Load Cell Input Module
|
|
- Denis Bridges
- 7 years ago
- Views:
Transcription
1 Load Cell Input Module FBs-1LC / FBs-2LC is one of the analog input modules of FATEK FBs series PLC. It supports one / two channel of load cell input for weight measurement. The conversion result is represented by a signed 16 bit integer value. In order to filter out the field noise imposed on the signal, it also provides the average of sample input function. Note: 1. The supporting of I/O configuration for FBs-1LC/2LC module is available only for PLC OS V4.71 and Winproladder V3.22 or later version. 2. For those early applications which do not use I/O configuration to work with 1LC module can still work properly provided that no additional FBs-2LC module control is required. 1 Specifications of FBs-PLC Load Cell Measurement Modules FBs-1LC/ FBs-2LC Load Cell Measurement Modules Specifications FBs-1LC FBs-2LC Total Channels one channel two channels A/D Converter Utilized 24-bit Δ-Σ A/D esolution 16 bits (include signed bit) I/O Points Occupied 1 I(Input egister) and 8 DO Conversion ate 5/ 10/ 25/ 30/ 60/ 80 Hz 1/ 3/ 5/ 8 Hz Non-Linearity 0.01% F.S. (@25 ) Zero Drift 0.2 μv/ Gain Drift 10 ppm/ Excitation Voltage 5V with 100Ω driving capability Sensitivity 2mV/V, 5mV/V, 10mV/V,20mV/V Software Filter Moving average Average Samples 1~8 configurable Isolation Transformer(Power) and photo-coupler(signal) Indicator(s) 5V PW LED Supply Power 24V-15%/+20%, 2VA Internal Power Consumption 5V, 100mA Operating Temperature 0 ~ 60 Storage Temperature -20 ~ 80 Dimensions 40(W)x90(H)x80(D) mm
2 2 The Procedures of Using FBs-PLC Load Cell Module Start Connects Load Cell Modules to the expansion interface on PLC in series and connects an external 24VDC source and load cell measure input wires. Execute the WinProladder and configure the load cell configuration table address, the register address, and working register in load cell configuration windows, then you can read the weight measurement value form register directly. 3 The Procedures of Configure the Load Cell Measurement Click the item I/O Configuration which in Project Windows: Project I/O Configuration Select LC Configuration : Once the setting page displayed, is able to measure the load cell module.
3 1. Starting register of configuration table : Assign a starting register value to store the load cell configuration table, there will allow the following inputs: XXXX or DXXXX The configuration table only occupies 4+N of registers, where N is the number of load cell modules. As shown in the above example, 5000~ 5005 stores the load cell configuration table. 2. Starting register of reading/control register : Please input the starting register number of a block register that were allocated for receiving the measurement value and control parameters for load cell There will allow the following inputs, XXXX or DXXXX one channel occupies 16 register. As shown in the above example, channel 1 used 0 ~ Starting register of working register : Assign a starting registers to reserve the working registers, there will allow the following inputs XXXX or DXXXX. The load cell measurement register occupies (Nx4)+5 registers, where N is the number of load cell modules. As shown in the above example, D0~D12 are the working registers. Notes: The above three settings can be used in all Load Cell modules. Load cell module installation information and setup 4. Module #1 ~ #16 : Display the name of the installed module and the analog starting address of its own, there are the following modules. 1 2 FBs-1LC (1 channel of load cell module) FBs-2LC (2 channels of load cell module) 5. Span Ch0# / Ch1# :Assign the following selection of the measurement range: 0~10mV(2mV/V), 0~25mV(5mV/V), 0~50mV(10mV/V), 0~100mV(20mV/V) 6. Scan ate :Assign the scan rate of reading value, there are two selections:
4 1 FBs-1LC has 5 / 10 / 25 / 30 / 60 / 80 Hz can be assigned 2 FBs-2LC has 1 / 3 / 5 / 8 Hz can be assigned 7. Times of Average :Assign the times of average for load cell measure, unbalanced average, 2 times the average, 4 times the average, and 8 times of the average can be assigned. 4 Load cell reading / control register In following table, let s assume the starting register of reading/control register is egister Description /W Offset +0 Engineering weight value +1 aw weight value +2 High reference engineering value. Max W Command register- +3 Bit 0 set zero/tare reference Bit 1 set high(full scale) reference W +4 Auto zero threshold 0~255 W +5 Status register Bit 0 Error indication Bit 1 Over range or sensor broke indication +6 SPAN value( high reference zero reference ) +7 Zero value set by performing set zero reference +8 Current compensated zero value +9 egister for internal process usage +10~+15 eserved Each channel occupies 16 registers. Note: 1. Only the register are set by user, the other register are set by system 2. +3: Bit 0 = 1, set current measurement value as zero reference Bit 1 = 1, for SPAN. set current measurement value minus zero reference value as high reference value which corresponding to the weight value set in User can convert the engineering value on their own with reference the value in +2,+6 register if necessary.
5 4. Error indication includes high reference engineering value(+2) or SPAN(+6) is zero or negative 5. Auto zeroing threshold - This value confines the zero value drift tolerance region. If the zero drift value falls in this region, the zero drift will be compensated. Set this value to zero will disable the auto zeroing function. 6. D4052 delay time for auto zeroing activation, range from 1000 ~ 5000 (ms), default is 3000 (ms).
6 5 Description of elated egisters for Load Cell Measurement Installation Status of Load Cell 4016 : B0=1 means that the 1 st channel is installed B15=1 means that the 15 th channel is installed (the default of 4016 is FFFFH) 4017 : B0=1 means that the 16 th channel is installed B15=1 means that the 31 th channel is installed (the default of 4017 is FFFFH) When the load cell is installed (the corresponding bit must be 1), the system will perform the line broken detection. If there is line broken happened, the broken value will be displayed. When the load cell is not installed (the corresponding bit must be 0), the system will not perform the line broken detection. The broken value will be 0. Depends on the user s installation, the ladder program may control the corresponding bit of 4016 and 4017 to perform or not perform the line broken detection. 6 I/O Addressing of Load Cell Module By the time domain multiplexing design method, each load cell module occupies 1 point of input register and 8 points of digital output for I/O addressing. For correct I/O access, the I/O addressing of extension modules following the load cell module must be added the I/O quantity which the corresponding module should have. The WinProladder provides an easy and convenient way to calculate the I/O address for the extension modules through the on-line I/O Numbering operation.
7 7 Wiring of Load Cell Modules Wiring of FBs-1LC 24V+ 24V- 24V +5V +EXC CH Bit Data 24-Bit Δ-Σ - A/D CH0- -EXC Load Cell
8 Wiring of FBs-2LC 24V+ 24V- 24V +5V +EXC CH0+ 16 Bit Data 24 Bit + Δ-Σ A/D - CH0- -EXC Load Cell #0 +5V +EXC 16 Bit Data 24 Bit Δ-Σ CH1+ Load Cell #1 A/D CH1- -EXC
FBs-7SG1. LED Display Control Module. Specification
Introduction FBs-7SG1 is one of the LED display control modules of FBs-PLC series. One 7SG1 module can support up to 8 digits of seven-segment LED display (include decimal point) or 4 digits of 16-segment
More informationProcess modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
More informationWEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK
WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue
More informationAnalogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001
Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.
More informationEZIO-4THIE * External CJC Sensor** (National LM19)
TM E Z I/O EZIO-4THIE * Enhanced Thermocouple Input Module Part Number: EZIO-4THIE EZIO family offers two modules for interfacing to thermocouples: EZIO-4THI (not recommended for new applications) EZIO-4THIE
More informationSMS GSM Alarm Messenger
SMS GSM Alarm Messenger Data Logging Alarm Input Relay Output Voice Temperature Humidity Analog Input Capture and Send Data via SMS Report triggered alarm via SMS Output triggered via SMS Auto pick up
More informationModel: DC-A2IO Advanced HVAC Controller
Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA
More informationTHERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES
TSI and TSI logo are registered trademarks of TSI Incorporated. SmartTune is a trademark of TSI Incorporated. THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES IFA 300 Constant Temperature Anemometry
More informationContents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
More informationTHE INPUT/OUTPUT SYSTEM. Key Points
M O D U L E T W O THE 2 INPUT/OUTPUT SYSTEM Key Points In the first module, you learned about the basic architecture and operation of the Allen-Bradley Micrologix 1000, including a brief introduction to
More informationNon-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power
July 2010 PACSystems* RX3i Non-Isolated Analog Output Module with HART Communications, IC695ALG728 Non-Isolated Analog Output Modules, IC695ALG704, IC695ALG708 MODULE OK FIELD STATUS TB IC695ALG708 Q1
More informationDifferential Charge Amplifier
Electronics Differential Type 58A... The differential charge amplifier is used for signal conversion of piezoelectric sensors with differential output. Executions Aluminum die-cast enclosure (IP64) Plastic
More informationEXTERNAL DIMENSIONS AND PARTS
FX2N-4DA SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4DA special
More informationDAM Series DAM124 4DIN+8AI+4DO Module Model No.:DAM124 WebSite: www.gsm-m2m.com
DAM Series DAM124 4DIN+8AI+4DO Module Model No.:DAM124 WebSite: www.gsm-m2m.com This handbook has been designed as a guide to the installation and operation of King Pigeon Hi-Tech.Co.,Ltd DAM series. Statements
More informationXC series BD board for special functions. Operate Manual
68117 XC series BD board for special functions Operate Manual Catalog 一 CONFIGURE METHOD OF BD BOARD...3 二 ANALOG INPUT AND OUTPUT SAMPLING BOARD XC-2AD2DA-BD...4 2 一 Configure method of BD board Configure
More informationWeb Datalogger. Unit RS232C. General-purpose modem RS485. IP address search screen
Equipment, facilities, and service networks for data collection/logging, data transfer via e-mail/website, and system streamlining can be established without special knowledge. Energy saving system in
More informationJNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
More informationFeatures, Benefits, and Operation
Features, Benefits, and Operation 2014 Decibel Eleven Contents Introduction... 2 Features... 2 Rear Panel... 3 Connections... 3 Power... 3 MIDI... 3 Pedal Loops... 4 Example Connection Diagrams... 5,6
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationIn regard to calculating system power requirements, refer to DBK Basics located near the front of this manual.
DBK42 16-Slot 5B Signal Conditioning Module Overview 1 Hardware Setup 2 DBK42 Connection 2 DBK42 Configuration 2 5B Module Connection 2 Power Considerations 2 Terminal Block Connections 3 DaqBoard/2000
More informationDisplayport Extender via 2 multimode fibers LC Duplex Connector Extends Displayport Link up to 200 meters
Description Displayport combines the audio and video through an interface. It supports high resolution displays and multiple displays with a single cable, and increases the efficiency and bandwidth of
More informationHITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE
HITACHI INVERTER SJ/L1/3 SERIES PID CONTROL USERS GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. HAL1PID CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ1/L1 INVERTERS 3
More informationDMX2PWM 9 Channel Dimmer Setup Manual
DMX2PWM 9 Channel Dimmer Setup Manual www.ecue.de DMX2PWM 9ch Dimmer - Setup Manual e:cue control GmbH An OSRAM Company Rev. 1.3_01/2010 DMX2PWM 9ch Dimmer - Setup Manual Table of Contents 1. Device Overview....................................4
More informationIsolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES AC averaging technique used to rectify, amplify, and filter 50 Hz to 400 Hz sine-wave signals. Accepts inputs of between 20 mv to 550 V rms to give
More informationPhysical Specifications (Custom design available.)
Helmholtz Coils A useful laboratory technique for getting a fairly uniform magnetic field, is to use a pair of circular coils on a common axis with equal currents flowing in the same sense. For a given
More informationMicroMag3 3-Axis Magnetic Sensor Module
1008121 R01 April 2005 MicroMag3 3-Axis Magnetic Sensor Module General Description The MicroMag3 is an integrated 3-axis magnetic field sensing module designed to aid in evaluation and prototyping of PNI
More informationMeasuring Temperature withthermistors a Tutorial David Potter
NATIONAL INSTRUMENTS The Software is the Instrument Application Note 065 Measuring Temperature withthermistors a Tutorial David Potter Introduction Thermistors are thermally sensitive resistors used in
More informationI2C PRESSURE MONITORING THROUGH USB PROTOCOL.
I2C PRESSURE MONITORING THROUGH USB PROTOCOL. Product Details: To eradicate human error while taking readings such as upper precision or lower precision Embedded with JAVA Application: Technology Used:
More informationHow To Use A Sound Card With A Subsonic Sound Card
!"## $#!%!"# &"#' ( "#' )*! #+ #,# "##!$ -+./0 1" 1! 2"# # -&1!"#" (2345-&1 #$6.7 -&89$## ' 6! #* #!"#" +" 1##6$ "#+# #-& :1# # $ #$#;1)+#1#+
More informationT O K I S T A R L I G H T I N G I N S T R U C T I O N M A N U A L LC-1CH-MULTI Dimmer Module
T O K I S T A R L I G H T I N G I N S T R U C T I O N M A N U A L Dimmer Module General The Dimmer Pack can be used with any of Tokistar s LED Lighting Systems operating from our 6, 8 or VDC LED Drivers.
More informationWhat Does Rail-to-Rail Operation Really Mean?
What Does Rail-to-Rail Operation Really Mean? 2004 Microchip Technology Incorporated. All Rights Reserved. What does Rail-to-Rail Operation really mean? 1 Agenda What does Rail-to-Rail output operation
More informationSpecifications for EM223 24 VDC 4 In/4 Out and EM223 24 VDC 4 In/4 Relay Out
SIMATIC S7-200 EM223 Digital Combination Modules EM223 2 VDC In/ Out and EM223 2 VDC In/ Relay Out Table 1 Specifications for EM223 2 VDC In/ Out and EM223 2 VDC In/ Relay Out EM223 2VDC In/Out 6ES7 2231BF200XA0
More informationProgrammable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
More informationCALIBRATION PROCEDURE NI 9219. Contents. Software Requirements. ni.com/manuals
CALIBRATION PROCEDURE NI 9219 Français Deutsch ni.com/manuals Contents This document contains information for calibrating the National Instruments 9219. For more information on calibration, visit ni.com/calibration.
More informationVision OPLC. V350-35-R34/V350-J-R34 Technical Specifications. Technical Specifications
Vision OPLC V350-35-R34/V350-J-R34 Technical Specifications The Unitronics V350-35-R34/V350-J-R34 offers the following onboard I/Os: 22 Digital Inputs, configurable via wiring to include 2 Analog and 3
More informationEPSON Perfection 1650/1650 PHOTO. Scanner Parts. Scanner Specifications. Basic Specifications. device Effective pixels
Scanner Parts Start and indicator light Photo Print USB port The has a transparency unit built into the scanner lid and holder for 35 mm film and slides: EPSON Perfection 1650 owners can purchase an optional
More informationTechnical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
More informationMCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description
Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V
More informationCPU systron S 200 - S 250 - S 250c. systron S 200 - S 250 - S 250c. CPUs to the process modules. Stand-alone PLC
E031019 000823 systron S 200 - S 250 - S 250c CPU systron S 200 - S 250 - S 250c 45 mm width Flexible and expandable Easy to use software for bus connection (S 250/ S 250c) CPUs to the process modules
More informationThe Answer to the 14 Most Frequently Asked Modbus Questions
Modbus Frequently Asked Questions WP-34-REV0-0609-1/7 The Answer to the 14 Most Frequently Asked Modbus Questions Exactly what is Modbus? Modbus is an open serial communications protocol widely used in
More informationElectronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
More informationAutomation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
More informationExternal temperature sensors for FSC Ultrasonic Flow Meter (thermal flow measurement function)
Application: Heat quantity measurement This function calculates the heat quantity received and sent with liquid (water) in cooling and heating. Two 4-20mA inputs are available for temperature measurements.
More informationMANUAL FOR RX700 LR and NR
MANUAL FOR RX700 LR and NR 2013, November 11 Revision/ updates Date, updates, and person Revision 1.2 03-12-2013, By Patrick M Affected pages, ETC ALL Content Revision/ updates... 1 Preface... 2 Technical
More informationTemperature & Humidity SMS Alert Controller
Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal
More informationRosemount 333 HART Tri-Loop
Product Data Sheet Rosemount 333 Rosemount 333 HART Tri-Loop HART-TO-ANALOG SIGNAL CONVERTER Convert a digital HART signal into three additional analog signals Easy to configure and install Accessory product
More informationSIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program
Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves
More informationHow To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
More informationPicture 1 Lead Color Code Lead Function V-Link Function V-Link Pin Table 2 Picture 2 Node Commander software
TN-W0026 MicroStrain Technical Note Connecting and Calibrating a Load Cell with V-Link V-Link and Futek LSB300 Load Cell (Applies to V-Link, SG-Link, SG-Link OEM, HS-Link ) Overview MicroStrain s V-Link
More informationSIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.
SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation
More informationMLC 9000+ TM Maximum Productivity and Versatility for Control without Compromise!
Data Sheet Maximum Productivity and Versatility for Control without Compromise! Basic Bus Communication Module DESCRIPTION The Basic Bus Communication Module (BCM) is part of the MLC 9000+ DIN rail mount
More informationIntelligent RS-485 I/O expansion unit: RU-87Pn Series
INTRODUCTION RU-87Pn series is a remote intelligent I/O expansion unit that used to expand i-87k series I/O modules over the RS-485 for industrial monitoring and controlling applications. There are more
More informationT7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
More informationDisturbance Recoder SPCR 8C27. Product Guide
Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power
More informationThe Universal DAQ Device. Connect and measure immediately!
The Universal DAQ Device. Connect and measure immediately! XXL performance in mini format 8 universal connectors 1) on each QuantumX device suited for most common transducer technologies: 1) See technical
More information24-Bit Analog-to-Digital Converter (ADC) for Weigh Scales FEATURES S8550 VFB. Analog Supply Regulator. Input MUX. 24-bit Σ ADC. PGA Gain = 32, 64, 128
24-Bit Analog-to-Digital Converter (ADC) for Weigh Scales DESCRIPTION Based on Avia Semiconductor s patented technology, HX711 is a precision 24-bit analogto-digital converter (ADC) designed for weigh
More informationThe Do s and Don ts of Pressure Transducers
The Do s and Don ts of Pressure Transducers ABSTRACT When specifying a pressure transducer for a process measurement, a number of items have to be considered. Some of the more important ones are discussed
More informationNTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter
NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter Description: The NTE2053 is a CMOS 8 bit successive approximation Analog to Digital converter in a 20 Lead DIP type package which uses a differential
More informationApplication/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
More informationRosemount 333 HART Tri-Loop
Product Data Sheet September 2014 00813-0100-4754, Rev GA Rosemount 333 HART Tri-Loop HART-to-Analog Signal Converter Convert a digital HART signal into three additional analog signals Easy to configure
More informationUsing the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master
Using the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master Page 1 of 13 Table of Contents 1 OVERVIEW... 3 2 INSTALLING AND CONFIGURING THE ANYBUS -X GENERIC GATEWAY AND ETHERNET
More informationUser s s Manual. LG Programmable Logic Controller GLOFA MASTER-K G3F TC4A G4F TC2A G6F TC2A. LG Industrial Systems
User s s Manual LG Programmable Logic Controller GLOFA MASTER-K G3F TC4A G4F TC2A G6F TC2A LG Industrial Systems REVISIONS Date REV. No Description 2001.4. 702004908 G6F-TC2A Module added SAFETY PRECAUTIONS
More informationEnergy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
More informationHIGH RELIABILITY POWER SUPPLY TESTING
HIGH RELIABILITY POWER SUPPLY TESTING Dale Cigoy Keithley Instruments, Inc. The reliability of a power supply must match or exceed the rest of the system in which it is installed. Generally, this requires
More informationNEW. EVEN MORE data acquisition and test stand automation
NEW EVEN MORE data acquisition and test stand automation the new class of data The plug&play complete package User benefits Expert Series is the latest generation of data acquisition Complete hardware
More informationSMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2]
SMS Alarm Messenger SMSPro_Setup Revision 090210 [Version 2.2] ~ 1 ~ Contents 1. How to setup SMS Alarm Messenger?... 3 2. Install the SMSPro_Setup software... 5 3. Connection Type... 6 4. Connection Port
More informationParallax Serial LCD 2 rows x 16 characters Non-backlit (#27976) 2 rows x 16 characters Backlit (#27977) 4 rows x 20 characters Backlit (#27979)
599 Menlo Drive, Suite 100 Rocklin, California 95765, USA Office: (916) 624-8333 Fax: (916) 624-8003 General: info@parallax.com Technical: support@parallax.com Web Site: www.parallax.com Educational: www.stampsinclass.com
More informationFiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers
Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers Analog Data Links Multi-Channel Contact Closures Multiplexers Digital Data Links - Contact Closures Power Supply
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More informationTCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...
More informationAPI Marine. BMS Presentation. Ballast Measurement Systems
API Marine BMS Presentation Ballast Measurement Systems BMS4 Typical Configuration BMS4 Typical Configuration BMS4 Extended Configuration BMS4 System (24 tanks) Air regulator Terminal block Drain/Air Filter
More informationVentostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:
GE Measurement & Control Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low
More informationUS-SPI New generation of High performances Ultrasonic device
US-SPI New generation of High performances Ultrasonic device Lecoeur Electronique - 19, Rue de Courtenay - 45220 CHUELLES - Tel. : +33 ( 0)2 38 94 28 30 - Fax : +33 (0)2 38 94 29 67 US-SPI Ultrasound device
More informationOrdering Part Numbers: Universal Signal Converter: USC-CVB225-01 Universal Signal Converter with a 4-20mA input and +/- 10V output: USC-CVB225-B10V
Description: The universal signal converter offers threeway isolation and translates one input control signal into one to three simultaneous outputs. Switches allow the user to select the desired input
More informationTire pressure monitoring
Application Note AN601 Tire pressure monitoring 1 Purpose This document is intended to give hints on how to use the Intersema pressure sensors in a low cost tire pressure monitoring system (TPMS). 2 Introduction
More informationTransmitter Interface Program
Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following
More informationQUICK START GUIDE FOR DEMONSTRATION CIRCUIT 956 24-BIT DIFFERENTIAL ADC WITH I2C LTC2485 DESCRIPTION
LTC2485 DESCRIPTION Demonstration circuit 956 features the LTC2485, a 24-Bit high performance Σ analog-to-digital converter (ADC). The LTC2485 features 2ppm linearity, 0.5µV offset, and 600nV RMS noise.
More informationDRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
More informationDPI 260 SERIES: Digital Pressure Indicators
DPI 260 SERIES: Digital Pressure Indicators INTRODUCTION The DPI 260, 261 and 262 range of digital pressure instruments measure and indicate pressure in any specified scale units and provide accuracies
More informationABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
More informationmecotron Safety relay ESTOP-2 For emergency stop monitoring
E0006 000824 Safety relay E-2 For emergency stop monitoring Description The safety module E-2 for emergency stop monitoring is used for safety breaking one or more circuits and is designed to be incorporated
More informationSmart DeviceNet Remote I/O Terminals
Smart DeviceNet Remote I/O Terminals ather and Use Information for Effective Preventive Maintenance et more useful data for preventive maintenance when you build cost-effective parallel information systems
More informationSpeed Control Relays SX2
SX2 File 850 CONENS Description.....................................................Page General Information................................................ 2-3 SX2DV General Information...........................................
More information22.302 Experiment 5. Strain Gage Measurements
22.302 Experiment 5 Strain Gage Measurements Introduction The design of components for many engineering systems is based on the application of theoretical models. The accuracy of these models can be verified
More informationDigital and Analog I/O
70072-0127-07 TECHNICAL NOTE 02/2007 Digital and Analog I/O This document discusses the application and configuration of digital and analog inputs/outputs (I/O). Details are for both onboard I/O and external
More informationGAM900/GAM900S. Acceleration precisely measured and safely monitored
GAM900/GAM900S Acceleration precisely measured and safely monitored The benefits at a glance: Less sensors more safety Minimum size, maximum performance Extremely reliable and robust IP 67 protection thanks
More informationProgramming Logic controllers
Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,
More informationTilt switches N3 / N4... MEMS technology, one or two axis. Use. Options. + long lifetime and highly reliability due to mechanism-free MEMS technology
Tilt switches MEMS technology, one or two axis N3 / N4... + long lifetime and highly reliability due to mechanism-free MEMS technology + combinable output signals + one or two axis measurement + tilt range
More information3500/62 Process Variable Monitor
3500/62 Process Variable Monitor Description The 3500/62 Process Variable Monitor is a 6-channel monitor for processing machine critical parameters (pressures, flows, temperatures, levels, etc.) that merit
More informationwww.kem-kueppers.com info@kem-kueppers.com Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter
www.kem-kueppers.com info@kem-kueppers.com Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter Description The coriolis mass flow meters measure simultaneously mass
More informationHow To Expand A Bus Slot On A Microsoft Powerbook (For Microsoft) (For A Microsusceptible) (Powerbook) (Microsuspera) ( For A Microsimplified) (Mini-S
Product We provide wide array of models to meet your desired bus specifications. Bus Extension & Chassis O03 System Expansion Unit / Bus An expansion system is used to expand the number of available bus
More information8 by 8 dot matrix LED displays with Cascadable Serial driver B32CDM8 B48CDM8 B64CDM8 General Description
8 by 8 dot matrix LED displays with Cascadable Serial driver B32CDM8 B48CDM8 B64CDM8 General Description The B32CDM8, B48CDM8 and the B64CDM8 are 8 by 8 (row by column) dot matrix LED displays combined
More informationM2M I/O Modules. To view all of Advantech s M2M I/O Modules, please visit www.advantech.com/products.
M2M I/O Modules 14 M2M I/O Modules Overview 14-2 M2M I/O Modules Selection Guide 14-6 ADAM-2510Z Wireless Router Node 14-8 ADAM-2520Z Wireless Modbus RTU Gateway 14-9 ADAM-2031Z ADAM-2632Z ADAM-2017Z ADAM-2018Z
More informationInwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
More informationLC 2 MOS Signal Conditioning ADC with RTD Excitation Currents AD7711
FEATURES Charge-Balancing ADC 24 Bits, No Missing Codes 0.0015% Nonlinearity 2-Channel Programmable Gain Front End Gains from 1 to 128 1 Differential Input 1 Single-Ended Input Low-Pass Filter with Programmable
More informationPROFIBUS fault finding and health checking
PROFIBUS fault finding and health checking Andy Verwer Verwer Training & Consultancy Ltd PROFIBUS PROFIBUS is a very reliable and cost effective technology. It is common to find extensive installations
More informationFieldbus slave modules with I/Os, DIO
140 Fieldbus slave modules with I/Os, DIO 1534CF00 1534CH00 1534PF00 1534PH00 1536CH00 1536CL10 1536PH00 1536PL00 Order number 1534CF00 1534CH00 1534PF00 1534PH00 Figure Type SM 153, CANopen slave, DIO
More informationProduct Datasheet P1110 915 MHz RF Powerharvester Receiver
DESCRIPTION The Powercast P1110 Powerharvester receiver is an RF energy harvesting device that converts RF to DC. Housed in a compact SMD package, the P1110 receiver provides RF energy harvesting and power
More informationDupline Car Park System Type GP6220 330x 724-US 3-Colour Ultrasonic Sensor
Dupline Car Park System Type GP6220 330x 724-US 3-Colour Ultrasonic Sensor Product Description GP6220 330x 724-US is an ultrasonic sensor with a built-in 3 colour LED indicator and part of the Dupline
More informationESP 20/20. Compressor Monitoring System
ESP 20/20 Compressor Monitoring System 2 ESP 20/20 Compressor Monitoring System At the customer s discretion, the manufacturer can view compressor performance or be notified of compressor advisories. ESP
More information