WHITE PAPER Fire & safety performance standards
|
|
|
- Camron Campbell
- 10 years ago
- Views:
Transcription
1 WHITE PAPER Fire & safety performance standards
2 Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable s fire performance in the intended application. This paper will provide a basic understanding of national as well as international fire performance standards and regulations and how important it is to select the correct cable with the right fire and safety performance. Terminology commonly used in the cable industry are, Flame Retardant, Low Smoke, Low smoke Zero Halogen, Low Smoke Fume (LSF) and Fire Resistant Cables which are commonly known as Fire Survival Cables. Below is a general explanation of what these Fire Performance Terminologies entails: Flame Retardant Fire retardant cables are designed for use in fire situations where the spread of flames along a cable route needs to be retarded. Due to relative low cost, fire retardant cables are widely used as cables compliant with the National Electrical Code (NEC). Regardless of cables installed in single wire or in bundles, during a fire, the flame spread will be limited; hence the fire will be confined to a small area, reducing the fire hazard due to fire propagation. Low Smoke & Halogen Free & Fire Retardant (LSZH) LSZH cables are not only characterized by the fire retardant performance but also by the halogen free properties, thus offering low corrosivity and toxicity. During a fire, the LSZH cables will emit less smoke and acid gases which may affect human health and damage expensive communication equipment. Compared with normal PVC cables, LSZH cables outperform PVC cables by providing low corrosivity and low smoke emission properties. Low Smoke Fume (LSF) The low halogen content and low corrosivity of low smoke fume cables lies somewhat in between that of fire retardant cables and LSZH cables. LSF cables also contain halogen but the content is much less than that of PVC cables. LSF cables are designed to reduce the spread of fire, toxic gases and smoke during fire. The LSF cables are usually manufactured from flame retardant PVC blended with HCL additive and smoke absorbent. These materials help improve the fire performance of the LSF cables. Fire Resistant (FR) Fire resistant cables are designed to maintain circuit integrity of those vital emergency services during the fire. The individual conductors are wrapped with a layer of fire resisting mica/glass tape, which prevents phase to phase, and phase to earth contact even after the insulation has been burnt away. The fire resistant cables can maintain performance even under fire with water spray or mechanical shock. Fire Performance Class The main concerns for the cables in their fire survival properties are their flame spread, smoke characterization and gas toxicity. In American fire standard, the concern lies more on the first two and it differs from the European standard, which concerns all these aspects. In USA, it is believed that the fire hazard is mainly due to CO toxic gas emitted and the heat release during the conversion of CO to CO2 during the fire. Therefore, to control the heat release is the most important concern for reducing the fire hazard. However, in European countries, halogen content, the corrosivity of the gases, the smoke density and the toxicity of the gas are equally important factors affecting the human safety during and after the fire. LOROM Cable & System Design Fire & Safety Performance Standards 2
3 IEC Standards for Fire performance IEC CENELEC HD 405 (Flame Test on Single Vertical Insulated Wires/Cables) IEC defines test method defining the flame propagation characteristics of a single wire or cable. Test comprises a DUT (Device under test) of 60cm cable fixed vertically inside a Metal enclosure. A 175mm long flame is applied at 45 angle applied by a Bunsen burner positioned in a distance of 450mm from the clamping point. The DUT is classified as passing the test, if after burning has ceased, the charred or affected position does not exceed a distance greater than 50mm measured from the top clamp. Caution should be made applying this test method to thin wire sizes, as the insulation material (depending on compound, except for high temperature materials such as fluorinated compounds) will most likely melt during the test. IEC /BS (Flame Test on Bunched Cables) IEC C describes a test method establishing fire propagation of bunched cables or bunched single wires. Test conducted by a DUT, comprising a selected number of 3.5m long DUT s placed on a metal vertical ladder tray The DUT is be subjected a flame from a burner in a specified times under controlled airflow. Dependent on the DUT fire propagation behavior the test result in four categories (A, B, C & D) based upon and distinguished by test duration and the volume of non-metallic material of the (DUT) sample under test. The (DUT)/ cable specimen is classified as passing the test if, after burning has ceased, the charred or affected portion does not exceed 2.5m measured from the above the bottom edge of the burner. UL Standards for Fire performance The National Fire Protection Agency (NFPA) publishes flame-resistance standards through its published National Electrical Code (NEC). Other agencies, such as UL and CSA also publish standards and define certain tests to determine flame resistance (or lack thereof). Flame resistance requirements are for the most part governed by local and national codes which define the various levels of flame hazard, plus the severity of the fires to which cables may be exposed. The important considerations are propagation of flame, support of further combustion, generation and propagation of smoke. The NEC deals primarily with fire hazards in buildings, whereas UL and CSA deal with requirements based on use. LOROM Cable & System Design Fire & Safety Performance Standards 3
4 CL2P, CL3P, CMP (Plenum Flame Test/ Steiner Tunnel Test, FT6) The most severe and stringent test requirement of fire performance testing. Plenum rated cables meet the NFPA -262 FT6 standard (formerly known as UL910) DUT/Cable samples on a horizontal metal tray in a Steiner tunnel chamber and are being exposed of 87.9KW (300,000 BTU/Hr) flame for 20 minutes. To pass the and have the CMP plenum rating marking, the DUT/ cable specimen can not exhibit flame spread exceeding 5 feet or 1.5 meters, over and above the smoke density is measured during the test with values not exceeding (a) 0.5 peak and (b) 0.15 maximum average. Plenum CMP rated cables are typically installed in air ventilation ducts, suspended ceilings, raised computer flooring etc, without any electrical tubing Plenum rated cables are predominantly used and applied in Canada and USA. Compared to other fie performance cables, fire retardant properties of CMP cables are significantly superior to those of LSZH cables complying with IEC and IEC CMR (Riser Flame Test, FT4) To pass and have the CMR plenum rating and marking cables with CMR, the DUT/Cable has to pass UL1666. DUT/ Cable samples on a metallic vertical shaft are exposed to a burner generating 154.5KW (527,500 BTU/Hr) for 30 minutes. The DUT/Cable samples qualifying for a riser rating, Flame spread cannot exceed 12ft beyond the ignition point The CMR riser flame test does not consider smoke density or toxicity index unlike that of CMP Plenum rated cables Riser rated marked approved cables are suitable where cables are used in vertical runs in a shaft that may penetrate more than one floor. CM, CL2, CL3, CM, CMG, PLTC (Vertical Tray Flame Test) General-purpose cables meet UL The DUT/Cable samples placed on a 8 feet metal vertical tray are burned at 20KW (70,000 BTU/hr.) for 20 minutes. The DUT/Cable samples pass the test if the flame spread will not exceed 8ft and fire extinguish by itself. UL 1581 is similar to IEC C except for that the number of testing samples is different. This standard and test does consider smoke density or toxicity. CMG (Vertical Tray Flame Test) FT-4/UL2556 The DUT/ Cable samples on a vertical tray and are burned at 20KW (70,000 BTU/hr.) for 20 minutes. The DUT/Cable Samples pass the test if the flame spread will not exceed 1.5m (4.92 ft.) These general-purpose cables also meet CSA FT-4/UL2556 CM and CMG are similar and both are recognized in Canada and USA. This test does not look at the smoke density or toxicity as a requirement. LOROM Cable & System Design Fire & Safety Performance Standards 4
5 CMX (Vertical Wire Flame Test) The restricted cables meet UL1581 Limited-use. The test consists of 25 feet long ventilated tunnel. The DUT/ cable specimen is placed on a metallic ladder inside the tunnel and the flame of 30,000 BTU/Hr is applied to the cable with intervals of 15 seconds on and 15 seconds off, this is repeated five times for a total exposure to the flame of 1 minute and 15 seconds. Compliance to CMX requires meeting the following; after the test flame is removed the cable specimen can flame for not more than 60 seconds and the charred portion will not exceed by 25%. UL 1581 VW-1 is similar to IEC except for the difference in the time for flame applied. This test does not look at the smoke density or toxicity. The CMG cables are suitable for use in dwellings and for use in raceway. These cables cannot be installed in bundles and must be protected in metal conduit. This type of cable is chosen as the minimum requirement for commercial installations. Standard for Fire Resistance IEC60331 Fire Resistance Test A cable sample is placed over a gas burner and connected to an electrical supply at its rated voltage. Fire is applied for a period of 3 hours. The temperature on the cable is between 750 and 800. After 3 hours, the fire and the power is switched off. 12 hours later, the cable sample is reenergized and must maintain its circuit integrity. IEC (Emission of Halogen) This specifies a test for determination of the amount of halogen acid gas other than the hydrofluoric acid evolved during combustion of compound based on halogenated polymers and compounds containing halogenated additives taken from cable constructions. Halogen includes Fluorine, Chlorine, Bromine, Iodine and Astatine. All these chemicals are toxic by their nature. In this test, when the burner is heated to 800, 1g sample is placed inside and the HCL is absorbed into water inside the chamber fed with air flow. The water is then being tested for acidity. If the hydrochloric acid yield is less than 5 mg/g, the cable specimen is categorized as LSZH. If the hydrochloric acid yield lies between 5mg/g to 15mg/g, the cable specimen is categorized as LSF. IEC cannot be used for measuring the exact HCL yield if the yield is less than 5mg/g. This test cannot determine if the cable is 100% halogen free or not. To determine if the cable specimen is 100% halogen free or not, IEC has to be employed. IEC (Corrosivity) This test specifies a method for the determination of degree of acidity of gases evolved during combustion of the cable specimen by measuring its ph and conductivity. The specimen is deemed to pass this test if the ph value is not less than 4.3 when related to 1 liter of water and conductivity is less than 10us/min. When the HCL yield lies between 2mg/g and 5mg/g, a cable specimen can pass IEC but its ph value will likely be less than 4.3 and therefore cannot pass the IEC test. LOROM Cable & System Design Fire & Safety Performance Standards 5
6 IEC /ASTM E662 (Emission of Smoke) This specifies a test for determination of smoke density. The 3-meter cube test measures the generation of smoke from electric cables during fire. A light beam emitted from a window is projected across the enclosure to a photocell connected to a recorder at the opposite window. The recorder is adjusted to register from 0% for complete obscuration to 100% luminous transmissions. A 1-meter cable sample is placed in the center of the enclosure and is applied with a fire. The minimum light transmission is recorded. The result is expressed as percentage of light transmitted. The specimen is deemed to pass this test (IEC & 2) if the value is greater than 60%. The higher the light transmittance, the less smoke emitted during a fire. ISO4589-2/BS2863 (Oxygen Index LOI) This is a test for assessing the oxygen index of the material in accordance with the test method specified in ASTM D (Measuring the minimum oxygen concentration to support candle-like combustion of plastics). At room temperature when the oxygen content in the air exceeds the oxygen index, the material will burn by itself automatically. The higher the oxygen index, the more retardant the cable will be. For example, if the oxygen index of a material is 21%, it means that the material will burn by itself even at room temperature because at room temperature the normal oxygen content is 21%. In general, the oxygen index of a LSZH cables ranges from 33% to 42%. ISO4589-3/BS (Temperature Index TI) This is a test for assessing the performance of a material when it is tested in accordance with BS2782 Part 1 Method 143A and 143B. The oxygen index of a material will drop when the temperature rises. When the temperature rises and the oxygen index drops to 21%, the material will burn automatically. This temperature is defined as temperature index. For example, the temperature index of coal is 50%. When the temperature climbs to 150, its oxygen index drop to 21% and the coal will burn by itself automatically. The temperature index of the coal will then be defined as 150. In general, the temperature index of LSZH cables ranges from 250 to 300. LOROM Cable & System Design Fire & Safety Performance Standards 6
Fire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
Click here to see a video example of cable being burned outside the controlled lab environment. UL-910 Test for Flame-Propagation and Smoke Density
Plenum (CMP) Rated Cable Often found on building material lists, the Plenum rating (CMP) signifies cable that has passed stringent burn testing and is suitable for installation into Air Plenum spaces.
The most important matter is to select the right product based on the environment in which it will be installed and on its use or application.
Communication cables and burning behaviour international regulations Different regulations and standards apply depending on the geographic location. Europe is normally governed by CENELEC (EN), but in
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations Fire Protection Review for the Fixed Target ES&H Review Committee September 2010 By James Priest PhD DRAFT Overview: When reviewing
D A T A C O M M U N I C A T I O N S C O M P E T E N C E C E N T E R
F l a m e T e s t S t a n d a r d s f o r D a t a C o m m u n i c a t i o n s C a b l e M a r c h 2 0 0 7 D A T A C O M M U N I C A T I O N S C O M P E T E N C E C E N T E R Table of Contents Executive
SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND
Belden Electronics Division P.O. Box 1980 Richmond, Indiana 47375-1980 2200 U.S. Highway 27 South Richmond, Indiana 47374-7279 Telephone: 765 983 5200 Facsimile: 765 983 5825 SUBJECT: NO MORE 300 VOLTS
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
17 FREE : A New Class of Halogen-Free Cables
DATACOM CABLE SOLUTIONS 7 FREE : A New Class of Halogen-Free Cables Written by: Alice Albrinck, Chemical Applications Engineer, General Cable July 00 TABLE OF CONTENTS INTRODUCTION What is a Halogen? Why
FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager
FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building
Limited Combustible: The New Standard for Fire Safety
Limited Combustible: The New Standard for Fire Safety Written by Daniel Kennefick Limited Combustible Product Business Manager Berk-Tek, A Nexans Company Since the advent of client server computing in
Fire safety standards for LAN cabling systems
HCS White Paper Fire safety standards for LAN cabling systems WP010112 Executive Summary Safety of people is compromised when inadequate fire standards are specified for LAN cabling systems. Most installations
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System July 28, 2003 We are pleased to provide the following joint statement by CII,
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Copper Cabling Infrastructure Offering
Copper Cabling Infrastructure Offering High-Speed Copper Cabling Systems The deployment of high speed cabling systems has been increasing rapidly as data centers enable their physical infrastructure with
FIRE RESISTANT CABLE CONSTRUCTION OF CABLES
FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the
How To Test For Premer Retardant
TEST REPORT NEBS COMPLIANCE CHOMERICS PREMIER CONDUCTIVE PLASTIC Prepared by: CHOMERICS R&D 84 DRAGON COURT WOBURN, MA 01801 Test Report Number: TR 1007 EN 0206 Chomerics Approved Signatory: This report
The proof is here!! Ron Goethals, Philadelphia; June 18, 2014
The proof is here!! The proof is here!! The proof is here!! The proof is here!! The proof is here!! The proof is here!! Highly flame-retarded non-halogen bedding compounds show remarkable effects on: BURNING
2011 National Electrical Code
2011 National Electrical Code Changes of Interest to Data/Comm Cabling Contractors, Users and Code Enforcement Officials The National Electrical Code is published by the National Fire Protection Association
Electrical Code (NEC) Snake Tray Cable Management Solutions
Cable Pathway Use and Selection and the National Electrical Code (NEC) By Eric J. Sadler, BSME MIT Snake Tray Cable Management Solutions References: All references to the NEC in this presentation are taken
WHY CABLE TRAY? BECAUSE A CABLE TRAY WIRING SYSTEM PROVIDES SAFE AND DEPENDABLE WAYS TO SAVE NOW AND LATER
Large numbers of electrical engineers have limited detail knowledge concerning wiring systems. There is the tendency by engineers to avoid becoming involved in the details of wiring systems, leaving the
New Cable Tie Type Classifications
1 New Cable Tie Type Classifications UL 62275 United States CSA C22.2 No. 62275 Canada NMX-J-623-ANCE Mexico Technically Equivalent to IEC 62275 All cable ties are not created equal!!! With an increasing
Safety & Performance in the Wire and Cable Industry
Safety & Performance in the Listed vs. Verified: Marks, Logos and Programs Written by: Antoine Pelletier, Team Leader, Global Cabling Products Larry Todd, Chief Engineer Intertek [email protected] 1-800-WORLDLAB
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.
UNDERSTANDING. C&M Corporation 51 South Walnut Street, Wauregan, CT 06387 Phone: 860.774.4812 Fax: 860.774.7330 www.cmcorporation.
UNDERSTANDING UNDERSTANDING NFPA 79 By Ned Lloyd and Mike Levesque NFPA-79 is the electrical standard that has been developed by the National Fire Protection Association (NFPA) and is intended to minimize
AWG: Cat5e: Cat6: Cat6A:
Some of the terms used in the cable business can be vexing to even the most seasoned folks in the industry. If any of this terminology has ever made you scratch your head, you are certainly not alone.
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
Halogen Free: What, Why and How. Presented by : Jim Cronin Environmental Monitoring and Technologies, Inc.
Halogen Free: What, Why and How Presented by : Jim Cronin Environmental Monitoring and Technologies, Inc. We will discuss What are Halogens and how we interact with them. Why Halogens, within consumer
Comprehensive safety concepts for building applications
Comprehensive safety concepts for building applications Preventive fire protection Experience, know-how, competence, quality and safety pyrofil for safety Fire reaction Dätwyler is the first european manufacturer
LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
Specification SFTP CAT6 Network Cable 23AWG CU
Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)
Session 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
PROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
Data Sheet 10/63-6.47-EN Rev. D PROFIBUS cable PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications PROFIBUS PA cables Non-Ex (Hazardous) applications Ex (Hazardous) applications
L O W - S M O K E, Z E R O - H A L O G E N C A B L E S :
L O W - S M O K E, Z E R O - H A L O G E N C A B L E S : B R I D G I N G T H E P E R F O R M A N C E G A P Next Generation Low-Smoke, Zero-Halogen (LSZH) Thermoset Insulation A Look at General Cable s
Flame Retardants and the Evolving Regulatory Landscape
THERM0PLASTIC ELASTOMERS STRUCTURAL WEAR CONDUCTIVE COLOR FLAME RETARDANT Flame Retardants and the Evolving Regulatory Landscape Derek LaRock Product Development Engineer Flame Retardant Products Overview
Fire Testing of Recycled Materials for Building Applications
Fire Testing of Recycled Materials for Building Applications Robert H. White Abstract To gain wide market acceptance of new building products made from recycled materials, fire testing may be necessary.
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
The cost effective replacement of halogenated materials for the wiring of buildings
The cost effective replacement of halogenated materials for the wiring of buildings James E. ROBINSON Over the passed two years the volume sales of new technology non halogen flame retardant materials
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY. (The following code explanations are to be used with a copy of the 2011 NEC.
AN IN-DEPTH LOOK AT 2011 NEC ARTICLE 392 - CABLE TRAY (The following code explanations are to be used with a copy of the 2011 NEC.) To obtain a copy of the NEC contact: National Fire Protection Association
HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
YOUR SAFETY IS IMPORTANT. Low fire hazard cables. PRAKAB
PRAGUE SAINT PETERSBURG YOUR SAFETY IS IMPORTANT. Low fire hazard cables. PRAKAB PRAGUE SCHWECHAT NITRA KIEV PRAKAB PRAŽSKÁ KABELOVNA, s.r.o. Ke Kablu 278 CZ-102 09 Praha 15 Tel. +420 272 070-111 Fax +420
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
furnishings flammability characteristics
Technical Bulletin 110104 New Options for Textiles The performance of Ingeo fibers in the standard flammability tests described below confirm that Ingeo fibers, without any flame retardant (FR) treatment,
Validation of Modeling Tools for Detection Design in High Airflow Environments
Validation of Modeling Tools for Detection Design in High Airflow Environments Joshua B. Dinaburg Dr. Jason Floyd, Ph.D. Dr. Sai Thumuluru, Ph.D FM Global MODELING DETECTION RESPONSE Establish validated
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Mechanical Systems Competency 1.20
Competency 1.20 Mechanical systems personnel shall demonstrate a working level knowledge of the safety and health fundamentals of mechanical systems and/or components. 1. Supporting Knowledge and Skills
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables
RoHS DATA, COAXIAL AND ELECTRONIC D A TA, C O A X I A L, A N D EL E CTRON I C Cables Index SOLID MULTI-CONDUCTOR CABLES STRANDED MULTI-CONDUCTOR CABLES SPEAKER/ZIP WIRE THERMOSTAT CABLE FIRE ALARM CABLE
International Electrotechnical Commission Standards
International Electrotechnical Commission Standards Standard IEC 60028 IEC 60038 IEC 60050-461 IEC 60055-1 IEC 60055-2 IEC 60092-101 IEC 60092-350 IEC 60092-351 IEC 60092-352 IEC 60092-353 IEC 60092-354
Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts
Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts Class Number 4922 April 2001 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
108-93018 05 APR 2016 Rev M
Product Specification 108-93018 05 APR 2016 Rev M Copper LAN Cable 1. SCOPE 1.1. Content This specification describes the general requirements for CommScope copper LAN cable. 2. APPLICABLE DOCUMENTS The
CABLE TRAY MANUAL Based on the 2011 National Electrical Code
2011 CABLE TRAY MANUAL Based on the 2011 National Electrical Code MAN-1 Table of Contents Page No. Introduction... MAN-3 Why Cable Tray? Safety... MAN-4 Dependability... MAN-4 MAN-5 Space Savings... MAN-5
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
1-085 Fire safety performance of materials
Transport for London London Underground Category 1 Standard 1-085 Fire safety performance of materials! Please read the Written Notices attached to this standard Issue: A3 MAYOR OF LONDON Contents 1 Purpose
2012 CATALOG AEROSPACE VVIRE & CABLE INC. aerospacewire.com
* 2012 CATALOG AEROSPACE VVIRE & CABLE INC. A VV aerospacewire.com W e p r o u d l y m a n u f a c t u r e h i - t e m p w i r e & c a b l e. PLENUM CABLE. INDUSTRIAL CABLE. TRAY CABLE. MILITARY WIRE.
Approval Standard for Plastic Suspended Ceiling Panels
Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2
STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers
The Quality Connection. BETAflam Fire Resistant Safety Cables
The Quality Connection BETAflam Fire Resistant Safety Cables 2 Contact Consulting and sales Switzerland Phone +41 (0)62 288 82 82 Fax +41 (0)62 288 83 83 [email protected] www.leoni-infrastructure-datacom.com
Lifeline Fire Protection Cable Systems. Cables
Lifeline Fire Protection Cable Systems Cables Lifeline - Superior Innovation in Fire Protection Cable Systems Leadership in two-hour cables Introduced by Draka Engineered Specialties, Lifeline two hour
Fire Event Electronic and Mechanical System Damage Mechanisms Is Acid Gas for Real?
Equipment Damage Consultants, LLC Fire Event Electronic and Mechanical System Damage Mechanisms Is Acid Gas for Real? Irreparable damage to electronic equipment and mechanical systems away from the actual
Specialty Engineered Materials for Wire & Cable
Industr y Over view Specialty Engineered Materials for Wire & Cable Developing innovative polymer solutions that help wire & cable manufacturers exceed consumer expectations, stand apart from their competition
Building Cables and Wires
Building Cables and Wires 4 Introduction alfanar is equipped with state-of-the-art manufacturing facilities such as latest machineries, instrumentation, quality control and testing laboratory, etc., for
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
Flexible and safe solutions, for decades. Cables for alarmand safety systems
Flexible and safe solutions, for decades. Cables for alarmand safety systems 2 We offer the widest range of cables on the market for every kind of installation. It s all about reliability. It is always
Terms and Definitions In Canada
Terms and Definitions In Canada Most of the following terms and definitions are taken directly from the National Building Code and referenced Test Methods. Learning these terms will provide an important
Safely Installing, Maintaining and Inspecting Cable Trays
Purpose U.S. Department of Labor Occupational Safety and Health Administration Directorate of Technical Support & Emergency Management Office of Technical Programs and Coordination Activities Safely Installing,
TECHNICAL BULLETIN 117-2013
State of California Department of Consumer Affairs BUREAU OF ELECTRONIC & APPLIANCE REPAIR HOME FURNISHINGS & THERMAL INSULATION 4244 SOUTH MARKET COURT, SUITE D SACRAMENTO, CA 95834-1243 TECHNICAL BULLETIN
Mineral Insulated Cable A cable for today and tomorrow!
Mineral Insulated Cable A cable for today and tomorrow! Bill Davis Technical and Business Development Director If MIC had never been introduced, the industry would be actively pursuing the development
W-2. Stranding Comparison
Wire Knowledge W-1 W-2 Stranding Comparison Conductor Coatings/Coverings PURPOSE To facilitate stripping of components applied over the conductor To prevent compound fall-in Improve solderability Prevent
Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants
Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Ram K. Saini, P.E. Principal Engineer, Chuck Emma, P.E. Principal Engineer, Burns and Roe Enterprises,
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
CABLE BASICS. Sizing and Selection Standard vs. Custom. Presented by
CABLE BASICS Sizing and Selection Standard vs. Custom Presented by 800.468.1516 +1 715.294.2121 2010 Northwire, Inc. All rights reserved A cable is a cable right? is a cable They all look sort of the same
Australian/New Zealand Standard
Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The
BETAtrans. Cables and Systems for Rolling Stock. Edition 2006
BETAtrans Cables and Systems for Rolling Stock. Edition 2006 Info Consulting and Sales By Phone To ask for Information or to place an order please use the following number: +49 (0)9172-6844-11 By Fax For
British Standards BSEN 3475-513:2005
s British Standard BS 91:1998 BS 215:1970 BS 638-4:1996 BS 1990-1:1984 BSEN 3475-100:2002 BSEN 3475-201:2002 BSEN 3475-301:2002 BSEN 3475-302:2002 BSEN 3475-303:2002 BSEN 3475-305:2002 BSEN 3475-306:2005
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
Global cable expertise for rolling stock
Global cable expertise for rolling stock Global cable expertise for rolling stock Single and multicore Low voltage control cables Jumper cables HV roof cables (25 kv) rubber cables for power needs of locomotives
SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM
Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System
RF & Microwave cable assemblies C291
ERTIFIED C AS 9100 RF & Microwave cable assemblies C291 B CONTENTS Pages Introduction... B-4 Specify the right cable for your application... B-5 Finder guide cables vs insertion loss... B-6 to B-7 Flexible
SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES
New York City Administrative Code - Title 29 New York City Fire Code SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES 2706.1 Scope. This section shall govern the storage, handling and use of laboratory
Fire Resistant Cables
109/4 Fire Resistant Cables SR 114H Standard - SR 114E Enhanced BS 5839-1 BS 7629-1 BS 6387 BS 8434-1/2 BS 6425 BS 7622 EN 50200 World-wide recognized high quality cables Firecel SR114 are used in: Data
Features. High Brightness LED Light source
www.edison-opto.com Solid-State Lighting Series 6W MR16 DATASHEET Features High Brightness LED Light source Ecologically Friendly Energy Efficient General Information... 1 Product Dimensions... 2 Product
Cable ladder installation at S.C.M. Chemicals Limited s titanium dioxide Plant in Western Australia
Exel Composites Cable Support Systems offer engineers a structural product for solving many design and plant engineering problems, enabling long term reliable support of expensive and often critical cables.
Fire Security Systems
Fire Security Systems Fire Security Systems [email protected] www.fire-security.net P: 1 604 941 1001 F: 1 604 648 9311 Who is Fire Security Systems For 25 years, Fire Security has been involved in
Reducing Injury and Damage Related to Electric Dryer Fires. Fire Containment Tests for the Second Edition of UL 2158
Reducing Injury and Damage Related to Electric Dryer Fires Fire Containment Tests for the Second Edition of UL 2158 Reducing Injury and Damage Related to Electric Dryer Fires: Fire Containment Tests for
Stainless steel cable fixing solutions for critical environments
Stainless steel cable fixing solutions for critical environments BAND-IT-IDEX is the world s leading manufacturer in quality clamping and banding systems. Since its inception in 1937, BAND-IT bands and
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
Meeting the Fire Code with Continuous Foam Plastic Insulation
Dow Building Solutions Meeting the Fire Code with Continuous Foam Plastic Insulation The 2012 International Building Code (IBC) specifies the fire tests that must be passed if a foam plastic material is
Fire Resistance and Safety in Case of Fire
Fire Resistance and Safety in Case of Fire Franck GYPPAZ Nexans Research Center [email protected] April 2014 Page 1/12 Table of content 1 Introduction... 3 2 Fire development... 3 2.1 Ignition...
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Fiber Optic Cordage. Interconnect A Furukawa Company. Product Description. Why OFS Interconnect Cordage?
Fiber Optic Cordage Interconnect A Furukawa Company Durable, Flexible Cordage Surpasses Industry Strength Standards for Interconnect Cables Product Description OFS Fiber Optic Interconnect Cordage offers
MaxCell Technical Manual Design Parameters
MaxCell Technical Manual Design Parameters Breaking Strength by Product Style, lbs Product Style Standard MaxCell Fire Resistant MaxCell Test Method 4 Cell 2,750 2,200 ASTM D 5 Bellcore 5 5.. Cell 2,50
Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide
Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management
MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS
MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS Richard W. Bukowski. P.E., FSFPE and Ralph Transue, P.E. Rolf Jensen and Associates, Chicago, IL 60661 USA Data Centers Society