SURGE PROTECTIVE DEVICES

Size: px
Start display at page:

Download "SURGE PROTECTIVE DEVICES"

Transcription

1 SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood of equipment dielectric failure. Several components can be used to limit and/or eliminate the surges. This document provides general specification for the surge protective devices (SPDs) to be installed in LV electrical systems. SPDs shall be installed near the origin of the installation or in the main switchboard assembly, however additional SPDs might be necessary to protect sensitive equipment and when the distance from the main SPD to the next distribution board is big (> 30m). These secondary SPDs shall be coordinated with the upstream SPDs. 2. SPECIFICATIONS 2.1. STANDARDS The accomplishment of the following standards are required: STANDARD EN Type 1, Type 2 and Type 3. Surge protective devices connected to low voltage power distribution systems. Part 1. This is the European variation of IEC which is mandatory in European countries IEC Class I, Class II and Class III test Edition 2 ( march 2005): Surge protective devices connected to low voltage power distribution systems. Part IEC Electrical installations of buildings - Part 4-443: Protection against overvoltages of atmospheric origin or due to switching IEC Electrical installations of buildings - Part 5-534: Devices for protection against overvoltages IEC Degrees of protection provided by enclosures (IP code) 2.2. CERTIFICATIONS Both EN & IEC Certifications are required CE marking (to IEC Class I, Class II and Class III test) METHOD Third Party Lab Third Party Lab or self certified A safety mark of conformity shall be required: ÖVE, NF, KEMA,. SPD Engineering Specification Latest.doc 1

2 2.3. SURGE CURRENT RATINGS AND PROTECTION LEVELS Iimp (Type 1)/ Imax (Type 2): The value of Iimp shall not be less than 12,5kA for each mode of protection [IEC ]. In case the connection type 2 is used (see ) the value of Iimp (N-PE) shall not be less than 50 ka for three-phase systems and 25 ka for single-phase systems [IEC ]. The preferred values for the impulse current for Type 1 test SPD are 35 /50 ka (L-PE or L-N), 50kA (N-PE single phase systems when using connection type 2) and 100kA (N-PE three phase systems when using connection type 2) The preferred values for the maximum surge current rating Imax for Type 2 tests SPDs are 8kA, 20kA, 40kA and 65kA. In: The nominal discharge current In shall not be less than 5kA for each mode of protection [IEC ]. Up: The protection level of the protective device (Up) shall not be higher than the level of overvoltage category II (2,5kV) [IEC ]. If sensitive electronics is to be protected the protection level shall not be higher than 1,5 kv. Uc: For a 230/400V network it is recommended the Maximum Continuous Operating System (Uc) to be no less than 340 V. Response time: The response time of Type I SPD shall be no more than 1μs, the response time of Type 2 SPD shall be no more than 25 ns MECHANICAL REQUIREMENTS SPD Engineering Specification Latest.doc 2

3 2.4.1 Housing Material Housing material must conform the necessary standards (including self flame-extinguishing characteristics), Required Housing Markings Compliance to IEC Section Test certification marks Terminal Connection 35mm2 is preferred End of Life Indicators All products (except products to be connected N-PE) will have an End of Life visual indicator. The indication shall be LED or mechanical. If LED is used must be ON for normal operation (green color). When reach the end of life LED or mechanical indication must be Red Mounting Method Standard Snap on 35 mm DIN Rail mounting Shock, Impact, Reference IEC Vibration Enclosure Protection Comply with IEC IP20 rating 2.5. ENVIRONMENTAL REQUIREMENTS Minimum Operating Range -5 C to +40 C Relative Humidity 5% to 90% Altitude 2000 Meters minimum without derating 2.6. ELECTRICAL REQUIREMENTS Remote Indication Thermal Protection Short circuit Protection System Frequency Breaker Coordination Optional. When required use Dry Contacts (250 VAC 1.5A, 125V 3A desired, min Amps at 250V required). Thermal fusing is required for MOVs. Not required for GDTs External dedicated circuit breaker to the SPD is required to guaranty the continuity of service and electrical installation safety in case of short circuit inside the SPDs. 47 Hz to 62 Hz Provide coordinated disconnect device requirements which will be put in the literature and on product as required by the manufacturer recommendations. SPD Engineering Specification Latest.doc 3

4 3 INSTALLATION RECOMMENDATIONS 3.1 SPD configuration depending on the grounding system: TT systems (connection type 2): TN-S, TN-C systems: For TN-S, TN-C systems it can be used connection type 2 (see ) or alternatively connection type 1 as per below (if there is significant distance between the N-PE bonding point it shall be used and additional SPD N-PE): SPD Engineering Specification Latest.doc 4

5 3.1.3 IT systems: 3.2 Connecting conductors: The length of the connecting conductors from the lines to the SPD added to the cable conductor from the SPD to the main earth terminal shall be less than 0,5 m (IEC ). The cross section of the cables shall not be less than 4 mm². When there is a lightning protection system, for type 1 products the cross section shall not be less than 16 mm ². SPD Engineering Specification Latest.doc 5

6 3..3 External dedicated protection: An external dedicated protection will be installed to protect against overcurrent and consequences of SPD failure and to optimize the continuity of service.... SPD Engineering Specification Latest.doc 6

wietap wietap Overvoltage Protection Tensions running high

wietap wietap Overvoltage Protection Tensions running high wietap wietap Overvoltage Protection Tensions running high 2 wietap wietap Overvoltage protection Important information on overvoltage The necessity of overvoltage protection on machines and systems as

More information

CATALOGUE SURGE PROTECTION LOW VOLTAGE

CATALOGUE SURGE PROTECTION LOW VOLTAGE CATALOGUE SURGE PROTECTION LOW VOLTAGE SALTEK, s.r.o. (limited liability company), is a Czech company specialising in the development and manufacture of surge protection devices (SPD). SALTEK offer a wide

More information

SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation

SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation 4 Compliance Proof of Compliance (Sub clause 4.1.1) The SABS safety mark The SABS approved performance mark

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

The power of nature, the control of technology From ABB's experience, OVR PV: surge protection in photovoltaic plants

The power of nature, the control of technology From ABB's experience, OVR PV: surge protection in photovoltaic plants The power of nature, the control of technology From ABB's experience, OVR PV: surge protection in photovoltaic plants Made for the sun, threatened by atmospheric discharges The importance of surge protective

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

Surge Protection for Photovoltaic Systems

Surge Protection for Photovoltaic Systems Surge Protection for Photovoltaic Systems 2 photovoltaic generator disconnection boxes Index Introduction 4 Protection of PV systems 5 Surge Protection Range for PV system 6 Surge Protection Panels for

More information

White paper. ABB solutions for switching and protection of low speed wind turbines

White paper. ABB solutions for switching and protection of low speed wind turbines White paper ABB solutions for switching and protection of low speed wind turbines ABB solutions for switching and protection of low speed wind turbines Index 1 Introduction...2 2 Full converter configuration...4

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

ABB - Pôle Foudre Soulé & Hélita OVR PLUS N1 40

ABB - Pôle Foudre Soulé & Hélita OVR PLUS N1 40 Presentation ABB - OVR PLUS N1 40 ABB France Lightning Protection Group All in one product SPDs with integrated back up protection are a solution that allow to have a complete surge protection design into

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

How To Build A Low Voltage Capacitor Lvcp

How To Build A Low Voltage Capacitor Lvcp Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

Electrical safety and protection devices

Electrical safety and protection devices Electrical safety and protection devices RCD PROTECTION The easy, economical way to safeguard yourself when working with electricity. RCDs are specifically designed to minimise the risk of a fatal electric

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

Intersection Preassembled 19-inch Rack

Intersection Preassembled 19-inch Rack Intersection Preassembled 19-inch Rack The intersection preassembled 19-inch rack comes fully assembled, wired and ready to be installed in a server rack. The rack provides communications, power conversion

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Class I surge protection with sparkover gaps

Class I surge protection with sparkover gaps for low-voltage supplies surge protection with sparkover gaps Lightning conductors with sparkover gap for lightning protection or equipotential bonding providing class I According to the requirements of

More information

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Surge protection for emergency alarm systems

Surge protection for emergency alarm systems Surge protection for emergency alarm systems White Paper Contents Lightning and surge protection for a burglar alarm system with pulse polling technology Lightning and surge protection for a fire alarm

More information

Main catalog. System pro M compact Surge and lightning protection solutions with QuickSafe technology

Main catalog. System pro M compact Surge and lightning protection solutions with QuickSafe technology Main catalog System pro M compact Surge and lightning protection solutions with QuickSafe technology System pro M compact Surge and lightning protection solutions with QuickSafe technology Presentation

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

How can a charging station for electric vehicles be set up simply and safely?

How can a charging station for electric vehicles be set up simply and safely? SB18 Building > Electromobility > Charging Station Design How can a charging station for electric vehicles be set up simply and safely? Requirement In order to supply electric vehicles with electric power,

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000. NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51 34 Series - Slim electromechanical PCB relays 6 34 SERIES Features 34.51 Ultra-slim 1 Pole - 6 relay Printed circuit mount - direct or via PCB socket 35 mm rail mount - via screw, screwless or push-in

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

DEHNshield Application-optimised multipole combined lightning current and surge arrester

DEHNshield Application-optimised multipole combined lightning current and surge arrester DEHshield Application-optimised multipole Application-optimised prewired combined lightning current based on spark gap technology simply equipped electrical installations with reduced technical requirements

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/2

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/2 Power Supply, Primary Switch Mode, Narrow Design -PS-100-240AC/24/2 POWER provides: Extra narrow widths of 22.5 and 45 mm (0.886 and 1.772 in.) Global use due to a wide range input A high level of operational

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/2x15DC/1

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/2x15DC/1 Power Supply, Primary Switch Mode, Narrow Design -PS-100-240AC/2x15DC/1 POWER provides: Extra narrow widths of 22.5 and 45 mm (0.886 and 1.772 in.) Global use due to a wide range input A high level of

More information

DC Combiner box and AC solutions. Leadership in circuit protection

DC Combiner box and AC solutions. Leadership in circuit protection DC Combiner box and AC solutions Leadership in circuit protection Eaton and Cooper united. Energizing a world that demands more. We deliver: Electrical solutions that use less energy, improve power reliability

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract

More information

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. Ensuring operational continuity To ensure the operational continuity of an electrical

More information

3-phase, bidirectional energy meter

3-phase, bidirectional energy meter Data sheet www.sbc-support.com 3-phase, bidirectional energy meter with S0 pulse output Bidirectional energy meter with S0-interface. The S0 interface is a hardware interface for the transmission of measured

More information

KNX Interface. User Manual PM00A00IRI

KNX Interface. User Manual PM00A00IRI KNX Interface User Manual PM00A00IRI 1/9 1. Index 1. Index...2 2. Preface... 3 2.1. Overview... 3 2.2. System description... 3 2.3. Application programs... 3 2.4. Documentation... 3 3. Mechanical reference...

More information

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket Technical Datasheet SNK636D00 Catalogue Page SNK636S00 ZS-SF-T Screw Clamp Terminal Blocks For x 0 and x fuses - with test socket - Protect your circuit with x and x0 fuse terminal blocks (fuse not supplied

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable

More information

ZS25 Screw Clamp Terminal Blocks Feed-through

ZS25 Screw Clamp Terminal Blocks Feed-through Technical Datasheet SNK668D0 Catalogue Page SNK678S0 ZS Screw Clamp Terminal Blocks Feed-through Save space by connecting conductors up to mm² AWG in just mm 0.47 in spacing. SNK68V004 SNK004F0000 D CAD

More information

A project to optimise quality and energy efficiency must include metering

A project to optimise quality and energy efficiency must include metering EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,

More information

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1

Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1 Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade Technical Datasheet SNK646D00 Catalogue Page SNK646S00 ZS6-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,

More information

TECHNICAL DESCRIPTION OF THE DISTRIBUTION SUBSTATION REMOTE MONITORING SYSTEM

TECHNICAL DESCRIPTION OF THE DISTRIBUTION SUBSTATION REMOTE MONITORING SYSTEM HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. NOTICE OF CALL FOR TENDERS No ND-xxx PROJECT: Pilot Telemetering and Management System for the Electric Power Supply Demand by Residential and Small

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Surge Protection. Electrical Installations. Photovoltaic. Telecom. Data. Radiocommunication

Surge Protection. Electrical Installations. Photovoltaic. Telecom. Data. Radiocommunication 9 th e d i t i o n Surge Protection Electrical Installations Photovoltaic Telecom Data Radiocommunication General atalog 9 th edition p. 6 DIN RAIL A POWER SURGE PROTETORS p. 60 P HOTOVOLTAI SURGE PROTETORS

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket Technical Datasheet SNK64D00 Catalogue Page SNK64S00 ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket - Ease your test operations with the built-in test sockets, - Screwdriver

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050 Extract from the online catalog DEK-REL- 24/1/SEN Order No.: 2964050 Relay terminal block for sensor, with soldered-in miniature relays, contact (AgNi+Au): small to medium loads, 1 N/O contact, input voltage

More information

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control

More information

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA

CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA Highlights & Features Reliable design, with expected life of 10 years Compact, rugged design for ease of handling and installation Multiple connections to terminals allowed Designed for Class I Div. 2

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

Thermal-Magnetic Circuit Breaker 3120-...-M1-..

Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping

More information

How To Understand The Electrical Power Supply Of A Power Supply System

How To Understand The Electrical Power Supply Of A Power Supply System 17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

PHOENIX CONTACT - 2012-12-14. Features

PHOENIX CONTACT - 2012-12-14. Features Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed

More information

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm

More information

ICON Server box installation manual Rev. 1.1

ICON Server box installation manual Rev. 1.1 ICON Server box installation manual Rev. 1.1 Contents 1.0 About this manual... 3 2.0 Intended use... 3 2.1 European WEEE directive... 3 3.0 Installation and service instructions... 4 Server box overview...

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

Installation instructions for mains wire-in protectors ESP D1, D1R, D1/LCD and D1R/LCD variants

Installation instructions for mains wire-in protectors ESP D1, D1R, D1/LCD and D1R/LCD variants Installation instructions for mains wire-in protectors ESP D1, D1R, D1/LCD and D1R/LCD variants Introduction This document explains how to install Furse Electronic Systems s for mains power supplies: Single

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00 Soft Starter Three Phase General Purpose Soft Starters Type RSGD Soft starting and soft-stopping of 3-phase squirrel cage motors 45mm wide IP20 housing Operational Voltage: RSGD40 (220-400V), RSGD60 (220-600V)

More information

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection

More information