XD1-T - Transformer differential protection relay

Size: px
Start display at page:

Download "XD1-T - Transformer differential protection relay"

Transcription

1 XD1-T - Transformer differential protection relay

2 Contents 1 Application and features 2 Design 3 Working Principle 3.1 Operating principle of the differential protection 3.2 Balancing of phases and current amplitudes 3.3 Transformer regulation steps 3.4 Working principle of the C.T. saturation detector SAT 3.5 Transformer inrush 3.6 Block diagram 4 Operation and settings 4.1 Parameter setting by using DIP-switches 4.2 Setting recommendations 5 Relay testing and commissioning 5.1 Power on 5.2 Secondary injection test Trip level I d Inrush blocking 5.3 Primary test Adjustment of the interposing C.T.s Function test 6 Technical data 6.1 Relay case 6.2 Technical Data 7 Order form 8 Setting-list XD1-T 1 Application and features Power transformers are classified as one of the most valuable equipments in a power system, hence their protection is of very high importance. The transformer differential protection provides fast tripping in case of a fault - before severe damage spreads out. The XD1-T relay is a strict selective object protection for two-winding transformers. Within a very short time this relay detects faults occuring within the zone to be protected and which require immediate tripping and isolation of the transformer. Such faults are: short circuits between turns, windings and cables inside the transformer housing earth faults inside the housing short circuits and earth faults outside the housing but within the protected zone (e.g. at bushings or supply lines). The XD1-T is also able to detect other operational conditions (e.g. faults outside the protected zone, circuit closing etc.) i.e. it does not issue tripping commands for faults or any other transient phenomena outside the protected zone. Additional to the transformer differential protection an overcurrent relay as backup protection is recommended. For this application we offer the relays MRI1/IRI1/XI1. The relay XD1-T of the PROFESSIONAL LINE has the following special features: Fault indication via LEDs Extremely wide operating ranges of the supply voltage by universal wide-range power supply Very fine graded wide setting ranges Extremely short response time Compact design by SMD-technology Very low C.T. burden Adjustment to transformation ratio and connection groups without external interposing C.T.s Two stage tripping characteristic Galvanic insulation between all independent inputs Additional printed circuits "Saturation Detection" can be retrofitted at a later time Self-supervision of stabilization circuits Wide setting ranges 2 TD_XD1-T_03.08_GB

3 2 Design Figure 2.1: Connection diagram Analog inputs Contact positions The analog secondary currents of the HV side are fed to the protection relay via terminals 1S1-3S2 and the secondary currents of the LV side via terminals 4S1-6S2. Operation without fault or dead conditions Auxiliary voltage supply Unit XD1-T needs a separate auxiliary voltage supply. Therefore a DC or AC voltage must be used. Unit XD1-T has an integrated wide range power supply. Voltages in the range from V DC or V AC can be applied at connection terminals A1 and A2. Figure 2.2: Contact positions of the output relays Contact positions after tripping TD_XD1-T_03.08_GB 3

4 3 Working Principle 3.1 Operating principle of the differential protection The fundamental operating principle of transformer differential protection is based on comparison of the transformer primary and secondary winding currents. For an ideal transformer, having a 1:1 ratio and neglecting magnetizing current, the currents entering and leaving the transformer must be equal. During normal operation or when a short circuit has occured outside the protected zone, the C.T. secondary currents in the differential circuit neutralize each other. In case that a differential current I d occurs, a fault in the transformer is detected. Protected Zone Because of different problems, however, in practice measures for adaption and stabilization have to be taken to ensure trouble-free function of the transformer differential protection: Due to possible mismatch of ratios among different current transformers. Phase differences between primary and secondary side, caused by transformer vector groups, have to be duly considered. Switching operations in the grid have to be recognized as such. Inrush currents of the transformer must not result in maloperation. Iin Transformer Iout 3.2 Balancing of phases and current amplitudes I1 Differential relay Current comparision I d Biasing circuit I s I2 First of all the phase difference between primary and secondary side, which is caused by transformer vector groups, has to be compensated and the current amplitudes to be balanced. Unlike most other differential protection relays available, this scheme includes interposing C.T.s integrated in the differential relay, extra interposing C.T.s are not required. U d U s Tripping characteristic Trip Connection of interposing C.T.s is dependent on the vector group of the power transformer. For instance, for transformers with star (Y) windings the interposing C.T.s are connected in delta (Δ) to reject residual currents (i.e. currents flowing to the transformer due to an earth fault outside the protected zone and which would produce a differential current I d ) and to prevent maloperation of the differential protection. Figure 3.1: General arrangement of differential protection: Id = differential (tripping) current Is = stabilizing current 4 TD_XD1-T_03.08_GB

5 3.3 Transformer regulation steps The XD1-T can universally be used i.e. also for regulating transformers with an adjustable transformation ratio to stabilize voltage fluctuations of the supplying systems. Since, however, as a result of vector group balance and transformation ratio balance the differential protection is adjusted to the nominal transformation ratio of the transformer, an apparent differential current I d arises proportionally to the flowing load current. Maloperation of the protection is prevented by the loadproportional stabilizing current I S. The figure 3.2 explains the saturation of the C.T. core due to a short circuit current. In the instant of a short circuit often a DC-component is present in the current. The high primary current induces a flux in the C.T. core, reaching the saturation level. The iron-core retains the high flux level even after the primary current falls to zero. In the time periods of saturation the C.T. does not transform the primary current to the secondary side but the secondary current equals zero. 3.4 Working principle of the C.T. saturation detector SAT With many transformer differential protection systems, relay instability may cause to trip if the main current transformers saturate. In the transient condition of saturation the C.T.s on both ends of the protected zones do not produce the correct secondary current according to the primary current. The differential relay measures a differential current on the secondary C.T. side which is not present on the primary side. Hence a nuisance tripping might occure. Such transient phenomena causing C.T. saturation may occur due to: Heavy through faults (external short circuit) Starting of big motors Magnetizing inrush currents of transformers Internal faults Figure 3.2: Current transformer saturation a) Primary current with DC offset b) Core flux density c) Secondary current TD_XD1-T_03.08_GB 5

6 Dissimilar saturation in any differential scheme will produce operating current. Figure 3.3 shows the differential measurement on the example of extremely dissimilar saturation of C.T.s in a differential scheme. Fig. 3.3 shows the secondary current due to C.T. saturation during an transformer fault (internal fault). The differential current id represents the fault current. The differential relay must trip instantaneously. Fig. 3.3 shows the two secondary currents in the instant of an heavy external fault, with current i1 supposed to C.T. saturation, current i 2 without C.T. saturation. The differential current id represents the measured differential current, which is an operating current. As this differential current is caused by an external fault and dissimilar saturation of the two C.T.s, the differential relay should not trip. Left Single end fed: i 1 = secondary output current from saturated C.T. (theoretical) i 2 = 0; Internal fault fed from side 1 only i d = measured differential current Right External fault: i 1 as in fig. 3.3 for an internal fault i 2 normal current from C.T. secondary on side 2 The wave forms for the differential current I d for internal and external faults are seen to be different for the two cases considered. i1, i2 i1 i2=0 i1, i2 i1 i2 t t id id id=i2-i1 id=i2-i1 t t Figure 3.3: Current comparison with C.T.s saturated by DC offset in fault current wave form internal fault 6 TD_XD1-T_03.08_GB

7 The saturation detector SAT analyses the differential current of each phase separately. The SAT module differentiates the differential current and detects: Rate of change of differential current d(i d )/dt Sign of d(i d )/dt Internal/external fault Duration of saturation, within one cycle DC or AC saturation The instant of an extreme rate of change of differential current d(i d )/dt clearly marks the beginning of a C.T. saturation. The sign of this d(id)/dt value distinguishes the internal fault from an external fault. One detected extreme d(i d )/dt value per cycle indicates a saturation due to DC-current contents. Whereas two extreme d(i d )/dt values per cycle indicate a C.T. saturation caused by a high alternating current. This logic control circuit provides a continuous self diagnostic, limiting any blocking function to maximum of 1.7 seconds. This approach has several advantages. For example, if a C.T. saturated as a result of an external fault, the relay remains stable because the measuring system recognizes the differential current is due to C.T. saturation arising from a fault outside the protected zone. However, if an internal fault occurs, this is immediately recognized, blocking is overridden and the relay trips immediately. Similarly, if a fault occurs during magnetizing inrush of a transformer this is immediately detected and the differential relay operates correctly tripping the transformer. The logic control evaluating above information derives. Only external faults lead to blocking of the trip circuit: In case of detected DC-current saturation the differential current measurement is blocked completely until: the transient condition ends, or an internal fault is detected (instantaneously), or AC-current saturation is detected. In case of detected AC-current saturation only the time periods of saturation are blocked during one cycle. This means that even under severe saturation the differential relay evaluates the differential current in "sound time periods. This is a major advantage to relays solely applying harmonic filters for saturation detecting. All detected transient phenomena change the tripping characteristic to the "coarse tripping characteristic" (pl. ref. to Technical Data). TD_XD1-T_03.08_GB 7

8 3.5 Transformer inrush When a transformer is first energized, a transient inrush current flows. This inrush current occurs only in the energized winding and has no equivalent on the other side of the transformer. The full amount of inrush current appears as differential current and would cause the differential relay to trip if there is no stabilisation against the inrush phenomenon. Typically the inrush current contains three components that distinguish it from other fault currents: The DC-component: The DC-component is present at least in one phase of the inrush current, depending on the instant of energizing. The second harmonic: The second harmonic is present in all inrush currents due to uni-directional flux in the transformer core. The fifth harmonic: The fifth harmonic is present when the transformer is subjected to a temporary overvoltage. The filter module "SAT" detects not only C.T. saturation due to external faults but also the inrush current of the transformer to be protected. The differential current i d of each phase is analysed separately. The signal of i d passes a filter arrangement detecting transient conditions due to the DCcomponent, the second harmonic and the fifth harmonic. Thus all three components are used for detecting an inrush current. The limits for blocking of the differential protection are: The restraining influence, resp. the blocking depends on the combination of the three components. If only a single component is present, the highest value applies. If a mixture of all three components is present, the lowest values apply. With this combined measurement of the three restraining components XD1-T achieves: Reliable inrush stabilisation Fast tripping if the incoming transformer is defective Restraining feature against C.T.-saturation. Whereas a complete blocking of the protection is only performed during the first energizing of the transformer, the harmonic content supervision restrains during normal operation against phenomena like C.T. saturation. This means that internal faults will be detected instantaneously (ms), whereas external faults do not cause tripping. The inrush blocking is stopped when: The differential current I d falls below the tripping characteristic, or the differential current I d shows an internal fault, according to the harmonic content, or the differential current I d exceeds 15 x nominal current, or a fixed period of time has elapsed. The basic relay version without module "SAT" does not provide the harmonic restrain feature. For applications on bigger transformers or for generator-transformer protection we recommend the use of module "SAT". DC-component: 2nd harmonic: 5th harmonic: 20%...60% of i d 20%...50% of i d 10%...25% of i d 8 TD_XD1-T_03.08_GB

9 3.6 Block diagram Figure 3.4: Block diagram TD_XD1-T_03.08_GB 9

10 4 Operation and settings All operating elements needed for setting parameters are located on the front plate of the XD1-T as well as all display elements. Because of this all adjustments of the unit can be made or changed without disconnecting the unit off the DIN-rail. Figure 4.1: Front plate XD1-T LEDs For adjustment of the unit the transparent cover has to be opened as illustrated. Do not use force! The transparent cover has two inserts for labels. LED ON is used for display of the readiness for service (at applied auxiliary voltage Uv). LEDs L1, L2, L3 and TRIP are provided for fault indication. LED Δ2/OO indicates inrush stabilization. For relays with an additional SAT module, changeover to the coarse measuring element is indicated. Reset push-button The Reset push-button is used for acknowledgement and resetting the LEDs after tripping. Potentiometer Figure 4.2: How to open the transparent cover The 3 potentiometer on the lower right side of the front plate are provided for adjustment of the interposing C.T.s (refer to chapter 5.3.1). 10 TD_XD1-T_03.08_GB

11 4.1 Parameter setting by using DIP-switches The XD1-T provides two DIP-switches for the adjustment of the tripping characteristic: I d1 represents the setting for the tripping area below nominal current. The I d1 setting relates to the nominal current of the relay and is independent of the through current. I d2 represents the setting for the tripping area above nominal current. The I d2 setting relates to the "stabilizing current Is". Whereas Is is the current flowing through the protected zone. This biasing area is important for external faults. The higher the current due to an external fault, the higher is the biasing influence. On through faults, large differential currents may be produced by the transformer tap changer or due to mismatching of the current transformers. The biased slope characteristic prevents incorrect operation of the relay under these conditions. Load tap changer (LTC). The automatic LTC may vary the ratio of the protected transformer as much as ±10%. This causes a current mismatch of the same amount. Die Abweichung, die sich durch die Transformator- Schaltgruppe ergibt, sollte durch die internen Stromwandler und deren Bürden kompensiert werden. Considering the example above, both settings I d1 and I d2 should be set to: 3% + 3% for C.T. errors 10% for transformer step changer 15% safety margin Arrives to a setting of 31%. The nearest possible setting is 30%. Hence both DIP-switches should be set to 30%. The pictures below show the DIP-switch setting as well as the actual tripping characteristic. With the additional module SAT the tripping characteristic changes to "coarse" in case of detected transient phenomena, as explained above. The fixed tripping values for the coarse measurement are: I d1 = 100 % I N I d2 = 60 % Is I d /I N TRIPPING Setting Id2 = 30% Setting recommendations Setting Id1 = 30% The tripping characteristic should be selected according to the known mismatch of the secondary currents fed to the relay plus a safety margin of 10 to 15 %. This setting avoids maloperation caused by normal load conditions Mismatch of the currents may be produced by: Ratio error and phase shifting of the C.T.s. E.g.: For protection C.T.s of 10P20 rating the ratio error at nominal current is max. 3 %. At 20 times nominal current the ratio error reaches 10 %. NO TRIPPING I 10 1 S /I N Figure 4.3: Adjustment example TD_XD1-T_03.08_GB 11

12 For this DIP-switches for I d1 and I d2 have to be in the following positions: 5 Relay testing and commissioning Correct connection of primary and secondary side of the C.T.s as well as the correct connection and adjustment of the internal matching C.T.s are the condition for a perfect service of the differential relay. Therefore please observe: The order form should be filled with great care. The transformer differential relay will be pre-adjusted at SEG according to the order form. Figure 4.4: Adjustment of step switches When taking the relay into service the commissioning checks explained below should be followed. The test instructions following below help to verify the protection relay performance before or during commissioning of the protection system. To avoid a relay damage and to ensure a correct relay operation, be sure that: the auxiliary power supply rating corresponds to the auxiliary voltage on site. the rated current correspond to the plant data on site. the current transformer circuits are connected to the relay correctly. Please pay special attention also to the primary connections of the C.T.s. the input circuits and output relay circuits are connected correctly. 5.1 Power on NOTE! Prior to switch on the auxiliary power supply, be sure that the auxiliary supply voltage corresponds with the rated data on the type plate. When the auxiliary supply is switched on please observe that the LED "ON" is alight. 5.2 Secondary injection test Test equipment: One adjustable current source up to two times nominal current of the relay Ammeter with class 1 Auxiliary supply source corresponding with the nominal auxiliary supply of the relay. Power diode (10 A) Switching device Test leads and tools NOTE! Before this test is initiated by means of secondary current, it must be ensured that the relay cannot cause any switching actions in the system (shut-down risk). 12 TD_XD1-T_03.08_GB

13 5.2.1 Trip level I d1 Inject a current into each current input according to the test circuit below and check the current value at which a trip occures. The tripping values should correspond to: For the relay side connected to the star-side of the transformer: 1.73 times the setting of I d1. For the relay side connected to the delta side of the transformer: 1.0 times the setting of I d2. The difference of tripping levels is explained by the internal matching C.T.s. The star-side matching C.T.s are internally connected in delta and transform the current to a value 0.58 times the input current. The delta side matching C.T.s are internally connected in star. Hence the transformation ratio is Primary test The test of the correct connection of the main C.T.s and the correct matching of the internal measuring values can only be done with the transformer in service. A minimum load of app. 50 % of the transformer load is recommended to avoid malinterpretation of measuring values. At low currents the magnetizing current of the transformer has a high influence on the test results. Make sure that the trip circuit of the differential relay is blocked and cannot cause unwanted tripping. On the other hand a backup protection, like an overcurrent relay, must protect the transformer in case of faults! Adjustment of the interposing C.T.s The correct connection and accurate adjustment of the C.T.s can be checked with a voltmeter. For this 7 terminals are provided at the lower terminal strip. The associated adjustment potentiometers are arranged above these terminals. Differences of the main C.T.s up to 15 % I N can be adjusted by the potentiometers. Figure 5.1: Test circuit Inrush blocking Figure 5.3: Connection of voltmeter Information about measuring results can be found on the following table. Figure 5.2: Test circuit for inrush blocking Adjust the input current to app. 1.5 times nominal current. Switch off the current. Switch the current on with the same adjustment. Observe that the inrush blocking LED lights up and no trip occurs. Observe that after a blocking time of 3.5 s the LED extinguishes and a trip occurs. This is caused by the maximum blocking time supervision. Switch the current off. If saturation detector SAT is used the maximum blocking time is reduced to 1.7 s. TD_XD1-T_03.08_GB 13

14 a) b) c) d) Measuring 1 (1L1 - GND) Measuring 2 (2L1 - GND) Measuring 3 (1L1-2L1) Measuring 1 (1L1 - GND) Measuring 2 (2L1 - GND) Measuring 3 (1L1-2L1) Measuring 1 (1L1 - GND) Measuring 2 (2L1 - GND) Measuring 3 (1L1-2L1) Measuring 1 (1L1 - GND) Measuring 2 (2L1 - GND) Measuring 3 (1L1-2L1) 550 mv 550 mv 1100 mv 550 mv 550 mv 0 mv 550 mv 550 mv 550 mv 550 mv 550 mv 950 mv Correct connection Current flow of a C.T. (S1 and S2) is mixed-up Phase position mixed-up (e.g. one current from phase L1, the other one from phase L2) Current flow and phase position of a C.T. is mixed-up Table 5.1: Measuring results The internal measuring voltages proportional to the input currents may be measured as follows. The measuring instrument should be a digital multimeter set to ACvoltage measurement, range 2.0 V. The readings stated below refer to nominal current of the transformer (referring to the order form). Any current value below may be calculated proportionally. Please also note that due to the C.T. errors and the transformer magnetizing current the measured values might deviate up to 10% from the theoretical values. Nominal load current of the transformer is generally transformed to the internal measuring voltage of 550 mv AC. Both amplitudes of the measuring voltages of one phase, e.g. 1L1 and 1L2, should be equal. The phase angle of the voltages of one phase, e.g. 1L1 and 1L2, must be 180 degrees. A slight deviation might be caused by the magnetizing current of the transformer. Hence the differential measurement in one phase, e.g. lead 1 connected to 1L1 and lead 2 connected to 2L1, must read twice the value of the measurement 1L1 to GND. In case there are deviations from the expected value please check all wiring to the relay. This check must include the connection of the primary C.T. side and the secondary side. In most cases a wrong connection of the C.T.s is the reason for maloperation of the differential protection. If all connections are correct and the internal measuring value still shows deviations from the expected values, please check if the transformer group given on the type plate corresponds to the transformer vector group. If the single ended measurements (e.g. 1L1 - GND) differ within one phase, e.g.: 1L1 - GND: 400 mv 2L1 - GND: 600 mv 1L1-2L1: 1000 mv but the differential measurement equals the sum of both the deviation may be balanced using the concerned potentiometer on the front plate Function test Attention! Disconnect all leads for adjusting the interposing C.T.s and perform the following function test: Load the transformer with minimum 50% load. Assure that the tripping of the transformer C.B. does not cause unwanted damages (blackout). To operate the differential relay use a shorting link between one of the phase terminals and GND, e.g. connect 1L1 to GND. The relay should trip immediately. If no trip occurs, make sure that the load current exceeds the set value of I d1. 14 TD_XD1-T_01.04_GB

15 6 Technical data 6.1 Relay case Relay XD1-T is designed to be fastened onto a DIN-rail acc. to DIN EN 50022, the same as all units of the PROFESSIONAL LINE. The front plate of the relay is protected with a sealable transparent cover (IP40). Figure 6.1: Dimensional drawing Connection terminals The connection of up to a maximum 2 x 2.5 mm 2 cross-section conductors is possible. For this the transparent cover of the unit has to be removed (see para. 4). TD_XD1-T_01.04_GB 15

16 6.2 Technical Data Measuring input Rated data: Rated current I N : Rated frequency f N : 1 A / 5 A Hz Power consumption in current circuit: at I N = 1 A <0.1 VA at I N = 5 A <0.5 VA Thermal withstand capability in current circuit: dynamic current withstand (half-wave) 250 x I N for 1 s 100 x I N for 10 s 30 x I N continuously 4 x I N Auxiliary voltage Rated auxiliary voltages U H : V AC (f = Hz) V DC General data Dropout to pickup ratio: >97% Returning time: <50ms Returning time after tripping: 100ms ±10ms Minimum operating time: 40ms Output relays The output relays have the following characteristics: Maximum breaking capacity: For DC-voltage: 250 V AC/1500 VA / continuous current 6 A ohmic L/R = 40 ms L/R = 70 ms 300 V DC 0,3 A/90 W 0,2 A/63 W 0,18 A/54 W 250 V DC 0,4 A/100 W 0,3 A/70 W 0,15 A/40 W 110 V DC 0,5 A/55 W 0,4 A/40 W 0,20 A/22 W 60 V DC 0,7 A/42 W 0,5 A/30 W 0,30 A/17 W 24 V DC 6,0 A/144 W 4,2 A/100 W 2,50 A/60 W Max. rated making current: 64 A (VDE 0435/0972 and IEC 65/VDE 0860/8.86) Making current: min. 20 A (16 ms) Mechanical life span: 30 x 10 6 operating cycles Electrical life span: 2 x 10 5 operating cycles at 220 V AC / 6 A Contact material: silver cadmium oxide (AgCdO) 16 TD_XD1-T_01.04_GB

17 System data Design standard: VDE 0435, T303; IEC 255-4; BS142 Specified ambient service Storage temperature range: - 40 C to + 85 C Operating temperature range: - 20 C to + 70 C Environmental protection class F as per DIN and per DIN IEC 68 part 2-3: Insulation test voltage, inputs and outputs between themselves and to the relay frame as per VDE 0435, part 303 and IEC 255-5: Impulse test voltage, inputs and outputs between themselves and to the relay frame as per VDE 0435, part 303 and IEC 255-5: High frequency interference test voltage, inputs and outputs between themselves and to the relay frame as per IEC 255-6: Electrostatic discharge (ESD) test as per VDE 0843, part 2 IEC 801-2: Radiated electromagnetic field test as per VDE 0843, part 3 IEC 801-3: Electrical fast transient (Burst) test as per VDE 0843, part 4 IEC 801-4: Radio interference suppression test as per DIN/VDE 57871: relative humidity 95 % at 40 C for 56 days 2.5 kv (eff.), 50 Hz; 1 min 5 kv; 1.2/50 μs; 0.5 J 2.5 kv/1mhz 8 kv electric field strength 10 V/m 4 kv/2.5 khz, 15 ms limit value class A Mechanical tests: Shock: class 1 as per DIN IEC 255 part 21-2 Vibration: class 1 as per DIN IEC 255 part 21-1 Degree of protection: Weight: Mounting position: Overvoltage class: Relay case material: IP40 at closed front cover ca. 1.5 kg any III self-extinguishing TD_XD1-T_01.04_GB 17

18 Tripping characteristics Setting Id2 60% 42,5% I d /I N 10 0 Coarse tripping characteristic Setting Id1 = 100% Setting Id1 = 42,5% 5% Normal tripping characteristic 10-1 Setting Id1 = 5% I 10 1 S /I N Figure 6.2: Tripping range t [ms] I d /I N Figure 6.3: Tripping time 18 TD_XD1-T_01.04_GB

19 Accuracy details Idtrip Idset for I S < I N : e = 100 % IN Idtrip Idset for I S I N : e = 100 % IS where Note: e = relative error I S = stabilizing current I N = rated current I dtrip = measuring differential current which results in tripping I dset = differential current setting The accuracy details quoted are based on interposing current transformer with exact correction ratio. Accuracy at reference conditions: Temperature range -5 C...40 C e 2.5 % Frequency range 50 Hz...60 Hz: e 2.5 % If the operating temperature or frequency are outside the ranges quote, additional errors are: Temperature range -20 C...70 C: e add < 2.5 % Frequency range 45 Hz...66 Hz: e add = 1 % TD_XD1-T_01.04_GB 19

20 7 Order form Differential protection relay XD1- Transformer protection (two windings) Primary rated current Secondary rated current 1 A 5 A 1 A 5 A none Latching relay and manual reset none Extra equipment for reliable functioning during CT saturation 1 * SAT * Please leave box empty if option is not desired Transformer rated capacity MVA Vector group Voltage High voltage side kv ± % Low voltage side Current transformer ratio High voltage side / Low voltage side / Rated current High voltage side / Low voltage side / T * SP Important instruction! In order to ensure the balancing of the transformer differential circuit, the variation of the current referred to the current transformer secondary shall be in the range from 50 % (0.5 A for 1 A CT and 2.5 A for 5 A CT) up to a maximum of 110 % (1.1 A for 1 A CT and 5.5 A for 5 A CT). We request you to kindly consider this factor while choosing the layout of the transformer. Please check by means of the following formula the correctness of your data: S= U I 3 Technical data subject to change without notice! 20 TD_XD1-T_01.04_GB

21 8 Setting-list XD1-T Project: SEG job.-no.: Function group: = Location: + Relay code: - Relay functions: Date: Setting of parameters Function Unit Default settings Actual settings Id1 Differential current 1 % In 5 Id2 Differential current 2 % In 5 TD_XD1-T_01.04_GB 21

22 Woodward SEG GmbH & Co. KG Krefelder Weg 47 D Kempen (Germany) Postfach (P.O.Box) D Kempen (Germany) Phone: +49 (0) Internet Homepage Documentation Sales Phone: +49 (0) Telefax: +49 (0) kemp.electronics@woodward.com Service Phone: +49 (0) Telefax: +49 (0) kemp.pd@woodward.com 22 TD_XD1-T_01.04_GB

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

Analog signal converters CC-E I/I Current / current isolators

Analog signal converters CC-E I/I Current / current isolators ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA w VOLTAGE MONITORING RELAY UR5U1011 w SCHRACK-INFO AC/DC voltage monitoring in 1-phase mains Undervoltage monitoring 1 change over contact Width 17.5 mm Installation design w TECHNICAL DATA 502 1. Functions

More information

CONSTANT CURRENT REGULATOR INDUPERM TYPE CCR 951. Standarddescription of CONSTANT CURRENT REGULATOR TYPE CCR 951.

CONSTANT CURRENT REGULATOR INDUPERM TYPE CCR 951. Standarddescription of CONSTANT CURRENT REGULATOR TYPE CCR 951. Standarddescription of TYPE CCR 951 List of contents: A. General Description B. General Data's and Functions C. CCR Working Principle D. Specifications Page 1 of 9 pages A. General Description. Induperm

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

Capacitor Protection Relay SPAJ 160 C. Product Guide

Capacitor Protection Relay SPAJ 160 C. Product Guide Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase

More information

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current. Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.

More information

Disturbance Recoder SPCR 8C27. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

SINEAX U553 Transducer for AC Voltage

SINEAX U553 Transducer for AC Voltage With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load

More information

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 Data sheet Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 The three-phase monitoring relays CM-PSS.x1 monitor the phase parameters phase sequence, phase failure as well as over- and undervoltage.

More information

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

Current transformers (CT) & Shunts

Current transformers (CT) & Shunts Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control

More information

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...

More information

40 Series - Miniature PCB/Plug-in relays 8-10 - 16 A. Features 40.31 40.51 40.52

40 Series - Miniature PCB/Plug-in relays 8-10 - 16 A. Features 40.31 40.51 40.52 Features 40.31 40.51 40.52 1 & 2 Pole relay range 40.31-1 Pole 10 A (3.5 mm pin pitch) 40.51-1 Pole 10 A (5 mm pin pitch) 40.52-2 Pole 8 A (5 mm pin pitch) PCB mount - direct or via PCB socket 35 mm rail

More information

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51 34 Series - Slim electromechanical PCB relays 6 34 SERIES Features 34.51 Ultra-slim 1 Pole - 6 relay Printed circuit mount - direct or via PCB socket 35 mm rail mount - via screw, screwless or push-in

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co.

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co. GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co., Mumbai ABSTRACT : For generator differential protection, one set of

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

60 Series - General purpose relays 6-10 A. Features 60.12 60.13

60 Series - General purpose relays 6-10 A. Features 60.12 60.13 Features 60.12 60.13 Plug-in mount 10 A General purpose relay 2 & 3 pole changeover contacts Cadmium Free contacts (preferred version) AC coils & DC coils UL Listing (certain relay/socket combinations)

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

Safety automation solutions

Safety automation solutions Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO

More information

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Control Devices Catalogue. Control Devices. Preferred and Standard Products Control Devices Catalogue Control Devices Preferred and Standard Products KOP.J Timer Electronic 22.5 mm Characteristics Mounting KOP.J 22.5 mm mono or multifunction high immunity to interference surface

More information

MINI MCR-SL-R-UI(-SP)

MINI MCR-SL-R-UI(-SP) Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/2

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/2 Power Supply, Primary Switch Mode, Narrow Design -PS-100-240AC/24/2 POWER provides: Extra narrow widths of 22.5 and 45 mm (0.886 and 1.772 in.) Global use due to a wide range input A high level of operational

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

Easy Multifunctional Safe

Easy Multifunctional Safe EMS Electronic motor starters www.eaton.eu Easy Multifunctional Safe EMS Multifaceted Performance with only 0 mm Eaton Moeller series products have always embodied quality and reliability in the machine

More information

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications 077 Series Analogue Features Monitors and controls any variable which can be converted to an A.C. or D.C. signal. Rugged, shock and vibration resistant design Indicator, relays and power unit in one housing

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

Digital Pressure Measuring Instrument MDR480

Digital Pressure Measuring Instrument MDR480 Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Generator Differential Relay Electrical Apparatus

Generator Differential Relay Electrical Apparatus Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

Manual Motor Starter MS 116 up to 16 A Technical Data

Manual Motor Starter MS 116 up to 16 A Technical Data Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates

More information

How To Protect Your Power Supply From Dangerous Currents And Voltages

How To Protect Your Power Supply From Dangerous Currents And Voltages ids ACOS 300 Protection equipment for medium and highvoltage grids ACOS 300 Protection Devices Already minor incidents, such as branches dropping on overhead lines or underground cables damaged by construction

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer

More information

PHOENIX CONTACT - 2012-12-14. Features

PHOENIX CONTACT - 2012-12-14. Features Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed

More information