1 STRA-14 Control equipment Fläkt Woods Functions STRA-14 Temperature control CO 2 level control Free cooling feature Occupancy detection Condensation risk detection Communication: Modbus or BACnet Mode selection (normal, boost or energy saving mode) STRA-14 is a pre-programmed room controller intended to control the temperature and the CO 2 level in rooms. It is preprogrammed with communication and is intended for use in premises with high comfort and low energy demands, e.g. offices, schools, shopping centres, airports, hotels and hospitals. The STRA-14 is able to optimise energy consumption in rooms depending on different parameters: occupancy, CO 2 level, outside conditions (free cooling feature) and timetable. The thermal actuator of the water coils (heating and cooling) are controlled by the STRA-14 through 24V PWM signal or 0 10V outputs. The linear actuator of the outlet induction system (WEGA, WEGA Power, STELLA and NOVA chilled beams equipped with Motorized Energy Control) is controlled through a 0 10V output. The room controller STRA-14 will manage the risks of condensation in the room thanks to a condensation sensor located over the piping or a windows contact. Product facts Supply voltage, V AC, Hz Built-in temperature sensor Display 3 or 6 positions controller for outlet induction Easy installation thanks to separate basic plate for cable connections Communication via RS485: Modbus, BACnet or EXoline Outputs for thermal actuator: 24V Ac or 0 10V Inputs: external room sensor, CO 2 sensor, occupancy sensor, condensation detector al. windows contact 5 different pre-programmed control sequences relevant for chilled beam applications Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

2 Applications Controller operating modes Unscheduled time mode (OFF) This mode is activated by communication or the ON/OFF button (if configured). The controller is off and no heating or cooling is performed. However, if the temperature falls below a certain point (default 8 C, configurable) the controller starts to heat to prevent freezing. The airflow is according to nozzle for Energy saving (parameter 306). is pushed. The room controller regulates the temperature around the temperature setpoint. Unoccupied mode This mode is activated from BMS, none presence when using occupancy sensor or by pushing the Function button more than 5 seconds. The heating and cooling setpoints are extended (default 19 C for heating and 27 C for cooling). The airflow is according to nozzle for Energy saving (parameter 306). If the temperature increases even though the cooling valve is fully open the airflow will increase step by step. If free cooling is available (signal from communication is adjusted with parameter 309), the airflow will increase step by step before it opens the cooling valve. If the occupancy sensor detects occupancy the controller will change to occupied mode. Standby mode This mode can be used instead of "unoccupied mode" for non presence when using occupancy sensor. If the occupancy sensor is not connected, this mode cannot be activated (e.g. in a Landscape office). When the occupancy detector does not detect anybody, the setpoints for heating and cooling are extended (configurable values, ±3 C). For the version with MEC, the airflow is according to nozzle for Energy saving (parameter 306). If the temperature increases even though the cooling valve is fully open the airflow will increase step by step. If free cooling is available (signal from communication or adjusted with parameter 309), the airflow will increase step by step before it opens the cooling valve. If the occupancy sensor detects occupancy the controller will change to occupied mode. Occupied mode The Occupied operating mode means that the room is in use and is adjusted according to comfort mode. The airflow is preset according to parameter 307. The room controller controls the temperature around the heating or cooling temperature setpoints. For the version with MEC, if the temperature still increases even though the cooling valve is fully open, the airflow will increase step by step. If free cooling is available (signal from communication or adjusted with parameter 309), the airflow will increase step by step before it opens the cooling valve. If a CO 2 -sensor is connected it will override the temperature control of the linear actuator output. Boost mode (only for MEC version) This mode is activated by the button from Normal mode. The maximum air level is set by parameter 308, boost mode, for a predefined period of time or until the button Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

3 Applications Functions 6 or 3 positions function (only for MEC version) The 6-position function works on the UO3-output (MEC linear actuator). It works in the way that a certain voltage from the controller corresponds to a certain position on the MEC linear actuator. So when the controller output is within a certain range the UO3-output sets a specified voltage. The output on the UO3 is also depending on the controller state. Each mode of the room controller is related to an air level and this is set by parameter 306, 307 and 308. Cooling sequence without free cooling When there is no free cooling available, the controller works with cooling output and linear actuator output in sequence. The cooling output works when the PID output is between 0 48% and the linear actuator output works when the PID output is between %. When there is no demand for the linear actuator output, it is controlled to its minimum position for the current controller mode. The maximum linear actuator position is a configurable parameter in the parameter list. Cooling sequence with free cooling (only for MEC version) When there is free cooling available, the controller works with linear actuator output and cooling output in sequence. The linear actuator output works when the PID output is between 0 48% and the cooling output works when the PID output is between %. When there is no demand for the linear actuator output, it is controlled to its minimum position for the current controller mode. Free cooling is used when the AHU can produce free cooling and sends a signal via the BMS or adjusted with parameter 309. The maximum linear actuator position is a configurable parameter and selected in a parameter list (Maximum Air Level Cooling). It is used in following modes: Unoccupied, Standby and Occupied mode. % Output signal Nozzle for maximum cooling, Parameter % Output signal Nozzle for maximum coolin Parameter 304 Airflow level default depending on mode 0 Airflow level depending on mode Cooling 1 Cooling 2 48% 52% % Cooling demand 0 Cooling 1 Cooling 2 48% 52% % Cooling demand Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

4 Applications Airflow sequence depending on CO 2 (only for MEC version) If there is a CO 2 -sensor connected to the controller, the airflow linear actuator (UO3) is controlled by the CO 2 -level in the room and the cooling valve (UO2) is controlled by the temperature in the room. For the CO 2 -sequence, the maximum nozzle is selected by parameter 305 (FS is nozzle 6). When there is a CO 2 -sensor connected to the controller the air level 6 is allowed as maximum air level. Below is a graph that shows the UO3-output when a CO 2 -sensor is connected. The UO2-output is controlled as in previous sequences. Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

5 Application example - Temperature control Purpose Note Control the temperature in the room thanks to the thermal actuators. External sensor STRZ-05 may be used when the internal temperature sensor doesn't measure the average room temperature (because of STRA-14 location). Condensation sensor and window contact cannot be connected together. Adapter may be required, if another thermal actuator than is used. Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

6 Application example - Temperature control with energy saving mode SCADA Purpose Note Control the temperature in a closed room thanks to the thermal actuators and/or motorized nozzles of primary air (if free - cooling is configured). Save the energy when in unoccupied mode thanks to the occupancy detector reducing the primary air External sensor STRZ-05 may be used when the internal temperature sensor doesn't measure the average room temperature (because of STRA-14 location). Condensation sensor and window contact can't be connected together. Adapter may be required, if another thermal actuator than is used. Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

7 Application example - CO 2 level and temperature control with energy saving mode Purpose Note Control the CO 2 level in a landscape office or in a meeting room thanks to motorized nozzles of primary air Control the temperature in a closed room thanks to the thermal actuators and/or motorized nozzles of primary air (if free - cooling is configured). Save the energy when in unoccupied mode thanks to the occupancy detector reducing the primary air External sensor STRZ-05 may be used when the internal temperature sensor doesn't measure the average room temperature (because of STRA-14 location). Condensation sensor and window contact can't be connected together. Adapter may be required, if another thermal actuator than is used. Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

8 Application example - Miscellaneous STRA CHILLED BEAM and valve STRA CHILLED BEAM and valve Occupancy detector STRZ-09-1 Condensation detector STRZ VAC 24 VAC 230 VAC Transformer STRZ VAC Transformer STRZ-24-1 and valve RADIATOR STRA CHILLED BEAM WITH HEATING AND COOLING STRA UP TO EIGHT CHILLED BEAMS Eight thermal actuators and valves 2 x thermal actuator and valve Condensation detector STRZ-16-1 Condensation detector STRZ VAC 24 VAC 230 VAC Transformer STRZ VAC Transformer STRZ-24-1 Eight thermal actuators and valves EIGHT RADIATORS STRA CHILLED BEAM and valve Condensation detector STRZ VAC 230 VAC Transformer STRZ-24-1 and valve RADIATOR Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

9 Technical data Supply voltage V AC, Hz Internal consumption 2.5 VA Ambient temperature 0 50 C Storage temperature C Ambient humidity Max 90% RH Protection class IP20 Communication RS485 (EXOline or Modbus) with automatic detection/change-over Modbus 8 bits, 1 or 2 stop bits. Odd, even (FS) or no parity. Communication speed 9600 bps (not changeable) Built-in temperature sensor NTC type, measuring range 0 50 C, accuracy +/-0.5 C at C Inputs External room sensor CO 2 sensor Occupancy detector Condensation detector alt. window contact PT1000-sensor, 0 50 C. Suitable sensor is Fläkt Woods STRZ-05 STRZ-18-1 Closing potential-free contact. Suitable detector is Fläkt Woods STRZ-09 Fläkt Woods condensation detector STRZ-16 alt. Window contact STRZ-38 resp. potential-free contact Wiring diagrams STRA-14 with: Window contact STRZ-38 External temperature sensor STRZ-05 Actuator for nozzles IQAZ-23 Actuator for cooling valve Transformer STRZ-24 Outputs Forced ventilation Valve actuator alt. thermal actuator Control Actuator exercise Terminal blocks 24 V AC actuator, max 0.5 A 2 outputs 0 10 V DC, max 5 ma 24 V AC, max 2.0 A Heating or cooling FS = 23 hours interval So-called lift type for cable cross-section 2.1 mm 2 Communication STRA-14 is equipped with BACnet and Modbus communication as standard. It can act as a stand-alone unit or be connected to a central SCADA-system via RS485 (BACnet, Modbus or Exoline). STRA-14 with: CO 2 sensor, STRZ-18 Occupancy sensor STRZ-09 Actuator for nozzles IQAZ-23 Actuator for cooling and heating valve Transformer STRZ-24 Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

10 Technical data Display functions Dimensions Thanks to the parameter 42, you can display the following information: 0 = Room temp (default value) 1 = Heating setpoint 2 = Cooling setpoint 3 = Average cooling/heating setpoint 4 = Only setpoint offset 5 = CO 2 level 6 = Heating setpoint plus setpoint offset 7 = Cooling setpoint plus setpoint offset 8 = Average cooling/heating setpoint plus setpoint offset The product fulfils the requirements for valid European EMC-standard CENELEC EN and EN , as well as valid European LVD-standard IEC , and is CE-marked. Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

11 Quick installation STRA-14 STRA-14 is a room controller for multiple beams. Each chilled beam has unique settings, configured in STRA-14. This quick installation guide will guide you through these settings. 1. Press the INCREASE and DECREASE buttons simultaneously for about 5 seconds until Service indication lights up in the display. 2. Double click the INCREASE button to enter the parameter list in which all parameters of the regulator are set. Adjust chilled beam type related parameters The room controller has factory settings for WEGA/ NOVA (IQFH). If you are using a WEGA/NOVA you can jump to 11. The room controller STRA-14 is working with six position control of the nozzles of the chilled beam. Each nozzle corresponds to DC voltage between 0-10 V on the linier motor. The following steps guide you how to enter the voltage in to the room controller for each nozzle. Nozzle 1 is fixed to 0 V and nozzle 6 fixed to 10V and does not need to be adjusted. 3. Press INCREASE or DECREASE button to parameter 300 and the 4. Enter the voltage (Voltage x 10) for nozzle 2 and confirm with FUNCTION button. STELLA 23 WEGA/NOVA 21 (Default value) WEGA Power Press INCREASE once to parameter 301 and then press the FUNCTION button. 6. Enter the voltage (Voltage x 10) for nozzle 3 and confirm with FUNCTION button. STELLA 40 WEGA/NOVA 38 (Default value) WEGA Power Press INCREASE once to parameter 302 and then press the FUNCTION button. 8. Enter the voltage (Voltage x 10) for nozzle 4 and confirm with FUNCTION button. STELLA 59 WEGA/NOVA 56 (Default value) WEGA Power Press INCREASE once to parameter 303 and then press the FUNCTION button. 10. Enter the voltage (Voltage x 10) for nozzle 5 and confirm with FUNCTION button. STELLA 75 WEGA/NOVA 73 (Default value) WEGA Power 23 Presence sensor If you do not have a presence sensor jump to Press INCREASE or DECREASE to parameter 45 and 12. Change value to 1 (Unoccupied). Confirm with FUNCTION button. 13. Press INCREASE or DECREASE to parameter 17 and 14. Change value to "3". Confirm with FUNCTION button External temperature sensor If you do not have a external presence sensor jump to Press INCREASE or DECREASE to parameter 15 and 16. Change value to 1 (External room sensor). Confirm with FUNCTION button. Window sensor If you do not have a Window sensor jump to Press INCREASE or DECREASE to parameter 18 and 18. Change value to 1 (Window sensor). Confirm with FUNCTION button. CO 2 -sensor If you don't have a CO 2 sensor jump to Press INCREASE or DECREASE to parameter 81 press FUNCTION button. 20. Change value to "5". Confirm with FUNCTION button. Condensate sensor If you don't have condensate sensor jump to Press INCREASE or DECREASE buttons to parameter 18 and 22. Change value to "2". Confirm with FUNCTION button. Lighting via occupancy sensor 23. Press INCREASE or DECREASE button to parameter 60 and 24. Change value to 1. Confirm with FUNCTION button. Set points Following steps are to adjust set point values for the room controller. Room controller has factory settings which are recommended by Fläkt Woods and they do not need to be adjusted. Set point value Heating (default 22 C) 25. Press INCREASE or DECREASE to parameter 1 and Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

12 Quick installation STRA Change value to set point temperature. Confirm with FUNCTION button. Set point value Cooling (default 24 C) 27. Press INCREASE or DECREASE to parameter 2 and 28. Change value to set point temperature. Confirm with FUNCTION button. Nozzle for Energy Saving (default nozzle 1) 29. Press INCREASE or DECREASE to parameter 306 and press the FUNCTION button 30. Change value for nozzle at Energy Saving (1-4). Confirm with FUNCTION button. Nozzle for Normal mode (default nozzle 2) 31. Press INCREASE or DECREASE to parameter 307 and 32. Change value for nozzle at Normal mode (2-5). Confirm with FUNCTION button. Nozzle for Boost mode (Function button) (Default nozzle 6) 33. Press INCREASE or DECREASE to parameter 308 and 34. Change value for nozzle at Boost mode - Function button (3-6). Confirm with FUNCTION button. Nozzle for Boost mode (at Maximum cooling request) (Default nozzle 5) 35. Press INCREASE or DECREASE to parameter 304 and 36. Change value for nozzle at Boost mode at Maximum cooling request (3-6). Confirm with FUNCTION button. Nozzle for Boost mode (at high CO 2 -level) (Default nozzle 6) 37. Press INCREASE or DECREASE to parameter 305 and 38. Change value for nozzle at Boost mode high CO 2 - level (3-6). Confirm with FUNCTION button. For more detailed information please see the maintenance instruction. Fläkt Woods 9248 GB Specifications are subject of alteration without further notice.

Controls for fan coil units and cassettes

Controls for fan coil units and cassettes Controls for fan coil units and cassettes Selection of controls for use with fan coil & cassette units. Stand alone, selection guide Control unit Motor Standard QZAZ-04-10 QZAZ-04-20 QZAZ-04-75 QZAZ-05-11

More information

IPSUM Optimization System

IPSUM Optimization System IPSUM Optimization System Demand Controlled Ventilation INNOVATIVE INTEGRATED INDUSTRIALIZED ENERGY EXPERTISE ENVIRONMENT Fläkt Woods has the capability to combine energy efficient (e 3 ) products into

More information

Fan-coil controller for wall mounting

Fan-coil controller for wall mounting 3 576 ACR2.44/ALG Fan-coil controller for wall mounting ACR2.44 Pulse width modulated (PWM) valve outputs for thermal actuators, AC 23 V P or PI control behaviour selectable 3-speed fan control, automatic

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

Flush-mounted Room Temperature Controllers with LCD

Flush-mounted Room Temperature Controllers with LCD 3 067 RDF310.2, RDF310.21 RDF410.21 Flush-mounted Room Temperature Controllers with LCD for 2-pipe fan coil units for use with compressors in DX type equipment RDF310 RDF410 Output for on / off valve actuator

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

T5000 T000 LCD Digital Fan Coil Thermostat

T5000 T000 LCD Digital Fan Coil Thermostat T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,

More information

RTC2 BACnet FAN COIL CONTROLLER / THERMOSTAT

RTC2 BACnet FAN COIL CONTROLLER / THERMOSTAT RTC2 BACnet FAN COIL CONTROLLER / THERMOSTAT BACnet Enabled C-030 BAC 07/10 Description The RTC2 temperature controller incorporates a LCD display and is specifically designed for zone temperature control

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

TF428 Series Digital Thermostat Fan Coil Unit Control

TF428 Series Digital Thermostat Fan Coil Unit Control TF428 Series Digital Thermostat Fan Coil Unit Control Features SPECIFICATION DATA General The TF428 series digital thermostat is designed for 3-speed fan and valve control in a fan coil system, including:

More information

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation

More information

Inwall Room Temperature Unit

Inwall Room Temperature Unit Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

TC-8900 All-in-one Controller Units and ES-8930 Remote Setpoint Module

TC-8900 All-in-one Controller Units and ES-8930 Remote Setpoint Module European Electronic Controls Catalogue Catalogue Section F Product Bulletin TC-8900 Issue date 06 2000 TC-8900 All-in-one Controller Units and ES-8930 Remote Setpoint Module Introduction TC-8900 is a family

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

HCE80/HCC80/HCE80R/HCC80R

HCE80/HCC80/HCE80R/HCC80R HCE80/HCC80/HCE80R/HCC80R UNDERFLOOR HEATING-ZONEING CONTROLLERS PRODUCT DATA FEATURES Easy and fast installation because the new wiring design Pluggable terminals for fast wiring connection because clamp

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese. Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

SMT-920 Viking. Modbus Addendum. Document version 1.1. Version 2.7 Viking firmware

SMT-920 Viking. Modbus Addendum. Document version 1.1. Version 2.7 Viking firmware SMT-920 Viking Modbus Addendum Document version 1.1 Version 2.7 Viking firmware Preface The SMT-920 Viking HVAC controller from Smart Temp Australia is a standalone commercial Air conditioning controller

More information

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on analog output

Application Sheet Fan coil unit with staged fan, heating/cooling coil (2 pipe) on analog output Heating with LHW and cooling with CHW changeover Modulating control of heating and cooling valve (2 pipe) on analog Automatic or manual 3-speed fan control Room temperature and fan speed operation via

More information

Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack

Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack Compatible with SmartStruxure solution SmartStruxure Lite solution Room Controllers Line Voltage Fan Coil Room Controller with SC3000 Relay Pack Application specific controller with customizable covers

More information

Air handling unit. REC Temovex 250S-EC-RS. Experts on indoor climate in low-energy houses

Air handling unit. REC Temovex 250S-EC-RS. Experts on indoor climate in low-energy houses REC Temovex 25S-EC-RS Experts on indoor climate in low-energy houses RT 25S-EC-RS REC Temovex 25S-EC-RS Made in Sweden ECO2 control system for low-energy and passive houses Comprises: - Air flow boost

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

BATIGYR BatiBUS Node FOR RCE86.X-VISONIK CONNECTION VISONIK 400/4000 PRV2.0 PRV PRV PRV

BATIGYR BatiBUS Node FOR RCE86.X-VISONIK CONNECTION VISONIK 400/4000 PRV2.0 PRV PRV PRV 8 942 BATIGYR BatiBUS Node FOR RCE86.X- CONNECTION PNB Scale 1 : 2 8942P015 System overview 400/4000 Building Level PRV2.0 PRV PRV PRV PNB PNE BatiBUS Field Level 8942B02E RCE86.x The PNB is an interface

More information

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a

More information

Wall-mounted room thermostat with LCD

Wall-mounted room thermostat with LCD 3 182 Wall-mounted room thermostat with LCD for VAV heating and cooling systems RDG400 Modulating PI control Control depending on the room or the return air temperature Output for DC 0 10 V actuator and

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Heating, air-conditioning, cooling

Heating, air-conditioning, cooling Series description Design High efficiency, single stage, low pressure, inline centrifugal pump Supplied with EC motor and electronic duty adaptation Available in glanded construction, mechanical shaft

More information

CR24-.. Single room controllers

CR24-.. Single room controllers Product information CR4- CR4- Single room controllers Table of contents wwwbelimocom Overview of the system Overview of functions 3 Technical data sheets CR4-B1 / CR4-A1 Single room controllers CR4-B /

More information

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS.  Construction Automotive Industry DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.

More information

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x

B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x B.IQ push button 3-5gang with room Product name: Design: ETS search path: B.IQ push button 3-, 4-, 5gang with room thermostat and display V2 Flush-mounted Push button / B.IQ / B.IQ push button xgang with

More information

B.IQ push button 3-5gang with RTR and display, Flush-mounted (Up) x, x, x

B.IQ push button 3-5gang with RTR and display, Flush-mounted (Up) x, x, x B.IQ push button 3-5gang with RTR and Functional description: Push button functionality: Depending on the parameterized software, the B.IQ push button RTR (Room Temperature Regulator) will send telegrams

More information

Technical Description

Technical Description abcxyz Contents 1. General...1 2. Block Diagram...2 3. First Steps...2 4. Technical Data...3 4.1 AS-Interface...3 4.2 Pin Out...4 4.3 Supply of Periphery...4 4.4 Inputs...5 4.5 Outputs...5 4.6 Mechanical

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

CM507 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

CM507 PROGRAMMABLE THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET CM507 PROGRAMMABLE THERMOSTAT PRODUCT SPECIFICATION SHEET The CM507 thermostat is designed to provide automatic time and temperature control of heating systems in villas and apartments. It can be used

More information

Cooling mode. Temperature adjustment button. Override button. 24 VAC COM AN1 COM OPEN CLOSED T2/AN2 T2/COM T3 T3 COM SENSOR COM C-Over COM NSB

Cooling mode. Temperature adjustment button. Override button. 24 VAC COM AN1 COM OPEN CLOSED T2/AN2 T2/COM T3 T3 COM SENSOR COM C-Over COM NSB TB6980/TB7980 1. Introduction The TB6980/TB7980 digital thermostats provide proportional plus integral individual space temperature control in zoned commercial HVAC systems such as hydronic and pressure

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

INSTALLATION AND USER GUIDE GSM CONTROLLER

INSTALLATION AND USER GUIDE GSM CONTROLLER GSM Controller INSTALLATION AND USER GUIDE GB GSM CONTROLLER ---------------------------------------------------------------------------------- 3-10 2 INSTALLATION AND OPERATION MANUAL GSM Controller IMPORTANT!

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Electromotoric Actuators

Electromotoric Actuators OEM SQS35954 with spring return function, without manual adjuster SQS35903, SQS35905, SQS85900, without spring return function, with manual adjuster Electromotoric Actuators for VVG549, VVP459, VXP459,

More information

Belimo Gateway MP to Modbus RTU - UK24MOD

Belimo Gateway MP to Modbus RTU - UK24MOD Product information UK24MOD MODBUS RTU Belimo Gateway MP to Modbus RTU - UK24MOD Contents Complete overview 2 Technical data 3 Safety notes 4 Product features 4 Installation and commissioning 4 Electrical

More information

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

INSTALLATION MANUAL. Room thermostat EKRTR EKRTETS

INSTALLATION MANUAL. Room thermostat EKRTR EKRTETS INSTALLATION MANUAL EKRTR EKRTETS 1 2 1 2 3 60 87 170 161 ±1.5 m >0.2 m 3 5 4 34 125 4 5 28 50 EKRTR EKRTETS Contents Read this manual attentively before starting up the unit. Do not throw it away. Keep

More information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.

More information

On/off room thermostats range. On/off V30 range. Master/slave PI V200 range. V3000 KNX networked PID range

On/off room thermostats range. On/off V30 range. Master/slave PI V200 range. V3000 KNX networked PID range Electromechanical controls Air control Water control On/off room thermostats range On/off room thermostats range Electronic controls Air control On/off V30 range On/off V30 range Water control Master/slave

More information

WS-0XX Wall Sensor AI-1. Open BO-7. Close. Supply Fan. 2-Pipe Fan Coil Personalities

WS-0XX Wall Sensor AI-1. Open BO-7. Close. Supply Fan. 2-Pipe Fan Coil Personalities General Description 2-Pipe Fan Coil General Description Optional Economizer Close,Min,Max BO-5 Open WS-0XX Wall Sensor AI-1 Discharge Air Temperature (Optional) AI-6 BO-6 Close Zone Temperature Cooling

More information

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings. 1100 & 1400 Energy Controllers Satchwell 1100 & 1400 for energy-efficient temperature control in smaller buildings. 02 1100 & 1400 Energy Controllers Features he 1100 and 1400 Energy Controllers are self-configuring

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

Electric Rotary Actuator - On/Off or programmable control actuator

Electric Rotary Actuator - On/Off or programmable control actuator Electric Rotary Actuator - On/Off or programmable control actuator Direct mounting on quarter-turn valves Manual override standard Corrosion resistant Adjustable limit switches Multi-voltage version Type

More information

Cooling with CHW (fan coil Heating with LTHW radiator Modulating control of heating and cooling valve Automatic or manual fan control

Cooling with CHW (fan coil Heating with LTHW radiator Modulating control of heating and cooling valve Automatic or manual fan control Fan coil with two-pipe system (cooling) and radiators FC8 Cooling with CHW (fan coil Heating with HW radiator odulating control of heating and cooling valve Automatic or manual fan control Plant diagram

More information

Programmable Relays. ZEN Series. ZEN Programmable Relays. Applications

Programmable Relays. ZEN Series. ZEN Programmable Relays. Applications Programmable Relays ZEN Series Relay, Timer, Counter, and Time Switch Functions Weekly Timer and Calendar Timer Functions Twin Timer Function (Separate ON/OFF Times) Two Analog Input Channels (DC Models

More information

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital

More information

Heating Controller. Building Technologies HVAC Products

Heating Controller. Building Technologies HVAC Products 2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

Optidrive Applications Support Library

Optidrive Applications Support Library Optidrive Applications Support Library Application Note Title AN-ODE-2-032 Related Products Optidrive E2 Overview Level 2 PI Closed Loop Feedback Control Applications 1 Fundamental - No previous experience

More information

Unica for KNX system 226

Unica for KNX system 226 Unica for KNX system 6 P117504 Greater flexibility and comfort, better energy efficiency with KNX More and more electronic appliances are needed for modern comfortable homes that contain everything from

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features: GE Measurement & Control Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low

More information

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx

Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx 756627xx, 756637xx, 756657xx Documentation Product name: Push button 2-, 3-, 5- gang RTR + display Design: UP (flush-mounting type) ETS search path: Push button / Push button xgang / Push button xgang

More information

Flush-mounted room thermostats

Flush-mounted room thermostats s 3 076 RDF300, RDF300.02, RDF340 RDF400.01 RDF600 RDF600 Flush-mounted room thermostats for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units for use with compressors in DX type equipment RDF300

More information

Adjustable room thermostat for heating only or cooling only systems

Adjustable room thermostat for heating only or cooling only systems 3 003 Room hermostat RAA30 Adjustable room thermostat for heating only or cooling only systems Room thermostat with manual O/OFF switch wo-position control witching voltage AC 24 250 V Use he RAA30 room

More information

Technical Support Bulletin Nr. 20 Special AC Functions

Technical Support Bulletin Nr. 20 Special AC Functions Technical Support Bulletin Nr. 20 Special AC Functions Summary! Introduction! Hot Start Control! Adaptive Control! Defrost Start Temperature Compensation Control! Anti-Sticking Control! Water Free Cooling

More information

Reference Guide for the DDC Controller

Reference Guide for the DDC Controller Part #474894 DDC Controller for Tempered Air Products TAP v2.00 Version Date: 9/22/11 Reference Guide for the DDC Controller Please read and save these instructions. Read carefully before attempting to

More information

CO2 Alarm. Operation. Application

CO2 Alarm. Operation. Application CO Alarm 100-77V AC Supply Voltage Two pre-configured alarm and control thresholds Thresholds factory set to customer requirements on dispersive infrared sensing technology Optional internal audible alarm

More information

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5 T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,

More information

Electromotoric Actuators

Electromotoric Actuators 4 554 Electromotoric Actuators for valves with 2 mm stroke SQX32.. SQX82.. SQX62 SQX32.. operating voltage AC 23 V, 3-position positioning signal SQX82.. operating voltage AC 24 V, 3-position positioning

More information

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

IntesisBox Modbus Server SAMSUNG Air Conditioners

IntesisBox Modbus Server SAMSUNG Air Conditioners IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information

Pressure transmitter (2 wire) / switch for continuous or On/Off Control

Pressure transmitter (2 wire) / switch for continuous or On/Off Control transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

flexotron 800: Electronic ventilation, air-conditioning and heating controller

flexotron 800: Electronic ventilation, air-conditioning and heating controller PDS 46.300 en product data sheet flexotron 800 flexotron 800: Electronic ventilation, air-conditioning and heating controller Areas of use Used universally in ventilation, air-conditioning and heating

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

Design Guidelines and Standards Manual 9/16/96 University of Cincinnati SECTION SEQUENCE OF OPERATION

Design Guidelines and Standards Manual 9/16/96 University of Cincinnati SECTION SEQUENCE OF OPERATION 1.01 SUBMITTALS SECTION 15985 - SEQUENCE OF OPERATION A. Written sequence of operation to be submitted with shop drawing submittal of Section 15970. PART 2 - PRODUCTS 2.01 GENERAL A. The HVAC with controls

More information

Air flow meter Model A2G-25

Air flow meter Model A2G-25 Electronic pressure measurement Air flow meter Model A2G-25 WIKA data sheet SP 69.04 Applications For measuring the air flows of radial ventilators For measuring air flows in ventilation pipes and ducts

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke

More information

TM1. Temperature Monitor - TM1

TM1. Temperature Monitor - TM1 Temperature Monitor - TM1 The Temperature Monitor, TM-1 is the latest generation of the widely applied temperature monitor MT1. Updated with all the experience acquired by Tree Tech over the last 6 years

More information

100% electricity. Generating set controller RGK 60

100% electricity. Generating set controller RGK 60 00% electricity Generating set controller RGK 60 Large graphic screen for measurement and 5-language help prompt display Operating mode selection touch keys Manual control of stand-by generating set Load

More information

COMPALARM C2C ALARM SYSTEM

COMPALARM C2C ALARM SYSTEM INSTRUCTION MANUAL IM670-U v0.1 COMPALARM C2C ALARM SYSTEM GENERAL Compact alarm system, with a basic module of 12 signals Multiple modules coupling possibility Easy printing of the alarm points description

More information

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control T Series arge CD Digital Thermostat 0/0 VAC -pipe/-pipe fan coil control Data sheet Application T digital thermostats are designed for application of -speed fan and s in fan coil system. Including: -pipe

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses REC Temovex 4S-EC-RS Experts on indoor climate in low-energy houses RT 4S-EC-RS REC Temovex 4S-EC-RS Made in Sweden ECO2 control system for low-energy and passive houses Comprises: - Air flow boost for

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date May 5, 2011 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

RXL21.1 RXL22.1. Room controllers. Building Technologies Building Automation RXL

RXL21.1 RXL22.1. Room controllers. Building Technologies Building Automation RXL 3 877 3877P01 RXL Room controllers Communicating controllers for fan-coil applications FC-10, FC-11, FC12 RXL21.1 RXL22.1 The RXL21.1 and RXL22.1 room controllers are used for temperature control in individual

More information

Touch Screen Flush-mount Room Thermostats with KNX Communications

Touch Screen Flush-mount Room Thermostats with KNX Communications s 3 175 RDD810KN/NF Touch Screen Flush-mount Room Thermostats with KNX Communications For heating applications KNX bus communications (S-mode and LTE mode) Large display with backlight 2-position (ON/OFF)

More information

T-100-R Installation Guide

T-100-R Installation Guide T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard

More information

Siemens BACnet Terminal Box (VAV) Controller

Siemens BACnet Terminal Box (VAV) Controller Technical Specification Sheet Document. 149-810 May 30, 2012 Siemens BACnet Terminal Box (VAV) Controller The Siemens BACnet Terminal Box (VAV) Controller provides high performance direct digital control

More information

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111 , GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,

More information

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions COMPUTHERM Q7 Programmable, digital room thermostat Operating Instructions GENERAL DESCRIPTION OF THE THERMOSTAT The COMPUTHERM Q7 type switched-mode room thermostat is suitable to regulate the overwhelming

More information

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL

More information

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB , GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well

More information

Label Applicator HERMA 400

Label Applicator HERMA 400 Label Applicator HERMA 400 Info GB V6.4 / 12.09.11 [ Facts & Data ] R Constructional variant Right-hand or left-hand version, always flexible to use L Power supply / Line voltage Wide range input 100V

More information

SIMEXR SWE-73-A 1.2.3. low-cost meter in a small case input: 0/4-20 ma 0/1-5V; 0/2-10V RS-485 / Modbus RTU. Process Meters. Typical applications

SIMEXR SWE-73-A 1.2.3. low-cost meter in a small case input: 0/4-20 ma 0/1-5V; 0/2-10V RS-485 / Modbus RTU. Process Meters. Typical applications Process Meters R SWE-7-A low-cost meter in a small case input: 0/4-20 ma 0/1-5V; 0/2-10V / Modbus RTU New pilot SIR-15 The SWE-7 efficiency indicators are low-cost and affordable panel-mounted digital

More information