TECHNICAL SPECIFICATION OF POTENTIAL TRANSFORMER.

Size: px
Start display at page:

Download "TECHNICAL SPECIFICATION OF POTENTIAL TRANSFORMER."

Transcription

1 TECHNICAL SPECIFICATION OF CTPT UNITS FOR 66 KV CONSUMERS * Name of Consumer : * Address : TECHNICAL SPECIFICATION OF POTENTIAL TRANSFORMER. SR.NO. DESCRIPTION UNIT PARTICULARS. A General A.. 1 Designation Potential Transformer A. 2 Type Out door, Oil filled, bottom and dead Tank type electromagnetic, with sealing arrangement. A. 3 Quantity Nos. As required. A. 4 Reference Standards IS A. 5 Nominal System Voltage. KV 66 A. 6 Highest System Voltage. KV 72.5 A. 7 Rated frequency. HZ 50 A. 8 System Neutral Earthing type. Effectively earthed. B DESIGN EQUIPMENTS B. 1 Rated Primary voltage KV / V3 B. 2 Rated Secondary Voltage. Winding-1 V 110 / V3 Winding-2 V 110 / V3 Winding-3 V 110 / V3 Winding-4 V 110 / V3 B. 3 Winding Material. Copper B. 4 Method of connection. 1 Primary winding Star 2 Secondary winding. Winding-1 Star Winding-2 Star B. 5 Application B. 6 Rated burden. Core-1 (Metering). Core-2 (ABT Metering). Core-3 (Yard/control room metering) Core-4 (Protection). DNH PDCL's Rakholi Sub- Station end DNH PDCL's metering at Consumer end B. 7 Rated Power Factor. Winding Winding Winding Winding

2 B. 8 Accuracy class. Winding Winding Winding Winding B. 9 Rated voltage factor. 1.2 continuous, 1.5 for 3 sec B.10 Class of winding insulator. Class A Max winding temperature at 110 % As per IS 3156 B.11 exaction & rated burden. B.12 Creepage distance. Total Protected 23 mm per KV B.13 Secondary cable size 4C x 4.0 mm sq. copper armoured. B.14 Earthing conductor. Material G.I. Size 65 X 10 B.15 Seismic coefficient. Please furnish. B-16 Terminal formation. Horizontal with no dummy/extra terminals. B-17 Terminal marking. Should be provided with metallic tag on primary and secondary side. B-18 Type of base/tank and all exposed 1) Hot deep galvaized. ferrous parts. 2)The PT's must be provided Nitrogen gas filling B-19 Name plate details and wiring diagram with terminal markings. Should be provided legibly on metallic sheet with provision for sealing. Note 1: At DNH PDCL's Sub-Station : The 66KV PT having four cores arrangement by -- (i) The secondary terminals of Metering First core & Second core should be in two different terminal box at one face of PT Unit with proper Sealing arrangement facility for DNH PDCL's Metering and ABT Metering purpose respectively. (ii) The Third core & fourth core for control panel metering and protection purpose & the secondary terminals sholud be in other terminal box at other face of PT unit with proper sealing arrangement facility. Note 2: At Consumer End : (i)(a) For DNH PDCL's Metering : The PT Units having Dual Metering Core as specified above & in which First core is only for DNH PDCL Metering with proper Sealing arrangement facility in one box. (i)(b) There is one hole for cable galnd of 4 core 4.0sqqmm. Armoured cable to be provided (ii) (a) For ABT Metering : The PT Units having Dual Metering Core as specified above & in which second core is only for ABT Metering with proper Sealing arrangement facility in other terminal box at other face of PT. (ii) (b) There is one hole for cable galnd of 4 core 4.0sqqmm. Armoured cable to be provided

3 (iii) For Protection & Operation : The separate PT Units are required to be installed for Metering, Protection & Operation of Consumer's Equipments. Note 3 : The primary terminal connection shall be provided at side of upper tank. Note : 4 Note : 5 Note : 6 (a) (b) (C ) (d) (e) (f) Note : 7 There are no PT Fuse link to be provided in the secodnary terminal box for Metering Core & ABT Metring core. The manufacturer shall furnish the TYPE Test reports for the 66KV PT of the type and Design offered by him. The Tyep Test Reports shall not be older than FIVE YEARS and shall be valid upto expiry of the validity of offer. All the 66KV PT Units to be tested and certified from the Govt. approved NABL Laboratory. The Routine test as per the IS 3156 to be carried out form the Govt. approved NABL Laboratory. The Test Cetificate of NABL Laboratory should comprise Test Result of Folowing Tests.The Polycarbonate / Plastic seals of NABL Laboratory to be provided on each units after succesfully completion of all tests. Accuracy Test : The Limits of Voltage Error and Phase Displacement error at 80%,100% & 120% of rated voltage and 25% and 100% of rated burden at power factor of 0.8 Lagging mandatorily for all windings. Verification of Terminal Markings & Polarity (optional). HV Test on Primary Winding at 3 KV for 1 min (optional). H.V.Test on Secondary winding at 3 kv for 1 min (optional). Induced Over Voltage Test at 140 KV for 40 seconds & 150 Hz (optional). Partial Discharge Test (optional). The secondary terminals should not connected with Elmec connectors. The secondary terminals wiring with Elemec Connectors will not be acccepted by the DNH PDCL. Executive Engineer (Lab.& Vig.) DNH POWER DISTRIBUTION CORPORATION LTD; Dadra & Nagar Haveli, Silvassa

4 TECHNICAL SPECIFICATION OF CURRENT TRANSFORMER. SR.NO. DESCRIPTION UNIT PARTICULARS. A GENERAL 1 Designation Current transformer. 2 Type Out door, oil filled, bottom and dead tank type with sealing arrangement. 3 Quantity Nos. As required. 4 Nominal System voltage KV 66 5 Highest System Voltage. KV Rated frequency. HZ 50 7 System neutral earthing type. Effectively earthed. 8 Rated Current Transformation Ratio 9 Secondary Details. a Nof of cores. Nos. b Rated VA / Accuracy class / ISF Core-1 (Metering). Core-2 (ABT Metering). Core-3 (Yard/control room metering). Core-4 (Protection). A As per requirement in consultation of E.E.(L&V), DNH PDCL for both at Consumer end & DNH PDCL's Sub- Station end. 2 (at Consumer End S/S End 4 (for DNH PDCL's S/S End) 10 / 0.2S / V / 0.2S / V / 0.2S/ V / 0.5 / V-5, 10/5P 10/- c PS Core details i Minimum Knee Point Voltage. V 300 ii Maximum magnetisation current at `Ma Vk. 120 iii Type of reactance. Low d Ratio selection On secondary side. e Terminal formation. Horizontal with no dummy/extra terminals. 10 Terminal marking. Should be provided with metallic tag on primary and secondary side. 11 Extended primary A 120% current rating (clause 4 of IS 2705 Part*2) 12 Short time thermal rating. Current KA 25 Duration Sec Dynamic rating KA 62.5 (Peak) 14 Winding material. Copper. 15 INSULATION a Class of insulation Class A b Maximum temp. rise of winding.

5 Ambient Deg Cent 45 Temp rise Deg Cent 50/ micro sec. impulse withstand KV 325 +ve & -ve. (Peak) 17 One minute power frequency withsta KV (rms) Type of base/tank and all exposed 1) Hot deep galvaized. ferrous parts. 2) The CT's must be provided Nitrogen gas filling with rubber Gasket will be acceptable in case of 66 KV class of voltage as per standard. 19 Name plate details and wiring diagram with terminal markings. Should be provided legibly on metallic sheet with provision for sealing Note 1: DNH PDCL's Sub-Station : The 66KV CT having Four core arrangement by -- (i) The secondary terminals of Metering First core & Second core should be in two different terminal box at one face of CT Unit with proper Sealing arrangement facility for DNH PDCL's Metering and ABT Metering purpose respectively. (ii) The third core for control panel metering and fourth core for protection purpose & the secondary terminals of second & third core sholud be in one combined terminal box at other face of CT unit with proper sealing arrangement facility. Note 2: At Consumer End : (i)(a) For DNH PDCL's Metering : The CT Units having Dual Metering Core as specified above & in which First core is only for DNH PDCL's Metering the secondary terminals of First core are to be in one box at one face of CT unit with proper Sealing arrangement facility.. (i)(b) There is one hole for cable galnd of 4 core 4.0sqqmm. Armoured cable to be provided (ii)(a) For ABT Metering : The CT Units having Dual Metering Core as specified above & in which second core is only for ABT Metering purpose. The secondary terminals of Second core are to be in one box at one face of CT unit with proper Sealing arrangement facility.. (ii)(b) There is one hole for cable galnd of 4 core 4.0sqqmm. Armoured cable to be provided (iii) For Protection & Operation : The separate CT Units are required to be installed for Metering, Protection & Operation of Consumer's Equipments. Note 3 : The primary terminal connection shall be provided at side of upper tank. Note-4 :- The unit should be hermetically sealed and suitable for hot line washing. Note 5 : The manufacturer has to be given the certificate that "There is no electronic Remote Device /Switch etc..are provided inside the CT unit" Note : 6 The manufacturer shall furnish the TYPE Test reports for the 66KV CT of the type and Design offered by him. The Tyep Test Reports shall not be older than FIVE YEARS and shall be valid upto expiry of the validity of offer.

6 Note : 7 (a) (b) (C ) (d) (f) Note : 7 All the 66KV CT Units to be tested and certified from the Govt. approved NABL Laboratory. The Routine test as per the IS 2705 to be carried out form the Govt. approved NABL Laboratory. The Test Cetificate of NABL Laboratory should comprise Test Result of Folowing Tests. The Polycarbonate / Plastic seals of NABL Laboratory to be provided on each units after succesfully completion of all tests. Accuracy Test : The Limits of Error and Phase Displacement error at 5%,20%,100% & 120% of rated Current and 25% and 100% of rated burden at power factor of 0.8 Lagging & Unity mandatory for all core, all ratio. Verification of Terminal Markings & Polarity (optional). HV Test on Primary Winding at 140 KV for 1 min (optional). H.V.Test on Secondary winding at 3 kv for 1 min (optional). Partial Discharge Test (optional). The secondary terminals should not connected with Elmec connectors. The secondary terminals wiring with Elemec Connectors will not be acccepted by the DNH PDCL. Executive Engineer (Lab.& Vig.) DNH POWER DISTRIBUTION CORPORATION LTD; Dadra & Nagar Haveli, Silvassa

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:

SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under: REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer 168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB KOLMA and IHDA Indoor Type Cable Current Transformers Index Description... 3 Technical

More information

Current transformer selection guide

Current transformer selection guide The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

OLI. Oil level indicator

OLI. Oil level indicator OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

Enhanced Quality with a Touch of Style

Enhanced Quality with a Touch of Style Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying

More information

Medium-voltage transformers

Medium-voltage transformers Medium-voltage transformers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: info@mbs-ag.com Web: www.mbs-ag.com Contents Current transformers Technical characteristics

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation

SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation 4 Compliance Proof of Compliance (Sub clause 4.1.1) The SABS safety mark The SABS approved performance mark

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

3-phase, bidirectional energy meter

3-phase, bidirectional energy meter Data sheet www.sbc-support.com 3-phase, bidirectional energy meter with S0 pulse output Bidirectional energy meter with S0-interface. The S0 interface is a hardware interface for the transmission of measured

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide 1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk 1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

13 SERIES. Electronic step relays 10-16 A 13.81 13.91

13 SERIES. Electronic step relays 10-16 A 13.81 13.91 13 Electronic step relays 10-16 A 13 13.81 - Electronic step relay - Rail mount - 1 Pole 13.91 - Electronic step relay and timing step relay Switch box mount - 1 Pole Fixed time (10 minutes) timing function

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

LOW-VOLTAGE CURRENT TRANSFORMERS

LOW-VOLTAGE CURRENT TRANSFORMERS LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: export@lumel.com.pl ul. Słubicka 657 Zielona Góra CONTENTS

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439

More information

Capacitor Voltage Transformer. Answers for energy.

Capacitor Voltage Transformer. Answers for energy. Capacitor Voltage Transformer Answers for energy. Capacitor Voltage Transformer Siemens Capacitor Voltage Transformers are based on technology from Trench, a recognized world leader in the design and manufacture

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

RENEWABLE ENERGY SUBSTATIONS SOLAR PHOTOVOLTAIC AND WIND POWER. tgood.com. Energy. Fast.

RENEWABLE ENERGY SUBSTATIONS SOLAR PHOTOVOLTAIC AND WIND POWER. tgood.com. Energy. Fast. RENEWABLE ENERGY SUBSTATIONS SOLAR PHOTOVOLTAIC AND WIND POWER tgood.com Energy. Fast. TGOOD is a world leading manufacturer of prefabricated renewable energy substations PRODUCT CONCEPT ENVIRONMENTAL

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W

Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

a Nexans company Catalogue 2014

a Nexans company Catalogue 2014 a Nexans company Catalogue 2014 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated

More information

HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI

HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI POLAND 01-330 WARSZAWA, ul. Mory 8, tel. (+48 22) 836-80-48, fax (+48 22) 836-80-48 e-mail: ewn@ien.com.pl EWN/70/E/11-1 APPENDIX 4 APPENDIX 4 for test report

More information

Tape Wound, Split Core and Ebony Current Transformers

Tape Wound, Split Core and Ebony Current Transformers Tape Wound, Split Core and Ebony Current Transformers Current Transformers Contents Page Tape Wound Measuring and Protection Current Transformers 2 6 Split Core Current Transformers 7 9 3-in-1 Current

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155

DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155 DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155 Technical information Version: 07.14 General Function The speed sensors family DSD.70 are suitable for generating

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System

KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System 2-32 A Lighting Busbar System 4-63 A Plug-in Busbar Distribution System / E-LINE KX Compact Busbar Distribution System 63...63 A E-LINE KB Compact Busbar Distribution System 8...63 A E-LINE KO Plug-in

More information

Current & Instrument Transformers

Current & Instrument Transformers Reliable & Accurate Inputs for Measuring & Protection Equipment Current & Instrument Transformers Type MKE11 Inside the Catalogue Range Specifications Ordering Code Delivering Value to You M-Kris Electric

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

Inductive Proximity Sensors

Inductive Proximity Sensors M12 Inductive Proximity Sensors Standard Length Mini's Extended Sensing 3 Wire DC 2 Wire DC 2 Wire AC (Wiring Schematic) 3 Wire DC PNP Normally Open (1) IMM32122C IMM35124C IMN32122C IMN35124C IMN32122M12

More information

Tape Wound, Split Core and Ebony Current Transformers

Tape Wound, Split Core and Ebony Current Transformers Tape Wound, Split Core and Ebony Current Transformers Table of contents Tape Wound Measuring and Protection Current Transformers 2 MR Series Measuring Range 3 PR Series Protection Range 4 Class PX Current

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

POWER RELAY. FTR-K1-KS Series. 1 POLE - 16A / Inrush 120A relay FTR-K1 SERIES FEATURES

POWER RELAY. FTR-K1-KS Series. 1 POLE - 16A / Inrush 120A relay FTR-K1 SERIES FEATURES POWER RELAY POLE - 6A / Inrush 20A relay FTR-K-KS Series FTR-K SERIES FEATURES pole 6A, form A or form C Peak inrush current 20A / TV-8 Coil power 400mW High insulation in small package (between coil and

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

0.84" x 2.00" Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP.

0.84 x 2.00 Z-TRAUQ INC. Tel.: (450)226-6997 Fax: (450)226-5837 z-trauq@qc.aira.com SPLIT CORE CURRENT TRANSFORMER MODEL 1SP. SPLIT CORE CURRENT MODEL 1SP 0.84" x 2.00" PAGE No 3-2 REV 18DEC00 UL 1015 LEAD WIRE, STANDARD LENGTH IS 36 E DIMENSIONS A = 0.84 MIN B = 2.00 MIN C = 3.31 MAX D = 3.09 MAX E = 0.61 MAX F = 0 MAX F C B

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

MOUNTING AND OPERATING INSTRUCTIONS

MOUNTING AND OPERATING INSTRUCTIONS MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall

More information

www.jameco.com 1-800-831-4242

www.jameco.com 1-800-831-4242 Distributed by: www.jameco.com 1-800-831-4242 The content and copyrights of the attached material are the property of its owner. SPECIFICATION CUSTOMER: JAMES DATE: 04.08.23 MODEL NO: DBU090030 DESIGNED

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials VDE Information General Information The voltage which can be applied to a terminal depends on the relevant regulations, the installation conditions and, of course, the dimensions and insulating materials

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Emergency lighting units EM powerled

Emergency lighting units EM powerled M BASIC 1 W Combined emergency lighting Driver 1 4 W Product description Emergency lighting Driver for manual testing SEV for output voltage < 60 V DC ow-profile casing (21 x 30 mm cross-section) 5-year

More information

AMIS. Automated Metering and Information System. Integration of meters from other manufacturers

AMIS. Automated Metering and Information System. Integration of meters from other manufacturers AMIS Automated Metering and Information System TD-3530/TACU30 Third-Party Device Gateway Integration of meters from other manufacturers Connection and integration of max. 3 meters from third party manufactureres

More information

Fiber Optic High Density ACC Sensor System Faser Optisches Beschleunigungs-Messsystem

Fiber Optic High Density ACC Sensor System Faser Optisches Beschleunigungs-Messsystem End Winding Remote unit PNR: 9600.30.180 Remote unit and 6 x One-Axis optical, MIC-Accelerometer Frequency response 1 1000 Hz Easy installation on the end-winding High voltage electrical insulation between

More information

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications 077 Series Analogue Features Monitors and controls any variable which can be converted to an A.C. or D.C. signal. Rugged, shock and vibration resistant design Indicator, relays and power unit in one housing

More information

Kit 106. 50 Watt Audio Amplifier

Kit 106. 50 Watt Audio Amplifier Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

SEISMIC VELOCITY TRANSDUCER T1-40

SEISMIC VELOCITY TRANSDUCER T1-40 SEISMIC VELOCITY TRANSDUCER T1-40 Measurement of Omnidirectional Absolute Vibrations Certified according to ATEX 94/9/CE directive OPERATION Transducer T1-40 serves for seismic measurement of the absolute

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information