1 David O Brien, CMP Products ([email protected])
2 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands? 5) Test Requirements 6) Earth Continuity Armour Termination 7) Product Certification Standards 8) AS/NZS Installation Standard 9) Selection Process - Flameproof Cable Glands 10) Compound Filled Barrier Glands 11) Currency of Certification 12) IEC 62444:2010
3 Environmental & Load Retention Seal on Cable Outer Sheath Earth Continuity by Means of Armour Clamping Explosion Protection Via Seal on Cable Inner Bedding Typical (SWA) Single Wire Armour Cable Ingress Protection Earth Continuity Cable Anchorage & Retention Protection technique / sealing cables in explosive atmospheres
4
5 When things go wrong Who is responsible? Who takes the blame?
6 Issue Doesn't maintain equipment integrity Incompatible with cable Doesn't meet required standards Over tightening Lack of earth continuity Cable not secured effectively Water Ingress / Corrosion Stakeholder Selection Client Engineer Product Design ISO 9001 Manufacturer Installation???? Contractor
7 Standards & Other Requirements to Consider MDA / QMD AS/NZS 2380 series IEC series AS/NZS 4871 AS/NZS 1972 AS/NZS AS/NZS 2381 series Certification Scheme Risk Assessment Dust Hazards (Zones 20, 21 & 22) AS/NZS Annex A AS/NZS AS/NZS No longer issued or current Withdrawn 2005 Fully endorsed by Australia Last updated in 2010 Last updated 2006 First published September Defines design, selection, and erection - Applies to Group I Mining situations along with Groups II & III Was to be withdrawn September AUS Ex, ANZ Ex, IEC Ex Equipment Protection Levels (EPL) DIP or Ex t IIIC A21 IP6X EPL Db to IEC or AS/NZS 61241? Clause A.2.5 (Release by a tool), Once installed cable glands should not be able to be opened by hand Flame transmission tests of cables and cable glands - per AS/NZS Section 4.7 (Environmental Conditions) All bolts and cable entries remain tight Section (Cable Glands) Inspectors check for tightness by hand
8 2.2.4 Unused openings and threaded entries Unused openings and threaded entries shall be closed or plugged so the degree of protection (see Clause 2.2.1) or the explosion-protection integrity of the enclosure or both is maintained. Precautions shall be taken to prevent release during normal service conditions. Ex d I Ex d I
9 Ex e II EPL Gb Ex d IIC EPL Gb Ex nr II EPL Gc Ex ia II EPL Ga Ex ta IIIC (DIP) EPL Da IP6X Ex d I EPL Mb
10 Generic Cable Type Sealing Ring Method of Protection / Sealing Barrier Seal Unarmoured Cable Armoured Cable Ex d I / IIC EPL Mb / Gb Ex d I / IIC EPL Mb / Gb IEC Ex certification is the same for all types Ex d I EPL Mb, Ex d IIC EPL Gb, How do we select? Ex e II EPL Gb, Ex nr II EPL Gc, When is a barrier seal Ex ta IIIC EPL Da required?
11 3.5.2 Explosion protected enclosures (c) Sealing - Where conductors are extended through a common wall between two flameproof enclosures or from a flameproof enclosure to external atmosphere, they shall be sealed in accordance with the enclosure certification. Where multicore or data cables, including fibre optic, are used they shall be sealed with a certified barrier gland or be verified by test for non-transmission of flame.
12 1.2 Application Cables shall comply with the relevant requirements of the following Standards, as appropriate for the types of cables specified. Section 2 AS/NZS Section 3 AS/NZS 1026 or AS/NZS Section 5 AS/NZS Type 1, 2, 2S, 3, 3S, 7, 7S, 8 Section 5 AS/NZS and AS/NZS Type 9
13 5.9.9 Tests (Type 9 Cable) The cable shall be tested in accordance with AS/NZS except that the high voltage test shall be carried out at a voltage of 1.5 kv. The cable construction shall comply with the requirements of the test for non-transmission of an internal ignition in AS/NZS when terminated through an Ex d gland to an Ex d enclosure except that the cable shall extend no more than 100 mm from the rear of the compression point and be flush with the point of entry.
14 5.5.6 Fillers Where used, fillers shall be non-hygroscopic Ex d I EPL Mb Cable Gland When is a Barrier Gland required?
15 For Group II Flameproof Type d enclosures, the cable should :- I. Substantially compact and circular (i.e. specifically the part of the cable entering the enclosure) II. III. Have an extruded bedding (penetrating around the conductors no gaps) Have fillers, if any are used, which are Non-Hygroscopic (Not have the ability to absorb or transport water molecules)
16 AS/NZS, IEC, BS, other Power, Control, Lighting, Instrument, Data, Fibre LV, MV, HV, EHV Shielded (IS or OAS), Unshielded Paper Insulated Lead Covered Unarmoured Armoured Single Wire Armour (SWA) Steel Tape Armour (STA, DSTA) Braided (GSWB, BWB, CWB) Pliable Wire Armour (PWA) Strip Armour (ASA) Corrugated Metal Clad or Steel Tape Must be selected, installed & sealed correctly
17 Type of wiring system (Group II Gas) EPL Ga EPL Gb EPL Gc Cables in metallic conduit and fittings complying with AS/NZS and AS/NZS and the appropriate protection technique for the area in which they are to be installed. P P P Served MIMS. * P P Thermoplastic, thermosetting or elastomeric sheathed unarmoured. Zone 2 Thermoplastic, thermosetting or elastomeric sheathed with armouring or braiding designed for mechanical protection. Cables (EPL in rigid Gc) and corrugated, sheathed non-metallic conduit, unarmoured. minimum light duty, complying with AS/NZS , AS/NZS and AS/NZS P * P P Metal sheathed, served and armoured. * P P Zone 1 & Zone 2 (EPL Gb, Gc) Flexible cords and cables in accordance with * P P Metal sheathed, served and unarmoured. Thermoplastic, thermosetting or elastomeric Thermoplastic, thermosetting or elastomeric sheathed with armouring or braiding designed for mechanical protection. Flexible steel conduit with non-metallic serving to AS/NZS and AS/NZS Trunking, ducts, pipes or trenches installed to meet the requirements of P P Flexible conduit assemblies complying with the relevant requirements of AS/NZS P P P denotes permitted use. * This wiring system may be installed in a location requiring EPL Ga, if provided with additional protection to counter the harmful environmental effects detailed in For additional requirements for conduit refer to 9.4. P P P
18 Flameproof Type d Cable Entry (AS/NZS ) Direct Entry Ex d
19 Group II Certified to AS/NZS Five options exist. a) Cable gland certified as part of the equipment along with specified cable. b) Cable gland with a sealing ring following Figure 2, provided cable selected suits defined criterion. c) M.I.M.S. cable with matching certified cable gland. d) Flameproof sealing device (e.g. sealing chamber with compound) plus certified cable gland. e) Flameproof cable gland with compound or elastomeric seal around the individual cores.
20 AS/NZS :2009 Section Figure 2 Yes Start Does this enclosure contain an internal source of ignition? No Apply d) or e) Yes Yes Does the hazardous gas require IIC apparatus? Is the volume of the enclosure bigger than 2 dm ³? Yes No Is the area of installation Zone 1? No No Use a suitable flameproof cable entry device with a sealing ring b)
21 Flame Path Exhaust Routes Seal to withstand 450 PSI of Pressure (30 bar) Flame Path Compound seal shall be at least 20% of the cross sectional area Direction of Flame / Pressure / Hot Gases Epoxy Resin Compound
22 AS/NZS :2009 Section Figure 2 Yes Start Does this enclosure contain an internal source of ignition? No Apply d) or e) Yes Yes Does the hazardous gas require IIC apparatus? Is the volume of the enclosure bigger than 2 dm ³? Yes No Is the area of installation Zone 1? No No Use a suitable flameproof cable entry device with a sealing ring b)
23 Flameproof Type d enclosure mounted in test chamber Test Condition: 5 tests with pre-pressure of 0.5 bar Mixture: H 2 -Air (28 +/- 1)% H 2 C 2 H 2 -Air (7.5 +/-1)% C 2 H 2 Cable Length: 145 mm Outer explosive atmosphere Inner Explosion 23
24 24
25 Flame Transmission possible 25
26 Growing number of fibre optic cables and other special cables for communication applications. 4 year period a series of 72 different ignition test series were carried out at the request of customers. Different cable glands from different manufacturers Pull tests according AS/NZS Appendix A, and ignition tests according to AS/NZS applied. 72 samples tested, 59 passed, 13 failed (18%)
27 Considering multicore, data, fibre optic and instrument cables, a liquid pour resin barrier gland would be ideal.
28 Equipment Form of Protection Product Certification Standards Australian Standards AS , AS & AS withdrawn Latest AS / NZS Standards EPL Category Equivalent Zone General Requirements AS AS/NZS : Ex d Flameproof AS AS/NZS :2007 EPL Gb 1 Ex e Increased Safety AS AS/NZS :2006 EPL Gb 1 Ex ia Intrinsic Safety AS AS/NZS :2011 EPL Gb 0 Ex ib Intrinsic Safety AS AS/NZS :2011 EPL Gb 1 Ex ic Intrinsic Safety AS AS/NZS :2011 EPL Ga 2 Ex na Ex nw Ex nl Ex nr Non-Sparking Enclosed Break Energy Limitation Restricted Breathing AS AS/NZS :2011 EPL Gc 2 Ex o Oil Immersion No Standard AS/NZS :2007 EPL Gb 1 Ex m Encapsulation AS 2431 AS/NZS :2011 EPL Gc 2 Ex p Pressurisation AS AS/NZS :2007 EPL Gb 1 Ex q Sand / Quartz Filled No Standard AS/NZS :2007 EPL Gb 1
29 The following referenced documents are indispensable for the application of this document. AS/NZS Parts 0, 1, 7, 15 etc. Also refers to AS/NZS 4871, Electrical equipment for underground coal mines. Products certified under AUS Ex or ANZ Ex schemes to AS 2380 series of standards do not fit in the spirit of the latest installation requirements
30 AS/NZS : 2005 (or later) Annex A 30
31 Cable Glands for Armoured Cables 1) Armour is for Mechanical Protection. 2) Mechanism for Earth Continuity The armour should be clamped, or crimped, securely to prevent loss of earth continuity. AS/NZS Clause A.2.5 (Release by a tool), states that Cable glands shall be designed so that after installation they are only capable of being released or dismantled by means of a tool. AS/NZS Section 4.7 (Environmental Conditions) states that If the equipment is subject to vibration, special care shall be taken to ensure that bolts and cable entries remain tight.
32 CURRENCY OF CERTIFICATION
33 AUS EX CERTIFICATION
34 ANZ EX CERTIFICATION
35 IEC EX CERTIFICATION
36 Performance standard, Introduced August 2010 Classifies cable glands according to :- Material Mechanical properties Cable retention Cable anchorage Resistance to impact Electrical properties Resistance to external influences Degree of protection IEC (IP Code) Resistance to corrosion Resistance to ultraviolet light See for more information 36
37 Main Issue Latest Explosive Atmospheres standards IEC 62444:2010 industrial cable gland standard MDA / QMD / AS/NZS 2380 Series IEC Ex Certification More careful evaluation of cable Selection of Group I & Group II barrier glands Tightness of cable glands to AS/NZS Long term performance meeting expectations? Qualification AS/NZS Series Should be considered Cannot be developed The Leading Scheme Of great importance Needs some review Do they pass inspection Reliability Measurement
38
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
Operating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
CMP PRODUCTS. Ex d / Ex e / Ex nr CABLE GLANDS AND CONNECTORS. Triple Certified. www.cmp-products.com www.cmp-products.ru
www.cmp-products.com www.cmp-products.ru IECEx & ATEX 95 CMP PRODUCTS CABLE GLANDS AND CONNECTORS FOR THE IEC & NEC WORLD ATEX 95 & BEYOND C US Triple Certified Single Solution - Three Forms of Protection
Electrical Equipment in Hazardous Areas: Field Inspections
Electrical Equipment in Hazardous Areas: Field Inspections Bill Rankin Electrical Engineer / Senior Electrical Inspector Abstract Electrical equipment and installations that fall within explosive gas atmospheres
CMP PRODUCTS CMP. Terminating Cables is our Business. Onshore Offshore Marine Mining Surface Underground
PRODUCTS Industrial and Explosive Atmosphere s and Conduit Accessories Terminating s is our Business Onshore Offshore Marine Mining Surface Underground Solutions complying with BS 6121, EN 50262, IEC 62444,
CABLE GLANDS AND CONNECTORS FOR THE IEC & NEC WORLD ATEX 95 & BEYOND ATEX 95 CMP PRODUCTS. Triple Certified
IECEx & ATEX 95 CMP PRODUCTS S AND CONNECTORS FOR THE IEC & NEC WORLD ATEX 95 & BEYOND Triple Certified Single Solution Three Forms of Protection Ex d / Ex e / Ex nr N O O T H E R M A CONTENTS Leading
Session 12 Ex Protection Concepts
Session 12 Ex Protection Concepts Ex Protection Concepts Electrical Electrical Symbol Typical Typical Zones IEC Standard Basic concept of protection IEC EPL Increased safety e Gb 1,2 IEC 60079-7 No arcs,
HAZARDOUS AREA TECHNICAL GUIDE
Page 1 HAZARDOUS AREA TECHNICAL GUIDE The Redapt Hazardous Area Technical Guide provides an overview for the design and use of equipment used within potentially explosive atmospheres created by gases,
IECEx & ATEX 95 CABLE GLANDS AND CONNECTORS FOR THE IEC & NEC WORLD ATEX 95 & BEYOND CMP PRODUCTS
NEWCASTLE (Headquarters) CMP Products 36, Nelson Way, Nelson Park East, Cramlington, Northumberland, NE23 1WH, England Tel: +44 191 265 7411 Fax: +44 01670 715646 E-Mail: [email protected] DUBAI CMP
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Explosion Proof. Explosion Proof
Explosion Proof Explosion Proof Table of Contents Lighting Fixtures...I Panels....II Sockets and Plugs.....III Motor Starters.....IV Fittings V Junction Box... VI CBLE GLND ND CBLE CONNECTION SPECILISTS
INTERNATIONAL STANDARD
IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60
Amphenol Cable Glands and Cord Grips 12-055-1. Amphenol
Amphenol Cable Glands and Cord Grips 12-055-1 Amphenol Table of Contents Page Number Introduction 1 Amphenol Cable Glands 2-3 ATEX Approved Glands Featuring Elastometric Seals EX-20 4-5 EX-25 6-7 EE-30
Safety instructions VEGADIS DIS81.CEIA/V****
Safety instructions VEGADIS DIS81.CEIA/V**** CSA 14.2662675 Ex d IIC T6 T1 Gb 0044 Document ID: 48926 Contents 1 Area of applicability... 3 2 General information... 3 3 Technical data... 3 4 Application
Ex q Powder Filling. This is a technique primarily used for oil filled switch-gear. The spark is formed under oil and venting is controlled.
Methods of explosion protection for electrical equipment Flammable atmospheres can be ignited by sparks or not surfaces arising from the use of electrical power. Other possible sources of ignition are
CONSULTING Training Courses
CONSULTING Training Courses 2 EXPLOLABS TRAINING MAKES THE DIFFERENCE 1. GENERAL Why training by Explolabs Consulting? For training in the specialized, high-risk field of explosion protection, one needs
Instructions for Safe Use
Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety
<< Previous Page Next Page >>
> CONTENTS INTRODUCTION 01 INDUSTRIAL CABLE GLANDS 03-09 COMPRESSION TERMINALS 10-22 CABLE CLEATING & FIXING SYSTEMS 23-33 STANDARD SELECTOR CHARTS 34-37
SEISMIC VELOCITY TRANSDUCER T1-40
SEISMIC VELOCITY TRANSDUCER T1-40 Measurement of Omnidirectional Absolute Vibrations Certified according to ATEX 94/9/CE directive OPERATION Transducer T1-40 serves for seismic measurement of the absolute
Terminal Box. Specifications TNCN
Terminal box The /TNCC range comprises many standard sizes of enclosures manufactured in stainless steel 316L for maximum environmental protection. The main body is manufactured from minimum 1,5 mm sheet
Technical data sheet TDS0070
Technical data sheet TDS0070 ATEX Certified II 2 G Ex d IIC T4 Gb IECEx Certified Ex d IIC T4 Gb Ta = -20ºC to +60ºC FEATURES INCLUDE: - ATEX and IECEx Certified explosion proof Exd housing for Premier
distributing & controlling system solutions
distributing & controlling system solutions your safety our reality Users > Oil and gas industry production storage transport > Petrochemical industry > Chemical industry > Pharmaceutical industry > Food
Terminal Boxes Series 8146
Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm
Compact pressure switch Flameproof enclosure Ex d Model PCA
Mechatronic pressure measurement Compact pressure switch Flameproof enclosure Ex d Model PCA WIKA data sheet PV 33.31 for further approvals see page 4 Process Compact Series Applications Pressure monitoring
Process of certification against the requirements of Annex C of ARP 0108. Roelof Viljoen Mining And Surface Certification CC
Process of certification against the requirements of Annex C of ARP 0108 Roelof Viljoen Mining And Surface Certification CC 1 Scope of presentation: Process of certification against the requirements of
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H***** FM 3046039 Class I Div 1, Groups A, B, C and D Class II Div 1, Groups E, F and G; Class III Class I, Zone 0, AEx ia IIC Ga, Ga/Gb, Gb Document ID:
EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL
PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
FIRE RESISTANT CABLE CONSTRUCTION OF CABLES
FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the
Linear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
2.12. page 223 2.12. Products for Explosion hazardous Environment
2.12 page 223 2.12 Products for Explosion hazardous Environment Non-electric valves for explosion 2.12.1 page 224 hazardous environment The following manually and mechanically actuated valves are available
3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35
CONTENTS INTRODUCTION 1 Cable selection, cable specification, cable services CABLES Constructional data: 3.6/6 kv XLPE insulated cables 5 SECTION 1 6/10 kv XLPE insulated cables 15 SECTION 2 8.7/15 kv
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
Session 13 Wiring Methods & Cable Standards
Session 13 Wiring Methods & Cable Standards NORSOK Standards The NORSOK standards are developed by the Norwegian petroleum industry to ensure adequate safety, value adding and cost effectiveness for petroleum
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
CONFLEX ELECTRIC CABLE
CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard
Hazardous Locations Training
Hazardous Locations Training If you are involved with projects associated with hazardous locations, which involves the installation or inspection and maintenance of electrical or non-electrical e.g. mechanical;
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
Specializing in the cable business for over 38 years, PT. SUPREME CABLE
Specializing in the cable business for over 38 years, PT. SUPREME CABLE MANUFACTURING & COMMERCE Tbk. (PT. SUCACO Tbk) has grown steadly to become a largest and leading cable manufacturer, with international
EASE OF INSTALLATION AND CRUCIAL CABLE CARE
EASE OF INSTALLATION AND CRUCIAL CABLE CARE TRITON TM delivers a unique concept in cable sealing techniques incorporating the patented Compensating Displacement Seal system, CDS TM Introduced to effectively
CMP PRODUCTS CMP SEPTEMBER 2007. Incorporating Triple Certified Products. Industrial and Hazardous Area Cable Glands and Accessories
CMP CMP PRODUCTS Incorporating Triple Certified Products SEPTEMBER 2007 Industrial and Hazardous Area s and Accessories Single Solution Three Forms of Protection Ex d / Ex e / Ex nr BRIEF HISTORY OF BRITISH
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS
Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM
Important Information: Complete Terms and Conditions are printed on sales invoices
Important Information: Complete Terms and Conditions are printed on sales invoices Notice: L&H Group is continually working to improve and add new products to the Cable Express product range. For this
Model 3051 Pressure Transmitter with HART Protocol
Model 3051 Pressure Transmitter with HART Protocol Start Step 1: Mount the Transmitter Step 2: Consider Housing Rotation Step 3: Set the Jumpers Step 4: Connect the Wiring and Power Up Step 5: Configure
Design, testing, certification, installation & maintenance
Legislation, Standards and Technology Design, testing, certification, installation & maintenance of electrical equipment in hazardous locations in India by Wolfgang Berner, Ashwini Bondale and Manikandan
FGM 160 ATEX EC type examination certificate
Document number: 75.120.223 Document title: FGM 160 ATEX EC type examination certificate Scope: EN 60079-0, 1, 7, 11, 26 Additional Information (when applicable) F 2015.06.03 New certificate issue Nemko
White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection
White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF) Please read these instructions thoroughly before installation and ensure they are passed
Offshore Transformer Platform. Technical Standard. Energinet.dk. HV, MV, LV and Signal Cables and Cable Routing
Offshore Transformer Platform Technical Standard Energinet.dk HV, MV, LV and Signal Cables and Cable Routing ETS - 03 Rev. 1 Acadre doc. 44858-09 Revision survey Chpt. Description Revision Date Resp. -
SAFETY ALERT SWITCHBOARD INTERNAL SEGREGATION AND IP RATING. May 2014 BACKGROUND
SAFETY ALERT SWITCHBOARD INTERNAL SEGREGATION AND IP RATING May 2014 BACKGROUND There has been a recent serious incident involving a large arc event caused by material falling through an opening in a switchboard
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
Technical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
I N D U S T R I A L C A B L E G L A N D S
Introduction 1/2 Industrial Cable Gland W Industrial Cable Gland WL Heavy Duty Industrial Cable Gland CW Industrial Cable Gland CZ Industrial Cable Gland 1W Industrial Cable Gland 1Z Industrial Cable Gland
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
Linear Luminaire for Fluorescent Lamps Series EXLUX 6001
> As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened
Separation of common services (above and below ground) INDUSTRY BULLETIN. Background. Separation distances. Proximity of services below ground
Government of Western Australia Department of Commerce Separation of common services (above and below ground) The purpose of this industry bulletin is to remind building practitioners of their responsibilities
TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
Floodlight Range Installation Guide
SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected
Hazardous location. Definitions
Hazardous location Definitions hazardous location means any location, where there may be a significant risk of igniting gas, dust, mist or vapour, including the following: 1.1 For underground coal mines
LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
CUSTOMS UNION. CUSTOMS UNION CERTIFICATE OF CONFORMANCE No. RU C-DE.ГБ05.В.00224 Series RU No. 0067507
EAC CUSTOMS UNION CUSTOMS UNION CERTIFICATE OF CONFORMANCE No. RU C-DE.ГБ05.В.00224 Series RU No. 0067507 CERTIFYING BODY Non-Profit Independent Research Organisation Certification Electrical Equipment,
Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1
Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader
BETAtrans. Cables and Systems for Rolling Stock. Edition 2006
BETAtrans Cables and Systems for Rolling Stock. Edition 2006 Info Consulting and Sales By Phone To ask for Information or to place an order please use the following number: +49 (0)9172-6844-11 By Fax For
Guide to enclosures for potentially explosive atmospheres
Guide to enclosures for potentially explosive atmospheres Guide to enclosures for potentially explosive atmospheres The safety of every application, in every environment, thanks to ATEX-certified steel,
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
MT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D
MT MOTORI ELETTRICI Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D TABLE OF CONTENTS 1. Introduction 2. Scope of application 3. Installation
Making sense of Intrinsic Safety and Intrinsically Safe Tools
Making sense of Intrinsic Safety and Intrinsically Safe Tools What is Intrinsically Safe? Intrinsic safety is a protection standard employed in potentially explosive atmospheres. Devices that are certified
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
Article 505. 505.1 Scope. 505.2 Definitions. Article 505. Class I, Zone 0, 1, and 2 Locations. 52 Cooper Crouse-Hinds Code Digest
Informational Note No. 2: In unclassified locations, identification is necessary to ensure that nonintrinsically safe wire will not be inadvertently added to existing raceways at a later date (C) Color
)454, !,5-).)5- #!",% 3(%!4(3 #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43. )454 Recommendation,
INTERNATIONAL TELECOMMUNICATION UNION )454, TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43!,5-).)5- #!",% 3(%!4(3
SECTION 18370 SIGNAL WIRE AND CABLE
SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory
HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001
NEW POL DEPOT AT HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & S GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 TECHNICAL SPECIFICATION OF XLPE, FRLS LT CABLES
Gulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
Australian Standard. Intruder alarm systems. Part 1: Systems installed in client s premises AS 2201.1 1998
AS 2201.1 1998 Australian Standard Intruder alarm systems Part 1: Systems installed in client s premises This Australian Standard was prepared by Committee EL/31, Intruder Alarm Equipment and Installations.
Flameproof Audible Signal 115 db (A) Series YA90
Clifford Snell www.stahl.de > Max sound output 115 db (A) / 1 m > 2 stage alarm, independently selectable 2nd stage > IP66 rated as standard > 32 selectable tones meeting international regulations > Light
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
WHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
Fire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
Level Switch LBFS. Technical Data. ATEX data Internal inductivity Li < 10 μh Internal capacity Ci < 43 nf Barrier data. Sensor
Special Features Wetted parts in stainless steel and PEEK Compact design Precise switching point with no requirement for calibration Process temperature 0... 5 C Measures media with DKvalues >.5 (DK =
Safety Standards For Electrical Installations JSP 482 Edition 4 And Equipment In Explosives Facilities CHAPTER 8
Safety Standards For Electrical Installations JSP 482 Edition 4 CHAPTER 8 SAFETY STANDARDS FOR ELECTRICAL INSTALLATIONS AND EQUIPMENT IN EXPLOSIVES FACILITIES CONTENTS Para 1 INTRODUCTION...5 1.1 Scope
Explosion Protected Electrical Apparatus in the Russian Federation
Legislation, Standards and Technology Explosion Protected Electrical Apparatus in the Russian Federation Adaptations of National Standards to International Standards, deviations and peculiarities by Vitaly
Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx
Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment
International Electrotechnical Commission Standards
International Electrotechnical Commission Standards Standard IEC 60028 IEC 60038 IEC 60050-461 IEC 60055-1 IEC 60055-2 IEC 60092-101 IEC 60092-350 IEC 60092-351 IEC 60092-352 IEC 60092-353 IEC 60092-354
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment
Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment Qatar General Electricity & Water Corporation KAHRAMAA Customer Services Department State of Qatar
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation
Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage
Terminal Boxes in Glass Fiber Reinforced Polyester (GRP)
Features Variants options Glass fiber reinforced polyester (GRP) enclosures Suitable for installation in Zones 0, 1, 2, 21 and 22 Certified Ex e, Ex ia and Ex tb 16 enclosure size options Various terminal
AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:
PRODUCT DATASHEET & APPLICATIONS GUIDE BASEC APPROVED AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2
AS/NZS 3000:2007 Amendment 2
AS/NZS 3000:2007 Amendment 2 Published 14 December 2012 Under Victorian legislation the day a revised standard is published it becomes the requirement. The aim of this document is to highlight the important
Flexible cables for submersible products
Flexible cables for submersible products Standards SUBCAB cables complies with the following general standards: IEC 6045 (general) IEC 608 class 5 (conductor) IEC 608-- CLAUSE 9 (oil resistant) IEC 608--
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY. (The following code explanations are to be used with a copy of the 2011 NEC.
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY (The following code explanations are to be used with a copy of the 2011 NEC.) To obtain a copy of the NEC contact: National Fire Protection Association
Attachment to GB/FME/ExTR08.006/05 Electrical Apparatus FEP3** ProcessMaster Electromagnetic Flowmeter FEP5** ProcessMaster Electromagnetic Flowmeter FEH3** HygienicMaster Electromagnetic Flowmeter FEH5**
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62305-3 Edition 2.0 2010-12 colour inside Protection against lightning Part 3: Physical damage to structures and life hazard INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE
Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered