Optical Fiber Data Center Field Testing. ANSI/BICSI Data Center Design and Implementation Best Practices
|
|
- Brian Park
- 8 years ago
- Views:
Transcription
1 Optical Fiber Data Center Field Testing ANSI/BICSI Data Center Design and Implementation Best Practices
2 Abstract Data Centers are a growing segment of the enterprise market. Regardless of whether the data center is an offsite company providing storage for one or more companies or the data center is the onsite central storage facility for an individual company the storage and access to the data is generally mission critical. Downtime in a data center or time to turn-up a data center circuit can cost significant dollars. The high speed networks require more stringent performance than typical LANs. To be sure the data center networks will support today s networking applications it is important to properly clean, inspect and test optical fiber networks. What tests are required and recommended for channels and links per the ANSI/BICSI and other standards; End Face Inspection, Optical Loss Testing, Polarity Verification, Optical Return Loss, and Fiber Characterization using an OTDR with both launch and tail cords. 2
3 Requirements Cleaning and Inspection Tier 1 testing with an Optical Loss Test Set (OLTS) Polarity verification Length verification Tier 2 testing with an Optical Time Domain Reflectometer (OTDR) Recommendations Tier 2 OTDR testing Reflectance Optical Return Loss (ORL) Length Outline- Data Center Testing 3
4 Fiber Safety Issues Laser Eye Safety Fiber Scrap Shards from fiber prep Puncture and Cut issues Ensuring all systems are off
5 Causes of Optical Network Failures Why is Test and Inspection important Prevent, detect, & resolve leading causes of optical network failures Contaminated, damaged, or poorly polished connectors Poor splices Micro- or Macro-bends induced in shipping or installation Verify quality of new optical fiber installations Diagnose, repair, and verify optical networks after activation Causes of Optical Network Failures As reported by: Source: NTT Advanced Technology
6 Standards and Requirements 6
7 Data Center Requirements TIA 942-A Data Center Standard Standardizes LC connectors for 1 or 2 fibers MPO connectors for more than 3 fibers Removes OM1 and OM2 fiber support Requires a minimum of OM3 fiber Recommends OM4 fiber or single-mode Eliminates the 100m horizontal cabling restriction Length restriction is now application based 7 AFL Company Confidential
8 Data Center Requirements ANSI/BICSI Data Center Design and Implementation Best Practices Tier 1: OLTS- OPM and OLS attenuation measurement- Required Attenuation Polarity Length if capable Tier 2: OTDR measurements Required Characterize Anomalies with traces Evaluate uniformity of connections (Loss of splices & connectors) Use manufacturers mean insertion loss of components to calculate link budget Inspection and Cleaning Required Other measurements Recommended OTDR: Fiber Length, Reflectance, ORL VFL: Polarity 8 AFL Company Confidential
9 Link Certification Tests and Test Equipment TIA/EIA 568-C.0 Annex E Tier 1 -- Required Link Insertion Loss Link Polarity Link Length OLTS (Certification Test Set or light source and optical power meter) OLTS or VFI (red laser) Can be verified by inspection (of cable markers) or measured using a Certification Test Set or OTDR Tier 2 -- Going beyond the minimum TIA specs Link baseline trace Connection or splice insertion loss Connection or splice reflectivity OTDR OTDR OTDR
10 Value / Features What test equipment options do I have? Visual Fault Locators/Inspection LS/PM & OLTS (Tier 1) OTDR & *OLTS (Tier 1 & *2) MT Tracer MPO Tester Certification Test kit OTDR/ Certification Test Kit FOCIS VFI s Light Source Power Meter OTDR w/ Light SOurce Product category 10
11 Cleaning, Inspection and Polarity Required
12 The Connector End-Face Inspection Verify no energy with power meter First Be sure to clean both connectors prior to mating to prevent moving the dirt between connectors One-click cleaners are easy, fast and effective; enabling user to clean patch cords and through bulkheads in patch panels
13 The Connector End-Face Inspection Inspect connector end-face for: Scratch goes near the core! Dirt Dirt particles Oil Scratches Epoxy Body Oil Don t touch the connector endface! Clean MPO end-face!
14 Inspection always required Live Image Snapshot Image Review
15 Basic Light Test Continuity/Polarity Visual Fault Identifier/Locator (VFI/VFL) Visually see breaks and faults Enables user to locate events that are too close together or too close to the OTDR (limited to 4 km range) Fiber polarity check
16 MPO Polarity check MPO trunk cables why polarity matters MPO-MPO trunks are typically one of three Methods: A, B or C Keying assures proper orientation of the MPO Keying does not assure proper polarity or Method Users should select one method for their networks to avoid polarity issues Method A 16 Source: Opticonx
17 MPO Polarity check MPO trunk cables why polarity matters Tracer / Tester can be used to trace polarity problems Visible light is sequentially injected into one end of the MPO trunk and the MT Tracer indicates which fiber it exits 17
18 MPO Polarity check MPO trunk cables why polarity matters Method A Straight through trunks; key-up to key-down adapters Patch cords: One end A to B straight thru One end A to A pair flipped Method B Straight through trunks; key-up to key-up adapters Patch cords: Both ends A to B straight thru Method C Pair flipped trunks; key-up to key-down adapters Patch cords: 18 Both ends A to B straight thru
19 Data Center Testing Tier 1 & Tier 2 Required and Recommended
20 Attenuation: Decrease in Optical Power Insertion Loss Measured in decibels (db) Limits the distance the signal travels Some attenuation is inherent in glass Connectors can be the single largest contributor to attenuation in the Data Center Some attenuation can be induced by people and the environment Signal below receiver threshold which is a 1 is read as a 0
21 Tier 1 test and OPM Applications Use the OPM function and OLS (MM/SM light source) to measure link loss in dbm/db measure optical power levels of electronics interchangeable adapters allow for 1 jumper reference method
22 Certification Test Set Measures Attenuation Length Checks Continuity Polarity Test Multiple wavelengths in two directions Two fibers at a time Capable of supporting end-face inspection
23 Tier 2 Testing and Characterization Why use an OTDR? Generates a baseline trace A visual characterization of the link - Measure Loss - Measure Reflectance - Measure Optical Return Loss - Measure Length Fiber acceptance tool Documentation Fault location tool Identify and evaluate specific events/problems in the link 23
24 Tools to meet Data Center Test Needs What s important to look for in an OTDR Data Centers have many connections and use short jumpers Very short dead-zones are required to characterize fibers and fault find Attenuation Dead Zone less than 3 m Event Dead Zone less than 1 m 24
25 Tools to meet Data Center Test Needs What s important to look for in an OTDR Easy to Use Interface such as Touch-and-Test TM Simple Job setup and renaming capability of results Auto set up modes to enable novices to get accurate and complete results Front Panel/First Connector checks to assure a quality launch is achieved Easy to define Launch and Tail cords which should be used to obtain link loss measurements Software to help the user find installation errors Macro/Micro-bends Pass/Fail Thresholds 25
26 Tools to meet Data Center Test Needs What s important to look for in an OTDR Multi-functionality in a Easy-to-use platform OTDR Optical Power Meter Visible Fault Locator Support for an Inspection probe Documentation software 26
27 Reflectance (-db) Reflectance: the ratio of reflected light to incident light at a point A concern in networks operating 10, 40 or 100GbE Reflectance is directly impacted by termination technique OTDRs best-suited to measure individual reflections of components in a fiber system and identify them as Events 27
28 Fresnel Reflections (Light reflected at changes in index of refraction) End of a cleaved fiber Two mated connectors Un-terminated connector Mechanical splice How an OTDR Works Air gap at poorly mated connectors Height (db) Appears as a sharp spike in the waveform, OTDR trace Cursor positioning is important in measuring location and loss of a reflective event Height of a reflective event relative to backscatter is its Reflectivity 28
29 Reflectance and Optical Return Loss (-db) Optical Return Loss (ORL): the ratio of the average reflected light from the entire fiber, measured at the launch point, to the average incident power level injected into the fiber at the launch point A high reflectance at the far end of a long fiber won t contribute much to ORL A high reflectance at the near end of a long or short fiber will be the primary contributor to the overall ORL 29
30 How an OTDR works: Tier 2 Testing Relative Power (db) P IN C1 Fiber C2 C3 S1 P OUT Distance The OTDR provides specific loss and distance measurements to all events that are in the link Event = Connection (C), Splice (S) or other anomaly in the fiber system 30
31 Importance of Launch and Tail Cords Should be at least 100m Are necessary to: Characterize the near and far end connectors Provide a Link Loss Measurement 31
32 Documentation - Certify against Industry and/or User cabling standards Pass and Fail results Displays headroom Qualify network applications Event table (OTDR) Cable & Route Summaries End Face Image Thumbnails 32
33 What s Important: Cabling Standards Telecommunication Industry Association (North America) TIA-568 ANSI/BICSI Data Center Design and Implementation Best Practices- European Committee for Electrotechnical Standardization CENELC EN50173 International Organization for Standardization / International Electrotechnical Commission ISO/IEC Optical fibre type size and grade Multimode 62.5µm (OM1) Wavelength Multimode 50µm (OM2) Multimode 50µm (OM3) Multimode 50µm (OM4) Singlemode (OS1) Singlemode (OS2) Fiber attenuation coefficient (db/km) Minimum modal bandwidth (MHz-km) ns N/A N/A N/A N/A Event Type Connector Multimode Connector Singlemode Fusion Splice Max Loss * (db) Reflectance (db) ORL (db) (UPC) (UPC) - 60 (APC) *For Data Center component insertion Loss use manufacturers values (db) 26
34 34
What testing is required for PREMISES Fiber Optic Cabling and the standards used
Testing Cabling in the Data Center Part 1 Fiber Testing Wayne Allen Product Marketing Engineer Asia Pacific Region Fluke Networks In this presentation What testing is required for PREMISES Fiber Optic
More informationRemoving the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications
Removing the Mystery from OTDR Measurements Keith Foord Product Manager Greenlee Communications Why an OTDR? Terminology Theory Standards Key specifications Trade-offs Cleaning and Inspection Measurements
More informationFibre optic testing best practices
Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is
More informationCabling & Test Considerations for 10 Gigabit Ethernet LAN
Introduction Current communication data rates in local networks range from 10/100 megabits per second (Mbps) in Ethernet to 1 gigabit per second (Gbps) in fiber distributed data interface (FDDI) and Gigabit
More informationBest Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
More informationM310 Data Center OTDR
Designed for Data Center Testing, Troubleshooting and Documentation Features Event Dead Zone 0.8 m Attenuation Dead Zone
More informationTesting and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM
Testing and troubleshooting enterprise fiber-optic cabling Presenter: Neftali Usabal Fluke Networks - LATAM Agenda Testing Methods and Standards Why we test optical systems Terminology & types of testing
More informationWhite Paper: 10GbE Fiber A Practical Understanding and Functional Approach
White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of
More informationM310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. www.aflglobal.com or (800) 321-5298, (603) 528-7780
Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Integrated Optical Power Meter and Visual Fault Locator Short dead zones provide testing of closely spaced events Industry
More informationNORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 10 00 STRUCTURE CABLING TESTING
RELATED SECTIONS: NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT Section 27 00 00 General Requirements Section 27 02 00 General Communication Requirements Section 27 05 26 Grounding and Bonding for Communications
More informationTEST & INSPECTION. Featured Data Center Products. OTDRs Certification Test Kits Inspection Cleaning
TEST & INSPECTION Featured Data Center Products M310 Enterprise OTDR with TruEvent Technology Designed for Enterprise Network Testing, Troubleshooting and Documentation, the M310 with TruEvent technology
More informationResolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009
Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made
More informationMTS/T-BERD Platforms Very Long Range (VLR) OTDR Module
COMMUNICATIONS TEST & MEASUREMENT SOLUTIONS MTS/T-BERD Platforms (VLR) OTDR Module Key Features CWDM/DWDM ready with 1310, 1383, 1490, 1550, and 1625 nm wavelengths FTTx ready with 1310/1490/1550 nm wavelengths
More informationAccurately Testing fibre Optic Cables
Accurately Testing fibre Optic Cables Note: You need to know what we mean when we say accurate that the measurement made gives a value close to the real value. Standards people prefer we refer to the uncertainty
More information12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)
1 1 9.41 115 0 Patch cables are used 143 12 Fibre MTP Jumper, MTP (non-pinned) to Patch cables are used for non -permanent connections between patch panels, transmission equipment, etc. Pre -assembled
More informationTracing Live or Dark FTTx PONs through Splitter using OFL280
Introduction AFL s PON-optimized OFL280-103 FlexTester is ideally suited for both out-of-service installation testing, as well as in-service fault location on FTTx PON networks. The OFL280-103 s unique
More informationSECTION 27 08 23 TESTING OF FIBER OPTIC CABLES
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
More informationField Measurements of Deployed Fiber
Field Measurements of Deployed Fiber Robert J. Feuerstein Level 3 Communications, 1025 Eldorado Boulevard, Broomfield, Colorado 80021 Robert.Feuerstein@Level3.com Abstract: New generations of ultra-long
More informationTechnical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations
The Fiber Optic Association, Inc. 1119 S. Mission Road #355, Fallbrook, CA 92028 1-760-451-3655 Fax 1-781-207-2421 Email: info@thefoa.org http://www.thefoa.org Technical Bulletin Guidelines For Testing
More informationFIBER OPTIC SYSTEM TEST PROCEDURES
FIBER OPTIC SYSTEM TEST PROCEDURES Data Systems Performance Engineering LLC performs three tests in order to determine fiber optic cable adequacy. The order in which the tests are to be performed is not
More informationFour Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method
Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method Jim Hayes, VDV Works, LLC Abstract: We often are asked questions about testing installed fiber optic cables
More informationPatch Cords for Data Center Applications
Applications General use of patch cords includes the interconnection of the optical fiber cable plant with opto-electronic equipment, and/or the cross-connection between cable plant segments. Pigtails
More information99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431. Visit us at www.testequipmentdepot.com
Datasheet: MultiFiber Pro First MPO tester to support both Singlemode and Multimode MPO fiber testing Data centers are growing, fueled by the proliferation of media, virtualization and the need for more
More informationTesting Fiber Optic Cables. Rudy De Winter C.N. Rood RDeWinter@cnrood.com
Testing Fiber Optic Cables Rudy De Winter C.N. Rood RDeWinter@cnrood.com LAN, WAN, MAN,... Testing Fiber Optic Cables The Goal: A network Testing Fiber Optic Cables The OSI Reference Model Application
More informationTIER-1/TIER-2 FIBER CERTIFICATION KITS
MaxTester 940 Fiber Certifier OLTS TIER-1/TIER-2 FIBER CERTIFICATION KITS EXFO s Fiber Certification kits cover all test requirements to perform clear, fast and first-time-right system acceptance. This
More informationLoss & Continuity Testing with MPO/ MTP Connectors
Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular
More informationStructured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems
SYSTIMAX Solutions Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems May 2016 TABLE OF CONTENTS 1. INTRODUCTION 1 2. PASSIVE LINK SEGMENTS 2 3. GENERAL TESTING
More informationHow To Properly Maintain A Fiber Optic Infrastructure
How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope
More informationFiber Optic Specifications
Fiber Optic Specifications All Fiber Optic shall be Corning Altos Single Mode OS1 Outdoor Loose Tube Gel Free Cable Corning Fiber Products only will be accepted and no substitutions or alternates will
More informationManaging High-Density Fiber in the Data Center: Three Real-World Case Studies
Managing High-Density Fiber in the Data Center: Three Real-World Case Studies CHALLENGE In today s data center, fiber optic links have become more vital than ever for transmitting data to and from a large
More informationSpecifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
More informationGuidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...
LANscape Solutions Recommended Fiber Optic Test Guidelines Table of Contents 1. Introduction...1 2. Why Test?...1 3. Tier 1 and Tier 2 Testing...2 4. Encircled Flux...3 5. Link-Loss Budgets...4 6. Proper
More informationSTATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007
804.01 Description 804.02 General 804.03 Materials 804.04 Fan-Out Kit 804.05 Drop Cable 804.06 Fiber Optic Patch Cord 804.07 Termination Panel 804.08 Fusion Splice 804.09 Fiber Optic Connector 804.10 Splice
More informationPolymer Coated Fiber Cable (PCF)
Polymer Coated Fiber Cable (PCF) Panduit has introduced a Polymer Coated Fiber (PCF) to their fiber cable offering available in 50µm and 62.5µm core diameters. Along with this cable having a stronger durability
More informationUpgrading Path to High Speed Fiber Optic Networks
SYSTIMAX Solutions Upgrading Path to High Speed Fiber Optic Networks White Paper April, 2008 www.commscope.com Contents Connectivity Method A 4 Upgrading Method A to Parallel Optics 4 Connectivity Method
More informationGigabit Passive Optical Networks
White Paper Gigabit Passive Optical Networks Passive Optical LAN Solutions (POLS) Theory, Design, and Installation Considerations Sean McCloud, RCDD Senior Applications Engineer, Leviton Network Solutions
More informationMigration Strategy for 40G and 100G Ethernet over Multimode Fiber
Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year
More informationOvercoming OM3 Performance Challenges
White Paper Overcoming OM3 Performance Challenges First Third-Party Test of Pre-terminated OM3 MTP System Demonstrates Flexibility in 10G Network Designs Gary Bernstein, RCDD Director of Product Management
More informationAs today s evolving data centers
IT CORNER Next Generation Optical Fiber Connectivity Solutions for the Mission Critical Data Center BY BILL CHARUK As today s evolving data centers confront bandwidth capacity challenges, the migration
More informationHoW confident are You about Your connector cleanliness?
HoW confident are You about Your connector cleanliness? Vincent Racine, Product Line Manager, Francis Audet, Advisor, CTO Offi ce, François Marcotte, Senior Technical Sales Specialist Gwennaël Amice, Senior
More informationExplanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces
Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces WP1281 Issued: November 2015 Supersedes: 2012 Author: Dr. Russell Ellis ISO 9001 Registered Background
More informationAttaching the PA-A1-ATM Interface Cables
CHAPTER 4 Attaching the PA-A1-ATM Interface Cables To continue your PA-A1-ATM port adapter installation, you must attach the port adapter cables. The instructions that follow apply to all supported platforms.
More informationTIA Releases Guidelines for Maintaining Polarity Using Array Connectors
Corning Cable Systems TIA Releases Guidelines for Maintaining Polarity Using Array Connectors What is new? ANSI/TIA-568-B.1-7-2006 Commercial Building Telecommunications Cabling Standard, Part 1 General
More informationSpecifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer
Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer tirujo@ofsoptics.com Outline Data Center Market Drivers Data Center Trends Optical Fiber and Related Standards Optical Fiber
More informationFTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD The ideal construction
More informationAgilent E6020B FTTx OTDR
Agilent E6020B FTTx OTDR Fast and Cost-effective Fiber Installation for Access Networks Technical Data Sheet Introducing the New FTTx OTDR Agilent's new E6020B FTTx OTDR is a cost-effective, easy to use
More informationA Quick Start Guide to Fiber Inspection, Cleaning, and Test INSPECT BEFORE YOU CONNECT SM
A Quick Start Guide to Fiber ion, Cleaning, and Test INSECT BEFORE YOU CONNECT SM Notice Copyright Trademarks Every effort was made to ensure that the information in this document was accurate at the time
More informationData Center Design for 40/100G
Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an
More informationCISCO 10GBASE X2 MODULES
DATA SHEET CISCO 10GBASE X2 MODULES Figure 1. Cisco 10GBASE X2 and Xenpak Module PRODUCT OVERVIEW The Cisco 10GBASE X2 modules (Figure 1) offers customers a wide variety of 10 Gigabit Ethernet connectivity
More informationUSE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION
USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION
More informationMigration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity
Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide
More informationMeasuring of optical output and attenuation
Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter
More informationNetwork Topologies and Distances
Network Topologies and Distances Chris Di Minico MC Communications cdiminico@ieee.org 1 Presentation objectives Considerations for 802.3ba fiber link distance objectives 2 HSSG Objectives Support full-duplex
More informationHP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable
Overview Models HP 0.5 m Multimode OM3 LC/LC Optical Cable HP 1 m Multimode OM3 LC/LC Optical Cable HP 2 m Multimode OM3 LC/LC Optical Cable HP 5 m Multimode OM3 LC/LC Optical Cable HP 15 m Multimode OM3
More informationThe Need for Low-Loss Multifiber Connectivity
WP_LowLoss_D_B 10/13/14 2:08 PM Page 2 The Need for Low-Loss Multifiber Connectivity In Today s Data Center Optical insertion loss budgets are now one of the top concerns among data center managers, especially
More informationFibre Channel Fiber Cabling
OVERVIEW This paper will discuss the Fibre Channel standards for fiber cables at both 1Gb and 2Gb speeds, and also some discussion of departures from standard. Items discussed will be cable types, plug
More informationMPO. Fast Fibre Solution for Data Centres
MPO Fast Fibre Solution for Data Centres Benefits The Plug & Play MPO solution of Nexans Cabling Solutions provides a comprehensive line of pre-terminated and pre-tested assemblies to meet the current
More informationFTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING
FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING i OLM R E A D Y 2014 GLOBAL PORTABLE FIBER OPTIC TEST EQUIPMENT MARKET LEADERSHIP AWARD The ideal construction
More informationBICSInews. plus. Show Issue. september/october 2012 volume 33, number 5. + Migration to High-Speed Ethernet
BICSInews m a g a z i n e september/october 2012 volume 33, number 5 plus + Migration to High-Speed Ethernet Show Issue + DAS in Your World + Planning Health Care Infrastructure + Fiber Considerations
More informationUniCam High-Performance Connectors, Multimode and Single-Mode
features and benefits Broad operating temperature (-40 to +75 C) Factory-polished end face Fast termination and no consumables Minimum insertion loss Performance guaranteed Utility and flexibility Consistent
More informationTURBOTEST 400 Fiber Optic Certification Test Set User s Guide
TURBOTEST 400 Fiber Optic Certification Test Set User s Guide T e s t & I n s p e c t i o n TURBOTEST 400 Fiber Optic Certification Test Set User s Guide T e s t & I n s p e c t i o n 2002, AFL Telecommunications,
More informationFiber Characterization Service
About JDSU JDSU s verifies the integrity and capacity of your fiber plant through the measurement of key fundamental properties, such as attenuation, reflectance, and dispersion. Comprehensive testing,
More informationSplicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber
Presented at NOC/EC 2000 Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber Mary Adcox, Optical Fiber, Corning Incorporated As non-zero dispersion-shifted
More informationInsertion Losses of Fiber Optical Connectors
Insertion Losses of Fiber Optical Connectors Martin Strasser, Fiber Optics, HUBER+SUHNER AG, Switzerland H+S Technical Series HUBER+SUHNER Excellence in Connectivity Solutions Table of contents 1 Origins
More informationGigabit Ethernet Turn-up Procedure using the JDSU T-BERD 8000 or T-BERD 6000A March 4, 2009
Gigabit Ethernet Turn-up Procedure using the JDSU T-BERD 8000 or T-BERD 6000A March 4, 2009 Table of Contents Background Information -------------------------------------------------------------------------------------
More information7.4 3M No Polish Connector
Cap Fibre Splice Element Description 3M No Polish Connector (NPC) enables fast, on-site installation of 250μm and 900μm connections utilizing a one piece, pre-assembled design. The SC compatible connector
More informationWhy Expanded Beam types are essential in military and other harsh environment applications
White paper Fiber Optic Connectors Bliek 18 4941 SG RAAMSDONKSVEER NEDERLAND Telephone: +31 162 518 208 Fax: +31 162 518 216 E-mail: info@mcap.nl Website: www.mcap.nl ABN-AMRO: 52.14.96.500 IBAN: NL28ABNA0521496500
More informationHow To Make A Data Center More Efficient
Data Center: Technology Drivers Infrastructure Trends 40G / 100G Migration Maurice F. Zetena III Vice President Leviton Technology Data Center Group Leviton Network Solutions Technology Drivers Convergence
More informationUnderstanding Fiber Polarity: Implications at 10G, 40G, & 100G
Understanding Fiber Polarity: Implications at 10G, 40G, & 100G FIBER POLARITY: 10G and 40/100G OPTIONS Why is this significant in the data center? Data centers will be one of the first places where we
More informationFiber-to-the-Home/FTTH
Hands-On Design, Installation, Maintenance & Troubleshooting Active and Passive Optical Networks Course Description This Hands-On 2-day course is designed to provide technicians with Hands-On practical
More informationOPERATIONS GUIDE OWL
- t c - T Optical Wavelength Laboratories OPERATIONS GUIDE OWLTrek Optical Time Domain Reflectometer (OTDR) Singlemode: WTO-S15 / WTO-S13 / WTO-S35 Multimode: WTO-M85 / WTO-M13 / WTO-M83 Opti l a c a W
More informationInfrastructure for the next three generations
Infrastructure for the next three generations Demand for bandwidth and storage is expanding at a breathtaking rate within the data center, which means that the environment is rapidly evolving, making the
More informationData Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
More informationThe Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
More informationArista 40G Cabling and Transceivers: Q&A
Arista 40G Cabling and Transceivers: Q&A 40G Cabling Technical Q&A Document 40Gigabit Cables and Transceivers Q. What 40G cables and transceivers are available from Arista? A. Arista supports a full range
More informationEnterprise Networks EMEA. Core Products FOR DATA CENTRES
Enterprise Networks EMEA Core Products FOR DATA CENTRES EMEA Data Centre Core Products 1 Data Centres GET IT RIGHT, Right Now. Corning Cable Systems offers tens of thousands of fibre optic products for
More informationHow To Make A Fibre Cable For A Data Centre
LANmark-OF Fibre Optic Solutions for Data Centres Complex Data Centres require fibre solutions CORE SWITCH ACCESS SWITCH SERVER SAN SWITCH LANmark-OF Slimflex Patch Cords LANmark-OF Single Mode LANmark-OF
More informationFiber Optic Light Sources
Phone 800/426 8688 Fax 800/626 0329 3 Fiber Optic Light Sources 7XT Light Source 375 The Photodyne 7XT Light Source is used as a stand alone single-mode dual wavelength laser light source, or in conjunction
More informationDesign Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution. www.commscope.com
Design Guide SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution www.commscope.com Contents Introduction 3 How Does a TAP Work? 3 The TAP Ecosystem 4 InstaPATCH 360 TAP Module Family 4 InstaPATCH
More informationThe following terms are defined within the context of the fiber optic industry
The following terms are defined within the context of the fiber optic industry Adapter A mechanical media termination device designed to align and join fiber optic connectors. Often referred to as coupling,
More informationData Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company
Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs
More informationINTRODUCTION FIGURE 1 1. Cosmic Rays. Gamma Rays. X-Rays. Ultraviolet Violet Blue Green Yellow Orange Red Infrared. Ultraviolet.
INTRODUCTION Fibre optics behave quite different to metal cables. The concept of information transmission is the same though. We need to take a "carrier" signal, identify a signal parameter we can modulate,
More informationAMP NETCONNECT Data Center Cabling Solutions
AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision
More informationReliable, Consistent, Quality
Reliable, Consistent, Quality 1-877-320-3143 www.fibertronics.com Reliable, Consistent, Quality Welcome To Fibertronics Inc. Reliability, consistency, and quality is what we put behind every Fiber optic
More informationOptical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network
Optical Fiber Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network Carl Roberts robertsc@corning.com Cabling considerations for DCs and
More informationCisco SFP Optics for Gigabit Ethernet Applications
Cisco SFP Optics for Gigabit Ethernet Applications The industry-standard Cisco Small Form-Factor Pluggable (SFP) Gigabit Interface Converter is a hot-swappable input/output device that plugs into a Gigabit
More informationRF Video Distribution System. Why Z-Band is The Right Choice for Quality Video
RF Video Distribution System Why Z-Band is The Right Choice for Quality Video Requirements for Quality RF Video Correct Signal & Noise Levels from Source/s Correct Signal & Noise Levels from Backbone Cabling
More informationTrace.Net OTDR Test Management Software User s guide
Trace.Net OTDR Test Management Software User s guide 2007-2009, AFL Telecommunications, all rights reserved. TRAC-01-1000 Revision B, 2009-06-10 Specifications are subject to change without notice. I Contents
More informationQuickSpecs. Models HP X131 10G X2 CX4 Transceiver. HP X131 10G X2 Transceivers (SR, LRM, LR, ER and CX4) Overview. HP X131 10G X2 SC LRM Transceiver
Overview Models HP X131 10G SC SR Transceiver HP X131 10G SC LR Transceiver HP X131 10G SC ER Transceiver HP X131 10G CX4 Transceiver HP X131 10G SC LRM Transceiver J8436A J8437A J8438A J8440C J9144A DA
More informationEuropean Normative EN50173-1. system
European Normative EN50173-1 for generic/structured cabling system Pietro Nicoletti Studio Reti s.a.s piero[at]studioreti.it www.studioreti.it Cabl-New-2003-Engl - 1 P. Nicoletti: see note pag. 2 Copyright
More informationPlug & Play Universal Systems
Plug & Play Universal Systems A LANscape Pretium Plug & Play Universal Systems for Data Centers and Storage Area Networks (SANs) Corning Plug & Play universal systems create a fiber optic tip-to-tip solution
More informationhome site map help ECMS Project: 70197 Standard / Federal Oversight Advertised
Page 1 of 6 S PECIAL PROVISION home site map help ECMS BP ADMIN Project: 70197 Standard / Federal Oversight Advertised Short Description: US 422 Schuylkill River Bridge - D/B: Retaining Wall; ITS Devices;
More informationField Testing Multimode 10 Gb/s (and beyond) Fiber Permanent Links
White Paper April 2011 WP-15 Field Testing Multimode 10 Gb/s (and beyond) Fiber Permanent Links Best Practices to Minimize Costs by Ensuring Measurement Repeatability, Reproducibility and Accuracy Authors:
More informationModule 13 : Measurements on Fiber Optic Systems
Module 13 : Measurements on Fiber Optic Systems Lecture : Measurements on Fiber Optic Systems Objectives In this lecture you will learn the following Measurements on Fiber Optic Systems Attenuation (Loss)
More informationCorning Cable Systems Optical Cabling Solutions for Brocade
Corning Cable Systems Optical Cabling Solutions for Brocade Building high-density, high-port-count, structured cabling solutions to scale storage area networks to thousands of ports Contents Executive
More informationBOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers
BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers WP4259 Issued: January 2015 Brillouin Optical Time Domain Reflectometry The Brillouin Optical
More informationFibre Optic Indoor/Outdoor Cable
Volition TM Fibre Optic Indoor/Outdoor Cable Tough enough to take it. Easy to handle. The Volition Network Solutions Indoor/Outdoor Fibre Optic Cable from 3M includes horizontal and backbone cable with
More informationDat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD
Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,
More information