Short circuit calculations
|
|
- Lorin Freeman
- 7 years ago
- Views:
Transcription
1 Short circuit calculations
2 Purpose of Short-Circuit Calculations Dimensioning of switching devices Dynamic dimensioning of switchgear Thermal rating of electrical devices (e.g. cables) Protection coordination Fault diagnostic Input data for Earthing studies Interference calculations EMC planning..
3 Short-Circuit Calculation Standards IEC 60909: Short-Circuit Current Calculation in Three-Phase A.C. Systems European Standard EN 60909» German National Standard DIN VDE 0102» further National Standards Engineering Recommendation G74 (UK) Procedure to Meet the Requirements of IEC for the Calculation of Short-Circuit Currents in Three-Phase AC Power Systems ANSI IIEEE Std. C37.5 (US) IEEE Guide for Calculation of Fault Currents for Application of a.c. High Voltage Circuit Breakers Rated on a Total Current Basis.
4 Short-Circuit Calculations Scope of IEC three-phase a.c. systems low voltage and high voltage systems up to 500 kv nominal frequency of 50 Hz and 60 Hz balanced and unbalanced short circuits three phase short circuits two phase short circuits (with and without earth connection) single phase line-to-earth short circuits in systems with solidly earthed or impedance earthed neutral two separate simultaneous single-phase line-to-earth short circuits in a systems with isolated neutral or a resonance earthed neutral (IEC ) maximum short circuit currents minimum short circuit currents
5 Short-Circuit Calculations Types of Short Circuits 3-phase 2-phase 1-phase Copyright Siemens AG All rights reserved.
6 Variation of short circuit current shapes fault at voltage peak fault at voltage zero crossing fault located in the network fault located near generator
7 Short-Circuit Calculations Far-from-generator short circuit I k Initial symmetrical short-circuit current i p Peak short-circuit current Steady-state short-circuit current I k A Initial value of the d.c component
8 Short-Circuit Calculations Definitions according IEC (I) initial symmetrical short-circuit current I k r.m.s. value of the a.c. symmetrical component of a prospective (available) short-circuit current, applicable at the instant of short circuit if the impedance remains at zero-time value initial symmetrical short-circuit power S k fictitious value determined as a product of the initial symmetrical short-circuit current I k, the nominal system voltage U n and the " factor 3: " S 3 U I k n k NOTE: S k is often used to calculate the internal impedance of a network feeder at the connection point. In this 2 case the definition given should be used in the following form: c Un Z " Sk
9 Short-Circuit Calculations Definitions according IEC (II) decaying (aperiodic) component i d.c. of short-circuit current mean value between the top and bottom envelope of a shortcircuit current decaying from an initial value to zero peak short-circuit current i p maximum possible instantaneous value of the prospective (available) short-circuit current NOTE: The magnitude of the peak short-circuit current varies in accordance with the moment at which the short circuit occurs.
10 Short-Circuit Calculations Near-to-generator short circuit I k Initial symmetrical short-circuit current i p Peak short-circuit current I k Steady-state short-circuit current A Initial value of the d.c component Symmetrical short-circuit breaking current I B 2 2 I B t B
11 Short-Circuit Calculations Definitions according IEC (III) steady-state short-circuit current I k r.m.s. value of the short-circuit current which remains after the decay of the transient phenomena symmetrical short-circuit breaking current I b r.m.s. value of an integral cycle of the symmetrical a.c. component of the prospective short-circuit current at the instant of contact separation of the first pole to open of a switching device
12 Short-Circuit Calculations Purpose of Short-Circuit Values Design Criterion Physical Effect Relevant short-circuit current Breaking capacity of circuit breakers Mechanical stress to equipment Thermal stress to equipment Protection setting Earthing, Interference, EMC Thermal stress to arcing chamber; arc extinction Forces to electrical devices (e.g. bus bars, cables ) Temperature rise of electrical devices (e.g. cables) Selective detection of partial short-circuit currents Potential rise; Magnetic fields Symmetrical short-circuit breaking current I b Peak short-circuit current i p Initial symmetrical shortcircuit current I k Fault duration Minimum symmetrical shortcircuit current I k Maximum initial symmetrical short-circuit current I k
13 Equivalent Voltage Source
14 Short-circuit Equivalent voltage source at the shortcircuit location real network Q A F equivalent circuit Z N Q Z T A Z L ~ cu. n I" K 3 Operational data and the passive load of consumers are neglected Tap-changer position of transformers is dispensable Excitation of generators is dispensable Load flow (local and time) is dispensable
15 Short circuit in meshed grid Equivalent voltage source at the short-circuit location real network equivalent circuit
16 Voltage Factor c c is a safety factor to consider the following effects: voltage variations depending on time and place, changing of transformer taps, neglecting loads and capacitances by calculations, the subtransient behaviour of generators and motors. Nominal voltage maximum short circuit currents Voltage factor c for calculation of minimum short circuit currents Low voltage 100 V 1000 V -systems with a tolerance of 6% -systems with a tolerance of 10% Medium voltage >1 kv 35 kv High voltage >35 kv
17 Short Circuit Impedances and Correction Factors
18 Short Circuit Impedances For network feeders, transformer, overhead lines, cable etc. impedance of positive sequence system = impedance of negative sequence system impedance of zero sequence system usually different topology can be different for zero sequence system Correction factors for generators, generator blocks, network transformer factors are valid in zero, positive, negative sequence system
19 Network feeders At a feeder connection point usually one of the following values is given: the initial symmetrical short circuit current I k the initial short-circuit power S k Z N cu cu 2 n n " " 3 I S k k X N Z N 1 ( R / X 2 ) If R/X of the network feeder is unknown, one of the following values can be used: R/X = 0.1 R/X = 0.0 for high voltage systems >35 kv fed by overhead lines
20 Network transformer Correction of Impedance Z TK = Z T K T general K T cmax 0,95 1 0,6 x at known conditions of operation T K T U U n b 1 x T c (I max b T IrT )sin b T no correction for impedances between star point and ground
21 Network transformer Impact of Correction Factor K T cmax = 1.10 cmax = x T [%] The Correction factor is K T <1.0 for transformers with x T >7.5 %. Reduction of transformer impedance Increase of short-circuit currents
22 Generator with direct Connection to Network Correction of Impedance Z GK = Z G K G general K G U U n rg 1 cmax x sin d rg for continuous operation above rated voltage: U rg (1+p G ) instead of U rg turbine generator: X (2) = X (1) salient pole generator: X (2) = 1/2 (X d " + X q ")
23 Generator Block (Power Station) Correction of Impedance Z S(O) = (t r 2 Z G +Z THV ) K S(O) G Q power station with on-load tap changer: K S U U 2 nq 2 rg U U 2 rtlv 2 rthv 1 x d c x max T sin rg power station without on-load tap changers: K SO U rg U nq (1 p G U ) U rtlv rthv 1 p t 1 cmax x sin d rg
24 Asynchronous Motors Motors contribute to the short circuit currents and have to be considered for calculation of maximum short circuit currents Z M I LR 1 /I rm U S 2 rm rm X M Z 1 (R M M / X M ) 2 If R/X is unknown, the following values can be used: R/X = 0.1 medium voltage motors power per pole pair > 1 MW R/X = 0.15 medium voltage motors power per pole pair 1 MW R/X = 0.42 low voltage motors (including connection cables)
25 Special Regulations for low Voltage Motors low voltage motors can be neglected if I rm I k groups of motors can be combined to a equivalent motor I LR /I rm = 5 can be used
26 Calculation of initial short circuit current
27 Calculation of initial short circuit current Procedure Set up equivalent circuit in symmetrical components Consider fault conditions in 3-phase system transformation into symmetrical components Calculation of fault currents in symmetrical components transformation into 3-phase system
28 Calculation of initial short circuit current Equivalent circuit in symmetrical components (1) (1) (1) (1) (1) (1) (1) (1) positive sequence system (2) (2) (2) (2) (2) (2) (2) (2) negative sequence system (0) (0) (0) (0) (0) (0) (0) (0) zero sequence system Copyright Siemens AG All rights reserved.
29 Calculation of initial short circuit current 3-phase short circuit L1-L2-L3-system L1 L2 L3 Z (1)l 012-system Z (1)r ~ ~ ~ c U n 3 (1) ~ ~ ~ -U f I sc3 c U 3 Z r (1) Z (2)l Z (2)r ~ ~ (2) Z (0)l Z (0)r ~ ~ (0) U L1 = U f U L2 = a 2 ( U f ) U L3 = a ( U f ) network left of fault location fault location U (1) = U f U (2) = 0 U (0) = 0 network right of fault location
30 Calculation of 2-phase initial short circuit current L1-L2-L3-system L1 L2 L3 Z (1)l 012-system Z (1)r ~ ~ ~ c U n 3 (1) ~ -U f I sc2 Z c U 1 r Z 2 Z (2)l Z (2)r ~ ~ (2) I sc2 cu I r sc2 2 Z sc3 1 I 2 3 Z (0)l Z (0)r ~ ~ (0) I L1 = 0 I L2 = I L3 U (1) U (2) I (0) = 0 c U n 3 network left of fault location fault location network right of fault location U L3 U L2 = U f I (1) = I (2)
31 Calculation of 2-phase initial short circuit current with ground connection L1-L2-L3-system L1 L2 L3 Z (1)l 012-system Z (1)r ~ ~ ~ c U n 3 (1) ~ -U f I sce2e Z 3 c U 1 2Z r 0 Z (2)l Z (2)r ~ ~ (2) Z (0)l Z (0)r ~ ~ (0) I L1 0 U a L2 U a L3 2 U n c 3 U n c 3 U (1) network left of fault location U (2) Un c 3 fault location U I (0) = I (1) = I (2) (1) U network right of fault location (0)
32 Calculation of 1-phase initial short circuit current L1-L2-L3-System L1 L2 L3 I " 3 c U sc1 ~ -U f Z (1) Z (2) Z (0) r Z (1)l 012-System Z (1)r ~ ~ Z (2)l Z (2)r ~ ~ c U n 3 ~ Z (0)l Z (0)r ~ ~ (1) (2) (0) U c L1 I L2 = 0 U n 3 U network left of fault location (0) U (1) U fault location (2) c U network right of fault location n 3 I L3 = 0 I (0) = I (1) = I (2)
33 Short Circuit Calculation Results Faults at all Buses
34 Short Circuit Calculation Results Contribution for one Fault Location
35 Example
36 Data of sample calculation Network feeder: 110 kv 3 GVA R/X = 0.1 Transformer: 110 / 20 kv 40 MVA u k = 15 % P krt = 100 kva Overhead line: 20 kv 10 km R 1 = 0.3 Ω / km X 1 = 0.4 Ω / km
37 Impedance of Network feeder Z I c U S 2 n " k Z I kV 3GVA 2 Z I R I X I
38 Impedance of Transformer Z Z T T u k U S 2 n n kV 2 40MVA R R T T P krt U S 2 n 2 n 100 kva 2 20kV 40MVA 2 Z T R T X T
39 Impedance of Transformer Correction Factor K T K T cmax x T K T Z TK R TK X TK
40 Impedance of Overhead Line R L R' X L X' R L 0.3 /km10km X L 0.4 /km10km R L X I
41 Initial Short-Circuit Current Fault location 1 R R I R TK R X X I X TK X R I " k 3 c U R 1 n j X 1 X I " k kV I " k 8.0kA
42 Initial Short-Circuit Current Fault location 2 R R I R TK R L R X X I X TK X L X R I " k 3 c U R 1 n j X 1 X I " k kV I " k 2.0kA
43 Peak current
44 Peak Short-Circuit Current Calculation acc. IEC maximum possible instantaneous value of expected short " circuit current ip 2 I k equation for calculation: e 3R / X
45 Peak Short-Circuit Current Calculation in non-meshed Networks The peak short-circuit current i p at a short-circuit location, fed from sources which are not meshed with one another is the sum of the partial short-circuit currents: G M M i p1 i p2 i p3 i p4 i p = i p1 + i p2 + i p3 + i p4
46 Peak Short-Circuit Current Calculation in meshed Networks Method A: uniform ratio R/X smallest value of all network branches quite inexact Method B: ratio R/X at the fault location factor b from relation R/X at the fault location (equation or diagram) =1,15 b Method C: procedure with substitute frequency factor from relation R c /X c with substitute frequency f c = 20 Hz R X R X c c f f c best results for meshed networks
47 Peak Short-Circuit Current Fictitious Resistance of Generator R Gf = 0,05 X d " for generators with U rg > 1 kv and S rg 100 MVA R Gf = 0,07 X d " for generators with U rg > 1 kv and S rg < 100 MVA R Gf = 0,15 X d " for generators with U rg 1000 V NOTE: Only for calculation of peak short circuit current
48 Peak Short-Circuit Current Fault location 1 I " k 8.0kA R X R/ X e R / X i 2 " p I k i p 21.8kA
49 Peak Short-Circuit Current Fault location 2 I " k 2.0kA R X R/ X e R / X i 2 " p I k i p 3.4kA
50 Breaking Current
51 Breaking Current Differentiation Differentiation between short circuits near or far from generator Definition short circuit near to generator for at least one synchronous machine is: I k > 2 I r,generator or I k with motor > 1.05 I k without motor Breaking current I b for short circuit far from generator I b = I k
52 Breaking Current Calculation in non-meshed Networks The breaking current I B at a short-circuit location, fed from sources which are not meshed is the sum of the partial short-circuit currents: G M M I B1 = μ I k I B2 = I k I B3 = μ q I k I B4 = μ q I k I B = I B1 + I B2 + I B3 + I B4
53 Breaking current Decay of Current fed from Generators I B = μ I k Factor μ to consider the decay of short circuit current fed from generators.
54 Breaking current Decay of Current fed from Asynchronous Motors I B = μ q I k Factor q to consider the decay of short circuit current fed from asynchronous motors.
55 Breaking Current Calculation in meshed Networks Simplified calculation: I b = I k For increased accuracy can be used: I b I " k i U" c U n / Gi 3 (1 i ) I " kgi j U" c U n / Mj 3 (1 q ) I j j " kmj U " Gi jx " dik I " kgi U " Mj jx " Mj I " kmj X dik subtransient reactance of the synchronous machine (i) X Mj reactance of the asynchronous motors (j) I kgi, I kmj contribution to initial symmetrical short-circuit current from the synchronous machines (i) asynchronous motors (j) as measured at the machine terminals and the
56 Continuous short circuit current Continuous short circuit current I k r.m.s. value of short circuit current after decay of all transient effects depending on type and excitation of generators statement in standard only for single fed short circuit calculation by factors (similar to breaking current) Continuous short circuit current is normally not calculated by network calculation programs. For short circuits far from generator and as worst case estimation I k = I k
DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
More information3 Calculation of Short-Circuit Currents in Three-Phase Systems
3 ABB_11_E_03 13.08.2007 8:19 Uhr Seite 69 3 Calculation of Short-Circuit Currents in Three-Phase Systems 3.1 Terms and definitions 3.1.1 Terms as per IEC 60909 Short circuit: the accidental or deliberate
More informationChapter 9 Balanced Faults
Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.
More informationThe following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
More informationEMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
More informationTWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationSimple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
More informationThe Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationPower Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
More informationJoslyn Clark Controls, Inc.
Joslyn Clark Controls, Inc. CAPACITOR SWITCHING VACUUM CONTACTORS vs. AIR BREAK CONTACTORS APPLICATION PRECAUTIONS & CALCULATIONS TO LIMIT HIGH FREQUENCY & HIGH CURRENT 2 QUESTION: WHY IS A VACUUM CONTACTOR
More informationTypical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
More informationPower Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant
More informationSHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS
Bachelor's Thesis Electrical Engineering June 2014 SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS MD FARUQUL ALAM SALMAN SAIF HAMID ALI School of Engineering Blekinge Tekniska
More informationSIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS
Sawsan Henein AIT Austrian Institute of Technology Electric Energy Systems Research Group SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sustainable Places 2015 Savona,
More informationPM734F - Technical Data Sheet Winding 28
- Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including
More information6 ELECTRICAL PARAMETERS
6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities
More informationPower transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
More informationGenerator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
More informationElectrical Fault Level Calculations Using the MVA Method
J.M. PNG & SH PT LTD Chapter lectrical ault Level Calculations Using the Method 5 With modern day personal computers, hand calculations for electrical fault level are becoming a thing of the past. The
More informationCIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
More informationSelecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
More informationSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
More informationTA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection
Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions
More informationMINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION
MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION REPORT ON NETWORK RELIABILITY ASPECTS OF THE CHOICE LINE VERSUS CABLE FOR
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationTRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
More informationANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
More informationUCI274C - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
More informationUCI274H - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
More informationVoltage regulation in distribution systems - Tap changer and Wind Power
CODEN:LUTEDX/(TEIE-5270)/1-59/(2010) Industrial Electrical Engineering and Automation Voltage regulation in distribution systems - Tap changer and Wind Power David Sáez Romero D of Industrial Electrical
More informationCONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
More informationElectrical and mechanical interface requirements for separable HR, LR and LRM voltage detecting systems
C Metal-encapsulated switchgear installations, typically SF6 gas-insulated, have become widely accepted in the field of switchgear construction. In these types of installation, conventional voltage detectors
More informationMeasurement, Modeling and Simulation of Capacitor Bank Switching Transients
Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: softic_mirza@yahoo.com).
More informationEARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
More informationPI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
More informationPI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
More informationThree phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
More informationProduct brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity
More informationALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
More informationHowever, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.
Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if
More informationMedium voltage circuit breaker
Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the
More informationPower Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationVOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES
VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB
More informationLIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
More information300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal
May 24 MW Variable Speed Drives for Aurélie Bocquel APCG / 4BOC4 (MW-Goldisthal 1-5-24).PPT MW Variable Speed Drives for Content Major benefits of the cyclo-converter driven doubly-fed induction machines
More informationPI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards
More informationMNS is Switchgear System Technical Overview
Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known
More informationThe standards mentioned in this document
The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation
More informationHCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards
More informationPermissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
More informationFIT TIER 2 Application
FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:
More informationProduct Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
More informationElectrical network protection. Protection guide. Guide
Electrical network protection Protection guide Guide A new path for achieving your electrical installations A comprehensive offer The Protection Guide completes the perfectly coordinated offer of products
More informationElectrical network protection. Protection guide. Guide 2003 51G 51G 51G 51G 51G. network protection solutions
Electrical network protection Protection guide Guide 2003 5 A H G G 4 D3 D2 D1 G G G 3 network protection solutions Protection guide Contents 0 Presentation 2 Power-system architecture Selection criteria
More informationDesign of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
More informationIsolated-Parallel UPS Configuration
Isolated-Parallel UPS Configuration 1 Inhalt 1 Introduction... 4 2 IP systems configuration... 6 3 Projects... 17 4 Conclusions... 17 2 Abstract The isolated-parallel UPS configuration has become well
More informationSAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the
More informationDHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationPower Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
More informationSPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan claudio.mardegan@engepower.com www.engepower.com Phone: 55 3579-8777
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.
More informationPI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS
PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section
More informationLow Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationElectronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationSingle and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of
More informationAMSC s Superconductor Cable Technologies for Electric Utilities
International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationGUIDE FOR TESTING POWER TRANSFORMERS
GUIDE FOR TESTING POWER TRANSFORMERS Routine test 11/11/02 Pagina 1 di 10 INDEX Introduction... 3 1 Dielectric tests Separate-source voltage withstand test... 4 2 Induced voltage test... 5 3 Voltage ratio
More informationHow To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationETAP Validation Cases and Comparison Results
ETAP Validation Cases and Comparison Results ETAP is Verified and Validated (V&V) against field results, real system measurements, published cases, other programs, and hand calculations in order to ensure
More informationTransformers. Special transformers Reactors products
Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
More informationChapter 12: Three Phase Circuits
Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in
More informationFigure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.
Crydom RHP Series 3 Phase Hybrid Solid State Contactor By Paul Bachman Fellow Engineer, Crydom, Inc. ABSTRACT Solid State Relays and Contactors (SSRs) have been available in one form or the other for over
More informationInstrument Transformers Application Guide
Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden
More informationW03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören
W03 Analysis of DC Circuits Yrd. Doç. Dr. Aytaç Gören ELK 2018 - Contents W01 Basic Concepts in Electronics W02 AC to DC Conversion W03 Analysis of DC Circuits (self and condenser) W04 Transistors and
More informationVariable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
More informationRISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
More informationDesign of Electrical Power Supply System in an Oil and Gas refinery. Master of Science Thesis in Electric Power Engineering
Design of Electrical Power Supply System in an Oil and Gas refinery Master of Science Thesis in Electric Power Engineering Reza Vafamehr Department of Energy and Environment Division of Electric Power
More informationATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
More informationRules for Classification and Construction Additional Rules and Guidelines
VI Rules for Classification and Construction Additional Rules and Guidelines 7 Guidelines for the Performance of Type Approvals 6 Test Requirements for Electrical Machinery Edition 1999 The following Guidelines
More informationType: DILM32 10(24V50HZ) Article No.: 277247
Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
More informationFor a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
More informationCT Application Guide for the 489 Generator Management Relay
g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates
More information6. Synchronous machine dynamics
1 6. Synchronous machine dynamics In the middle of eighties, the present Type 59 synchronous machine model program was implemented and put into practical use in EMTP. In the first half of nineties, also
More informationRack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
More informationNetwork Theory Question Bank
Network Theory Question Bank Unit-I JNTU SYLLABUS: Three Phase Circuits Three phase circuits: Phase sequence Star and delta connection Relation between line and phase voltages and currents in balanced
More informationEarth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationLightning current simulation in the laboratory - parameters, procedures and test equipment -
Lightning current simulation in the laboratory - parameters, procedures and test equipment - Dipl.-Ing. J. Schönau, Dr.-Ing. M. Naß, CE-LAB GmbH Prof. Dr.-Ing. F. Berger, Ilmenau University of Technology
More informationNuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the
More information