Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Size: px
Start display at page:

Download "Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596"

Transcription

1 Installing the Tracer ZN517 Unitary Controller Ordering number: , Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital zone control. The controller can operate as a stand-alone device or as part of a building automation system (BAS). The Tracer ZN517 is designed to control the following types of equipment: 2-heat/2-cool rooftop unit with optional economizer control 4-cool rooftop unit with optional economizer control 2-compressor heat pump with optional economizer and auxiliary heat control Split system The Tracer ZN517 follows the guidelines of the LonMark Space Comfort Controller (SCC) profile. The Tracer ZN517 is available in two different versions: frame-mount ( ) and metal enclosure ( ). (See Figure 3 and Figure 4 on page 3.) The frame-mount package contains: A Tracer ZN517 circuit board fastened to a metal back plate A removable molded resin cover The metal-enclosure package contains: A Tracer ZN517 circuit board fastened to the back piece of the metal enclosure A removable metal cover Shipment Visually inspect all parts for obvious defects or damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred in shipping should be filed with the carrier. Storage environment An indoor storage environment is recommended that meets the following requirements: Temperature: 40 F to 185 F ( 40 C to 85 C) Relative humidity: 5 95%, noncondensing Operating environment Make sure that the operating environment conforms to the specifications listed in Table 1. Dimensions and clearances are illustrated in Figure 1 and Figure 2 on page 2: Table 1. Operating environment specifications Temperature Humidity Power Mounting weight (framemount) Mounting weight (metal enclosure) From 40 F to 160 F ( 40 C to 70 C) 5 90%, noncondensing Vac (24 Vac nominal), Hz 9 VA per controller and a maximum of 12 VA per output utilized Mounting surface must be able to support 2 lb (1 kg) Mounting surface must be able to support 8 lb (4 kg) Altitude 6,500 ft (2,000 m) Installation Category 3 Pollution Degree 2 Location For most applications, the Tracer ZN517 can be installed within the unit it is controlling. It is suitable for extended ambient s. If installed in an outdoor environment, it must be fully enclosed for protection from the elements. Trane also recommends locating the Tracer ZN517 unitary controller: Where public access is restricted to minimize the possibility of tampering or vandalism In or near the controlled piece of equipment to reduce wiring costs Where it is easily accessible for service personnel Trane A Business of American Standard Companies American Standard All rights reserved D

2 Figure 1. Dimensions and clearances for the frame-mount controller 1 in. (25 mm) in. (160 mm) 2 in. (51 mm) 4 in. (102 mm) AC POWER AC OUT OPN CLS ECONOMIZER Rc Rh G NO 5COM HVAC UNIT 5NC BINARY OUTPUT STATUS LED 4 in. (102 mm) in. (137 mm) 4 in. (102 mm) in. (175 mm) SERVICE LED PIN COMM5 BINARY INPUTS A B A B -BI1- -BI ANALOG INPUTS AI1 -AI2 - -DAT- ZONE SENSOR COMM5 ZN SET LED in. (143 mm) Clearances Dimensions 1 in. (25 mm) Figure 2. Dimensions and clearances for the metal-enclosure controller 1 in. (25 mm) in. (48 mm) 6.5 in. (165 mm) 2 in. (51mm) 9 in. (229 mm) 2 in. (51 mm) 7 in. (178 mm) 9 in. (229 mm) 24 in. (610 mm) in. (263 mm) width with cover 1 in. (25 mm) 2.25 in. (58 mm) 1 in. (25 mm) in. (260 mm) width without cover Clearances Dimensions D 2

3 Mounting the frame-mount controller IMPORTANT Mount the Tracer ZN517 controller with the cover on to avoid damaging the circuit board during installation. To mount the frame-mount controller: 1. Using the module as a template, mark the location of the two mounting holes on the mounting surface (Figure 3). 2. Set the module aside and drill holes for the screws at the marked locations. Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry. 3. Insert wall anchors if needed. 4. Secure the module to the mounting surface with #10 (5 mm) screws (not included). Attach the frame-mount module securely so that it can withstand the vibrations of associated heating, ventilating, and air-conditioning (HVAC) equipment. Mounting the metal-enclosure controller To mount the metal-enclosure controller: 1. Remove the two cover screws and then the cover. 2. Using the enclosure as a template, mark the location of the four mounting holes on the mounting surface (Figure 4). 3. Set the enclosure aside and drill holes for the screws at the marked locations. Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry. 4. Insert wall anchors if needed. 5. Secure the enclosure to the mounting surface with #10 (5 mm) screws (not included). Figure 4. Mounting the metal-enclosure Tracer ZN517 controller Figure 3. Mounting the frame-mount Tracer ZN517 zone controller Agency conformance CE marked UL and C-UL listed: 916, Energy management equipment UL 94-5V (UL flammability rating for plenum use) FCC Part 15, Class A, CFR D

4 Configuring for equipment type Set the DIP switches on the Tracer ZN517 circuit board for the type of equipment that is going to be controlled. See Table 2 for DIP switch settings for each type of equipment. Table 2. DIP switch settings Equipment type (not used) Heating: 71.0 F (21.7 C) Cooling: 74.0 F (23.3 C) In unoccupied mode, the controller will operate at: Heating: 60.0 F (15.6 C) Cooling: 85.0 F (29.4 C) Inputs and outputs. For individual input and output factory defaults, See Tables 3, 4, and 5. 2-heat/2-cool (default) Off Off Off N/A Table 3. Binary inputs 2-heat/2-cool w/economizer Off Off On N/A Binary input Functions Defaults Rating 4-cool On Off Off N/A 4-cool w/economizer On Off On N/A Heat pump Off On Off N/A Heat pump w/economizer Off On On N/A Invalid On On Off N/A Invalid On On On N/A ON DIP Factory defaults 2-heat/2-cool (default) The Tracer ZN517 controller is shipped with the following default settings. To change defaults, use DIP switches, a Rover service tool, or a BAS, as appropriate. Equipment type. The Tracer ZN517 ships from the factory configured to control a 2-heat/2-cool rooftop unit without economizer. To change this configuration, see Configuring for equipment type. Setpoints. In occupied mode, the controller can receive a setpoint from either a zone sensor (default) or from a BAS. If neither a zone sensor value or a communicated value is received, the Tracer ZN517 will operate at the following default setpoints: BI1 Occupancy or generic Occupancy Volt-free dry contact BI2 Fan status Fan status Volt-free dry contact Note: Do not apply power to these inputs. Table 4. Analog inputs Analog input AI1 AI2 DAT ZN SET Functions Defaults Rating Generic, RH, CO 2, or not used Outdoor air or generic Discharge air Zone Temperature setpoint Not used Generic Discharge air Zone Zone setpoint 10,000 Ω at 77 F (25 C) 10,000 Ω at 77 F (25 C) 10,000 Ω at 77 F (25 C) 10,000 Ω at 77 F (25 C) 1000 Ω potentiometer Note: For best results and accuracy, use only Trane sensors D 4

5 Table 5. Binary outputs Binary output 2-heat/ 2-cool 4-cool Heat pump Rating OPN Economizer, drive open Economizer, drive open Economizer, drive open Triac, 24 Vac, max 500 ma, min 50 ma CLS Economizer, drive closed Economizer, drive closed Economizer, drive closed Triac, 24 Vac, max 500 ma, min 50 ma Rc 24 Vac from HVAC system 24 Vac from HVAC system 24 Vac from HVAC system 24 Vac nominal Rh 24 Vac from HVAC system 24 Vac from HVAC system 24 Vac from HVAC system 24 Vac nominal G Supply fan Supply fan Supply fan Form A relay, powered contact, 24 Vac, 1 A max 1 Cool stage 1 (Y 1 ) Cool stage 1(Y 1 ) Compressor 1(Y 1 ) Form A relay, powered contact, 24 Vac, 1 A max 2 Cool stage 2 (Y 2 ) Cool stage 2 (Y 2 ) Compressor 2 (Y 2 ) Form A relay, powered contact, 24 Vac, 1 A max 3 Heat stage 1 (W 1 ) Cool stage 3 (Y 3 ) Reversing valve (O) Form A relay, powered contact, 24 Vac, 1 A max 4 Heat stage 2 (W 2 ) Cool stage 4 (Y 4 ) Auxiliary heat (W 1 ) Form A relay, powered contact, 24 Vac, 1 A max 5NO/ Exhaust fan*/generic/ Exhaust fan*/generic/ Exhaust fan*/generic/ Form C relay, pow 5COM/ occupancy occupancy occupancy ered contact, 24 Vac, 5NC 1 A max *Factory default AC-power wiring See Figure 5 on page 6 or Figure 6 on page 6 for the location of the ac-power connections. IMPORTANT Make sure that the 24 Vac power supplies are consistently grounded. Do not share 24 Vac between controllers. The recommended wire for ac power is 16 AWG copper wire. All wiring must comply with National Electrical Code and local codes. If you are providing a new transformer for power, use a UL-listed Class 2 power transformer supplying a nominal 24 Vac (19 30 Vac). The transformer must be sized to provide adequate power to the Tracer ZN521 zone controller (14 VA) and output devices, including relays and valve actuators (a maximum of 12 VA per output utilized). Please read the warning and cautions before proceeding. WARNING Hazardous voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. CAUTION Injury and equipment damage! Make sure that the 24 Vac transformer is properly grounded. Failure to do so may result in personal injury and/or damage to equipment D

6 A B A B Rh 2 CAUTION Equipment damage! Complete input/output wiring before applying power to the controller. Failure to do so may cause damage to the controller or power transformer due to inadvertent connections to power circuits. Do not share 24 Vac between controllers. Failure to do so may cause controller damage. Wiring AC-power to the frame-mount controller Please read the preceding warning and cautions. To connect ac-power to the frame-mount controller: 1. Connect the ground wire from the 24 Vac transformer to the terminal shown in Figure Connect the power wire to the terminal. Figure 5. AC-power wiring for frame-mount 24 Vac transformer N H AC POWER AC OUT Wiring AC-power to the metal-enclosure controller Please read the preceding warnings and cautions. To connect ac-power wiring to the enclosure: 1. Remove the cover of the enclosure. 2. Remove the knockout for the 0.5 in. (13 mm) conduit from the enclosure and attach the conduit. 3. Feed the power wire into the enclosure. 4. When mounting on dry wall or other non-conductive surface, connect an earth ground to the earth-ground screw on the enclosure (Figure 6). 5. Connect the ground wire from the 24 Vac transformer to the terminal shown in Figure Connect the power wire to the terminal. 7. Replace the cover of the enclosure. Figure 6. AC-power wiring for metal enclosure SERVICE LED PIN COMM5 BINARY INPUTS ANALOG INPUTS ZONE SENSOR COMM5 -BI1 -BI2 +20 AI1 -AI2- -DAT- ZN SET LED Communication-link wiring OPN CLS Rc AC POWER AC OUT ECONOMIZER HVAC UNIT BINARY OUTPUT G NO 5COM 5NC LED AC POWER Ground screw The Tracer ZN517 communicates with the building automation system (BAS) and with other controllers by means of a Comm5 communication link. Comm5 is Trane s implementation of LonTalk. For instructions on Comm5 communication wiring and addressing, follow the Tracer Summit Hardware and Software Installation guide (BMTX-SVN01A), the Tracker Building Automation System Hardware Installation guide (BMTK-SVN01D), or another BAS installation manual. HVAC unit electrical circuit wiring The terminals labeled Rc and Rh are provided as inputs for 24 Vac power from the transformer(s) of the HVAC system. Note: The Tracer ZN517 is shipped from the factory with terminals Rc and Rh coupled with a jumper at J1 on the controller circuit board. Packaged units If the HVAC unit combines heating and cooling (referred to as a packaged unit), it will typically have one R transformer. For 24 Vac wiring of packaged units, the Rc terminal must be wired as shown in this procedure: 1. Locate the jumper at J1 on the controller circuit board (Figure 7 on page 7). Place the jumper on both pins at J1 on the circuit board (Figure 8 on page 7). 2. Wire the Rc terminal to the transformer on the unit (Figure 9 on page 8) D 6

7 Split systems If the unit is a split system (a unit with physically separate heating and cooling sections), there is typically a separate transformer for each function. For 24 Vac wiring of split systems, the Rc and Rh terminals must be wired as shown in this procedure: Figure 8. Coupling and uncoupling terminals Rc and Rh for 24 Vac wiring of the HVAC unit For packaged units Place the jumper on both pins at J1. J1 1. Locate the jumper at J1 on the controller circuit board (Figure 7). Remove the jumper from the pins at J1 on the circuit board (Figure 8). 2. Replace the jumper on one of the pins at J1 for possible future use. 3. Wire Rc to the transformer for the cooling section of the unit (Figure 10 on page 8). 4. Wire Rh to the transformer for the heating section of the unit (Figure 10 on page 8). Figure 7. Location of J1 on Tracer ZN517 circuit board For split systems Remove the jumper from the pins at J1. (Replace the jumper on one of the pins for possible future use.) J1 J1 (location of jumper for Rc, Rh terminals) D

8 Figure 9. Wiring for packaged heating and cooling units Primary Secondary, 24 Vac Tri-state modulating economizer Fan Compressor 1 contactor Compressor 2 contactor Heat stage 1 24 Vac H N R G Y1 Y2 Heat stage 2 W1 W2 Generic binary output OPN CLS AC POWER AC OUT ECONOMIZER Rc Rh G NO 5COM 5NC HVAC UNIT BINARY OUTPUT STATUS LED Figure 10. Wiring for split system applications Primary Secondary, 24 Vac Primary Secondary, 24 Vac Tri-state modulating economizer Fan* Compressor 1 contactor Compressor 2 contactor Heat stage 1 24 Vac H N Rc Rh G Y1 Y2 W1 W2 Heat stage 2 Generic binary output OPN CLS AC POWER AC OUT ECONOMIZER Rc Rh G NO 5COM 5NC HVAC UNIT BINARY OUTPUT STATUS LED *Wire the fan (G) to the appropriate section of the split system. Input/Output terminal wiring All input/output terminal wiring for the Tracer ZN517 unitary controller is application specific. Input/output terminal wiring must meet the following requirements: All wiring must be in accordance with the National Electrical Code and local codes. Use only AWG, stranded, tinned-copper, shielded, twisted-pair wire. Binary input and output wiring should be a maximum length of 300 ft (100 m). Analog input wiring should be a maximum length of 300 ft (100 m). Do not run input/output wires in the same wire bundle with any ac power wires D 8

9 Binary inputs, binary outputs, and analog inputs are identified by label and function in Table 3 on page 4, Table 5 on page 5, and Table 4 on page 4, respectively. Figure 11. Wiring diagram for the 2-heat/2-cool application See example wiring diagrams that include all required and optional components for: 2-heat/2-cool applications (Figure 11 on page 9) 4-cool applications (Figure 12 on page 10) Heat pump applications (Figure 13 on page 11) Power* Tri-state modulating economizer Fan Compressor 1 contactor Compressor 2 contactor Heat stage 1 24 Vac H N R G Y1 Y2 W1 W2 Heat stage 2 Generic binary output Comm5 In Out *Terminals Rc and Rh are provided as inputs for 24 Vac power from the controlled device. If the device has a separate heating and cooling units, use Rh Occupancy or generic for heat and Rc for cooling. If combined, use only Rc (see HVAC unit electrical circuit wiring on page 6). Dry contacts only Typical 3-wire sensor Fan status (default: closed = no flow open = flow) Discharge air Outdoor air Comm D

10 Figure 12. Wiring diagram for the 4-cool application Power* Tri-state modulating economizer Fan Compressor 1 contactor Compressor 2 contactor Compressor 3 contactor 24 Vac H N R G Y1 Y2 Y3 Y4 Compressor 4 contactor Generic binary output Comm5 In Out *Terminals Rc and Rh are provided as inputs for 24 Vac power from the controlled device. If the device has a separate heating and cooling units, use Rh for heat and Rc for cooling. If combined, use only Rc (see HVAC unit electrical circuit wiring on page 6). Occupancy or generic Dry contacts only Typical 3-wire sensor Fan status (default: closed = no flow open = flow) Discharge air Outdoor air Comm D 10

11 Figure 13. Wiring diagram for the heat pump application Power* Tri-state modulating economizer Fan Compressor 1 contactor Compressor 2 contactor Reversing valve 24 Vac H N R G Y1 Y2 O W1 Auxiliary heat Generic binary output Comm5 In Out *Terminals Rc and Rh are provided as inputs for 24 Vac power from the controlled device. If the device has a separate heating and cooling units, use Rh for heat and Rc for cooling. If combined, use only Rc (see HVAC unit electrical circuit wiring on page 6). Occupancy or generic Dry contacts only Typical 3-wire sensor Fan status (default: closed = no flow open = flow) Discharge air Outdoor air Comm5 The following are trademarks or registered trademarks of American Standard Inc.:Tracer, Tracer Summit, Trane. The following are trademarks or registered trademarks of their respective companies or organizations: LonTalk from Echelon Corporation, National Electrical Code from the National Fire Protection Association D

12 Declaration of Conformity Manufacturer s Name: Manufacturer s Address: The manufacturer hereby declares that the product Product Name: Model Number: Conforms to the following standards or other normative documents: Electromagnetic Emission: (by Council Directive 89/336/EEC) Trane 4833 White Bear Parkway St. Paul MN USA Unitary Controller ZN517 ( and ) EN :1992 EN :1995 EN :1995 Radiated EN55011:1999 Conducted EN55011:1999 Class B limit: Class A limit: Class B limit: Class B limit: Electromagnetic Immunity: (by Council Directive 89/336/EEC) EN :1995 EN :1999 IEC :1995 EN IEC :1995 EN :1996 Amendment A1:1998 IEC :1995 EN IEC :1995 EN IEC :1996 EN IEC :1993 EN IEC :1994 EN ±4.0 kv by contact 10.0 V/m MHz ±1.0 kv signal lines ±2.0 kv ac power lines ±2.0 kv ac power lines 10 V MHz 30 A/m When and Where Issued Electromagnetic Emission 12/27/2001 Electromagnetic Immunity 12/27/2001 Mark of Compliance John Olson, Design/Compliance Engineer European Contact Societe Trane (Epinal, France) 1, rue des Ameriques, B.P. 6 F Golbey Cedex, France Phone: (33) Fax: (33) This document validates CE conformity of the European unitary controller, ZN D 12

Product Catalog BAS-PRC010-E4. Tracker Version 12 Building Automation System. August 2010

Product Catalog BAS-PRC010-E4. Tracker Version 12 Building Automation System. August 2010 Product Catalog Tracker Tracker Version 12 Building Automation System August 2010 BAS-PRC010-E4 Introduction The Tracker Version 12 building automation system (BAS) is a heating, ventilating, and air conditioning

More information

Tracker. Tracker Version 12 Building Automation System BAS-PRC010-EN. March 2008

Tracker. Tracker Version 12 Building Automation System BAS-PRC010-EN. March 2008 Tracker Tracker Version 12 Building Automation System March 28 BAS-PRC1-EN Introduction The Tracker Version 12 building automation system (BAS) is a heating, ventilating, and air conditioning (HVAC) energy

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Tracer ZN524 for water-source heat pumps Order No: CNT-SVX11A-EN Date: August 2003 CNT-SVX11A-EN Notice Notice Warnings and Cautions appear at appropriate sections throughout

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

T5000 T000 LCD Digital Fan Coil Thermostat

T5000 T000 LCD Digital Fan Coil Thermostat T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,

More information

T7079A,B Solid State Remote Temperature Controllers

T7079A,B Solid State Remote Temperature Controllers T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed. FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

Model: DC-A2IO Advanced HVAC Controller

Model: DC-A2IO Advanced HVAC Controller Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting

More information

Adjustable room thermostat for heating only or cooling only systems

Adjustable room thermostat for heating only or cooling only systems 3 003 Room hermostat RAA30 Adjustable room thermostat for heating only or cooling only systems Room thermostat with manual O/OFF switch wo-position control witching voltage AC 24 250 V Use he RAA30 room

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

Comm5 Wiring Installation

Comm5 Wiring Installation Comm5 Wiring Installation This wiring information applies to the following Trane products: Tracer Summit systems (Comm5 communications, Version 12.0 and higher) Tracker systems (BMTK models) Tracer loop

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Tracer Summit Web Server

Tracer Summit Web Server Tracer Summit Web Server Web-based access for the Tracer Summit building automation system March 2003 BAS-PRC014-EN Introduction The Tracer Summit Web Server provides the ability to operate a Tracer Summit

More information

Install Guide CT101. Caution. Caution

Install Guide CT101. Caution. Caution Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Workshop 7 PC Software - Tracker

Workshop 7 PC Software - Tracker Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work. Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module

NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date May 5, 2011 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN

Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit

More information

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features: GE Measurement & Control Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

T-100-R Installation Guide

T-100-R Installation Guide T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard

More information

SMM. Installation Operation Maintenance

SMM. Installation Operation Maintenance SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

TAC I/NETTM MR-AHU-HP. Application Specific Controller

TAC I/NETTM MR-AHU-HP. Application Specific Controller TAC I/NETTM MR-AHU-HP Both the MR-AHU and MR-HP controllers are application specific controllers (ASCs). The intention of the design is to reduce total install cost through pre-engineered control algorithms

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

Heating Controller. Building Technologies HVAC Products

Heating Controller. Building Technologies HVAC Products 2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

Thyristor power units and Solid state contactors. TC2000 series. Two-phase control of a three-phase load or control of two single-phase loads

Thyristor power units and Solid state contactors. TC2000 series. Two-phase control of a three-phase load or control of two single-phase loads Thyristor power units and Solid state contactors TC2000 series Two-phase control of a three-phase load or control of two single-phase loads User Manual Copyright Eurotherm Automation 1995 All rights reserved.

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

Flush-mounted room thermostats

Flush-mounted room thermostats s 3 076 RDF300, RDF300.02, RDF340 RDF400.01 RDF600 RDF600 Flush-mounted room thermostats for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units for use with compressors in DX type equipment RDF300

More information

USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920

USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 [This page intentionally left blank] Warning for Your Protection 1. Read these instructions. 2. Keep these

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

ST Series POWER SUPPLIES USER INSTRUCTIONS

ST Series POWER SUPPLIES USER INSTRUCTIONS Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional

More information

How To Size A Stenner Pump

How To Size A Stenner Pump Metering Pumps Manufactured Since 1957 PCM Series Pump Control Module INSTALLATION AND MAINTENANCE MANUAL Table of Contents WarrantyandServicePolicy...3 Safety Information...............................................

More information

Model 3000-51 20 SPDT Relays 90401460

Model 3000-51 20 SPDT Relays 90401460 Model 3000-51 20 SPDT Relays 90401460 Page 1 All technical data and specifications in this publication are subject to change without prior notice and do not represent a commitment on the part of Giga-tronics,

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be

More information

Install Guide 3M-50. Caution. Caution

Install Guide 3M-50. Caution. Caution PG 1 Install Guide 3M-50 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the HVA system before installing or servicing thermostat or any part of the system.

More information

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine

More information

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function Document No. 155-751 SKP15U.. Description Only when assembled to Series VGU Gas valves SKP15 electro-hydraulic actuators combine with

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Safety Manual BT50(T) Safety relay / Expansion relay

Safety Manual BT50(T) Safety relay / Expansion relay Safety Manual BT50(T) Safety relay / Expansion relay ABB Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this document

More information

1756 ControlLogix Chassis Specifications

1756 ControlLogix Chassis Specifications Technical Data 1756 ControlLogix Chassis Specifications Catalog Numbers 1756-A4/B, 1756-A4K/B, 1756-A4/C, 1756-A4K/C, 1756-A7/B, 1756-A7K/B, 1756-A7/C, 1756-A7K/C, 1756-A10/B, 1756-A10K/B, 1756-A10/C,

More information

Installation Instructions

Installation Instructions TP-PRH-A, TP-NRH-A Performance Series Edge Thermidistat Control Installation Instructions Programmable Control A07049 A07048 Non Programmable Control Designed and Assembled in the USA. NOTE: Read the entire

More information

IntesisBox DK-RC-ENO-1iC. EnOcean Interface for DAIKIN Air Conditioners Compatible with SKY and VRV lines

IntesisBox DK-RC-ENO-1iC. EnOcean Interface for DAIKIN Air Conditioners Compatible with SKY and VRV lines IntesisBox DK-RC-ENO-1i DK-RC-ENO-1iC EnOcean Interface for DAIKIN Air Conditioners Compatible with SKY and VRV lines User's Manual r1 eng Issue Date: 02/2012 Intesis Software S.L. All Rights Reserved.

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output Forced current sharing at parallel operation Power OK signal

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information