1 CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety

2 Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical installing work carried out in Western Australia complies with the relevant standards, including Australian/New Zealand Standard AS/NZS 3000 (known as the Wiring Rules) and the WA Electrical Requirements. The application of minimum electrical requirements and Standards is essential for the safety of persons, livestock and property. A clear understanding of these requirements is essential for those involved with electrical installing work carried out in Western Australia. All completed electrical work must be checked and tested by a licensed electrician before the electrical contractor certifies the work to the relevant supply authority. This booklet has been produced as a guide to meet the checking and testing requirements for electrical installing work, as specified in the Wiring Rules. Whilst the details are focussed on domestic electrical installations, the principles apply to all electrical installing work. The testing methods in this booklet are not exclusive. Other test methods may be used provided that they meet the minimum requirements of the Wiring Rules. More detailed testing information is contained in the Australian/New Zealand Standard AS/NZS 3017 Electrical installations - Testing and inspection guidelines.

3

4 Table of Contents Checking, Testing and Certification of Electrical Installing Work 1 Installation Test Certificate 2 Checking and Testing 4 Checking and Testing Procedure 5 1. Visual Inspection 5 2. Earth Resistance and Continuity Tests 5 Test Equipment 6 Test Procedure 7 3. Insulation Resistance Test 8 Test Equipment 8 Test Procedure 8 4. Polarity/Functional Test 10 Test Equipment 10 Test Procedure Correct Circuit Connections Fault-loop Impedance Test 11 Test Equipment 11 Test Procedure Verification of RCD 12 Testing Alterations and Additions 12 Test Equipment 13 Table 1 - Maximum resistance values of final subcircuit 14 protective earthing conductor Table 2 - Comparison of voltage drop and fault-loop 15 impedance to determine circuit maximum distance. Further Information 16 Notes 17

5 IV CHECKING AND TESTING ELECTRICAL INSTALLING WORK

6 Checking, Testing and Certification of Electrical Installing Work All completed electrical installing work must be checked and tested to confirm that it complies with the Wiring Rules and is safe for connection to the electricity supply. The required steps to comply with the current regulatory requirements are as follows: 1. When the electrical installing work has been completed, a licensed electrician (which may be the contractor or an employee) is required to carry out checks and tests of the installation, to ensure the electrical work meets the requirements of the Wiring Rules. The checking and testing should be carried out in accordance with a formalised checking and testing procedure. 2. Once these checks and tests have been completed, the electrician confirms on the relevant section of the Notice of Completion or Notice of Completion- Minor Work, that the checking and testing has been carried out. 3. For electrical installing work that requires the supply authority to attend (eg. for electricity supply connection or alteration to the supply service apparatus), the electrician then completes an Installation Test Certificate and fixes it inside the meter enclosure of the installation. 4. Then, in the usual manner, the electrical contractor (or nominee) completes the Notice of Completion, thereby certifying the work, and submits the Notice to the supply authority. 5. When the Notice of Completion is received, the supply authority will determine if an inspection of the installing work will be carried out, to ensure that the standards of electrical safety of the installation are being maintained. The supply authority will also arrange for the connection of the electricity supply if necessary. Notes 1. Minor work, ie. alterations and additions to existing electrical installations, is also subject to a similar system except that the work is connected to the electricity supply by the electrician. 2. Western Power s Contractor Connect Scheme permits accredited electrical contractors and authorised electrical workers to connect the electricity supply to the installation and to then submit the Notice of Completion following connection. 1

7 Installation Test Certificate When a Notice of Completion is to be submitted for completed electrical installing work that may require the supply authority to attend (eg. new connection or upgrade of supply), the electrician carrying out the checking and testing must complete an Installation Test Certificate. An Installation Test Certificate is an adhesive label (included in books of Preliminary Notices/Notices of Completion and also available from supply authorities) that must be filled in by the electrician who performed the checking and testing of the completed electrical installing work. An Installation Test Certificate is to be fixed by the electrician to the inside of the meter enclosure to indicate to the supply authority and the customer that the installation is completed, has been checked and tested and is safe to be connected to the electricity supply. The electrician is requested to record the following key installation test results and the underground consumer s mains cable route on a self adhesive label which is also to be placed inside the meter enclosure: main earth conductor resistance; either the earth continuity or fault-loop impedance values for each sub circuit; and insulation resistance values for each sub circuit. The information will benefit subsequent electrical work and inspection, as well as assist in preventing electric shocks and accidents. 2

8 INSTALLATION TEST CERTIFICATE Installation Address: I confirm that I have carried out the checks and tests of this electrical installation, as required by Electricity (Licensing) Regulations Signature of A Grade Electrical mechanic Date E.W. Licence No This work has been carried out for and on behalf of: Electrical contractor s name and licence No. Note 1. The Electrical Mechanic is responsible for the issue of this Test Certificate. 2. This Test Certificate is to be fixed to the inside of the meter enclosure. DON T MEDDLE WITH ELECTRICITY - ALWAYS USE A LICENSED ELECTRICAL CONTRACTOR 3

9 Checking and Testing On completion of the electrical work and before the electricity supply is connected and energised, the electrical contractor is responsible to ensure that: the electrical work has been carried out in accordance with the Electricity (Licensing) Regulations 1991; and the installation has been checked and tested and is safe for connection to the electricity supply. To achieve this, the following minimum checks and tests should be carried out by the electrician: 1. Visual Inspection - should be carried out whilst referring to a plan (to ensure a systematic check to pick up any omissions and to verify that the work complies with the requirements of the applicable standards). 2. Earth Resistance and Continuity Tests - this test is to include the main earthing conductor, protective earth conductor and bonding conductor. 3. Insulation Resistance Test - this test is necessary to ensure that the insulation resistance between live parts/conductors and earth is adequate. 4. Polarity Test - used to ensure correct connection of active, neutral and earthing conductors. 5. Correct circuit connections - this test checks earthing conductors do not carry current during normal operation and no short circuit exists. 6. Fault Loop Impedance - measures the fault loop impedance of each circuit to verify the protective device will operate. 7. Verification of RCD (residual current device) operation - testing of RCDs is carried out to ensure that the RCD operates. 4

10 Checking and Testing Procedure The following procedure will meet the key checking and testing requirements. Ensure that test results are recorded carefully. Other testing procedures may be used, provided that they meet the minimum requirements of the Wiring Rules. It is also recommended that the tests be carried out whilst there is no electricity supply connected (except for the Fault Loop Impedance verification or the RCD operation test) to the installation, or, in the case of alterations to an existing installation, that the circuits to be tested have been isolated from the electricity supply and have been securely tagged and where possible padlocked. 1. Visual Inspection A visual inspection is carried out to ensure that all work has been correctly completed, by checking that: all cables and equipment have been correctly installed and terminated, and the installation complies with the relevant parts of the Wiring Rules and the WA Electrical Requirements. 2. Earth Resistance and Continuity Tests Earth resistance tests are required to confirm the installed earthing system will cause circuit protective devices to operate and maintain cable integrity if there is a fault between live parts and exposed conductive parts. Earthing System Impedance The resistance from any point of the electrical installation required to be earthed, to the point where the main earthing conductor is connected to the neutral conductor (MEN connection) of the supply system, shall be low enough to permit the passage of current necessary to operate the circuit protective devices. To confirm this value (which is dependent upon the type and rating of the protective device and the fault-loop impedance of the associated conductors) requires the following test to be performed: Test 1: Obtain the resistance value of the protective earthing conductor using a quality ohm meter (see next page for procedure) and compare this value with the maximum allowable resistance as tabulated in Table 1, page 14 of this booklet. 5

11 Or, where the electricity supply IS connected: Test 2: Obtain the fault-loop impedance of each sub circuit using a quality faultloop impedance meter (refer to manufacturer s instructions and page 11 of this booklet for procedure). Compare the measured fault-loop impedance value with the maximum value provided at Appendix B, Table B4.1 of the Wiring Rules. Notes: 1 If the application of a fault-loop impedance test onto an RCD protected sub circuit results in the RCD operating, then: the earth resistance and continuity test requirements are considered to be satisfied; and the fault-loop impedance value need not be considered further. 2 If the value measured is GREATER than the allowable maximum, then the following steps must be performed: Test 2.1 Check the MEN connection, active, neutral and earth conductor/equipment connections are all solidly made. Repeat the fault-loop impedance test 2, above. If the fault-loop impedance values exceed the requirements of Table B4.1, then perform Test 2.2 Test 2.2 Perform the earth continuity measurement, Test 1 and confirm results. Repeat the fault-loop impedance Test 2, above. If the fault-loop impedance values do not satisfy the requirements of Table B4.1 then you must contact the supply authority advising them of the discrepancy. Main Earthing Conductor The resistance from the earthing electrode to the point where the main earthing conductor is connected to the neutral conductor of the supply system shall not exceed 0.5 ohms. Test Equipment A multimeter set to ohms. Insulated copper conductor of suitable length (long lead). 6

12 Test Procedure Preparation: 1. Ensure that the electricity supply has been disconnected. 2. Connect an insulated copper conductor of suitable length (long lead) to one terminal of the ohm meter. 3. Connect a standard length test lead to the other terminal of the ohm meter (short lead). 4. Connect the two leads together, and zero the multimeter or, if this is not possible, record the resistance of the test leads. 5. Disconnect the water pipe equipotential bonding conductor and the water heater earthing conductor (if applicable). Care must be taken that there are no parallel earth paths when conducting this test, ie. the earthing system must not be connected to either the water or gas pipes. 6. Disconnect the MEN link from the main neutral link and connect it to the long lead (ie. long lead now connected to the earth bar). A: Main Earthing Conductor Connect the short lead to the earth electrode and measure the earth resistance of the main earthing conductor. The resistance shall not exceed 0.5 ohms for the main earthing conductor. B: Earth Continuity Test Using the long lead and zeroed multimeter, measure, for each circuit, the earth conductor resistance from the circuit extremity to the switchboard. Confirm the measured values are LESS THAN those values as provided at Table 1, page 14 of this booklet for each sub circuit. This test is applicable to all circuits, including socket outlet circuits, lighting circuits and fixed equipment (eg. water heater supply) circuits. 7. Re-connect the MEN link to the main neutral link. 8. Re-connect the water pipe equipotential bonding conductor. 7

13 3. Insulation Resistance Test An insulation resistance test is performed to ensure that the resistance between all live conductors and earth, or as the case maybe, all live parts and earth, is adequate to prevent electric shock hazards, fire hazards and equipment damage. It is a requirement of Clause of the Wiring Rules that the insulation resistance between all live conductors (including the neutral) connected together, and earth, measured with all protective devices in circuit and all switches on, is not less than 1 Megohm (see Note below). This applies to the complete installation and all parts of the installation. This does not preclude the use of appliances incorporating heating elements provided that, when tested with all elements in circuit, the insulation resistance between live parts and the earthing terminal or earthing contact of the appliance is not less than 0.01 Megohm (10,000 ohms). Note: Whilst the minimum reading is 1 Megohm, the ideal reading is infinity. This indicates a sound installation. Test Equipment Where the supply voltage does not exceed 250 volts between conductors and earth, a 500 volt insulation tester should be used to perform this test. Test Procedure 1. Ensure that all protective devices are in circuit and that all switches are on. If there are two way lighting circuits in the installation, tests must be carried out with the two way switches in all positions, so all circuit conductors are tested. 2. Set the insulation tester (eg. Megger) to Megohms. 3. Connect one lead of the insulation tester to the main earthing bar (MEN Link disconnected) and the other lead to the actives and neutrals connected together. Do not test between actives and neutrals. 4. Measure the insulation resistance of the total installation (including the consumers mains). If the insulation resistance is 1 Megohm or more - re-connect the MEN Link and return the installation to normal. 8

14 If the insulation resistance is less than 1 Megohm - test all circuits individually, starting with circuits supplying appliances incorporating heating elements. Where a circuit is less than 1 Megohm, disconnect the appliance or appliances. Then test the circuit and appliance (separately) to ensure that the insulation resistance of both the circuit and the appliance complies with the following: not containing a heating element - is not less than 1 Megohm, or containing a heating element - is not less than 0.01 Megohm Note: Where the insulation resistance of an appliance containing heating elements is found to be less than 0.01 Megohm and the defect cannot be rectified at the time of checking and testing, the electrical contractor must make arrangements for correction of the defect prior to submission of the Notice of Completion. Alternatively, the following procedure may be used: a) Isolate the defective circuit, including the neutral conductor, by disconnecting at the appropriate switchboard. b) Attach an out of service tag to the circuit protection device, advising that the circuit has been disconnected due to low insulation resistance. c) Check that the earth conductor has been reconnected at the MEN point. d) Then submit the Notice of Completion. Ensure that all circuits and the MEN connection are re-connected when the testing is complete. 9

15 4. Polarity Test Polarity tests are carried out to ensure the correct connection of active, neutral and earth conductors to electrical equipment and to ensure that switches are not installed in neutral conductors. Clause Polarity of the Wiring Rules specifies the testing requirements for this mandatory test. Test Equipment To carry out these tests, a continuity tester such as a multimeter (set to ohms) should be used. Test Procedure To ensure that the installation circuits/equipment will function as intended, it is necessary that the following tests be performed: Isolate the active conductors by turning the main switch OFF and tagging. Confirm consumer and sub mains cables/connections by simply testing from the point of supply or distribution board to the main switchboard using an ohm meter and long test loads. Test result 0 Ω. Confirm active conductor switching by using an ohm meter with the long lead connected to the active conductor at the switchboard and the short lead connected to the switch terminals (one at a time) in the following manner: i) Switch ON 0 Ω for both terminals ii) Switch OFF 0 Ω for one terminal and infinity for the other terminal With the MEN link in place, confirm the polarity of socket outlets using a 10Ω resistor and an ohm meter. Connect the 10Ω resistor between the circuit active conductor and the neutral bar then at each socket outlet connect one lead of the multimeter to the earth terminal and the second lead to the active terminal. Test the resistance value for: i) socket outlet switch OFF infinity ii) socket outlet switch ON 10Ω. 10

16 5. Correct Circuit Connections These tests are required to ensure the following: 1. that protective earthing conductors do not carry current; 2. to prove there are no short circuits within the installation; and 3. for the circuit continuity test to prove each circuit for electrical continuity and that all switches operate in the active conductors. 6. Fault-loop Impedance Test This test is carried out to confirm the fault-loop impedance value of each circuit will be low enough to ensure the operation of the protective device during a fault. Test Equipment To perform the fault-loop impedance test, a fault-loop impedance meter is required. Test Procedure Energise all circuits Using the fault-loop impedance meter, proceed to the equipment to be tested and measure the earth-loop impedance at this point. Repeat for other items on the circuit. The measured value must be less than the maximum values as tabulated at Table B4.1 of the Wiring Rules. If an RCD operates during the test, the test result can be considered satisfactory. 11

17 7. Verification of RCD Operation This is normally achieved by operation of the integral test device (typically test button on the RCD) to confirm: 1. the RCD is functioning correctly; and 2. the tripping device mechanisms are operating. Warning: Operation of the integral test device does not provide a means of checking: continuity of the main earthing conductor or the associated circuit protective earthing conductor; or any earth electrode or other means of earthing or the associated electrical installation earthing. Testing Alterations and Additions When alterations are carried out to an existing electrical installation, it is essential that the electrician tests the work to ensure compliance with the relevant standards and specifications. The tests described in this booklet must also be carried out on alterations and additions to ensure the electrical installing work is safe to remain connected to the electrical installation. The majority of tests described in this booklet are designed to be carried out without power being connected. When performing these tests, make sure that electricity supplies are disconnected where necessary and that the appropriate isolation and tagging has been carried out. A Notice of Completion form must be submitted to the supply authority to certify this type of work. 12

18 Test Equipment Before performing any tests, ensure that the test equipment is correctly set, is functional and is in good condition, particularly the test leads. Remember, when testing: check that the test equipment is operating correctly perform the required tests re-check the test equipment to confirm that it still operates correctly. Some types of test equipment (eg. multimeters) are fitted with fuse protection. Ensure that at all times only the correct type and rated fuse is used. This is for your protection. Electrical test equipment is a very important part of an electrician s tools. Test instruments should be tested at intervals not exceeding one year and records kept to verify this. 13

19 Table 1 Maximum resistance values of final sub circuit protective earthing conductors Protective Circuit - breakers Type B Type C Type D Fuses Device Earthing Disconnection times Rating Conductor Size 0.4sec 0.4sec A mm 2 Maximum final subcircuit earth conductor resistance Ω

20 Table 2 Comparison of voltage drop and fault-loop impedance to determine circuit maximum distance This table details the single phase voltage drop for a combination of conductor size, maximum demand current and distance. It also displays the maximum circuit length for a Type C circuit breaker (as normally used in most installations) to ensure the operation of the circuit breaker during an earth fault. You will notice that compliance for voltage drop is the predominant requirement compared to the fault-loop distance for the given circuit breaker type. Conductor Size Protective Device Rating Maximum Demand Distance 20m 30m 40m 60m 80m Voltage Drop Maximum Distance m For Voltage Drop #2 For Type C Circuit Breaker #3 mm 2 A A #1 V (11.5V = maximum) * * * * * * * Denotes limiting parameter * * Notes: #1: Maximum demand determined using (a) full load, and (b) half the rating of the protective device assuming distributed load. Refer to Wiring Rules Clause #2: Voltage drop determined using 5% = 11.5V maximum allowable. #3: Distances obtained from Wiring Rules table B

21 Further Information For further information on testing electrical installing work, please contact the Electrical Inspector at the relevant supply authority, as listed in the manual WA Electrical Requirements. For further information, please contact: ENERGY SAFETY 20 Southport Street WEST LEEDERVILLE WA 6007 Telephone: Facsimile: Website: 16

22 Department of Consumer and Employment Protection Issued by Energy Safety 20 Southport Street West Leederville WA 6007 Telephone: (08) Facsimile: (08) Website: ESWA E

S.D.F Electrical Pty Ltd QLD. LICENSE NO ABN PROCEDURE

S.D.F Electrical Pty Ltd QLD. LICENSE NO ABN PROCEDURE OBJECTIVE To detail the electrical tests that shall be completed before and after electrical installation work is connected to supply. This testing procedure can be used for the testing of new installations

More information

Trouble-shoot and repair faults in low voltage electrical apparatus and circuits

Trouble-shoot and repair faults in low voltage electrical apparatus and circuits UEENEEG108A Trouble-shoot and repair faults in low voltage electrical apparatus and circuits AS3000:2007 & AS3017:2007 Summary MANUFACTURING AND ENGINEERING DIVISI M & E UEENEEG108A TESTING Before any

More information

16th Edition. a guide to 16th Edition Testing. The Requirements. Continuity of protective conductors

16th Edition. a guide to 16th Edition Testing. The Requirements. Continuity of protective conductors The Requirements Regulation Groups 713-02 to 713-12 set out the requirements for testing new installations and should be performed in the order shown. a guide to 16th Edition Testing Only relevant tests

More information

Contractor Connect Scheme Electrical Contractor and Worker Handbook

Contractor Connect Scheme Electrical Contractor and Worker Handbook Contractor Connect Scheme Electrical Contractor and Worker Handbook January 2016 Document release information Document number 13553681 Document title Revision status Contractor Connect Scheme handbook

More information

Service Connection Test Multimeter Guide

Service Connection Test Multimeter Guide Service Connection Test Multimeter Guide Meters in Multiple Master Meter Panels Form: Service Connection Test Multimeter Meters in Multiple Master Meter Panels (DM# 11484590) This Revision: 0 May 2016

More information

ELECTRICAL CONTRACTOR NEWS AND UPDATES

ELECTRICAL CONTRACTOR NEWS AND UPDATES ELECTRICAL CONTRACTOR NEWS AND UPDATES NEWSLETTER No. 13 JULY 2011 This newsletter is produced by Bruce Blacker of Insight Electrical Consulting & Training Pty Ltd to inform and aid the electrical contracting

More information

Guidance Notes. Installation & Inspection of Fuel Cells May What is a fuel cell? Page 1

Guidance Notes. Installation & Inspection of Fuel Cells May What is a fuel cell? Page 1 Guidance Notes Installation & Inspection of Fuel Cells May 2011 This document has been prepared by Energy Safe Victoria to provide guidance for electrical contractors and licensed electrical inspectors

More information

Electrical and Lighting Public Buildings Environmental Health Guide

Electrical and Lighting Public Buildings Environmental Health Guide Electrical Installations Electrical and Lighting Public Buildings Environmental Health Guide All electrical installations must comply with the supply authority or Office of Energy requirements, AS 3000,

More information

DETAILS AND EXTENT OF THE INSTALLATION Tuin, Ashwelthorpe Industrial Estate, Norwich, Norfolk, NR16 1ER. Earth electrode resistance:

DETAILS AND EXTENT OF THE INSTALLATION Tuin, Ashwelthorpe Industrial Estate, Norwich, Norfolk, NR16 1ER. Earth electrode resistance: DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with British Standard BS 7671 - Requirements for Electrical Installations 1 Client: Address: DETAILS OF THE CLIENT Tuin LTD NR16 1ER Certificate

More information

MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing

MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing Release: 1 MEM10019 Select circuit protection devices by type and rating, fit to switchboards and

More information

chapter8 Testing and commissioning Unit 2 outcome 2

chapter8 Testing and commissioning Unit 2 outcome 2 Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.

More information

ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations

ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with British Standard BS 7671 Requirements for Electrical Installations Certificate Reference 0039291 1. DETAILS OF THE CLIENT Client 2. DETAILS

More information

Installation Requirements

Installation Requirements Installation Requirements Installation and inspection of Grid-connected PV systems July 2011 (no battery storage) This document has been prepared by Energy Safe Victoria to provide guidance for electrical

More information

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks

More information

Approved By: Chief Executive Officer: Ron Josias Senior Manager: Mpho Phaloane Author

Approved By: Chief Executive Officer: Ron Josias Senior Manager: Mpho Phaloane Author CALIBRATION OF INSTALLATION AND APPLIANCE TESTERS Approved By: Chief Executive Officer: Ron Josias Senior Manager: Mpho Phaloane Author Specialist Technical Committee Members: Electrical DCLF Date of Approval:

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

ELECTRICAL EARTHING RISK MANAGEMENT STRATEGIES FOR THE WATER INDUSTRY. John Werda. Sydney Water Corporation

ELECTRICAL EARTHING RISK MANAGEMENT STRATEGIES FOR THE WATER INDUSTRY. John Werda. Sydney Water Corporation ELECTRICAL EARTHING RISK MANAGEMENT STRATEGIES FOR THE WATER INDUSTRY Paper Presented by: John Werda Authors: John Werda, Business Relationship Mgr, Water Services Division, Janssen Chan, Manager Policy,

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

A Guide to 17th Edition Testing

A Guide to 17th Edition Testing Seaward, Bracken Hill, South West Industrial Estate, Peterlee, County Durham, SR8 2SW United Kingdom Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227 Email: sales@seaward.co.uk Web: www.seaward.co.uk

More information

Candidates need to obtain 75% or more to pass this assessment. Reading Time: 15 Minutes Working Time: 2 hours

Candidates need to obtain 75% or more to pass this assessment. Reading Time: 15 Minutes Working Time: 2 hours Suite 3 Level 22185 187 Boundary Boundary Rd Rd North Melbourne VIC 3051 Phone VIC 3051 (03) 9654 1299 Phone (03) 9654 1299 Facsimile (03) 9329 0014 Facsimile (03) 9329 0014 www.epicitb.com Surname: Given

More information

Electrical safety of grid-connected solar installations in Western Australia December 2011

Electrical safety of grid-connected solar installations in Western Australia December 2011 Electrical safety of grid-connected solar installations in Western Australia December 2011 Level 1, 303 Sevenoaks Street (cnr Grose Avenue) Cannington, Western Australia 6107 PO Box 135 Cannington WA 6987

More information

Continuity of Protective Conductors

Continuity of Protective Conductors Continuity of Protective Conductors Electrical Quals 2007 1 Introduction This test is of great importance and arguably the most important of them all for many reasons, despite of this fact at times shortcuts

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

ELECTRICAL SYSTEMS A.

ELECTRICAL SYSTEMS A. I=Inspected NI=Not Inspected NP=Not Present R=Not Functioning or In Need of Repair I NI NP R Inspection Item II. ELECTRICAL SYSTEMS A. Service Entrance and Panels Comments: Items noted during the visual

More information

PROTECTIVE MULTIPLE EARTHING AND THE RADIO AMATEUR

PROTECTIVE MULTIPLE EARTHING AND THE RADIO AMATEUR PROTECTIVE MULTIPLE EARTHING AND THE RADIO AMATEUR RSGB EMC Committee Leaflet EMC 07 Iss 2 1 Disclaimer This leaflet is intended for members of the RSGB who have passed the Radio Amateur s Examination

More information

INSTALLATION REQUIREMENTS

INSTALLATION REQUIREMENTS INSTALLATION REQUIREMENTS INSTALLATION AND INSPECTION OF GRID-CONNECTED PV SYSTEMS APRIL 2015 (NO BATTERY STORAGE) This document has been prepared by Energy Safe Victoria (ESV) to provide guidance for

More information

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

PROTECTION AGAINST ELECTRIC SHOCK by John Ware 16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created

More information

Trade of Electrician. Earthing and Bonding

Trade of Electrician. Earthing and Bonding Trade of Electrician Standards Based Apprenticeship Earthing and Bonding Phase 2 Module No. 2.2 Unit No. 2.2.6. COURSE NOTES Created by Eugene Trindles Cork TC Revision 1 April 2000 by Eugene Trindles

More information

ELECTRICITY: RESIDUAL CURRENT DEVICES

ELECTRICITY: RESIDUAL CURRENT DEVICES WORKSAFE WESTERN AUSTRALIA COMMISSION ELECTRICITY: RESIDUAL CURRENT DEVICES Guidance Note Occupational Safety and Health Regulations 1996 Regulation 3.60 Protection against earth leakage current when portable

More information

ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT AT PUBLIC EVENTS

ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT AT PUBLIC EVENTS ELECTRICAL INSTALLATIONS AND ELECTRICAL EQUIPMENT AT PUBLIC EVENTS GUIDELINES Scope This document aims to provide guidance on key electrical safety and compliance issues for electricity supplies to and

More information

Introduction. What Aspects of the Electrical Installation are covered? Legislation. an employer shall ensure that

Introduction. What Aspects of the Electrical Installation are covered? Legislation. an employer shall ensure that Guidance-Note on Periodic Inspection and Testing of Electrical Installations required by the 2007 Safety Health and Welfare at Work (General Application) Regulations Introduction. Electrical installations,

More information

FAQ ON EARTHING STANDARDS 27/07/2012

FAQ ON EARTHING STANDARDS 27/07/2012 FAQ ON EARTHING STANDARDS 27/07/2012 1) What minimum readings do we have to get for: a) Standalone RMU maximum 10 ohms per electrode where 2 electrodes exist per RMU. b) Standalone TX (up to 1,000kVA)

More information

Guidance Notes for. The Safe Isolation of Electricity Source at Work

Guidance Notes for. The Safe Isolation of Electricity Source at Work Guidance Notes for The Safe Isolation of Electricity Source at Work Occupational Safety and Health Branch Labour Department Occupational Safety & Health Council The Guidance Notes is prepared by the Occupational

More information

The Electrical Contractor Safety Program Guide

The Electrical Contractor Safety Program Guide The Electrical Contractor Safety Program Guide September 2013 Electrical Hazard Warning Sign Disclaimer Whilst this guide endeavors to provide general information on work health and safety issues relating

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

Corporate Safety Procedure Low Voltage Electrical Testing for De-Energisation and Re-Energisation. Table of Contents

Corporate Safety Procedure Low Voltage Electrical Testing for De-Energisation and Re-Energisation. Table of Contents Table of Contents 1. Purpose and Scope... 2 2. References... 2 3. Definitions and Abbreviations... 2 3.1 Authorised Person... 2 3.2 Instructed Person... 2 3.3 Person in Control of electrical equipment...

More information

Protection and Safety

Protection and Safety MECH3005 Building Services http://www.hku.hk/bse/mech3005/ Electrical Supply Protection and Safety Dr. Sam C M Hui Department of Mechanical Engineering The University of Hong Kong E-mail: cmhui@hku.hk

More information

Portable Appliance Testing (PAT)

Portable Appliance Testing (PAT) Policy Portable Appliance Testing (PAT) Contents Introduction 2 Summary of duties 2 Definition of portable electrical equipment 2 Responsibilities 2 Estates Director 2 Estates Supervisor 3 Testing personnel

More information

Guideline for Adoption of CMEN Earthing System

Guideline for Adoption of CMEN Earthing System PURPOSE AND SCOPE The purpose of this document is to provide for adoption of CMEN earthing system in the Ergon Energy distribution network. This document provides an interim guideline / methodology for

More information

Electrical practices: construction and demolition sites

Electrical practices: construction and demolition sites FACT SHEET Electrical practices: construction and demolition sites This fact sheet provides an overview of the requirements shown in AS/NZS 3012: 2010 Electrical installations construction and demolition

More information

Electrotechnology. Total marks 80. Section I Pages marks Attempt Questions 1 15 Allow about 20 minutes for this section

Electrotechnology. Total marks 80. Section I Pages marks Attempt Questions 1 15 Allow about 20 minutes for this section 2011 HIGHER SCHOOL CERTIFICATE EXAMINATION Electrotechnology Total marks 80 Section I Pages 2 4 General Instructions Reading time 5 minutes Working time 2 hours Write using black pen or blue pen Black

More information

General technical information

General technical information Circuit breakers 2 Ingress protection 4 Nuisance / unwanted tripping 5 Circuit breakers Prospective Fault Current Calculation of Prospective Short Circuit Current Several excellent proprietary computer

More information

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured. SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation

More information

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational

More information

Customer Installation Safety Plan. March 2015

Customer Installation Safety Plan. March 2015 Customer Installation Safety Plan March 2015 Document History Issue No. Date Approved By Summary of Changes 1 June 2014 Chief Engineer Updated and revised in line with requirement for biennial review under

More information

Polarity. Electrical Quals 2007 1

Polarity. Electrical Quals 2007 1 Polarity Electrical Quals 2007 1 Polarity testing Introduction The polarity test is the 8th test in the sequence. Some people will think of it as the 4th test, (which to a certain extent they are correct).

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

4.3 Principals and managers should ensure that only electrical equipment with a current inspection/test tag is used in DET workplaces.

4.3 Principals and managers should ensure that only electrical equipment with a current inspection/test tag is used in DET workplaces. POLICY TITLE: ELECTRICAL EQUIPMENT POLICY AND SAFETY PROCEDURES PUBLISHED: 2006 IDENTIFIER: ESS200610 POLICY OWNER: LEGISLATION: Director, Finance and Corporate Support Australian Standard AS 3760 2003

More information

The Industry Standard Guide to Electrical Earth Monitoring

The Industry Standard Guide to Electrical Earth Monitoring ide Systems td, Unit 3 Swaffield ark, Hyssop Close, Cannock, Staffs. WS11 7FU SYSTMS RTA OI The Industry Standard Guide to lectrical arth Monitoring Guide 0 Introduction The possibility of damage to, disconnection

More information

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Continuity of Protective Conductors

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Continuity of Protective Conductors C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Continuity of Protective Conductors 1 Outcomes of this Session State the requirements which need

More information

REVIEW QUESTIONS. A6 Test Preparation

REVIEW QUESTIONS. A6 Test Preparation A6 Test Preparation Note: The lessons, exercises and tests in this manual are great preparation for taking the ASE A6 (electrical) certification test. However, that s only for the topics we ve covered.

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

Pre-Apprenticeship Training Apprentice Training Post-Trade Training Short Refresher Courses

Pre-Apprenticeship Training Apprentice Training Post-Trade Training Short Refresher Courses The College of Electrical Training (CET) is the major private training provider for the Western Australian electrical & telecommunications industries. Course Delivery Profile Pre-Apprenticeship Training

More information

GUIDE TO THE AM2 EXAM

GUIDE TO THE AM2 EXAM AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test

More information

AS/NZS 3000:2007 Amendment 2

AS/NZS 3000:2007 Amendment 2 AS/NZS 3000:2007 Amendment 2 Published 14 December 2012 Under Victorian legislation the day a revised standard is published it becomes the requirement. The aim of this document is to highlight the important

More information

THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE

THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE December 2013 Electrical Hazard Warning Sign Disclaimer Whilst this guide endeavours to provide general information on work health and safety issues relating

More information

11. Assessment of service 12. S-phase supply 13. Water heaters NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS

11. Assessment of service 12. S-phase supply 13. Water heaters NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS By-law PART I - PRELIMINARY 1. Citation 2. Repeal 3. Interpretation 4. Qualifications of inspector PART II - INSPECTORS PART III

More information

Electrical safety code of practice 2013. Managing electrical risks in the workplace

Electrical safety code of practice 2013. Managing electrical risks in the workplace Electrical safety code of practice 2013 Managing electrical risks in the workplace This Queensland code of practice has been approved by the Attorney-General and Minister for Justice and commences on 1

More information

NZQA registered unit standard 15848 version 6 Page 1 of 5. Demonstrate and apply knowledge of safeguards for use with portable electrical appliances

NZQA registered unit standard 15848 version 6 Page 1 of 5. Demonstrate and apply knowledge of safeguards for use with portable electrical appliances Page 1 of 5 Title Demonstrate and apply knowledge of safeguards for use with portable electrical appliances Level 2 Credits 3 Purpose This unit standard covers knowledge of safeguards used in conjunction

More information

Electrical safety and you

Electrical safety and you Electrical safety and you A brief guide Introduction Electricity can kill or severely injure people and cause damage to property. Every year many accidents at work involving electric shock or burns are

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Time to lay down the law for portable appliance testing

Time to lay down the law for portable appliance testing Time to lay down the law for portable appliance testing By Joules Newell MInstSCE Note; No recommendations or advice within these notes may contravene or supersede any legislative requirements, neither

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

NORTHERN IRELAND SAFETY GROUP

NORTHERN IRELAND SAFETY GROUP NORTHERN IRELAND SAFETY GROUP STATUTORY ELECTRICAL INSPECTIONS 26/08/2010 1 Introduction Paul Kane Commercial Operations Manager Contract Services NI Limited We welcome the opportunity to provide you with

More information

Procedure: Electrical safety management

Procedure: Electrical safety management Procedure: Electrical safety management Purpose The University has developed this electrical safety procedure to ensure the safe and reliable supply and use of electricity within the University and to

More information

Preventative Maintenance & Statutory Testing

Preventative Maintenance & Statutory Testing Preventative Maintenance & Statutory Testing Emergency Evacuation Lighting - Inspection and Maintenance It is an Occupational Health and Safety Act requirement that employers have a legal duty of care

More information

Code of Practice for the Inspection and Testing of Portable Electrical Equipment (PAT)

Code of Practice for the Inspection and Testing of Portable Electrical Equipment (PAT) Code of Practice for the Inspection and Testing of Portable Electrical Equipment (PAT) Reviews and Revisions Action Date Reason Reviewer Updated details of External PAT Contractor Updated to reflect outsourced

More information

Candidate Self-Assessment Checklist

Candidate Self-Assessment Checklist General Information This is a compulsory document which must be completed by all candidates due to undertake the AM2 Assessment of Occupational Competence and provided to the assessment centre prior to

More information

MANAGING ELECTRICAL RISKS IN THE WORKPLACE

MANAGING ELECTRICAL RISKS IN THE WORKPLACE MANAGING ELECTRICAL RISKS IN THE WORKPLACE Code of Practice MARCH 2015 Safe Work Australia is an Australian Government statutory agency established in 2009. Safe Work Australia consists of representatives

More information

Welcome to the Electrical and Electronics Industry Module.

Welcome to the Electrical and Electronics Industry Module. Welcome to the safe@work Electrical and Electronics Industry Module. Have you read the General Module, completed the test and printed your safe@work General Award of Attainment? The Electrical and Electronics

More information

VICTOR TEST INSTRUMENT APPROVED PROCEDURE

VICTOR TEST INSTRUMENT APPROVED PROCEDURE 1. SCOPE This document details the Approved procedure for the use of the VICTOR test instrument on 11/6.6kV circuits via the spouts of metal-enclosed withdrawable switchgear that are not Live. This can

More information

Residual Current Devices. Switching on to Safety

Residual Current Devices. Switching on to Safety Residual Current Devices Switching on to Safety Contents What is a Residual Current Device? 2 Types of RCDs 3 Switchboard RCDs 3 1 Residual Current Devices Socket outlet RCDs 4 Portable RCDs 4 Changes

More information

FORMS for Amd No 2. FORMS for Amd No 2, v2

FORMS for Amd No 2. FORMS for Amd No 2, v2 FORMS for Amd No 2 Usage and Reproduction of IEE Forms Subject to your agreement to the following conditions, you are permitted to, free of charge, photocopy and/or electronically manipulate the forms

More information

Changes to the Electricity (Safety) Regulations effective from 1 July 2013. www.energysafety.govt.nz www.ewrb.govt.nz www.standards.co.

Changes to the Electricity (Safety) Regulations effective from 1 July 2013. www.energysafety.govt.nz www.ewrb.govt.nz www.standards.co. Changes to the Electricity (Safety) Regulations effective from 1 July 2013 www.energysafety.govt.nz www.ewrb.govt.nz www.standards.co.nz Changes to the electrical certification regime under the Electricity

More information

Title: Australian Guidelines for grid connection of energy systems via inverters.

Title: Australian Guidelines for grid connection of energy systems via inverters. Title: Australian Guidelines for grid connection of energy systems via inverters. Foreword 28 April, 1998 The guidelines have been developed by a group of utility, photovoltaic and inverter industry experts

More information

EARTHING: YOUR QUESTIONS ANSWERED

EARTHING: YOUR QUESTIONS ANSWERED 18 EARTHING: YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing

More information

UT528 PAT Tester Manual

UT528 PAT Tester Manual P/N:110401104472X UT528 PAT Tester Manual Overview - UT528 The UT528 is a handheld, battery powered Portable Appliance Tester suitable for carrying out electrical safety tests on: Class I Appliances Class

More information

Page 1. Q1. The diagram shows the inside of a mains plug. Label the earth, live and neutral pins.

Page 1. Q1. The diagram shows the inside of a mains plug. Label the earth, live and neutral pins. Q. The diagram shows the inside of a mains plug. (a) Label the earth, live and neutral pins. (3) (b) (i) Explain how the earth wire and the fuse protect a person from an electric shock when there is a

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

Electrical installations on construction sites

Electrical installations on construction sites Industry standard Electrical installations on construction sites Edition No. 3 January 2011 The information presented in the Industry Standard Electrical installations on construction sites is intended

More information

The Hong Kong University of Science and Technology Health, Safety and Environment Office. Electrical Safety. Dr. C. M. LI Senior HSE Manager

The Hong Kong University of Science and Technology Health, Safety and Environment Office. Electrical Safety. Dr. C. M. LI Senior HSE Manager The Hong Kong University of Science and Technology Health, Safety and Environment Office Electrical Safety Dr. C. M. LI Senior HSE Manager Electrical Hazards Electrical Safety - Electrocution/ Electric

More information

LOW VOLTAGE ELECTRICAL WORK

LOW VOLTAGE ELECTRICAL WORK LOW VOLTAGE ELECTRICAL WORK CODE OF PRACTICE 2007 WorkCover. Watching out for you. New South Wales Government Revised 2nd Edition 2007 Disclaimer This publication contains information regarding occupational

More information

GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS

GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS 2008 EDITION www.st.gov.my CONTENTS Chapter Title Page 1. 1.1 1.2 1.3 Introduction Purpose References 4 4 5 2. Supply System 6 2.1 Electricity

More information

Grounding and Bonding

Grounding and Bonding ARTICLE 250 Grounding and Bonding INTRODUCTION TO ARTICLE 250 GROUNDING AND BONDING No other article can match Article 250 for misapplication, violation, and misinterpretation. Terminology used in this

More information

What Every Homeowner Should Know About the Electrical System in Their Home

What Every Homeowner Should Know About the Electrical System in Their Home What Every Homeowner Should Know About the Electrical System in Their Home Primary components are the service entry, service panel, and branch circuits. In unaltered buildings built since about 1940, the

More information

Release: 1. MEM18102 Fault-find, test and rectify single and three-phase transformers

Release: 1. MEM18102 Fault-find, test and rectify single and three-phase transformers Release: 1 MEM18102 Fault-find, test and rectify single and three-phase transformers MEM18102 Fault-find, test and rectify single and three-phase transformers Modification History Release 1. New unit Application

More information

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies Introduction In electrical circuits, voltage is always measured between two points: a point of high potential

More information

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont Test Before Touch Easier Said Than Done Ken Crawford, DuPont Kent Haggerty, Dupont Overview Test Before Touch (TBT) Principles Key Learnings by One Company One Method for Performing a TBT Induced Voltages

More information

ELECTRICAL SAFETY REGULATION 2002

ELECTRICAL SAFETY REGULATION 2002 Queensland Electrical Safety Act 2002 ELECTRICAL SAFETY REGULATION 2002 Reprinted as in force on 1 January 2004 (includes commenced amendments up to 2003 Act No. 63) Reprint No. 1F This reprint is prepared

More information

DIOCESE OF LINCOLN GUIDELINES

DIOCESE OF LINCOLN GUIDELINES DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006 Electrical Installations inside Churches As with all

More information

Electrical Safety Tester Verification

Electrical Safety Tester Verification Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that

More information

STATEMENT OF WORK Upgrade of Electrical Service and Primary Electrical Panel 208 Ratu Sukuna Road, Suva

STATEMENT OF WORK Upgrade of Electrical Service and Primary Electrical Panel 208 Ratu Sukuna Road, Suva STATEMENT OF WORK Upgrade of Electrical Service and Primary Electrical Panel 208 Ratu Sukuna Road, Suva INTRODUCTION: The United States Embassy in Suva, Fiji is seeking contractor proposals to upgrade

More information

24/07/2015. Session Aims. Introduction. Good Practice - IET. Legislative Framework. Today s speaker

24/07/2015. Session Aims. Introduction. Good Practice - IET. Legislative Framework. Today s speaker Today s speaker Electrical Safety in a Modern Working Environment Mike Taylor Health, Safety and Environmental Technical Director BEng MBA CEng CMIOSH CEnvMIET MIEMA Mobile: 07525 278980 Email: michael.taylor@santiaconsulting.com

More information

The Electrical Safety Regulation (pre and post 1 January 2014)

The Electrical Safety Regulation (pre and post 1 January 2014) The Electrical Safety Regulation (pre and post 1 January 2014) The following table provides an overview comparison between the Electrical Safety Regulation 2002 (the ESR 2002) current as at 1 July 2013

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE

More information

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by

More information

Technical Guideline for. Section 7. Approval of plans, drawings and specifications for installation work

Technical Guideline for. Section 7. Approval of plans, drawings and specifications for installation work Technical Guideline for Section 7. Approval of plans, drawings and specifications for installation work Ontario Regulation 22/04 Electrical Distribution Safety January 12, 2005 General Legal Disclaimer

More information