Electrical Isolation Safety Procedure
|
|
|
- Melvyn Carr
- 9 years ago
- Views:
Transcription
1 Pars Oil & Gas Company Electrical Isolation Safety Procedure HEALTH, SAFETY AND ENVIRONMENT PROCEDURE Electrical Isolation Safety Procedure DOCUMENT ID - PR-82-POGC-001 REVISION 0.0
2 Pars Oil & Gas Company Pages 15 Revision 00 Electrical Isolation Safety Procedure Document ID. PR 82 POGC 001 HSE Department Electrical Isolation Safety Procedure Document Authorization Document Type Security Classification Document Authority/Owner Document Custodian Safety Procedure Unrestricted P.O.G.C HSE Document Author HSE-S Approved By M.Ansari HSE-S593443
3 Table of Contents 1. INTRODUCTION PURPOSE SCOPE RESPONSIBILITIES PROCEDURE General Electrical Isolation Principles LV Equipment Isolation Electrical Isolation Principles De-Isolation Sanction for test TRAINING DEFINITION & Abbreviation APPENDIXES...12 SUGGESTION FORM September Electrical Isolation Safety procedure Page 2
4 1. INTRODUCTION Pars Oil and Gas Company (POGC), a subsidiary of National Iranian Oil Company (NIOC), was established in POGC is a developmental and manufacturing organization that specializes in the fields of engineering and management of development projects, production, operation and integrated management of oil and gas reservoirs. POGC s mission is to ensure sustainable and preservative production and development of Iran s oil and gas industry in the areas under its responsibility, development of oil and gas value chain as well as optimization of energy supply processes at national, regional and international levels. POGC is also in charge of development of joint and nonjoint oil and gas fields of the country including South Pars, North Pars, Golshan and Ferdowsi. Aimed at creating superior value and boosting the level of satisfaction of the beneficiaries and with an approach focusing on sustainable, integrated and knowledge-oriented production and development, the company feels committed to comply with national and international requirements, regulations and standards in such areas as quality, safety, as well as occupational and environmental health. 2. PURPOSE This Procedure describes requirements to ensure safety at work of personnel and equipment and to provide details of methods and principles for safe Electrical Isolation of electrical equipment. 3. SCOPE This Specification applies to all electrical powered equipments and substations and other premises belonging to or occupied by POGC, Contractors or Sub- Contractors authorised to work on behalf of POGC. 4. RESPONSIBILITIES 4.1 Operations Field Supervisor The Operations Assistant is responsible for ensuring that isolations are carried out by authorised responsible persons and in accordance with this procedure. 4.2 Head of Process /Head of Utility / Shift Superintendents Head of Process /Head of Utility / Shift Superintendents are responsible for: Ensuring that all procedures and safeguards are fully implemented. Facilitating preparatory works in connection with work permits. Ensuring that equipment is operational after maintenance works are completed 4.3 Electrical Safety Supervisor September Electrical Isolation Safety procedure Page 3
5 The Electrical Safety supervisor is responsible for: Conducting periodic checks on status of isolations and conformance with this procedure. Providing advice and / or assistance as requested / when required. 4.4 Authorised Electrical Persons Senior Authorized Electrical Person SAEP An authorized electrical person who has been appointed in writing by the electrical discipline head to carry out high voltage and low voltage switching and isolation, the issue and cancellation of electrical permit to WORK, sanction for test, limitation of access, isolation/de-isolation certificate. 4.5 Authorized Electrical Person AEP A competent electrical person who has been appointed in writing by the electrical discipline head to carry out high voltage switching and low voltage switching, low voltage isolation and to receive electrical permit to work, sanction for test, limitation of access, electrical isolation and de-isolation certificate and permit to work. See POGC PTW Manual (Doc. No. MA-64-POGC-001) The Authorised Electrical Persons are responsible for: Performing electrical isolations as requested on Electrical Isolation Permits / Certificates and within the limits of their authorisation. Demonstrating to Operators and Working Party that concerned equipment will not / cannot start under any conditions or circumstances. Reinstating switching equipment to normal on completion of works. Participating in test runs with Operators and Working Party before cancellation of Permit to Work. 5. PROCEDURE 5.1 General Requests to electrically isolate equipment, or a package, is made by the Working Party when first raising the Permit to Work by completion of the Complementary Electrical Isolation Permit(s). In the particular case of generators, a Process / Mechanical Isolation Certificate must also be raised. All equipment subject to electrical isolation must be padlocked by using a safety padlock. The safety padlock number must be mentioned on the Isolation Certificate. If there are several Permits to Work rose for the same item of equipment to be electrically isolated, there must be different number of Isolation Certificates and safety padlocks applied. One PTW is not valid for different trades. PTW to be raised for different trade and task. As example: Electrical: One PTW cannot cover work on transformer and switchboard together September Electrical Isolation Safety procedure Page 4
6 Electrical: Work on HV transformer or HV-LV transformer need one PTW and one Electrical Isolation complementary (by ticking HV-LV box). Mechanical: Electrical isolation certificate of Electrical PTW cannot cover mechanical work 5.2 Electrical Isolation Principles Electrical Isolation is a preparatory operation to allow a Permit to Work to be issued and to ensure that general safety precautions are observed when carrying out the isolations. General safety precautions are: Correct Personal Protective Equipment (PPE) must be worn. Work together with Shift Authority. Make sure that any equipment to be isolated is switched off. Check scope of work on equipment to be isolated: if equipment removal is contemplated, cables must be disconnected at concerned equipment and cable ends taped to prevent damage to connections or moisture ingress. Apply safety padlocks where necessary to ensure proper isolation. Log safety padlock numbers and document numbers in the sub-station Log Book provided for this purpose. Apply Isolation tag on which the complementary and main permit numbers registered. As safety padlocks have a unique key, they must be stored in the substation key-box to avoid risk of loss. Provide, wherever necessary, a multi hasp device to allow for fitting of several padlocks. Demonstrate to Shift Authority and to Working Party that equipment will not / cannot start under any conditions or circumstances HV Equipment Isolation Motor Feeders Some types of HV motor feeders are (but not limited) as below: 6 kv motors fed from 33 kv switchboards through a captive step-down transformer. 6 kv motors fed from 6 kv switchboards through circuit breaker. 6 kv motors fed from 6 kv switchboards through contactor and HRC fuses. Depending on the work to be done on equipment, isolation may consist only of locking-off the main control device (circuit breaker or contactor). If any work is required on conductive parts however, EARTHING of HV cables is mandatory in addition to locking-off and tagging them. Control device locking-off consists of racking out the withdraw able circuit breaker / contactor in order to separate it from bars, although not necessarily removing it from the cubicle, and fitting safety padlock(s) at appropriate location(s) in such a way that racking-in is impossible without removing the safety padlock. Locking-off isolation is only performed by an Authorised Electrical Person. September Electrical Isolation Safety procedure Page 5
7 Earthing of HV cables is achieved by closing the earth-switch associated with the circuit breaker / contactor and locking-off in the closed position with a safety padlock. This type of isolation (locking-off and earthing) is performed by a Senior Authorised Electrical Person who issues a Complementary Electrical Isolation Permit describing the work to be done by electrical personnel on conducting parts. If work by electrical personnel is to disconnect the motor to allow removal by others (mechanical engineers, for example), this is part of the preparatory work and must be done before issue of the Main Permit to Work. (To mechanical engineers) The scope of work is described on the Main Permit to Work and the Authorised Electrical Person is responsible for safety of personnel working under his directions and the equipment to be worked on. Distribution Transformer Feeders Some types of distribution transformers are (but not limited) as below: 33 to 6 kv 6 kv to 400 V Some transforms such as (6kV to 400V) differ in that the secondary sides of transformers and are not provided with EARTHING facility at switchboard level. Before isolation is performed, ensure that busbar which is supplied by this transformer is fed from another source by implementation automatic transfer (ATS) or automatic change over (ACO). For this operation, the Shift Authority or Working Party (if a Permit to Work is issued) must ensure that any switching is done from the PDCS console located in CCR before effective isolation is started thus avoiding disturbance to running equipment. Primary circuit breaker is also to be opened from PDCS / PMS console after the source change. Every change in breaker position must be confirmed by radio or telephone from the concerned locations to PDCS / PMS Console Operator. Once this is done, the following actions may be performed at the concerned switchboards: Racking out of circuit breakers. Closure of earthing switches (on 33, 6 kv switchboards). Fitting of safety padlocks. For 33 to 6 kv transformers, access to terminals is only possible if the appropriate keys are retrieved from switchboards (keys are free when earthing switch is closed). The same applies for 6 kv to 400 V transformers, but on the low voltage side. The key is free when the circuit breaker is racked out as there is no earthing mechanism. This type of isolation must be performed under the supervision of a Senior Authorised Electrical Person. Similarly for motors, if working on conducting parts to allow others to work, the Senior Authorised Electrical Person must issue a complementary Electrical September Electrical Isolation Safety procedure Page 6
8 Isolation Permit to describe the scope of work by electricians. This is part of the Main Permit to Work preparatory works. This work is not to be done by electricians on the Own Isolation basis, the work must start under the responsibility and supervision of a Senior Authorised Electrical Person on the Normal Isolation (or his delegate who cannot be less than an Authorised Electrical Person) until all works on isolated equipment are complete. Restoration to a live condition must be under the supervision of a Senior Authorised Electrical Person. Generators: TYPE OUTPUT CONNECTIONS Diesel engine-driven 6 kv Connected to 6 kv essential switchboard through circuit breakers In order to allow safe work on packages, isolations are made at following locations: Electrical switchboard where power lines are connected. Generator UCP where excitation controls output is located. Gas and / or diesel oil supply line (Mechanical / Process isolations). Auxiliary package switchboard (depending on scope of works). Starting systems (Mechanical / Process and / or Electrical Isolation). Similarly as for previous equipment, preparatory works start by bringing the machine off-line and control of main circuit breakers is to be done from PDCS / PMS console. Electrical isolations may be of the simple lock-off type when work does not involve conductive parts, otherwise EARTHING must be done at switchboards and at generator terminals for main generators. Package-dedicated switchboards may also need to be isolated at incomers. In all cases there must be the same number of Isolation Certificates as items of equipment. Isolations must be performed under the supervision of a Senior Authorised Electrical Person. Switchboards All HV switchboards (33 or 6 kv) are composed of two busbars, A and B, which can be interconnected by means of a bus-tie circuit breaker. Isolation of busbars is strictly electricians work but, as this may have consequences on running plant; preparatory works are of prime importance to ensure a minimum of disturbance to running equipment. Such works should not take place more than once in every three to five and should ideally be planned during an area shutdown although this may not always be possible. This procedure considers this last case scenario, i.e., out with an area shutdown period. This type of isolation must be performed under the supervision of a Senior Authorised Electrical Person after development of a detailed Procedure agreed by the Process / Utility / Shift Superintendents. This Procedure must highlight: September Electrical Isolation Safety procedure Page 7
9 Actions by Operators to put the plant in a safe running condition. Possible risks and hazards. Back-up solutions in the event of a failure. Main actions and responsibilities to complete preparatory work and begin maintenance work are shown in the Table 1: Table 1: Action & responsibility ACTIONS RESPONSIBILITY/LOCATION All preparatory works. Operators Switching (to ensure that all switchboards depending on bus to be isolated) are fed by alternate source. Position change-over enable / disable control switch to OFF position. Open primary circuit breaker of transformer supplying the busbars to be worked on. Busbar is now de-energised. Every circuit breaker movement must be confirmed by radio or telephone. All circuit breakers and contactors must be removed from cubicle (including bus-tie breaker). Shutters at bus-tie breaker compartment must be locked with safety padlock. Certain keys must be retrieved to allow earthing of busbars. A detailed procedure per switchboard will be developed later to consider specifics and key numbers of each switchboard. PDCS console Switchboard location electrician PDCS / PMS console PDCS / PMS console operator 5.3 LV Equipment Isolation Motor Feeders At this voltage level (400 V) isolation consists only of locking-off the main control device (circuit breaker or contactor). Control device locking-off consists of racking out breaker / contactor and applying safety padlock(s) at appropriate location(s) in such a way that racking-in is impossible without removing the safety padlock. This type of isolation (locking-off) is only performed by a Competent Electrical Person. If the scope of work of a Main Permit to Work involves removal of the motor from site, then the preparatory work must also include disconnection of cables at the motor. This fact must be clearly mentioned on the Isolation Certificate. Distribution Transformer Feeders As there is no possibility of back feed, isolation of LV distribution transformers is carried out in the same way, and by the same Authorised Electrical Person, as the motor feeders. Switchboards There are three types of switchboards: September Electrical Isolation Safety procedure Page 8
10 . Switchboards comprising two busbars and a bus-tie circuit breaker. Switchboards with only one busbar and double feed. Switchboards with only one busbar and single feed SWITCHBOARD TYPE Two busbars and bus-tie circuit breaker Single busbar and double feed Single busbar and single feed DETAILS These are isolated using the same principles as HV switchboards but EARTHING of buss bars is performed using approved portable EARTHING devices made of flexible cables ending with C clamp type connectors. Such isolations are performed under the supervision of an Authorised Electrical Person. As above except that there is no bus-tie circuit breaker. As for motor feeders UPS & DCP In principle, UPS & DCP systems (whether AC or DC) are critical items that cannot be isolated entirely. Maintenance teams may only begin work after preparation of concerned area is completed under the supervision of an Authorised Electrical Person and proper Limitation of Access (LOA) is documented. Because of the presence of batteries in these UPS systems, it is possible to be exposed to contact with voltages that are hazardous to the human body. 5.4 Distribution Boards Small power distribution boards can be isolated as for motor feeders when it is necessary to work on common bars or wiring. Isolation of individual out goers from such switchboards by use of safety padlock will also need a suitable locking device fitting to concerned circuit breakers to prevent accidental closure. As with UPS units, shutdown of associated distribution boards may not be possible without a major upset to the running plant. Maintenance works may have to be done in live conditions, in which case a Limitation of Access (LOA) Certificate must be prepared and documented before starting work. If a shutdown is unavoidable, a procedure detailing other disciplines specific works requires to be prepared and agreed before the shutdown can take place. 5.5 De-Isolation De-Isolation is the reverse process of Isolation and consists of: Cancelling main permit in complete case. Removing all safety padlocks, tags and keys. Restoring all open and racked-out, or closed (earth switches), switching devices to working order. Cancelling / closing Electrical Isolation Permit. Updating log books etc. September Electrical Isolation Safety procedure Page 9
11 This process can take place only when Working Party has declared the work is complete or if requested to do so by Shift Authority. Main Permits to Work are cancelled by Shift Authority only after running tests have been successfully conducted. Responsible Persons are the same as for Isolation. If running tests are not conclusive, and it is not possible to complete troubleshooting or repair work on the spot, Isolations must be re-instated as they were originally and new documentation must be prepared. 5.6 Sanction for test A form of declaration signed and issued by a Senior authorized electrical person to an authorized electrical person in charge of testing high voltage equipment or a competent electrical person in charge of testing low voltage equipment for the purpose of making known to such persons exactly what equipment is to be tested and the conditions under which testing is to be performed. The Sanction for test permit, when signed by involved disciplines and Area Authority in allocated location, to be de-isolated by HSE Electrical Person (S.A.E.P or A.E.P) for performing the test. Complementary sanction for test permit will be attached to Main permit and Complementary electrical Isolation permit will be held in HSE electrical office up to end of the test.if the result of test is satisfied the main permit will be signed Off and all isolations on PTW' s to be reinstated to the original isolations as before. 6. Training All people shall be trained based on permit requirements and their responsibilities. 7. DEFINITION & Abbreviation: CAUTION NOTICE A notice in an approved form attached to electrical equipment or its controls conveying a warning against interference with such EQUIPMENT. These notices will be attached to all points of ISOLATION from which EQUIPMENT can be made LIVE. DANGER It is a risk of bodily injury or loss of life or health from shock, burn, asphyxiation or other causes. DANGER NOTICE A notice in an approved form reading DANGER with any additional wording that can call attention to the DANGER of approaching or interfering with such LIVE EQUIPMENT. EARTH, EARTHED / EARTHING Connecting to or connected to the general mass of earth in such a manner as will ensure at all times that the body being earthed discharges immediately any electrical energy stored in it and furthermore, is maintained at a safe potential with respect to the general mass of earth. September Electrical Isolation Safety procedure Page 10
12 LV Earth LV Earth is an earth of an approved design that may be used on low voltage equipment when it is worked on under an electrical permit to work. EARTHED NOTICE A notice in an APPROVED form reading EARTHED that can be used to identify EQUIPMENT that has been used to apply a CIRCUIT MAIN EARTH to a circuit. ELECTRICAL ISOLATION An act which ensures safe isolation of electrical EQUIPMENT by physically opening electrical circuits by removing and padlocking in open position the main circuit control EQUIPMENT. ELECTRICAL ISOLATION /DE-IAOLATION PTW A form of request raised by a working party and signed and issued by a responsible member of a Custodian Department to a suitably authorized electrical person to ensure the safe ISOLATION of electrical circuits prior to non-electrical works by a third party. OWN ISOLATION A statement by electrician in charge of works on main PERMIT to WORK to indicate that works to perform under his responsibility will require ELECTRICAL ISOLATION of EQUIPMENT, such ISOLATION being made and documented by himself for himself and his team. ELECTRICAL ISOLATION/DE-ISOLATION CERTIFICATE must be used the same way, as above with the exception that signature of Area Authority is not required. ELECTRICAL PTW/ CERTIFICATE A form of declaration signed and issued by a SENIOR AUTHORISED ELECTRICAL PERSON to a COMPETENT ELECTRICAL PERSON in charge of work to be carried out on any EQUIPMENT, for the purpose of making known to such a person exactly what HIGH VOLTAGE EQUIPMENT is DEAD, ISOLATED from all LIVE conductors, has been discharged, connected to EARTH, and it is safe to work. An ELECTRICAL PERMIT to WORK shall also be issued to a person in charge of work on LOW VOLTAGE EQUIPMENT when either it is necessary to: Apply a CIRCUIT MAIN EARTH to the HIGH VOLTAGE side of a transformer feeding the LOW VOLTAGE EQUIPMENT Or Apply a LV EARTH to the bus-bars of a LOW VOLTAGE switchboard. HIGH VOLTAGE EQUIPMENT (HV) Any equipment, apparatus and conductor which are normally operated at a voltage exceeding 1000 V AC or 1500 V DC. LOW VOLTAGE EQUIPMENT (LV) Any equipment, apparatus and conductor which is not EXTRA LOW VOLTAGE and which are normally operated at a voltage not exceeding 1000 V AC or 1500 V DC. EXTRA LOW VOLTAGE EQUIPMENT Any equipment, apparatus and conductor which are normally operated at a voltage not exceeding 50 V AC or 70 V DC. ISOLATED / ISOLATION September Electrical Isolation Safety procedure Page 11
13 EQUIPMENT disconnected from LIVE system by an open disconnecting or by an adequate physical gap. LOTO Lock out Tag out is a safety system including of all Safety padlocks, keys, Tags and tokens used to lock means of ISOLATION and EARTHING. LIMITATION of ACCESS (LOA) A form issued and cancelled by a SENIOR AUTHORISED PERSON to a COMPETENT ELECTRICAL PERSON, defining the limits and nature of work which may be carried out on, or in the vicinity of, LIVE EQUIPMENT. A LIMITATION of ACCESS may be issued when an ELECTRICAL PERMIT to WORK or a SANCTION for TEST is not applicable and when verbal instructions are not considered sufficient. PDCS Power Distribution Control System PSMS Power System Monitoring and Simulation PMS Power Management System POGC Pars Oil & Gas Company UPS Uninterruptable Power Supply SLD Single Line Diagram LOA Limitation Of Access DCP Display and Control Panel ACO Automatic Change Over ATS Automatic Transfer System 8. APPENDIX : N/A September Electrical Isolation Safety procedure Page 12
14 SUGGESTIONS FOR THE POGC ELECTRICAL ISOLATION SAFETY PROCEDURE MANAGER, HSE Department Pars Oil & Gas Company Tehran I.R. Iran Please consider the following suggestion(s) relative to the POGC Electrical Isolation safety procedure (Signature) (Date) (Address) Contact Telephone Number Contact FAX Number September Electrical Isolation Safety procedure Page 13
High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance
Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety
Circuit Electrical Testing
Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved
RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016
RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.
MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV
MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
Electrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
Electrical Safety Policy
Electrical Safety Policy Version Number: V2 Name of originator/author: Director of Estates and Facilities Name of responsible committee: Estates and Facilities Committee Name of executive lead: Chief Operating
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
Chapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Lockout / Tagout Program
Lockout / Tagout Program Table of Contents Page Scope... 2 Definitions... 2 Authorization... 3 Responsibilities... 4 Compliance and Enforcement... 4 When to Lockout/Tagout (LOTO)... 5 Lockout Procedure...
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM
1 UNIVERSITY OF WEST FLORIDA LOCKOUT/TAGOUT (LOTO) SAFETY PROGRAM (EQUIPMENT HAZARD DE-ENERGIZING AND ISOLATION) DEPARTMENT OF ENVIRONMENTAL HEALTH AND SAFETY 11000University Parkway Pensacola, FL 32514
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Current Transformers Ratio / Polarity / Types
CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
Keeping electrical switchgear safe
Keeping electrical switchgear safe Keeping electrical switchgear safe Health and Safety Failure of electrical switchgear can cause death, serious injury and major damage. If you own or operate this type
This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department. This edition July 2004
This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department This edition July 2004 This Guidance Notes is issued free of charge and can be obtained from offices of the
3088 Lockout-Tagout Training Program Course Outline
3088 Lockout-Tagout Training Program Course Outline The following outline summarizes the major points of information presented in the course. The outline can be used to review the course before conducting
Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions
Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions Owner Name Title Signature Steve White Head of Network Control and Operations Date 16 February 2016 Authoriser Name
VoCALL - CFVCM/CFVCWM & CFVCX8. Fire Telephone & Disabled Refuge Network System. User Manual & Log Book
VoCALL - CFVCM/CFVCWM & CFVCX8 Fire Telephone & Disabled Refuge Network System User Manual & Log Book VoCALL Fire Telephone & Disabled Refuge Network System Introduction A VoCALL Emergency Voice Communications
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
The Electrical Safety Regulation (pre and post 1 January 2014)
The Electrical Safety Regulation (pre and post 1 January 2014) The following table provides an overview comparison between the Electrical Safety Regulation 2002 (the ESR 2002) current as at 1 July 2013
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
LOCK-OUT/TAG-OUT PROGRAM I. Purpose
LOCK-OUT/TAG-OUT PROGRAM I. Purpose This procedure establishes requirements for the lockout of energy isolating devices. It should be used to ensure that the machine or piece of equipment is isolated from
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
WEEKLY SAFETY MEETING All Euramax Subsidiaries LOCKOUT / TAGOUT. Safety Meeting Contents. Meeting Notice. Leaders Guide.
Safety Meeting Contents Meeting Notice Leaders Guide Employee Handout Employee Quiz Meeting Sign-In Sheet Employee Puzzle PRIOR TO THE WEEKLY MEETING: - Post the meeting notice by the timeclock - Read
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
Union County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
Electricity at work Safe working practices
Electricity at work Safe working practices The guidance covers the key elements to consider when devising safe working practices and is for people who carry out work on or near electrical equipment. It
CAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
LOCKOUT GUIDELINE. To ensure that a piece of equipment cannot be turned on, pressurized or switched on accidently while an employee is working on it.
Background LOCKOUT GUIDELINE Both Aspasa in its ISHE (Initiating Safety Health & Education) program and Sarma in its SHREQ (Safety, Health, Road Transport, Environment & Quality) program have seen that
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Control of Hazardous Energy (Lockout / Tagout)
WAUKESHA COUNTY TECHNICAL COLLEGE Control of Hazardous Energy (Lockout / Tagout) Release Date: March 26, 2012 Revision Date: March 26, 2012 Revision Level: 1 TABLE OF CONTENTS Purpose... 1 Scope... 1 Responsibilities...
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
Regulation IO-6.0: Electrical Safety Regulations
Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5
OPITO APPROVED STANDARD
OPITO APPROVED STANDARD Offshore Oil & Gas Industry Transformation Scheme Electrical Program Training Standard The content of this document was developed by OPITO. Guidance and advice on this training
Electrical Shore Connections / Cold Ironing
STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400
OSHA REGULATION: 29 CFR 90.7 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) DATE: 0/5/2008 DATE: /2/202 A. POLICY. This procedure follows requirements set forth in 29 CFR 90.7. 2. It is the policy
2013 VTech Printed in China 91-009656-000 US
Rechargeable Power Pack User s Manual 2013 VTech Printed in China 91-009656-000 US INTRODUCTION The Rechargeable Power Pack makes it easier than ever to keep the InnoTab 3 or InnoTab 3S charged and ready
Sense Components. Sense monitor. Antenna assembly. External mounting kit Current sensors. Download the Sense app. Go to sense.com/app.
Sense Components Sense monitor Antenna assembly External mounting kit Current sensors Download the Sense app. Go to sense.com/app Power cable Technical Specifications Sense is a home energy monitoring
ROLE PROFILE ELECTRICAL MAINTENANCE TECHNICIAN
ROLE PROFILE ELECTRICAL MAINTENANCE TECHNICIAN 2 Role Profile - Electrical Maintenance Electrical Maintenance Level 3 Technician Status Occupation OVERVIEW Electrical maintenance technicians are responsible
section 5 machine guarding and lockout
section machine guarding and lockout This section covers ways to physically protect people working in and around machinery. It includes information on: machinery guards lockout systems emergency stop confined
TECHNICAL SERVICES Guideline
1.0 INTRODUCTION 1.1 Purpose The purpose of this guideline is to describe the qualification requirements and assessment process of becoming a Competent Person (CP) and/or Authorised Person (AP) to work
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
Earthing Guidance Notes
Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head
Electrical safety of grid-connected solar installations in Western Australia December 2011
Electrical safety of grid-connected solar installations in Western Australia December 2011 Level 1, 303 Sevenoaks Street (cnr Grose Avenue) Cannington, Western Australia 6107 PO Box 135 Cannington WA 6987
Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits
Release: 2 UEENEEJ194A Solve problems in low voltage refrigeration circuits UEENEEJ194A Solve problems in low voltage refrigeration circuits Modification History Not Applicable Unit Descriptor Unit Descriptor
Electrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
Electrical safety rules
Electrical safety rules 2015 DISCLAIMER The material contained in this publication has been developed for the use of ActewAGL, its contractors and all others working on or near ActewAGL s electricity
INSPECTION AND TESTING OF EMERGENCY GENERATORS
INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
Energy Control Lockout/Tagout
Energy Control Lockout/Tagout Page Introduction Purpose. 2 Background. 2 Who s Covered... 3 Responsibilities. 3 Explanation of Key Terms. 4 How It Works General Lockout/Tagout Procedure. 5 General Lock/Tag
Guideline for Energy Efficient Electrical systems for building. Presentation by TERI
Guideline for Energy Efficient Electrical systems for building Presentation by TERI Objective of study The study highlights how BBMP can implement energy efficiency measures in building in co-ordination
Work in Substations - General
Work in Substations - General Summary: This document supports the Power System Safety Rules and its requirements assembled under Work in Substations General Category 3 and apply to all persons working
Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
CONTROL OF HAZARDOUS ENERGY (Lockout Tagout)
CONTROL OF HAZARDOUS ENERGY (Lockout Tagout) Many workplace accidents are caused by machinery that accidentally becomes activated while being serviced or maintained. This accidental activation is called
LOCK-OUT / TAG-OUT SAFETY TRAINING
LOCK-OUT / TAG-OUT SAFETY TRAINING Introduction Welcome to Lock-out Tag-out Training "So I m on the job one day, doing some repair on a cutting machine.replacing a guide on the table. Pretty routine everything
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
L O C K O U T / TA G O U T A D M I N I S T R AT I V E G U I D E
L O C K O U T / TA G O U T A D M I N I S T R AT I V E G U I D E 2009 Comprehensive Loss Management, Inc. This material is the property of CLMI Safety Training and may not be reproduced or distributed in
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
Design of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series
Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series Operating Instructions WARNING CONCERNING THE REMOVAL OF COVER: CAUTION: TO PREVENT THE RISK OF ELECTRIC
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the
FIREFIGHTER SAFETY. Stay safe during substation fires
FIREFIGHTER SAFETY Stay safe during substation fires FIREFIGHTERS AND SUBSTATIONS Electrical substations reduce the high voltages used to move electricity over long distances to the lower voltages that
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Five Nines and Infrared (IR) Testing at Data Centers
Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse
How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission
BWC Division of Safety and Hygiene
BWC Division of Safety and Hygiene A SAMPLE LOCKOUT/TAGOUT PROCEDURE A good Lockout/Tagout Procedure, at a minimum, should contain the following elements: 1. All maintenance personnel shall be provided
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
Current Monitoring Kit QUICK START GUIDE
Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
Guide to Gate Safety Legislation & the Machinery Directive. In Association with:
Guide to Gate Safety Legislation & the Machinery Directive In Association with: Tel: 0191 267 4922 [email protected] Tel: 0191 267 4922 Email: [email protected] Guide to Gate Safety
Occupational Health Program Safety Training Series. Lockout/Tagout Safety Awareness Training
Occupational Health Program Safety Training Series Lockout/Tagout Safety Awareness Training 1 Lock out/tag out Lock out: the placement of a lockout device (lock) on an energy isolating device in accordance
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
Current Monitoring Kit
Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added
About the HotWire 7900 10-Slot Standalone Shelf
TM HotWire Model 7900 10-Slot Standalone Shelf Installation Instructions Document Number 7900-A2-GN10-10 About the HotWire 7900 10-Slot Standalone Shelf The HotWire 7900 10-Slot Standalone Shelf is designed
CURRENT TRANSFORMERS INSTALLATION GUIDE
CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright
Lockout - Tagout Program
Created by: Nora Velazquez Date: 02/13/03 Approved by: Nora Velazquez Supersedes: New Lockout - Tagout Program 3.1 Purpose 3.1.1 The safe control of hazardous energy is the purpose of the Lockout- Tagout
ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas
ENERGY NETWORKS ASSOCIATION Electricity Industry EMF Measurement Protocol for High Field Areas Contents 1 Introduction 1.1 Background 1.2 High Field Areas 2 High Field Area - Generation Businesses 2.1
Electrical test equipment for use on low voltage electrical systems
Electrical test equipment for use on low voltage electrical systems Guidance Note GS38 (Fourth edition) This general series guidance note is aimed at people (including electricians, electrical contractors,
ELECTRICAL SAFETY Information Bulletin
ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to