Manual motor starter MS116
|
|
|
- Arthur Ellis
- 9 years ago
- Views:
Transcription
1 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less against short-circuit, overload and phase failures. Fuse less protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. Fuse less starter combinations are setup together with contactors. Description Phase unbalance and phase loss sensitivity Disconnect function Temperature compensation from C Adjustable current setting for overload protection Suitable for three- and single-phase application Trip-free mechanism Clear switch position indication ON/OFF Ordering details MS116 screw terminal Setting range Type Trip Order code Packaging Weight [A] class unit [Pcs] [g] MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R MS A 1SAM250000R Note: MS116 with pre-assembled auxiliary contact HKF1-11, please order as follow 1SAM250005Rxxxx
2 Application The manual motor starters protect the load and the installation against short-circuit and overload. They are three pole protection devices with thermal tripping elements for overload protection and electro-magnetic tripping elements for shortcircuit protection. Furthermore, they provide a disconnect function for safely isolation of the installation and the supply and can be used for the manual switching of loads. The manual motor starters have a setting scale in Amperes, which allows the direct adjusting of the device without any additional calculation. In compliance with international and national standards, the setting current is the rated current of the motor and not the tripping current (no tripping at 1.05 x I, tripping at 1.2 x I; I = setting current). Operation mode Single-phase operation Three-phase operation Connections Terminals 1L1, 3L2, 5L3 Test function Current setting range Terminals 2T1, 4T2, 6T3 Resistance and power losses per phase Type Lower value Upper value Resistance Power dissipation per Phase [W] at setting range setting range per phase Lower value of Upper value of [A] [A] [W] setting range setting range MS MS MS MS MS MS MS MS MS MS MS MS Manual motor starter MS116 Data sheet
3 Dimensions Manual motor starter MS116 80,1 / 3,15" 70 / 2,76" 1,5 / 0,06" 5,5 / 0,22" 43,5 / 1,71" 90 / 3,54" 1,7 / 0,07" 75 / 2,95" 35 / 1,38" 45 / 1,77" 14 / 0,55" 14 / 0,55" 45 / 1,77" Maßbild_MS116_mm_inch Manual motor starter MS116 with FS116 Ø4,5 / Ø 0,18" 9 / 0,35" 5,4 / 0,21" 122 / 4,8" 110 / 4,33" 17,5 / 0,69" Maßbild_MS116-Festschraubvorr Wiring diagram Data sheet Manual motor starter MS116 3
4 Data at T A = 40 C and at rated values, if nothing else indicated Type Technical data Main circuit Terminals 1L1-3L3-5L5 2T1-4T2-6T3 Rated operational voltage U e acc. to IEC/EN AC 690 V Rated operational current I e Rated current I n / Conventional free-air thermal current I th Setting range - thermal overload protection Rated instantaneous short-circuit current setting I i Rated service short-circuit breaking capacity I cs Rated ultimate short-circuit breaking capacity I cu Trip class acc. to IEC/EN Rated frequency acc. to IEC/EN DC - Number of poles 3 Resistence per phase MS116 see Rated Operational Current see ordering data see ordering data 50 / 60 Hz Power dissipation per phase lower value of setting range upper value of setting range Isolation data Rated impulse withstand voltage U imp acc. to IEC/EN kv Rated insulation voltage U i acc. to IEC/EN V Pollution category acc. to IEC/EN Electrical connection Connecting capacity solid 1/2 x mm 2 flexible with ferrule 1/2 x mm 2 flexible with ferrule isolated 1/2 x mm 2 flexible without ferrule 1/2 x mm 2 Stripping length 9 mm Tightening torque Nm connection screw M3.5 (Pozidrive 2) General data Mechanical durability Electrical durability Duty time 100% Dimensions (W x H x D) see dimension drawing Weight see ordering data Mounting DIN-rail (EN 60715) Mounting position optional for single mounting (position 1-6) Group Mounting on request Minimum distance to other units same type horizontal none vertical 150 mm Minimum distance to electrical conductive wall (earthed) horizontal 25 mm vertical 75 mm Degree of protection acc. to IEC/EN enclosure / terminals IP20 Utilization Category acc. to IEC/EN A Altitude up to 2000 m 4 Manual motor starter MS116 Data sheet
5 Type MS116 Environmental data Ambient air temperature range Operation open - compensated -25 C C open -25 C C Storage -50 C C Temperature compensation continuous Vibration (sinusoidal) acc. to IEC/EN (Fc) 5 g / Hz Shock (half-sine) acc. to IEC/EN (Ea) 25 g / 11 ms Standards / Directives Product standard IEC/EN , ICE/EN , IEC/EN , UL 508, CSA 22.2 No. 14 Low Voltage Directive 2006/95/EC EMC Directive 2004/108/EC RoHS Directive 2002/95/EC Electromagnetic compatibility Approvals, markings Approvals Markings not applicable see last page see last page UL/CSA Max. operational voltage 600 V General purpose rating at max. 600 VAC Motor ratings Horse power Full load amps (FLA) Locked rotor amps (LRA) Short circuit rating RMS at 480 VAC A 30 ka A 18 ka Short circuit rating RMS at 600 VAC 5 ka Short-Circuit Protective devices Electrical connection Connecting capacity solid 1/2 x AWG16... AWG12 stranded 1/2 x AWG16... AWG12 flexible without ferrule 1/2 x AWG16... AWG12 Stripping length 9 mm Tightening torque 10 lb-in connection screw M3.5 (Pozidrive 2) Data sheet Manual motor starter MS116 5
6 Type Rated instantaneous Rated operational current [A] short-circuit current setting [A] MS MS MS MS MS MS MS MS MS MS MS MS Short-Circuit protection Setting range, short-circuit breaking capacity and max. back-up fuse Maximum rated current of the back-up fuses if l CC > l CS Setting ranges 230 V AC 400 V AC 440 V AC 500 V AC 690 V AC A A I CU gg, am I CU gg, am I CU gg, am I CU gg, am I CU gg, am ka ka A ka ka A ka ka A ka ka A ka ka A No back-up fuse required up to l cc = 30 ka No back-up fuse required up to l cc = 50 ka l CS = Rated service short-circuit breaking capacity l CU = Rated ultimate short-circuit breaking capacity l CC = Prospective short-circuit current at installation location l CU = l CS in case of MS116 6 Manual motor starter MS116 Data sheet
7 UL / CSA ratings Type Motor rating, single phase 120 V AC 240 V AC 480 V AC 600 VAC hp FLA LRA hp FLA LRA hp FLA LRA hp FLA LRA MS MS MS MS MS MS / MS / / /2 - - MS / / / /2 - - MS / / MS / / MS / MS /2 - - Type Motor rating, three phase 120 V AC 240 V AC 480 V AC 600 V AC hp FLA LRA hp FLA LRA hp FLA LRA hp FLA LRA MS MS MS MS MS /2 - - MS / /4 - - MS / /2 - - MS MS / / MS /2 - - MS / / MS Type General purpose Protective devices rating at max. Fuse K5 / RK5 Circuit breaker 600 VAC [A] [A] [A] MS MS MS MS MS MS MS MS MS MS MS MS Data sheet Manual motor starter MS116 7
8 Contact us ABB STOTZ-KONTAKT GmbH P. O. Box Heidelberg, Germany Phone: +49 (0) Fax: +49 (0) [email protected] You can find the address of your local sales organisation on the ABB home page -> Low Voltage products Approvals culus UL 508 CCC GOST-F GL GOST-R Order Number 2CDC D0201 printed in Germany (08/09-x-xxx) CB Scheme RMRS Markings CE Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2009 ABB All rights reserved
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
Electronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
Manual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection
Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41
Data sheet Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 The three-phase monitoring relays CM-PSS.x1 monitor the phase parameters phase sequence, phase failure as well as over- and undervoltage.
Catalog. Modular DIN rail components Installation contactors
Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation
Bimetallic Overload Relay Specifications
Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions
Type: DILM32 10(24V50HZ) Article No.: 277247
Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
System pro M compact Miniature Circuit Breaker S 200/S 200 M
Data Sheet System pro M compact Miniature Circuit Breaker S 200/S 200 M 2CDC021023S0012 2CDC021038S0012 The miniature circuit breakers of the System pro M compact series S 200 and S 200 M provide state-of-the-art
Thermistor motor protection relays CM-MSS.22 and CM-MSS.23
Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
Technicaldata General
Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description
Molded Case Circuit Breaker Specifications Bulletin Number 140U-D
Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents
Type: DILM9 10(24VDC) Article No.: 276705
Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50
ZS6-S Screw Clamp Terminal Blocks Disconnect with blade
Technical Datasheet SNK646D00 Catalogue Page SNK646S00 ZS6-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,
ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket
Technical Datasheet SNK636D00 Catalogue Page SNK636S00 ZS-SF-T Screw Clamp Terminal Blocks For x 0 and x fuses - with test socket - Protect your circuit with x and x0 fuse terminal blocks (fuse not supplied
Technical catalogue. Modular DIN rail components Installation contactors
Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
ZS25 Screw Clamp Terminal Blocks Feed-through
Technical Datasheet SNK668D0 Catalogue Page SNK678S0 ZS Screw Clamp Terminal Blocks Feed-through Save space by connecting conductors up to mm² AWG in just mm 0.47 in spacing. SNK68V004 SNK004F0000 D CAD
Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection
Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional
Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1
MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual
ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket
Technical Datasheet SNK64D00 Catalogue Page SNK64S00 ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket - Ease your test operations with the built-in test sockets, - Screwdriver
PSR The compact range Description
Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides
LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil
Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -
Manual Motor Starter MS 116 up to 16 A Technical Data
Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates
Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA
Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA Miniature Circuit Breaker SU 200 M The next generation MCB for UL/CSA applications within
Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)
Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic
Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43
Data sheet Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43 The three-phase monitoring relay CM-MPS.43 monitors the phase parameters phase sequence, phase failure, over- and undervoltage
Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00
Soft Starter Three Phase General Purpose Soft Starters Type RSGD Soft starting and soft-stopping of 3-phase squirrel cage motors 45mm wide IP20 housing Operational Voltage: RSGD40 (220-400V), RSGD60 (220-600V)
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,
Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Relés e Contatores de Estado Sólido SIRIUS
Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico
Pluggable interface relays CR-P Pcb relays
2CDC 293 034 F0004 1 2 4 3 Features 9 different supply s: DC versions: 12 V, 24 V, 48 V, 110 V AC versions: 24 V, 48 V, 110 V, 120 V, 230 V Output contacts: 1 c/o (16 A) or 2 c/o (8 A) Cadmium-free contact
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
CompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA
Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control
W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6
W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6 W SCHRACK-INFO Any mains connection If using 4-pole. switches with 3 or 2-poles, ensure connection acc. to assembly instructions
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
SMC -3 Specifications
Technical Data SMC -3 Specifications Bulletin Number 150 Topic Page Product Overview 2 Standards Compliance and Certifications 2 Features 3 Catalog Number Explanation 4 Wiring Diagrams 6 General Specifications
48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
Redundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.
Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview
BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
Thermal-Magnetic Circuit Breaker 3120-...-M1-..
Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping
E-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear
Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
RY2 miniature industrial relays
6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,
Safety automation solutions
Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO
D-Line Contactors, Overload Relays and Accessories
D-Line Contactors, Overload Relays and Accessories Class 850 CONTENTS Description......................................................Page General Information...............................................
Plug and Socket Devices CES 63 A Series 8579
www.stahl.de > Switch socket / plug 63 A > Large switch handle with clear switch position indication padlockable in 0- and I-position > Low insertion and withdrawal forces through individually encapsulated
ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011
, 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.
ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011
Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are
Contact expander modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:
PHOENIX CONTACT - 2012-12-14. Features
Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
MNS is Switchgear System Technical Overview
Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known
Breakers and Switches. Switches Switch-disconnectors OT, OETL, OTDC and OTM
Breakers and Switches Switches Switch-disconnectors OT, OETL, OTDC and OTM Switch-disconnectors OT 16...2500, OETL 3150, OTDC16...32 and OTM160...2500 Contents 4 Product overview, features 8 Technical
34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51
34 Series - Slim electromechanical PCB relays 6 34 SERIES Features 34.51 Ultra-slim 1 Pole - 6 relay Printed circuit mount - direct or via PCB socket 35 mm rail mount - via screw, screwless or push-in
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
Contact expansion modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts
Catalog January. Heavy industrial power applications Motor contactors and starters
Catalog January Heavy industrial power applications Motor contactors and starters 2006 General contents 0 Heavy Industrial Power Applications Motor Contactors and Starters 1 Contactors and Starters, Type
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
Feed-through terminal block - SSK 110 KER-EX - 0502058
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011
, 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially
CUSTOMER CLASS FILE. ABB STOTZ-KONTAKT GmbH 3215-30 098793_0_000
Seite 1 von 6 Certification Record CUSTOMER CLASS FILE ABB STOTZ-KONTAKT GmbH 3215-30 098793_0_000 Eppelheimer Strasse 82, SUPPLEMENTARY PROTECTORS- COMPONENT ACCEPTANCE PROGRAM Heidelberg Baden-Wurttemberg
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Product description Wide rated operational voltage 208 600 V AC Wide rated control supply voltage 100 250 V, 50/60 Hz Rated operational current 18 to 370 A Wide ambient temperature range, -25 to +60 ºC
Rotary Disconnect Switch Specifications
Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources