor connector OK? It connects Inverter cooling fan is running. Inspect cooling fan Replace cooling fan Is fastening of the power transistor to the heat dissipation fins OK? Fastening screws Apply heat dissipation silicone. Does not recur. Fastened correctly. OK Display conditions If the power transistor s temperature exceeds the set value, the compressor stops. When the temperature drops to 90 C or lower, the compressor restarts, but if this occurs 5 times within 1 hour, or if this condition continues uninterrupted for 1 hour. Abnormal temperature detection. Compressor stop Re-starting Power transistor temp. ( C) Thermistor resistance (kω)[t < 80 C] Temperature-resistance characteristics of power transistor thermistor (ThO-P) T< 80 C T> 80 C Temperature [T] ( C) Thermistor resistance (kω)[t > 80 C]
30 14 [Current cut] 7-segment display : 1 time flash (1) Note (1) Single flashing of outdoor unit LED indicates current cut (CM1) and double flashing indicates current cut (CM2). Is the power supply voltage correct proper? Is the high pressure appropriate during operation? Check the compressor s insulation resistance and winding resistance. Check of power supply Check the refrigeration circuit. compressor Frequency during current cutoff. Display Conditions The compressor stops if the inverter s output current exceeds the set value. After a 3-minute delay, the compressor restarts. If this operation repeats 4 times in 15 minutes. Starts when the frequency is less than 60 Hz. Check of power transistor module (Reference to 345). inverter PCB OK Is installation space for the indoor and outdoor units appropriate? Is there any short circuits in the indoor/outdoor units? During Cooling: Is FM0 operaing? At heating: Is FMI operaing? Is the service valve (gas side) opened fully? Is the filter clogged? Is liquid flowing back to the compressor? Is overheating level control normal? Is the low pressure sensor normal? Is the compressor emitting an abnormal noise? If the power supply is reset (2~3 times), does it return to normal? inverter PCB It may be malfunctioning as a result of transient noise. If there is a noise source, nearby, take countermeasures to eliminate it
31 15 7-segment display : [Excessive number of indoor units connected] 1 time flash (1) Doesn't the number of indoor unit connected exceed the specified value? Power supply reset Is it normalized Repair Defective outdoor unit PCB Notes (1) The maximum number of connectable units of each model is as follows : FDCA224 type 13, FDCA280 type 16 FDCA335 type 20, FDCA400 type 23 FDCA450 type 26, FDCA735 type 43 FDCA800 type 47, FDCA850, 900 type 48. (2) Outdoor No. setting check for indoor units (to see if outdoor No. is of other system) (3) In case of auto addressing erase the addresses stored in memory and perform re-setting Unit is normal (malfunction by accidental noise) 16 [Transmission error between inverter and PCB] 7-segment display : 1 time flash (1) Note (1) Single flashing of outdoor unit LED indicates transmission error bitween inverter and outdoor unit PCB (CM1). Double flashing of outdoor unit LED indicates transmission error bitween inverter and outdoor unit PCB (CM2). Is the connection good at the connectors between the control board and the inverter board? Correction Are all the switches (except SW2-1 ())? Correction outdoor unit PCB Did it return to normal? inverter PCB
32 17 Automatic address setting and remote controller 7-segment display : address setting coexstents in the same network Are automatic address and remote controller address coexstent on the same network Repair to remote controller address Defective outdoor unit PCB 18 [Abnormalities in an outdoor fan motor] 7-segment display : 1 time flash (1) Note (1) Single flashing of outdoor unit LED indicates FM01 and double flashing indicates FM02. When outdoor unit is running Is a foreign object caught in the rotating parts of the fan motor? Remove the foreign object. Does the fan turn smoothly when turned by hand? Is the voltage at the red and black leads of CNDCW1, ~ 339V DC? Reset the power supply. Replace the fan motor. Check the power supply voltage. Did it return to normal? Replace the fan motor. It occurred due to transient noise. Display Conditions If an overcurrent or overheating signal is received from the outdoor fan motors (FMO1, 2), the compressor and outdoor fans stop. They start again after 3 minutes, but if this same trouble occurs 5 times (separately for FMO1, 2) again within 1 hour, or once within 45 minutes of the power being turned, an abnormal stop occurs
33 19 [Low pressure abnormal] 7-segment display : 1 time flash Is the connection of the low pressure sensor connector OK? Correction Does the pressure (actual measurement) match with the value in the 7-segment display? (Code No. 29) low pressure sensor Is the refrigerant level appropriate? Is there any abnormality in the refrigeration circuit? Change of outdoor unit PCB Display conditions If the low pressure sensed by the low pressure sensor is MPa or lower, the compressor stops. After a 3 minute delay, the compressor restarts. If this occurs 2 times within 60 minutes. If the pressure sensed by the low pressure sensor while the compressor is stopped is 0.18 MPa or lower. If this occurs 5 times within 60 minutes. Note (1) It recovers only if there is a power supply reset. Did it return to normal? Abnormal pressure detection CM operation CM stop Low pressure (MPa)
34 20 [Power transistor overheating (15 minute continuation)] 7-segment display : [Conbination unit only] 1 time flash (1) Note (1) Single flashing of outdoor unit LED indicates power transistor (CM1) overheat and double flashing indicates power transistor (CM2) overheat. If the compressor s stopped state continues for about 10 minutes, abnormal reset is possible. inverter PCB Is the indoor unit s installation space proper? Correction Does the outdoor unit fan rotate? Replace either the fan motor or control board. Are the power transistor thermistor characteristics OK is there any broken wire? power transistor thermistor Is the power transistor thermistor connector OK? It connects Inverter cooling fan is running. Inspect cooling fan Replace cooling fan Is fastening of the power transistor to the heat dissipation fins OK? Fastening screws Apply heat dissipation silicone. Does not recur. Fastened correctly. OK Display conditions A power transistor temperature error occurs when a temperature of 110 C or higher continues for 15 minutes, including compressor stops. Abnormal temperature detection. Compressor stop Re-starting Power transistor temp. ( C) Thermistor resistance (kω)[t < 80 C] Temperature-resistance characteristics of power transistor thermistor (ThO-P) T< 80 C T> 80 C Temperature [T] ( C) Thermistor resistance (kω)[t > 80 C]
35 21 [Defective suction pipe temperature thermistor] 7-segment display : 1 time flash Is the suction pipe thermistor connector OK? Are the suction pipe thermistor characteristics OK, is there any broken wire? Defective outdoor unit PCB (Defective suction pipe thermistor input circuit Suction pipe thermistor (Tho-S) Resistance temperature characteri stics Repair Defective suction pipe thermistor 15 Display conditions If the temperature detected by the thermistor is 50 C or lower continuously for 5 seconds between 2 minutes and 2 minutes 20 seconds after the compressor goes, the compressor stops. After a 3 minute delay, the compressor restarts. If this condition is detected 3 times within 40 minutes. Resistance(kΩ) kΩ at 25 C Temperature ( C) 22 [Defective low pressure and high pressure sensor] 7-segment display : 1 time flash (1) Note (1) Single flashing indicates PSL and double flashing indicates PSH. Is the connection of the low pressure sensor connector and high pressure sensor connector OK? Correction Does the pressure (actual measurement) match with the value in the 7-segment display? (Code No. 28 or 29) low pressure or high pressure sensor Is the refrigerant level appropriate? Is there any abnormality in the refrigeration circuit? Change of outdoor unit PCB Did it return to normal? Display conditions If the voltage detected by the sensor is 0V or lower or 3.49 V or higher continuously for 5 seconds between 2 minutes and 2 minutes 20 seconds after the compressor goes, the compressor stops. After a 3 minute delay, the compressor restarts. If this condition is detected 3 times within 40 minutes
36 23 [Abnormalities in compressor starting] 7-segment display : 1 time flash (2) Notes (1) Check if the power supply system is normal. (2) Single flashing of outdoor unit LED indicates abnormalities in compressor (CM1) starting and double flashing indicates abnormalities in compressor (CM2) starting. Is the power supply voltage correct proper? Is the balance pressure proper during starting? Check the compressor s insulation resistance and winding resistance. OK Check of power transistor module (Reference to 345) NG power transistor module NG OK (1) Check of power supply Check the refrigerant level and refrigeration circuit. compressor Try operating (starting) the unit another 2 or 3 times. Did it improve? compressor Note (1) While attempting to restart the compressor 2 or 3 times, the liquid refrigerant inside the compressor may be dispelled to outside the compressor and the starting abnormality may improve and recover. Display conditions (1) If it can t be started 2 times in 7 attempts. (2) A remote control reset is possible after 3 minutes passes. 24 [Compressor loader position detection error] 7-segment display : 1 time flash (2) Notes (1) Check if the power supply system is normal. (2) Single flashing of outdoor unit LED indicates compressor (CM1) loader position detection error and double flashing indicates compressor (CM2) loader position detection error. Operation. Does the compressor start? (E59) Does E42 occur? Does the compressor make an abnormal noise? Does it return to normal when the power reset? E60 recurs. It doesn t recur. Transient noise may be causing it to malfunction. Take measures to eliminate any nearby noise sources. E59 diagnosis E42 diagnosis Compressor check inverter PCB Display conditions (1) After rotor position detection operation, if the rotor s position cannot be detected again (4 times in 15 minutes), an error is displayed. (2) A remote control reset is possible after 3 minutes passes
37 25 [Communications error between the master unit and slave units] 7-segment display : [Conbination unit only] 1 time flash Are the address Nos. of outdoor units set correctly between the master and slave units? Correct. Turn the power, then turn it on again. Is an error message displayed? Replace the outdoor unit PCB. Abnormal noise, etc. 26 [Scram] 7-segment display : Note (1) Check if the power supply system is normal. 1 time flash Is a refrigerant leak indicated by a refrigerant leakage sensor input (at indoor CnT emergency stop input)? Refrigerant circuit check Scram input check
38 Checking the power transistor module (including the drive circuit) Is there any breakage or burn damage in the power transistor module? Is there a short circuit between the power transistor module terminals? *1 Compressor operation Is the compressor current inter-phase balance good? There is a difference of 10% or greater in the current between phases. (except during acceleration and deceleration) 1 Power transistor module terminal short circuit check procedure Disconnect the compressor wiring, then check for short circuits using a tester. P-U, P-V, P-W N-U, N-V, N-W Check between the P and N terminals. It is easy to make tester contact with the following locations on each of the terminals. P: Red harness side of the power transistor module terminal block. N: Blue harness side of the power transistor module terminal block. U: End of red harness to the compressor. V: End of white harness to the compressor W: End of blue harness to the compressor Normal power transistor module (d) How to advance checks for each faulty symptom (i) Inspection method when there is no error display 1) Louver motor does not operate sinspect at the indoor unit side. Operate more than 1 min. later Does the louver operate at power on? Is LM wire broken? Is LM locked? Defective indoor unit PCB Repair the wire Replace LM Is the louver operated with the remote controller Normal It is normal if it stops with 2 pushes on LS Turn off and back on again the power and check the motion of LS Only case of FDTQ, FDTS Note (1) LM: Louver motor LS: Limit switch Does the louver link push the LS till a click sound is heard? Adjust LS lever and check again Defective LS Defective indoor unit PCB - 37-
39 2) When the indoor unit blower does not operate sinspect at the indoor unit side. All of cooling, blower, heating, thermaldry do not operate Check FM1 When some modes only operate. Defective indoor unit PCB Check with the Hi, Me, Lo of blower mode. Is Voltage detected between CNF terminals? Defective indoor unit PCB Defective FMI, capacitor (CFI) 3) Four way valve does not switch during heating operation Is the voltage between connector CNN1 or CNN5 and AC 380/415 V? Defective 20S or 20SL Defective outdoor unit PCB (ii) When the cooling (heating) effect is felt insufficient. (Check also the refrigeration cycle for the refrigerant quantity, etc. in addition to the following.) 1) When the cooling effect is insufficient. Check if the protective function has tripped and, as a result, the compressor operation frequency has dropped below the specified frequency Does the indoor expansion valve operate properly? Is it clogged? Is the frosting prevention function operated? Check method of the indoor unit electronic expansion valve Check the indoor controller output to the expansion valve with the following procedures. scheck how much volt is detected at the expansion valve (SM) connector and at the pin at control side of the connector CnA (white, 7P (5 cores)), and measure also how many seconds the voltages are applied. White~Brown Approx. DC 5V Yellow~Brown (2) is detected for approx. 15 seconds (1) at Orange~Brown the power on. Blue~Brown sthe indoor controller is normal if the seconds and voltages as indicated at left are confirmed. When the expansion valve does not operate while the voltages are detected (operating sound is not heard), the expansion valve is defective. sif the thermostat setting is changed, the expansion valve will operate approx. 20 seconds later. Then, approx. 5V will be confirmed at the CnA same as above. Notes (1) 5V is maintained for 8 seconds after the power on, then it drops momentarily and recovers 5V for approx. 7 seconds. Notes (2) When measured with a digital multi-tester, voltages of approx. 6~3V are output one after another
40 2 OUTLINE OF OPERATI CTROL BY MICROCOMPUTER (1) Remote controller (a) Wired remote controller The figure below shows the remote controller with the cover opened. Note that all the items that may be displayed in the liquid crystal display area are shown in the figure for the sake of explanation. Characters displayed with dots in the liquid crystal display area are abbreviated. Pull the cover downward to open it. Central control display Displayed when the air conditioning system is controlled by the option controller. Vent Indicator Indicates operation in the Ventilation mode. Timer operation display Displays the settings related to timer operation. Weekly timer display Displays the settings of the weekly timer. Operation setting display area Displays setting temperature, airflow volume, operation mode and operation message. Temperature setting switches These switches are used to set the temperature of the room. TIMER switch This switch is used to select a timer mode. 27 C Operation/Check indicator light During operation: Lit in green In case of error: Flashing in red Operation/Stop switch This switch is used to operate and stop the air conditioning system. Press the switch once to operate the system and press it once again to stop the system. MODE switch This switch is used to switch between operation modes. Timer setting switches These switches are used to set the timer mode and time. GRILL switch This switch has no function. When this switch is pressed, (Invalid Operation) is displayed, but it does not mean a failure. AIR C No. (Air conditioning system No.) switch Displays the number of the connected air conditioning system. CHECK switch This switch is used at servicing. FAN SPEED switch This switch is used to set the airflow volume. VENT switch Switch that operates the connected ventilator. LOUVER switch This switch is used to operate/stop the swing louver. SET switch This switch is used to apply the timer operation setting. This switch is also used to make silent mode operation settings. TEST switch This switch is used during test operation. *If you oress any of the switches above and " But it does not mean a failure. " is display, the switch has no function. RESET switch Press this switch while making settings to go back to the previous operation. This switch is also used to reset the FILTER CLEANING message display. (Press this switch after cleaning the air filter.)
41 (e) Check abnormal operation data with the remote controller Operation data are recorded when there is an abnormal state and these data can be displayed in the remote controller by operating the remote controller buttons. (1) Press the CHECK button. The display will change from FUNCTI SET OPERATI DATA (2) Press the button once. The display will change to ERROR DATA. (3) Press the SET button to enter the abnormal operation data display mode. (4) If there are abnormalities from the past, they will be displayed by an error code and unit No. (Example) E8 (Lighted up) I/U No. 00 (Flashing) (5) Using the or button, select the indoor unit No. you want to display the error data for. If only one indoor unit is connected, the indoor unit No. does not change. (6) Fix the selection using the SET button. (The displayed indoor unit No. will change from flashing to light up continuously.) (Example) E8 DATA LOADING (This message flashes while data are being read.) E8 ERROR DATA The data are then displayed beginning with item No. 01. Displayed items are as shown below. (7) Display the other data for when the error occurred in order from the currently displayed operation data No. 01 using the or button. Depending on the model, items for which corresponding data do not exist are not displayed. (8) To change the indoor unit, press the AIR C No. button and return to the indoor unit selection display. (9) Press the / button to end the abnormal operation data check. If you press the RESET button during the settings, the display returns to the previous setting screen. No. Data item 01 (Operation mode) 02 SET TEMP. 27 C 03 RETURN AIR 28 C 04 I/U HEAT EXCH1 6 C 05 I/U HEAT EXCH2 5 C 06 I/U HEAT EXCH3 4 C 07 I/U FAN Hi 08 REQUIRED HERTZ 45Hz 09 SELECTED HERTZ 45Hz 10 EEV 480PULS 11 TOTAL I/U RUN 10500H 21 OUTDOOR 35 C 22 O/U HEAT EXCH1 55 C 23 O/U HEAT EXCH2 56 C 24 COMP HERTZ 85.0Hz 25 Hi PRESSURE 2.0MPa 26 Lo PRESSURE 0.40MPa 27 DISCHARGE 98 C 28 DOME BOTTOM 56 C 29 CT 26A 31 O/U FAN Hi 32 SILENT MODE 34 63H1 35 DEFROST 36 TOTAL COMP RUN 8500H 37 EEV1 480PULS 38 EEV2 480PULS
42 Maintenance Schedule Unit Item Period Check Test Maintenance Fan & Motor 6 Months Running Noise No Abnormal Noise Clean Blade/Replace Motor Measure Winding Res Insulation 1MOhm + If less, replace Indoor Outdoor Air Filter 3 Months Clean Clean Visually Check For Damage Replace if Damaged Condensate 6 Months Check connections, mountings Tighten as necessary Drain system Check for blockage and dirt Clean as necessary Check Pump and Float Switch Pump clears drain tray. Replace if necessary Float switch gives alarm Replace if necessary Coil and refrig. 12 Months Check operation Unit produces Cooling Investigate and fix any faults system (Heating) on demand Check of contamination Clean as necessary Controllers 12 Months Check operation Operate in all modes Replace if necessary Compressor 6 Months Running Noise No Abnormal Noise Replace if necessary Measure Winding Res Insulation 1MOhm + If less, replace Fan & Motor 6 Months Running Noise No Abnormal Noise Clean Blade/Replace Motor Measure Winding Res Insulation 1MOhm + If less, replace Coil and refrig. 12 Months Check operation Unit produces Cooling Investigate and fix any faults system (Heating) on demand Check of contamination Clean as necessary Electrical 6 Months Check tightness of terminals Tighten as necessary system
43 AIR CDITIING MAINTENANCE CHECK LIST SITE.. issue 04/03/02 Clients' Name. Sheet No Indoor Unit tick each box if applicable Unit A Unit B Unit C Unit D Unit E Unit F Unit G Unit H Model No Serial No Unit No/Location Check for unusual noise/vibration Check unit mtg brackets/fixings Check duct connections where applicable Check condensate drain runs clear Check condensate pump operation where applicable Check fan runs smoothly Check electrical mains connections for tightness Record FLA fan motor Check for evidence of gas leaks Clean air filter, reset filter light Use Biocide clean capsule or liquid in drain tray Outdoor Unit System 1 System 2 System 3 System 4 Model No Serial No Unit No/Location Check for unusual noise/vibration Check unit mounting brackets/fixings Check electrical mains connections for tightness Note nameplate amps Record actual running current Check overload settings where applicable Check for evidence of gas leaks Check Coil & clean if necessary System System 1 System 2 System 3 System 4 Note if fault code displayed E?? (Last recorded fault will be shown) Investigate if fault remedied and reset display Run system in each mode to check operation System left fully operational Engineer.. Clients' Signature Date.... Print Name. If you have any technical queries, please contact the 3D Air Sales Technical Department on
44
45 TICE The installation of this equipment must comply with all NATIAL, STATE and LOCAL CODES. This Service Guide does not cover all installation circumstances and is meant for guidance only and therefore will not form part of any legally binding contract. An installation guide is provided with the air conditioning equipment. CE These Air Conditioners comply with: - EMC Directive 89/336/EEC LV Directive 73/23/EEC 3D Air Sales Ltd Sales & Marketing Office 840 Brighton Road, Purley, Surrey, CR8 2BH Telephone: Facsimile: D Air Sales Ltd Technical, Sales Admin., Spares, Warranty Anglia House, Priors Way, Coggeshall, Essex, CO6 1TL Telephone: Facsimile:
INDEX MITSUBISHI HEAVY INDUSTRIES - PAC SERVICE MANUAL MAINTENANCE DATA 2 ERROR CODES 4 PCB INDOOR UNITS 8 ERROR DISPLAY & REMEDY CHART 12
SERVICE MANUAL FDA Series Split Systems FDA Series Multi Systems MITSUBISHI HEAVY INDUSTRIES - PAC SERVICE MANUAL INDEX MAINTENANCE DATA 2 ERROR CODES 4 PCB INDOOR UNITS 8 ERROR DISPLAY & REMEDY CHART
LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR CDITIING & HEAT PUMP SYSTEMS SERVICE GUIDE Including outdoor unit (FDC 6 Series and 8 Series) FDT 4-Way Cassette FDEN Ceiling Suspended FDKN Wall Mounted FDR Ducted Cassette FDU Ducted - gh Static
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL
1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target
4-2 ABNORMAL OPERATI 4-2-1 An is represented by 3 digit characters. The first 2 digit means the subsection, and the last 1 digit means the specifics. Ex.) Indoor unit Network communication Error Subsection
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
Service manual. The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V
Resistance The voltage in P3 and P4 in outdoor PCB is high voltage about 310V The voltage in P5 and P6 in outdoor PCB is high voltage about 310V 9.2 Troubleshooting for indoor unit E0 E1 E2 E3 E5 E6 P0
INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type )
Manual No. 06. SRK-T. 050 updated September 29, 2009 INVERTER WALL MOUNTED TYPE ROOM AIR-CDITIER ( Split system, air to air heat pump type ) SRK20ZD-S1, SRK25ZD-S1, SRK35ZD-S1, SRK50ZD-S1 SRK63ZE-S1, SRK71ZE-S1
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Split and Multi Split air conditioners Service information
Split and Multi Split air conditioners Service information Programming LG wired controllers 2 New type 2 Old type 7 Fault codes 9 Wall units (single split) 9 Universal split and multi split 10 Detailed
SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/
SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the
Simple Self-Diagnosis by Malfunction Code
Simple Self-Diagnosis by Code After Sales Service Division (SM-TS2) Detail Division 0 Indoor Unit System Others A C E F H J L P U M 7 8 9 External device activated (unified) Protection devices activated
Technical service manual 2009
MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features
SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT
Repair Guideline for SANYO New Erp. DC Inverter Air Conditioner (Published in May, 2013)
Repair Guideline for SANYO New Erp DC Inverter Air Conditioner (Published in May, 2013) Contents I. Electronic Control of DC Inverter Air Conditioner 2 1. Main parts of the electronic control of DC inverter
How To Measure Temperature On A Thermostat
Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK20HD-S, SRK28HD-S, SRK40HD-S, SRK20CD-S, SRK28CD-S, SRK40CD-S CTENTS 1. GENERAL INFORMATI... 1 1.1 Specific features...
Haier Air conditioner
For Europe Haier Air conditioner HAND in HAND HIGHER and HIGHER Page:1 For Europe HSU-09/12HVA103/R2(DB) HSU-09/12RHA103/R2(DB) Page:2 Error Codes and Description indoor and outdoor display(1) indoor Code
FILE NO. SVM-07013 11. HOW TO DIAGNOSE THE TROUBLE
FILE. SVM-070. HOW TO DIAGSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below.
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit
Troubleshooting 13. Troubleshooting Indoor unit s LED indication of Corona DC inverter unit MCAC-HTSM-2007-11 E0 E1 E2 E3 E5 E6 P0 P1 P2 P3 P5 EEPROM error outdoor communication error Zero-crossing examination
sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved
Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section
Repair Guideline for TCL DC Inverter Air Conditioner
Repair Guideline for TCL DC Inverter Air Conditioner Contents I. Electrical Control of Inverter Air Conditioner 2 1. Main compositions of the electrical control of inverter air conditioner 2 2. Wiring
SERVICE MANUAL AE-X2M14LR MULITI SPLIT TYPE ROOM AIR CONDITIONERS (OUTDOOR UNIT) MODEL. No. S2038AEX2MLRT CONTENTS AEX2M14LR
TopPage AEX2M14LR SERVICE MANUAL. S2038AEX2MLRT MULITI SPLIT TYPE ROOM AIR CONDITIONERS (OUTDOOR UNIT) MODEL AE-X2M14LR In the interests of user-safety (Required by safety regulations in some countries)
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
SERVICE MANUAL INDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: "How to check miswiring and serial signal error" for MUZ type has been added. The description about "Low standby power control" has been added to "TECHNICAL CHANGES".
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
Technical service manual
GD Midea Refrigeration Equipment Co.,Ltd ODMI-A-1202 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual R410A Multi DC inverter 220~240V-1Ph-50Hz Outdoor units Models M2OC-14HRDN1 M2OC-14HRDN1-Q
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
SERVICE MANUAL INDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1
HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS
HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS SET FREE FSG(1)/FS3, FS5 SERIES AND SET FREE FXG/FX3 SERIES Models In-the-Ceiling Type RPI-0.8FSG1 RPI-2.5FSG1 RPI-8FSG1
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM
SECTION 7D AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM TABLE OF CONTENTS Description and Operation... 7D- General... 7D- FATC Control... 7D- FATC Input/Output Routing Diagram...
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
SERVICE MANUAL INDOOR UNIT MSZ-EF35VEW MSZ-EF22VEB - - E1 MSZ-EF25VEB E1 MSZ-EF35VEB - - E1 MSZ-EF35VEB E1 MSZ-EF35VES - E1 - E1 MSZ-EF22VEW -
SPLIT-TYPE AIR CONDITIONERS Revision A: Airflow in the Silent mode in the cooling operation has been changed. "TROUBLESHOOTING" has been corrected. Please void OBH589. INDOOR UNIT SERVICE MANUAL. OBH589
Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU
Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems
Hoshizaki America, Inc.
Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1301SAH/3, SWH/3, SRH/3 KM-1400SWH-M, SWH3-M KM-1601SAH/3, SWH/3, SRH/3 KM-1900SAH/3, SWH/3, SRH/3 KM-2100SWH3, SRH3 KM-2500SWH3, SRH3 KMH-2000SWH/3,
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC
HVAC SYSTEM (AUTO A/C) (DIAGNOSTICS) AC Page. Basic Diagnostic Procedure.... General Description...3 3. Electrical Components Location...6 4. A/C Control Module I/O Signal...8 5. Self-diagnosis...0 6.
SERVICE MANUAL MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA INDOOR UNIT. No. OBH647. Models. Revision A: MSZ-HJ50VA- E1 has been added.
SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-HJ50VA- E1 has been added. Please void OBH647. INDOOR UNIT SERVICE MANUAL. OBH647 REVISED EDITION-A Models MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA - E1 - E1 - E1 CONTENTS
REMOTE CONTROL MANUAL
REMOTE CONTROL MANUAL ENGLISH CONTENT PRECAUTIONS...1-2 USING THE REMOTE CONTROL UNIT...3 OPERATION...4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
*.ppt 11/2/2009 12:48 PM 1
Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type )
Manual No. 08. SRK-T. 079 INVERTER WALL MOUNTED TYPE ROOM AIR-CDITIER ( Split system, air to air heat pump type ) SRK50ZHX-S, SRK60ZHX-S - 3 - CTENTS 1 GENERAL INFORMATI... 1 1.1 Specific features... 1
Fire Alarm Control Panel. Family. Operating Manual
Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...
A/C-HEATER SYSTEM - AUTOMATIC
A/C-HEATER SYSTEM - AUTOMATIC 1995 Volvo 850 1995-96 Auto. A/C-Heater Systems Volvo 850 * PLEASE READ THIS FIRST * WARNING: To avoid injury from accidental air bag deployment, read and carefully follow
DTC B1423/23 Pressure Sensor Circuit
AIR CONDITIONI AIR CONDITIONI SYSTEM (for Manual Air Conditioning System) 145 DTC B1423/23 Pressure Sensor Circuit DESCRIPTION This DTC is output when the refrigerant pressure is either extremely low (0.19
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED
Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06
A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner
ENERGY SMART TROUBLESHOOTING GUIDE TABLE OF CONTENTS:
ENERGY SMART TROUBLESHOOTING GUIDE TABLE OF CONTENTS: COMPONENTS/BOARD LAYOUT... 2 HOT WATER... 3 1 FLASH (GREEN DIAGSTIC LIGHT)... 4 2 FLASHES (GREEN DIAGSTIC LIGHT)... 5 3 FLASHES (GREEN DIAGSTIC LIGHT)...
Repair Guideline for TCL DC Inverter Air Conditioner
Repair Guideline for TCL DC Inverter Air Conditioner FLOS SERIE---V3 0 CONTENTS Ⅰ. Introduction of New control board for outdoor unit...2 1. The structure of control board... 2 2. Diagram of outdoor unit........4
OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump
R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
Split Air Conditioner
Split nditioner plit itsplit ir onditioner Split Split Split Split Split User s WNER'S 'S ER'S For s: AWI/AWO-21HPR1 Delta AWI/AWO-25HPR1 Delta AWI/AWO-32HPR1 Delta AWI/AWO-53HPR1 Delta AWI/AWO-65HPR1
SERVICE & MAINTENANCE MANUAL
SERVICE & MAINTENANCE MANUAL 2005 TABLE OF CONTENTS PAGE NO. 1. Precautions for Service & Maintenance 2 2. Split System Description 3 3. Unit Model Designation & Identification 4 4. Unit Models & Part
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
ON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
TECHNICAL MANUAL. INVERTER RESIDENTIAL AIR CONDITIONERS (Split system, air to air heat pump type) Ceiling concealed type SRR25ZJ-S SRR35ZJ-S
Manual No.'10 SR-T-091 TECHNICAL MANUAL INVERTER RESIDENTIAL AIR CONDITIONERS (Split system, air to air heat pump type) Wall mounted type SRK20ZJ-S SRK25ZJ-S SRK35ZJ-S 50ZJ-S SRK20ZJX-S SRK25ZJX-S SRK35ZJX-S
Business/Home GSM Alarm System. Installation and User Manual
Business/Home GSM Alarm System Installation and User Manual Brief Introduction: GSM 900/1800/1900 bands, can be used in most parts of the world Full duplex communication with the host Monitor the scene
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09
0000-00 01-3 6810-20 1. FFH SPECIFICATION 01-4 0000-00 2. SYSTEM LAYOUT AND COMPONENTS 0000-00 01-5 01-6 0000-00 3. FFH GENERAL INFORMATION The system is to increase the coolant temperature quickly by
Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
Single Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O
SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE TAS-18MVHN/O TAS-27MVHN/O TAS-36MVHN/O DC MULTI OUTDOOR UNITS CONTENTS 1. General information of Outdoor Units... 3 2. Dimensions... 4 3. Wiring Diagram...
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
LOCAL INTERCONNECT NETWORK (LIN)
54B-1 GROUP 54B LOCAL INTERCONNECT NETWORK (LIN) CONTENTS GENERAL INFORMATION 54B-2 SPECIAL TOOLS 54B-3 54B-4 DIAGNOSIS FUNCTION 54B-4 DIAGNOSTIC TROUBLE CODE CHART 54B-6 DIAGNOSTIC TROUBLE CODE PROCEDURES
Thermo Top - Troubleshooting Tree
Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may
SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor
LOCAL INTERCONNECT NETWORK (LIN)
54C-1 GROUP 54C LOCAL INTERCONNECT NETWORK (LIN) CONTENTS GENERAL INFORMATION...54C-2 SPECIAL TOOL...54C-3...54C-4 DIAGNOSTIC FUNCTION...54C-4 DIAGNOSTIC TROUBLE CODE CHART...54C-6 DIAGNOSTIC TROUBLE CODE
Fault Code Check List
FAULT COVER&TABS_COVERS 26/09/2011 17:14 Page 1 Fault Code Check List This Fault Code Check List is intended to provide an easy-to-use, quick reference guide on all Fault Codes across our product range.
SERVICE & MAINTENANCE MANUAL
SERVICE & MAINTENANCE MANUAL Specifications are subject to change without notice according to Carrier Policy of continuous development. 03502566 Revision : (0) - 2009 TABLE OF CONTENTS PAGE NO. 1. Precautions
Multi-Protocol decoder 76 200 with Load regulation
Multi-Protocol decoder 76 2 with Load regulation For locomotives with universal motors on digital layouts operating in the DCC and Motorola data format. Features 76 2 Load regulated multi-protocol decoder
Midea Commercial Air Conditioner Malfunction Handbook
Midea Commercial Air Conditioner Malfunction Handbook May 1, 2008 Customer Service Philosophy of Midea Air Conditioner Service Target: 100% Customer Satisfaction Service Standard: 100% Earnestness Service
Doc.No. NDP 192U-02. Electric Pump Controller CE-124P. Instruction Manual
Doc.No. NDP 192U-02 Electric Pump Controller CE-124P Instruction Manual 1. Parts Name and Function 1) POWER LED Indicate that CE-124P is powered up. 2) START/STOP KEY (SELECTOR KEY) Used to start and stop
800-292-3279 916 638-0828
800-292-3279 916 638-0828 http://easycleansystems.com/heaters/heater-parts.html VAL6 KBE5S and KBE5L Service manual KBE5S 1 2 Specifications Type VAL6 KBE5S Heat Output 111,000BTU/h Fuel Kerosene, Diesel
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
GSM HOME SECURITY SYSTEM
Cell /Mobile phone home security system GSM HOME SECURITY SYSTEM Model : GSM-120 TABLE OF CONTENTS 1. FEATURES... 1 2. APPLICATION... 2 3. SPECIFICATIONS... 3 4. FRONT PANEL & LAYOUT DESCRIPTION...6 5.
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
WALL MOUNTED SPLIT TYPE AIR CONDITIONER
WALL MOUNTED SPLIT TYPE AIR CONDITIONER MANUAL 8 OM-G12-ACSON CONTENTS - Operating Guide page 1 - G12 Remote Controller Indication page 2 - Indicator Lights page 4 - Installation of Aroma page 5 - Auto
HEAT PUMP PROGRAMMABLE THERMOSTAT
HEAT PUMP PROGRAMMABLE THERMOSTAT SA PM 3 COOL TEMP Form 44014-01 r010408 Model 43168 Owners Manual 1 Congratulations! Heat Pump Programmable Thermostat Model 43168 THERMOSTAT CONTROLS Switches & Buttons...15
VX 2400 Dimmer User's Manual
TM VX 2400 Dimmer User's Manual 21-2119C Manual Revision 1.01 Software Version 1.0 10 March 1994 Table of Contents 1. General Description...3 1.1. Standard Features:...3 2. Installing Options...4 2.1.
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Operational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
