Offshore Transformer Platform. Technical Standard. Energinet.dk. HV, MV, LV and Signal Cables and Cable Routing

Size: px
Start display at page:

Download "Offshore Transformer Platform. Technical Standard. Energinet.dk. HV, MV, LV and Signal Cables and Cable Routing"

Transcription

1 Offshore Transformer Platform Technical Standard Energinet.dk HV, MV, LV and Signal Cables and Cable Routing ETS - 03 Rev. 1 Acadre doc

2 Revision survey Chpt. Description Revision Date Resp. - 1st edition and revision SGH Appendix no. and description Revision None ETS - 03 Rev. 1

3 Table of contents 1. Scope 1 2. References Statutory Regulations Codes and Standards 1 3. Definitions Definitions 2 4. Technical Requirements General Requirements Cable segregation Cable ladders and trays Cable installation Cable pulling force and bending radius Cable cleating and strapping Cable splicing Temporary cables Cable gland selection Termination Spare conductors Marking HV cables Specification Selection MV cables Specification Selection LV cables Specification Power supply cable Selection Signal cables Specification for category 5e cables Specification for coax cables Specification for optical fibre cables Specification for twisted pair cables Selection Certificates / Data books Appendix 13 ETS - 03 Rev. 1

4 1. Scope This technical standard specifies the basic requirements for the High, Medium and Low Voltage and signal cables to be used on an offshore located transformer platform for offshore wind farms established in the Danish offshore sector. Further the installation, segregation and support of cables is described in general terms. 2. References 2.1 Statutory Regulations Energi Styrelsen RETNINGSLINIER FOR DESIGN AF FASTE OFSHOREANLÆG Direktiv 2006/95/EF Lavspændingsdirektivet BEK nr. 27 af 10/01/2007 Bekendtgørelse om radio-og teleterminaludstyr og elektromagnetiske forhold (EMC Direktiv 2004/108/EF) 2.2 Codes and Standards ANSI/TIA 568B Communications cabling standard EN Sectional specification for horizontal floor wiring cables with a common overall screen for use in digital communication EN Information technology Generic cabling systems IEC Information technology Generic cabling for customer premises IEC IEC standard voltages IEC Electrical installations in ships IEC Guide to the selection of high-voltage cables IEC Electric cables Calculating of the current rating IEC Conductors of insulated cables IEC Tests for electrical cables under fire conditions IEC Tests on electric and optical fibre cables under fire conditions IEC Low-voltage electrical installations IEC Short-circuit temperature limits of electric cables with rated voltages from of 1 kv (U m =1,2 kv) and up to 3 kv (U m =3,6 kv) IEC Test on gasses evolved during combustion of electric cables ETS - 03 Rev. 1 1

5 IEC Optical fibres IEC Optical fibre cables IEC Power cables with extruded insulation and their accessories for rated voltages above 30 kv (U m = 36 kv) up to 150 kv (U m =170 kv) Test methods and requirements IEC Electrical test methods for electrical cables IEC Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects IEC Short-circuit temperature limits of electric cables with rated voltages from of 6 kv (U m =7,2 kv) and up to 30 kv (U m =36 kv) IEC Measurement of smoke density of cables burning under IEC Measurement of smoke density of cables burning under defined conditions IEC Short-circuit temperature limits of electric cables with rated voltages above 30 kv (U m =36 kv) IEC Mobile and fixed offshore units Electrical installations IEC/TR Electric cables Calculation for current ratings Finite element method 3. Definitions 3.1 Definitions Shall: Verbal form used to indicate requirements to be strictly followed in order to conform to the standard and from which no deviation is permitted, unless accepted by all parties. Should: Verbal form used to indicate that among several possibilities one is recommended as particularly suitable, without mentioning or excluding others, or that a certain course of action is preferred but not necessarily required. May: Verbal form used to indicate a course of action permissible within the limits of the standard. Can: Verbal form used for statements of possibility and capability, whether material, physical or casual ETS - 03 Rev. 1 2

6 4. Technical Requirements 4.1 General Requirements Cables shall comply with the relevant standards applicable for the particular use of the cable. All cables used shall be minimum flame retardant (IEC 60332). Fire resistant cables shall be used for essential services such as fire detection and alarming and emergency lighting. Generally all cables should have a tinned copper braid armouring and an outer sheath which is UV resistant. Cables without armour may be used in staff rooms and in control equipment rooms Cable segregation Signal cables shall be routed separate from HV, MV and LV cables. Minimum distance should be 600mm to HV and MV cables and 300mm to LV cables. Instrument cables and communication cables can generally be routed together. Signal cables crossing at a right angel with LV cables is acceptable without further segregation. High voltage cables shall in the full length be separated from medium voltage and low voltage cables by at least 300 mm unless mechanically separated by earthed metal partitions or pipes. Medium voltage cables shall in the full length be separated from High voltage and low voltage cables by at least 300 mm unless mechanically separated by earthed metal partitions or pipes. Considerations must be taken during installations of cables entering and leaving equipment like power transformers, crane etc. related to the requirements of segregation Cable ladders and trays All cables should be routed on cable ladders, cable trays and/or J-tubes. Outdoor cable ladders and trays shall be fibre reinforced plastic. Indoor cable ladders and trays may be galvanized steel. Conduits may be used for special mechanical protection of single field routed cables for shorter distances. ETS - 03 Rev. 1 3

7 The cable ladders and trays should not be filled so the height of their side rail is exceeded. Further the ladders and trays should not be filled beyond 50% of their total capacity. Redundant cable systems shall as far as possible be routed separately. MV cables should be routed and grouped depending of the chosen current carrying capacity estimation method, according to section Cable installation Access for maintenance and an orderly layout shall be ensured when cabling below raised floor is performed. Once a cable has been cut, a protective cap/sealing shall be applied on the end, when being exposed to humid atmosphere. All cable entries to equipment located outdoor and in deluge covered areas should be from below. Top entry is not allowed and side entry shall be provided with additional protection against ingress of moisture. Sufficient cable spare length shall be provided for equipment which needs future adjustments (floodlights, loudspeakers, TV cameras etc.) or where equipment have to be dismounted for maintenance and calibration without disconnecting the cable. Single core cables for three-phase AC shall run in trefoil formation. The braided armour shall be earthed in one end only. Single core cables shall not be installed separately through openings surrounded by magnetic materials. Non-magnetic stainless steel separation walls and stay plates shall be used in cable transits used for single core cables Cable pulling force and bending radius The maximum pulling force and minimum permissible bending radius specified by supplier shall be adhered to Cable cleating and strapping All cables shall be fixed properly to the cable support systems. Plastic coated stainless steel straps shall be used for all cable runs outside and in non ventilated areas. UV resistant nylon straps may be used in indoor and ventilated locations. The Plastic coated stainless steel straps shall be used for vertical runs and for horizontal runs in the vertical plane both indoor and outdoor. For strapping of fibreoptical and coaxial cables, supplier guidelines shall be adhered to. ETS - 03 Rev. 1 4

8 The distance between cable straps shall not exceed: 600mm for horizontal runs 300mm for vertical runs and for horizontal runs in the vertical plane Ten times the cable outer diameter from cable entry to the first strap Single core power cables for three-phase AC shall be fixed with trefoil cable cleats which shall be approved for the potential short circuit stress. The cleats shall outdoors, in naturally ventilated areas and deluge covered areas be made of stainless steel. The distance between trefoil cleats shall be as specified by the cable manufacturer based on the calculated short circuit level. The distance shall be selected such that the cable will not be damaged by a possible short circuit. Normal distance is 300mm, and on every step on bends and risers Cable splicing Cable splicing should be avoided. If splicing seems unavoidable it shall be agreed with Energinet.dk for the installation in question Temporary cables Temporary cables routed on permanent cable support systems shall be installed such that they will not obstruct permanent installations and are easy to remove Cable gland selection Cable glands, bushings, modular multi cable transits (MCT) or fittings for screwed conduits, shall be provided according to the way in which the cables enter the equipment or rooms. All entries shall maintain the degree of protection provided by the enclosure of the associated equipment or room. These shall apply to the whole range of cable dimensions specified by the manufacturer of the cable entries as suitable for use with those entries. Bottom entry is preferred for outdoor or deluge protected areas. Side entry is acceptable by use of drip nose installation for the cable in question. Types, maximum numbers and positions of Cable glands and blanking element entries for mounting in electrical apparatus for installation in explosive gas atmospheres shall be specified in a document submitted by the manufacturer. Shrouds and similar shall not be used on cable glands Termination All cable conductors shall be terminated by use of compression lugs or ferrules dependent upon the type of termination. The compression ferrule should be the type ETS - 03 Rev. 1 5

9 where the conductor strands are inserted through the whole ferrule and reach the bottom of the terminal. Support for cleating of cables when entering the panels should be provided. In switchboards and distribution boards adequate space shall be provided for the use of a clip-on ampere meter without causing undue stress on the cable conductors or connections. The braid armour and the screen shall be separated from each other as well as from the conductors, twisted and fitted as required. This shall be done without any reduction of the cross sectional area. Where the screen shall be left disconnected, which is applicable for field instruments, it shall be sealed and isolated with an isolating cap, allowing for insulation testing without any disconnecting. Only one conductor is allowed in each terminal of a terminal block/row for external connections. This is not related to terminals as integrated part of internal components (e.g. relays and contactors) of the equipment. Two conductors may in certain cases be used in one approved type ferrule connected to one terminal Spare conductors Spare conductors in instrument and telecom cables shall be terminated at the cabinet end and left floating at the field end. In cabinets all spare conductors shall be marked with terminal number and connected to terminals linked together by solid terminal links, which shall be connected to the relevant earth bar. Spare cores in instrument and telecom cables shall be connected to instrument earth in supply end only. If there are no spare terminals left in the cabinet, all spare conductors shall be covered with yellow/green sleeves and marked with relevant cable number and connected directly to the relevant earth bar Marking Numbering of cables shall be in accordance to the relevant document standard for the platform. Each cable shall be marked with indelible and non-corrosive cable markers indicating the cable number. The cable markers shall be clearly visible after cleating and strapping. Outdoors, in exposed- and deluge covered areas the cable markers should be made of stainless steel. Each cable shall have a cable marker located: ETS - 03 Rev. 1 6

10 At both sides of cable transits At both ends Outside cabinets with gland entries Inside cabinets with open entries 4.2 HV cables The designation High Voltage cables (HV cables) applies to submarine cables in a.c. three-phase systems having a nominal voltage above 35 kv and not exceeding 250 kv. The characteristics of the High Voltage range is specified according to IEC 60038, IEC standard voltages Specification The cable shall be three-core submarine cable with conductors made of copper. The insulation shall be dry extruded (XLPE) and longitudinally watertight. The sheat shall be made of lead or lead alloy. The cable shall be armoured with additional external corrosion protection capable of resisting forces acting on the cable during laying, embedding and possible repair. the armouring shall be applied in a continuous process. The cable shall have integrated optical fibres Selection A guidance for the selection of the cable conductor size, cable insulation level and cable construction is given according to IEC The lightning overvoltage of the cable must comply with the defined lightning protection zones and the effects of the installed lightning protection provisions. The choice of cables of appropriate cross-sectional area of conductors and current carrying capacity should be estimated according to information given in IEC and IEC/TR The selected cables and their insulated conductors shall be capable of withstanding the mechanical and thermal effects of the maximum short circuit current which can flow in any part of the circuit in which they are installed, taking into consideration not only the time/current characteristics of the circuit protective device, but also the peak value of the prospective short circuit current during the first half cycle. The cable short-circuit current withstand capability should be evaluated according to information given in IEC and IEC New and modified cable installations should be electrically tested as specified according to IEC ETS - 03 Rev. 1 7

11 4.3 MV cables The designation Medium Voltage cables (MV cables) applies to cables for fixed installations in all installations, whether permanent, temporary, transportable or hand-held, to a.c. three-phase systems having a nominal voltage above 1 kv and not exceeding 35 kv. The characteristics of the Medium Voltage range is specified according to IEC 60038, IEC standard voltages Specification Cables constructed in accordance with IEC , IEC , IEC and IEC are recommended for use as MV cables on fixed offshore units Selection The selection of the standard MV cable characteristics and type is based on the actual nominal system voltage and the demanded current carrying capacity. The choice of standard cables of appropriate voltage designations for particular systems depends upon the system voltage and the system earthing arrangements. A guidance for the selection of the cable conductor size, cable insulation level and cable construction is given according to IEC The rated voltage of any cable shall not be lower than the nominal voltage of the circuit for which it is used. To facilitate the choice of the cable, the values of U recommended for cables to be used in three-phase systems are listed in Table 1 in which systems are divided into the following three categories, A, B and C. Category A This category comprises those systems in which any phase conductor that comes in contact with earth or an earth conductor is automatically disconnected from the system. Category B This category comprises those systems that, under fault conditions are operated for a short time, not exceeding 8 hours on any occasion, with one phase earthed. Category C ETS - 03 Rev. 1 8

12 This category comprises all systems that do not fall into Categories A and B. Table 1 - Choice of cables for a.c. systems System voltage System Category Minimum rated voltage of cable U 0 /U Nominal voltage U kv Maximum sustained voltage, U m kv Unscreened kv Single-core or screened kv 3 3,6 A or B 1,8/3,0 1,8/3,0 3 3,6 C 3,6 / 6,0 6 7,2 A or B 3,6 / 6,0 6 7,2 C 6,0/ A or B 6,0/ C 8,7 / ,5 A or B 8,7 / ,5 C 12 / A or B 12 / C 18 / A or B 18 / C NA A or B NA C NA The lightning overvoltage of the cable must comply with the defined lightning protection zones and the effects of the installed lightning protection provisions. The choice of standard cables of appropriate cross-sectional area of conductors and current carrying capacity should be estimated according to one of the following methods: - As described according to IEC By calculation using a recognized method provided that the method is stated - According to IEC , Annex A - According to IEC , Annex B ETS - 03 Rev. 1 9

13 The estimated current carrying capacity should be modified with the adequate correction factors for different ambient air temperatures, according to IEC , clause The selected cables and their insulated conductors shall be capable of withstanding the mechanical and thermal effects of the maximum short circuit current which can flow in any part of the circuit in which they are installed, taking into consideration not only the time/current characteristics of the circuit protective device, but also the peak value of the prospective short circuit current during the first half cycle. The cable short-circuit current withstand capability should be evaluated according to information given in IEC 60724, IEC and IEC New and modified cable installations should be electrically tested as specified according to IEC LV cables The following specified LV cables are intended for use in power supply to installations such as lighting, socket outlets, heaters, panels etc. Same cables shall be used whether AC or DC power Specification Power supply cable With the exception of single core cables, all power supply cables from switch gear to consumers shall have an integral dedicated green/yellow earth wire. Cable design for non-essential services should be: Conductor: Stranded bare copper Insulation: Cross linked polyethylene (XLPE) Inner covering: Halogen free filler (i.e. polyolefin) Armouring: Copper braid (Tinned) Outer sheath: Polyolefin Cable design for essential services should be: Conductor: Stranded tinned copper Insulation: Mica tape and XLPE ETS - 03 Rev. 1 10

14 Inner covering: Polyolefin Armouring: Tinned copper braid Outer sheath: Polyolefin Selection LV cable types shall be selected to meet the requirements specified according to IEC , Clause 3.1. All cables or insulated wiring shall meet the requirements for flame spread as specified according to IEC , Clause The cable voltage rating shall comply with the requirements specified according to IEC , Clause 3.2. Cable cross-sectional areas and current carrying capacity of conductors shall comply with the requirements specified according to IEC , Clause 3.3. Cable current ratings for continuous service shall, according to IEC , Clause 3.3.3, be selected from Annex B, Tabulated Current Carrying Capacities General Installations. The conductor current carrying capacity of parallel connections of single core cables or multi core cables shall comply with the requirements specified according to IEC , Clause 3.6. Cables and their insulated conductors shall be capable of withstanding the mechanical and thermal effects of the maximum short circuit current which can flow in any part of the circuit in which they are installed, taking into consideration not only the time/current characteristics of the circuit protective device, but also the peak value of the prospective short circuit current during the first half cycle. Further information is given in IEC and IEC Cables for essential/emergency power supply shall fulfil the requirements of IEC Signal cables The following systems shall have their own dedicated cables: Digital communication (category 5e, optical fibre and coax) Fire detection and alarming (Twisted pairs) Equipment monitoring and alarm (Twisted pairs) The detailed specifications in the following sections should be regarded as recommendations. Other cable specifications may be used provided accepted by Energinet.dk ETS - 03 Rev. 1 11

15 4.5.1 Specification for category 5e cables Category 5e communication cables should be standard twisted 4 pair 100 MHz manufactured in accordance with ANSI/TIA 568B. Conductor: Bare copper (D. 0.52mm) Conductor insulation: Polyethylene, PE Collective screen: Outer sheath: Aluminium/polyester tape with tinned copper drain wire and tinned copper braid Orange Polyolefin Specification for coax cables Coax cables should be standard 50 ohms. Conductor: Bare copper-stranded 7 x 0.75mm Dielectric: Solid polyethylene Ø7.24mm Inner screening: Inner jacket: Bare/tinned copper braid Halogen free compound (outer sheath if used inside) Armouring: Tinned copper braid (applicable for outdoor use) Outer Sheath: Halogen free compound (applicable for outdoor use) Specification for optical fibre cables Optical fibre cables should be carefully chosen for the particular use. Preferably patch cables shall be used for indoor connections between panels Specification for twisted pair cables Twisted pair cables should normally be with common screen unless the particular installation require individual screen. Conductor: Stranded bare copper (Ø 0.75mm 2 ) Twisted in pairs Insulation: Cross linked polyethylene, XLPE Collective screen: Armouring: Aluminium/polyester tape with tinned copper drain wire and tinned copper braid Tinned copper braid Outer sheath: Polyolefin ETS - 03 Rev. 1 12

16 4.5.5 Selection The Category 5e cable should be used for all communication which is not fibre based. This cable should be for indoor use only, if used outdoor it shall be protected from the sun and from mechanical damage. The coax cable should be used for the transmission of signals from control panel to VDU, and for radio transmission via externally fixed antennas. The optical fibre cable should be used for most other communication. It shall be noted that the optical fibre for communication to shore will be integrated in the main 150kV power cable to shore. 5. Certificates / Data books NA. 6. Appendix NA. ETS - 03 Rev. 1 13

International Electrotechnical Commission Standards

International Electrotechnical Commission Standards International Electrotechnical Commission Standards Standard IEC 60028 IEC 60038 IEC 60050-461 IEC 60055-1 IEC 60055-2 IEC 60092-101 IEC 60092-350 IEC 60092-351 IEC 60092-352 IEC 60092-353 IEC 60092-354

More information

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Fire Resistant Cables

Fire Resistant Cables 109/4 Fire Resistant Cables SR 114H Standard - SR 114E Enhanced BS 5839-1 BS 7629-1 BS 6387 BS 8434-1/2 BS 6425 BS 7622 EN 50200 World-wide recognized high quality cables Firecel SR114 are used in: Data

More information

The Quality Connection. BETAflam Fire Resistant Safety Cables

The Quality Connection. BETAflam Fire Resistant Safety Cables The Quality Connection BETAflam Fire Resistant Safety Cables 2 Contact Consulting and sales Switzerland Phone +41 (0)62 288 82 82 Fax +41 (0)62 288 83 83 sales@leoni-studer.ch www.leoni-infrastructure-datacom.com

More information

BETAtrans. Cables and Systems for Rolling Stock. Edition 2006

BETAtrans. Cables and Systems for Rolling Stock. Edition 2006 BETAtrans Cables and Systems for Rolling Stock. Edition 2006 Info Consulting and Sales By Phone To ask for Information or to place an order please use the following number: +49 (0)9172-6844-11 By Fax For

More information

MV CABLE TYPE C 33-226

MV CABLE TYPE C 33-226 MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation

More information

Session 14 Cable Support Systems

Session 14 Cable Support Systems Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load

More information

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: sales@supremeco.com Website:

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables

More information

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

Section 5 161 kv Power Cables

Section 5 161 kv Power Cables Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper

More information

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both

More information

Flexible and safe solutions, for decades. Cables for alarmand safety systems

Flexible and safe solutions, for decades. Cables for alarmand safety systems Flexible and safe solutions, for decades. Cables for alarmand safety systems 2 We offer the widest range of cables on the market for every kind of installation. It s all about reliability. It is always

More information

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the

More information

CONFLEX ELECTRIC CABLE

CONFLEX ELECTRIC CABLE CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard

More information

NORSOK STANDARD ELECTRICAL, INSTRUMENTATION AND TELECOMMUNICATION INSTALLATION

NORSOK STANDARD ELECTRICAL, INSTRUMENTATION AND TELECOMMUNICATION INSTALLATION NORSOK STANDARD ELECTRICAL, INSTRUMENTATION AND TELECOMMUNICATION INSTALLATION Z-010 This NORSOK standard is developed by NTS with broad industry participation. Please note that whilst every effort has

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

SECTION 18370 SIGNAL WIRE AND CABLE

SECTION 18370 SIGNAL WIRE AND CABLE SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory

More information

RADOX railway cables acc. to EN 50264 and EN 50306. Edition 2009

RADOX railway cables acc. to EN 50264 and EN 50306. Edition 2009 RADO railway cables acc. to EN 50264 and EN 50306 Edition 2009 Bridging our know how Interdisciplinary knowledge The HUBER+SUHNER Group is a leading international manufacturer of electrical and optical

More information

British Standards BSEN 3475-513:2005

British Standards BSEN 3475-513:2005 s British Standard BS 91:1998 BS 215:1970 BS 638-4:1996 BS 1990-1:1984 BSEN 3475-100:2002 BSEN 3475-201:2002 BSEN 3475-301:2002 BSEN 3475-302:2002 BSEN 3475-303:2002 BSEN 3475-305:2002 BSEN 3475-306:2005

More information

High Voltage Systems. Today. The history of cables

High Voltage Systems. Today. The history of cables High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

FIRE RESISTANT CABLES FP200 GOLD

FIRE RESISTANT CABLES FP200 GOLD FIRE RESISTANT CABLES FP200 GOLD FIRE RESISTANT CABLES FP200 GOLD BS7629-1:2008 Certificate No 077f Certificate No 077k FP200 GOLD The original highly durable and dressable, easy to terminate and install

More information

David O Brien, CMP Products (David.OBrien@cmp-products.com)

David O Brien, CMP Products (David.OBrien@cmp-products.com) David O Brien, CMP Products (David.OBrien@cmp-products.com) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

CABLES FOR PHOTOVOLTAIC SOLAR ENERGY INSTALLATIONS FOR CLEAN ENERGY

CABLES FOR PHOTOVOLTAIC SOLAR ENERGY INSTALLATIONS FOR CLEAN ENERGY CABLES FOR PHOTOVOLTAIC SOLAR ENERGY INSTALLATIONS FOR CLEAN ENERGY One Company Connecting The World POWERFUL PRESENCE PRODUCTS PERFORMANCE PEOPLE General Cable has been a wire and cable innovator for

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

CABLE ACCESSORIES 110-220 kv

CABLE ACCESSORIES 110-220 kv CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

Standard Buccaneer - Ethernet

Standard Buccaneer - Ethernet IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2

More information

SECTION 16461 DRY-TYPE TRANSFORMERS

SECTION 16461 DRY-TYPE TRANSFORMERS SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any

More information

COAX Cables Radio Frequency Cables

COAX Cables Radio Frequency Cables COAX Cables Radio Frequency Cables Contents Page Table of contents Pictographs General information Introduction Types and abbreviations Temparature range Construction Characteristics Special constructions

More information

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored

More information

Structured Cabling, Earthing & Equipotential Bonding

Structured Cabling, Earthing & Equipotential Bonding White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,

More information

MEDIUM VOLTAGE CABLES Up to and including 36 KV

MEDIUM VOLTAGE CABLES Up to and including 36 KV MEDIUM VOLTAGE CABLES Up to and including 6 KV NOTICE As this catalogue is not intendedto cover all of LIBAN CABLES SAL possibilities in special cables manufacturing, the hereafter listing of the types

More information

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS: PRODUCT DATASHEET & APPLICATIONS GUIDE BASEC APPROVED AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Uniprise Solutions COAX 101. White Paper. www.commscope.com

Uniprise Solutions COAX 101. White Paper. www.commscope.com Uniprise Solutions COAX 101 White Paper www.commscope.com Structured cable systems have very thorough standards for fiber optic and twisted pair installations. The cabling components and installed systems

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

VIPERFLEX ELECTRIC CABLE

VIPERFLEX ELECTRIC CABLE VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07

More information

Power and Wiring Cables

Power and Wiring Cables 1 Single-Core PVC 1X...................... 1: Single-Core PVC/PVC 1Y.................. 1: Flat Twin & Flat Three Core PVC /Y........ 1: Multicore XLPE/LSF/SWA/LSF BS Control Cable.............................

More information

HV Submarine Cable Systems Design, Testing and Installation

HV Submarine Cable Systems Design, Testing and Installation HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications

More information

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1 Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment

Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment Qatar General Electricity & Water Corporation KAHRAMAA Customer Services Department State of Qatar

More information

Fire Performance Standard

Fire Performance Standard Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

Festoon 715 P PUR cable for flexible application in festoon systems

Festoon 715 P PUR cable for flexible application in festoon systems CABLES FOR CRANE AND CONVEYOR APPLICATIONS Festoon 715 P PUR cable for flexible application in festoon systems S AB BRÖCKSKES D-VIERSEN Festoon 715 P 1 x 16.0 mm 2 C Marking for Festoon 715 P 07150162:

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Specializing in the cable business for over 38 years, PT. SUPREME CABLE

Specializing in the cable business for over 38 years, PT. SUPREME CABLE Specializing in the cable business for over 38 years, PT. SUPREME CABLE MANUFACTURING & COMMERCE Tbk. (PT. SUCACO Tbk) has grown steadly to become a largest and leading cable manufacturer, with international

More information

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

Specification SFTP CAT6 Network Cable 23AWG CU

Specification SFTP CAT6 Network Cable 23AWG CU Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)

More information

VDE-approved PVC-Control Cables

VDE-approved PVC-Control Cables Works photo: HELUKAEL VDE-approved PVC-Control Cables VDE-approved PVC-Control Cables This certification/licency is issued according to the rules of the HAR Agreement, wherein the certification/ licency

More information

Outside Telephone Cable

Outside Telephone Cable Outside Telephone Cable Filled Core. Moisture Barrier. Description Soft copper wires insulated with high density polyethylene, foam skin or solid. Filled core, conformed by groups of pairs or by unit of

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS . HARTING RJ INDUSTRIAL ETHERNET CONNECTORS Ethernet is is coming up to standard industrial interface. Therefore, automation devices such as controllers, sensors and actuators feature possess on one or

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

MICROCABLES. A complete vision of your connectivity needs. Catalogue

MICROCABLES. A complete vision of your connectivity needs. Catalogue MICROCABLES A complete vision of your connectivity needs Catalogue ELECTRONIC Filotex Introduction Application Nexans s line of microcables is designed towards the increasing requirements of electronics

More information

e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies

e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies www.echtzeit.com e-mobility Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies Special cables for electric vehicles Wittener Straße 271 D-42279 Wuppertal Phone +49(0)202.2681.228 Fax +49(0)202.2681.360

More information

HIGH VOLTAGE SHORE CONNECTION

HIGH VOLTAGE SHORE CONNECTION Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.

More information

Securing your electrical installations Prisma,

Securing your electrical installations Prisma, Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

APPLICATION ORIENTED DESIGN OF CABLES

APPLICATION ORIENTED DESIGN OF CABLES APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. rohinib@ducab.com Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. Nawaf@ducab.com

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Operating Instructions

Operating Instructions Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4

More information

MEDIUM VOLTAGE POWER CABLES

MEDIUM VOLTAGE POWER CABLES MEDIUM VOLTAGE POWER CABLES CONTENTS 1 GENERAL INTRODUCTION 4 TECHNICAL INFORMATION 15 25 35 45 Single Core XLPE Insulated PVC Sheathed Cables UNARMOURED CABLES COPPER UNARMOURED CABLES ALUMINUM ALUMINUM

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials VDE Information General Information The voltage which can be applied to a terminal depends on the relevant regulations, the installation conditions and, of course, the dimensions and insulating materials

More information

Power Separation Guidelines for SYSTIMAX Installations

Power Separation Guidelines for SYSTIMAX Installations SYSTIMAX Solutions Power Separation Guidelines for SYSTIMAX Installations Design and installation guidelines August 2011 www.commscope.com 1.0 General These guidelines are based on extensive testing and

More information

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2 STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers

More information

Global cable expertise for rolling stock

Global cable expertise for rolling stock Global cable expertise for rolling stock Global cable expertise for rolling stock Single and multicore Low voltage control cables Jumper cables HV roof cables (25 kv) rubber cables for power needs of locomotives

More information

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum

More information

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility

More information

KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System

KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System 2-32 A Lighting Busbar System 4-63 A Plug-in Busbar Distribution System / E-LINE KX Compact Busbar Distribution System 63...63 A E-LINE KB Compact Busbar Distribution System 8...63 A E-LINE KO Plug-in

More information

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001 > As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened

More information

Terminal Boxes Series 8146

Terminal Boxes Series 8146 Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm

More information

1756 ControlLogix Chassis Specifications

1756 ControlLogix Chassis Specifications Technical Data 1756 ControlLogix Chassis Specifications Catalog Numbers 1756-A4/B, 1756-A4K/B, 1756-A4/C, 1756-A4K/C, 1756-A7/B, 1756-A7K/B, 1756-A7/C, 1756-A7K/C, 1756-A10/B, 1756-A10K/B, 1756-A10/C,

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information