MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Size: px
Start display at page:

Download "MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description"

Transcription

1 Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V DC and converts them to standardized analog signals. DC voltages can be processed with both positive and negative polarity. The input voltage ranges listed at input terminal blocks to can be varied by ±0% using a calibration potentiometer. The voltage transducer is calibrated by default to 0... ± V input and 0... ±0 V output and is ready for operation when delivered. To use the device with other input or output variables, carry out a ZERO/SPAN adjustment using the potentiometer on the front.. Features -way electrical isolation True r.m.s. value measurement Adjustable voltage ranges ZERO/SPAN adjustment ±0%. Method of Operation The input circuit divides the DC voltage at terminal blocks to. The resulting signal is electrically isolated and transmitted to the output circuit and is available at the output as a standardized analog signal.. Field of Application When using the voltage transducer, please ensure that the potential difference between terminal blocks to to ground potential PE or terminal block 8 to ground potential PE U does not exceed ±0 V (this condition applies to circuits that are not grounded). In DC voltage networks, this potential difference must not exceed U = ±00 V (this condition applies to circuits that are grounded). When these conditions are met, safe isolation is ensured between input, output, and supply. Make sure you always use the latest documentation. It can be downloaded at A conversion table is available on the Internet at This data sheet is valid for all products listed on the following page:

2 Ordering Data Description Type Order No. Pcs./Pck. MCR voltage transducer, for DC voltages from 0... ±0 V DC to 0... ±0 V DC, output signal ±0 V/±0 ma 8 Technical Data Voltage Measuring Input Input voltage range (input resistance) Maximum input voltage Maximum input voltage ±0 V DC (0 kω) ±0 V DC (0 kω) ±0 V DC (0 kω) ±0 V DC (0 kω) ±0 V DC (0 kω) ±80 V DC (80 kω) ± V DC ( kω) ± V DC ( kω) ± V DC ( kω) ±0 V DC (not grounded) ±00 V DC (to ground) When these values are observed, safe isolation (EN 08/D EN 08/VDE 00) is ensured between input, output, and supply. Voltage Output Voltage output signal Maximum voltage output signal Load/output load voltage output Ripple -0 V... 0 V ± V > 0 kω < 0 mv PP Current Output Current output signal Maximum current output signal Load/output load voltage output Ripple -0 ma... 0 ma ±0 ma < 00 Ω < 0 mv PP Power Supply Supply voltage range Maximum current consumption 8. V DC V DC < 0 ma General Data Limit frequency ( db) 0 Hz Measuring principle True r.m.s. value measurement Maximum transmission error < % (of final value) Maximum temperature coefficient < 0.0%/K Zero adjustment ±0% Span adjustment ±0% Step response (0-90%) ms Degree of protection IP0 000_en_0 PHOENIX CONTACT

3 General Data (Continued) Pollution degree Width x height x length. mm x 99 mm x. mm Housing version Polyamide PA, non-reinforced, green Connection Data Conductor cross-section, solid 0. mm.... mm Conductor cross-section, stranded 0. mm.... mm Stripping length 8 mm Safe Isolation Safe isolation According to EN 08 Test voltage input/output. kv (0 Hz, min.) Surge voltage category II Ambient Conditions Ambient temperature (operation) - C C Conformance/Approvals Conformance UL, USA/Canada CE-compliant u Conformance With EMC Directive 89//EEC Noise Immunity According to EN Electrostatic discharge EN kv air discharge Electromagnetic HF field Amplitude modulation Pulse modulation EN V/m 0 V/m Fast transients (burst) EN Input/output/supply: kv/ khz Surge current loads (surge) EN Input/output: kv/ Ω Supply: 0. kv/ Ω Conducted interference EN Input/output/supply: 0 V Noise Emission According to EN Noise emission according to EN EN 0 Class A 000_en_0 PHOENIX CONTACT

4 Block Diagram ±0V ± ±0V ± ±0V ±80V ±V ±V ±V D 8 Safety Notes 9 I 0 U D D + VDC + VDC D D CAUTION Installation, operation, and maintenance may only be carried out by qualified electricians. When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. CAUTION: Electrostatic discharge The module contains components that can be damaged or destroyed by electrostatic discharge. When handling the module, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 0-- and EN 0--. Structure 8 U U U U U U U D 0V 0V 8 8 Art.-Nr.: ±0V I ± U ±0V D ± D ±0V +VDC ± 80V +VDC ± V/± V/± V D D D APPROBATIONEN / APPROVALS Supply voltage Output Potentiometer for adjustment Inputs Upper part of the housing can be removed to set the jumpers Universal snap-on foot for EN D rails SPAN 9 OU 0! " $ % & ZERO +V +V D D I U D D OU Installation A B B The assignment of the connection terminal blocks is shown in the block diagram. The module can be snapped onto all mm D rails according to EN 0. Install the module in suitable housing to meet the requirements for the protection class. Screw Connection Insert the wires in the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block. B 000_en_0 PHOENIX CONTACT

5 8 Configuration U U U U U U U D 8. Opening the Module Using a screwdriver, release the locked upper part of the housing on both sides. The upper part of the housing and the electronics can now be pulled out approximately cm. 8. umper Settings 8 0V 0V 8 ± ± ± Place the jumper () in the desired setting for the input voltage. Close the housing again until it engages with a click. Carry out a ZERO/SPAN adjustment each time the input or output range is changed. WARNG: Risk of electric shock Never carry out work when voltage is present. ATTENTION: Module damage due to excess voltage If the voltage signal exceeds the voltage range specified at the input signal terminal block by more than % (for 0... ±0 V more than %), the input circuit may be damaged. V V V HYBRID TV PHOENIX CONTACT V V V 8. Selecting the Input Voltage Range Input Voltage Adjustment Range (±0%) [V DC] Input Terminal Block umper/ Setting 0... ±0 V (0... 0) V (9... ) V ( ) V (... 0) V (9... ) V (... 9) 0... V (... ) /setting 0... V (8... ) /setting 0... V (9... 9) /setting (default setting) 000_en_0 PHOENIX CONTACT

6 9 ZERO/SPAN Adjustment U U U U U U U D Potentiometer SPAN ZERO +V +V D D Art.-Nr.: 8 I U D D OU 9 OU 0! " $ Allow the module to warm up for minutes before starting the adjustment procedure. The module is calibrated by default to 0... ± V input and 0... ±0 V output. There are two potentiometers on the front of the module for the adjustment: ZERO: Zero point adjustment SPAN: Final value adjustment 9. Zero Point Adjustment (ZERO) Connect a calibration device to the input terminal blocks (U ( - ) and D) and specify a voltage of 0 mv. Set the output signal value using the ZERO potentiometer: Voltage output (0 ±0 V): U = 0 V Current output (0 ±0 ma): I = 0 ma 9. Final Value Adjustment (SPAN) Use the calibration device to specify the maximum voltage used within the input voltage range (see "Selecting the Input Voltage Range" on page ). Set the output signal value (U = 0 V or I = 0 ma) using the SPAN potentiometer. 000_en_0 PHOENIX CONTACT GmbH & Co. KG 8 Blomberg Germany Phone: PHOENIX CONTACT P.O.Box 00 Harrisburg PA -000 USA Phone:

MINI MCR-SL-R-UI(-SP)

MINI MCR-SL-R-UI(-SP) Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

PHOENIX CONTACT - 2012-12-14. Features

PHOENIX CONTACT - 2012-12-14. Features Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed

More information

Analog signal converters CC-E I/I Current / current isolators

Analog signal converters CC-E I/I Current / current isolators ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/2

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/2 Power Supply, Primary Switch Mode, Narrow Design -PS-100-240AC/24/2 POWER provides: Extra narrow widths of 22.5 and 45 mm (0.886 and 1.772 in.) Global use due to a wide range input A high level of operational

More information

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/2x15DC/1

Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/2x15DC/1 Power Supply, Primary Switch Mode, Narrow Design -PS-100-240AC/2x15DC/1 POWER provides: Extra narrow widths of 22.5 and 45 mm (0.886 and 1.772 in.) Global use due to a wide range input A high level of

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

PHOENIX CONTACT - 01/2007

PHOENIX CONTACT - 01/2007 Uninterruptible power supply INTERFACE Data Sheet 103123_00_en PHOENIX CONTACT - 01/2007 Description Especially compact and easy-to-use, the new MINI-DC-UPS/ 24 DC/2 is a combination of the power supply

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Contents. Document information

Contents. Document information User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

PSI-REP-PROFIBUS/12MB

PSI-REP-PROFIBUS/12MB Repeater for PROFIBUS Systems up to 12 Mbps INTERFACE Data Sheet 102986_02_en PHOENIX CONTACT - 03/2007 1 Description The PSI-REP-PROFIBUS/12MB DIN rail-mountable modular PROFIBUS repeater is designed

More information

PLC-RS /21. PLC INTERFACE With PDT Relay, Universal Version. INTERFACE Data Sheet 101780_en_02. 1 Description

PLC-RS /21. PLC INTERFACE With PDT Relay, Universal Version. INTERFACE Data Sheet 101780_en_02. 1 Description PLC INERFCE With PD Relay, niversal Version INERFCE Data Sheet 780_en_02 PHOENIX CONC - 03/08 Description PLC-RS /2 relay modules, which can be used universally, comprise 6.2 mm basic terminal blocks and

More information

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Control Devices Catalogue. Control Devices. Preferred and Standard Products Control Devices Catalogue Control Devices Preferred and Standard Products KOP.J Timer Electronic 22.5 mm Characteristics Mounting KOP.J 22.5 mm mono or multifunction high immunity to interference surface

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51 34 Series - Slim electromechanical PCB relays 6 34 SERIES Features 34.51 Ultra-slim 1 Pole - 6 relay Printed circuit mount - direct or via PCB socket 35 mm rail mount - via screw, screwless or push-in

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

JUMPFLEX 857 Series. 0...20 ma 2...10 V. 4...20 ma. Transducers / Relay and Optocoupler Modules

JUMPFLEX 857 Series. 0...20 ma 2...10 V. 4...20 ma. Transducers / Relay and Optocoupler Modules 0888-0172/0002-3601 JUMPFLEX 857 Series 2.0 E 12/08 Printed in Germany Subject to design changes 2...10 V 0...20 ma 4...20 ma WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 32385 Minden Hansastraße 27

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES AC averaging technique used to rectify, amplify, and filter 50 Hz to 400 Hz sine-wave signals. Accepts inputs of between 20 mv to 550 V rms to give

More information

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current

More information

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 Data sheet Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 The three-phase monitoring relays CM-PSS.x1 monitor the phase parameters phase sequence, phase failure as well as over- and undervoltage.

More information

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

APD336.221/.421 3 Outputs 19" DC/DC Converter, 50 Watt

APD336.221/.421 3 Outputs 19 DC/DC Converter, 50 Watt APD336.221/.421 3 Outputs 19" DC/DC Converter, 50 Watt High efficiency: 79% (@ 48V) DCin wide range: 9...36V or 18...72V DC 8 HP plug in width H15 standard pinout Active inrush current suppression Voltage

More information

Ordering Part Numbers: Universal Signal Converter: USC-CVB225-01 Universal Signal Converter with a 4-20mA input and +/- 10V output: USC-CVB225-B10V

Ordering Part Numbers: Universal Signal Converter: USC-CVB225-01 Universal Signal Converter with a 4-20mA input and +/- 10V output: USC-CVB225-B10V Description: The universal signal converter offers threeway isolation and translates one input control signal into one to three simultaneous outputs. Switches allow the user to select the desired input

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Features. Picture. Specifications

Features. Picture. Specifications Type: for level measurement Order No.: see Table 1 / Page 4 Features Picture Two wire system Piezoresistive measuring element Output signal 4-20 ma Conformity error ±0.5 % FS or Standard DIN measuring

More information

TEP 200WIR Series, 180 240 Watt

TEP 200WIR Series, 180 240 Watt TEP 200WIR Series, 180 240 Watt Features Chassis mount with screw terminal block Including EMI filter to meet EN 55022, class A Ultra wide 4:1 input voltage ranges 8.5 36, 16.5 75, 43 160 VDC EN 50155

More information

Operating Manual UWAPS-TINY Series

Operating Manual UWAPS-TINY Series Operating Manual UWAPS-TINY Series Powecon Oy WWW.POWECON.FI 1/9 Table of content 1 Warranty...3 2 Safety information...3 3 Abbreviations and terminology...3 4 List of appendices...4 5 Introduction...4

More information

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

2002 IS Catalog. Page

2002 IS Catalog. Page 00 IS Catalog Page Introduction... 47 Transmitter (8 V entity parameter) KFD-CR-Ex1.30.00 (-wire transmitter)... 48 KFD-CR-Ex1.30.300 (- or 3-wire transmitter)... 49 KFD-CR-Ex1.30.300 90C (- or 3-wire,

More information

3-phase, bidirectional energy meter

3-phase, bidirectional energy meter Data sheet www.sbc-support.com 3-phase, bidirectional energy meter with S0 pulse output Bidirectional energy meter with S0-interface. The S0 interface is a hardware interface for the transmission of measured

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Digital Pressure Measuring Instrument MDR480

Digital Pressure Measuring Instrument MDR480 Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic

More information

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050 Extract from the online catalog DEK-REL- 24/1/SEN Order No.: 2964050 Relay terminal block for sensor, with soldered-in miniature relays, contact (AgNi+Au): small to medium loads, 1 N/O contact, input voltage

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

SINEAX U553 Transducer for AC Voltage

SINEAX U553 Transducer for AC Voltage With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Adjustment functions for both span and shift have been incorporated

Adjustment functions for both span and shift have been incorporated SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 6 A 80. Multi-function and mono-function timer range - Multi-function & multi-voltage 80. - ON delay, multi-voltage 7.5 mm wide Six time scales from 0.s to 24h 35 mm rail (EN

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

Signal converters Index

Signal converters Index Signal converters Index Power supplies 2 - Signal converters Signal converters... 2. 2.24 Selection Accessories, CC-U...2.7 Analog signal converters, CC-E/STD & CC-E x/x...2.3 Analog standard signal converter,

More information

IEC 1000-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

IEC 1000-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays IEC 00-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays Application Note July 1999 AN9612.2 Author: Wayne Austin The SP720, SP721, SP723, and SP724 are protection

More information

Solarcheck string monitoring. User manual

Solarcheck string monitoring. User manual Solarcheck string monitoring User manual User manual Solarcheck string monitoring 2013-06-14 Designation: Revision: UM EN Solarcheck String Monitoring 00 This user manual is valid for: Designation Order

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000. NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24

More information

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary

More information

PHOENIX CONTACT - 03/2007

PHOENIX CONTACT - 03/2007 PSI-WL-PLUG-USB/ Bluetooth USB Adapter INTERFACE Data Sheet 103170_00_en PHOENIX CONTACT - 03/2007 Description The Bluetooth USB adapter provides an easy wireless connection between devices with a USB

More information

SVR 12/24V and SVR Akku 12V Installation instructions

SVR 12/24V and SVR Akku 12V Installation instructions U aus Akku Na 12/24V SVR 12V/24V 700 800 500 SVR Akku 12V 700 800 550 230V~ L1 N SVR 12/24V and SVR Akku 12V Installation instructions Table of Contents General.... 3 Installation Putting into Operation...

More information

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer

More information

Speed sensor MiniCoder GEL 247

Speed sensor MiniCoder GEL 247 Speed sensor MiniCoder GEL 47 Flange assembly Technical information version 08.0 The MiniCoder family from Lenord + Bauer offers spacesaving solutions for the contactless measurement of rotational movements

More information

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features Central 48 V DC Power Supplies for PoE-Components MICROSENS Description Active network equipment which is supporting the Power-over-Ethernet functions, typically requires a powerful 48 V DC power supply.

More information

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

Preset Counter signo 721

Preset Counter signo 721 Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

J TB/TW Temperature limiter, temperature monitor

J TB/TW Temperature limiter, temperature monitor JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

400-800. Series OMEGA WATTS POWER SUPPLY AC/DC SINGLE OR MULTIPLE OUTPUT. Flexible modular design. Programmable outputs** Power factor correction***

400-800. Series OMEGA WATTS POWER SUPPLY AC/DC SINGLE OR MULTIPLE OUTPUT. Flexible modular design. Programmable outputs** Power factor correction*** INPUT Input protection Thermal protection Switching frequency internal fuse standard 100KHz Input with PFC : (MML400PFC, MML600, MML800) Input voltage range 85*-264VAC Inrush current (peak) MML400PFC

More information

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01 ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Application Note TMA Series

Application Note TMA Series 1W, SIP, Single & Dual Output DC/DC Converters Features SIP Package with Industry Standard Pinout Package Dimension: 19.5 x 10.2 x 6.1 mm (0.77 x 0.4 x 0.24 ) 5V&12V Models 19.5 x 10.2 x 7.1 mm (0.77 x

More information

Kit 106. 50 Watt Audio Amplifier

Kit 106. 50 Watt Audio Amplifier Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

EMR measuring and monitoring relays

EMR measuring and monitoring relays EMR and monitoring relays The power of fusion. 1874 1886 1893 1899 1906 1908 1911 1934 1962 1963 1967 1976 1977 1983 1984 1989 1999 There s a certain energy at Eaton. It s the power of uniting some of

More information

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting Series - Relay interface modules 8-10 - 16 A Features.01.02 1 & 2 pole relay interface modules, screw terminal socket, mm wide. Ideal interface for PL and electronic systems.01-1 Pole 16 A.02-2 Pole 8

More information

ST Series POWER SUPPLIES USER INSTRUCTIONS

ST Series POWER SUPPLIES USER INSTRUCTIONS Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional

More information

93.68/93.69. Time scale: from 0.1s to 6h Multi-function For use with 34.51 (EMR) and 34.81 (SSR) relays. Screw terminal and push-in terminal

93.68/93.69. Time scale: from 0.1s to 6h Multi-function For use with 34.51 (EMR) and 34.81 (SSR) relays. Screw terminal and push-in terminal Series - Timed socket for 34 series Features.68/.69 Slim timed sockets for 34 series, 6.2 mm wide Timer adjustment via top mounted rotary knob accessible after assembly Control signal terminal DIP-switch

More information