Best Practices For Underfloor Air Systems

Size: px
Start display at page:

Download "Best Practices For Underfloor Air Systems"

Transcription

1 The following article was published in ASHRAE Journal, October Copyright 2004 American Society of ing, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. Best Practices For Underfloor Air Systems By Mike Filler Between 1995 and 2002, the number of new office buildings with raised floors that use underfloor air distribution (UFAD) increased approximately 40%. 1 This rapid growth can be attributed to four potential benefits UFAD offers over traditional ceiling-based air distribution: 1. Lower churn costs allows for fast and inexpensive reconfiguration of office space, 2. Improved IAQ supplies conditioned air directly to the breathing zone, 3. Lower energy costs reduces fan and refrigeration energy, and 4. Potential to reduce floor-to-ceiling heights creates cost savings in structural and façade systems. Although UFAD has increased in popularity, knowledge of how to apply the technology is not widespread. This article addresses the design, construction and commissioning phases of the UFAD building project. Design Phase: Cooling-Airflow Calculations During the design phase, engineers carefully must determine load calculations for the building. These will differ from the calculations for a ceiling-based air-distribution system. One difference is the amount of a particular load that enters the occupied zone. For a ceiling-based system, the occupied zone is effectively floor-to-ceiling, because the space is well-mixed. For UFAD systems, the occupied zone is the vertical space from the floor to 6 ft (1.8 m) above the floor. This means that some loads never enter the occupied zone. Further, if return-air grilles are placed close to the building s perimeter wall, convective heat gain occurring there can be carried into the return air before it has an opportunity to enter the occupied zone. Both of these factors can reduce the heat load in the occupied zone. Ultimately, this reduction in space heat gain affects the calculation of cooling airflow in direct proportion (see Figure 1). About the Author Mike Filler is a product marketing engineer, Engineered Systems Group, YORK International, York, Pa. O c t o b e r A S H R A E J o u r n a l 3 9

2 Return Grill Return Airway 80 F Unoccupied Zone Ceiling Convective Energy 9 ft 6 ft 76 F Thermostat Occupied Zone Radiant Energy Raised Floor 0 ft 72 F Supply Airway Supply Airway 62 F Figure 1: Typical loads that do and do not enter the occupied zone. Another difference is the room-air temperature that is used for load calculations. With a ceiling-based system, the room-air temperature is considered to be uniform, floor to ceiling. With UFAD, there is temperature stratification within the space, with heat and pollutants concentrated in the upper levels. In fact, ANSI/ ASHRAE Standard allows a vertical temperature variation of 5.4 F (3 C) between head and ankle levels. (If an all-air UFAD system is designed for no stratification in the occupied zone, it will use more airflow, wasting fan energy [see Figure 2]). Because of stratification, it is recommended that engineers consider using 2 3 F (1 2 C) higher thermostatic temperature for UFAD systems, compared to overhead distribution. 2 This should have a direct impact on the cooling airflow calculations. The third airflow-calculation difference concerns the heat transfer from the warm, occupied zone above, and from the warm, return airway below in multistory buildings, into the cool underfloor airway 3 (see Figure 3). This heat transfer and the resulting thermal decay (loss of supply-air cooling ability) should be counted as part of the airflow requirement for each zone. The heat transferred from the occupied zone would be a credit (reduction) for cooling supply airflow quantities. As a rule of thumb, the supply-air temperature should not be allowed to increase more than 3 F (2 C) from the time it enters the underfloor airway until it is discharged into the conditioned space through the furthest terminal. If a greater thermal decay is possible because of a large floorplate, unlined stub ductwork should be used to carry the supply air further into the airway. Design Phase: Variable-Air-Volume Versus Constant-Air-Volume Thermal decay is another good reason to specify a variableair-volume (VAV) UFAD system. It has been found that the supply-air temperature is not always uniform in an underfloor airway, and may change throughout the day. A properly designed VAV/UFAD system is adept at accommodating these temperature variations. There is a belief that placing a manually adjustable diffuser Figure 2: Temperature stratification in UFAD-cooled space. near each occupant will result in greater temperature satisfaction. However, it has been found that most occupants do not understand that they can control airflow in their workspace, and that those who do understand typically do not make changes anyway. 4 As a result, engineers may find that automatic VAV diffusers provide better comfort than manual VAV diffusers. Design Phase: Ventilation In any VAV system, ensuring minimum ventilation is always a concern, because reduced loads could cause supply-air volumes to fall so far that insufficient ventilation is supplied to the room. To prevent inadequate ventilation in VAV/UFAD systems, some manufacturers offer optional collars to serve as a minimum stop for their dampers. Other manufacturers recommend using a series fan-powered VAV box that pulls supply air from the underfloor airway and heats the air as necessary. Minimum-ventilation requirements may also be met if the designer takes into account leakage from the underfloor airway into the conditioned space. Like the ducts in an overhead system, the underfloor airway experiences a small amount of air leakage through diffusers, raised-floor panels, and power-voice-data (PVD) boxes. This leakage may meet much, if not all, of the minimum-ventilation requirement. This will also affect the amount of diffuser airflow needed to satisfy the space heat gain. With precise CO 2 monitoring of the room, UFAD may also be able to reduce overall ventilation-air quantities more than overhead systems. Rather than having to ventilate the entire floor-to-ceiling space, a UFAD system only requires ventilation of the occupied zone. A CO 2 monitoring system will recognize when the occupied zone is adequately ventilated, regardless of the situation above 6 ft (1.8 m). Design Phase: Leakage Rates While a small amount of airway leakage is desirable to handle minimum ventilation requirements, excessive leakage through the floor panels into the space and other uncontrolled airflow 4 0 A S H R A E J o u r n a l a s h r a e. o r g O c t o b e r

3 can cause comfort problems and waste energy. For this reason, it is important to specify and detail how to ensure a leak-tight airway. Engineers need to pay especially close attention to the intersection of floor slabs with exterior walls and interior shafts (for elevators and risers) to ensure proper sealing. Also examine furred-in columns, stud walls penetrating the raised floor, and all penetrations for pipes, ducts, and cables. Because the slab will (hopefully) be tightly sealed, thought should be given to flood control. The structural engineer should determine whether a flood caused by a broken pipe or the sprinkler system would collapse the slab. If that possibility exists, floor drains with pressure valves should be incorporated in the design. Raised-floor leakage rates vary by manufacturer and floorcovering type and layout. During the design phase, specify an airway leak rate no more than the minimum VAV airflow, and specify a leak test to be performed as part of commissioning. A marginal UFAD system may leak as much as 20% to 25% of the system s total air volume, but a good system typically will leak no more than 10% to 15%. While even 10% to 15% leakage may seem excessive to some, it is important to remember that overhead duct systems leak an average of 20% of their airflow, and that leakage flows to the return-air airway and not to the occupied space. Figure 3: Thermal decay in the supply airway. Design Phase: Airway Height It is important to design enough room for and access to the equipment that needs to be located under the raised-access floor (RAF). Space becomes important when it is time to perform routine maintenance or make repairs or adjustments to the equipment. UFAD installations typically use 12- to 18-in. (305 to 457 mm) RAF. Laboratory testing has concluded that the minimum RAF height is 8 in. (203mm) for uniform air-distribution. 5 However, RAF height is often driven by the height of the underfloor fan terminals (if used) or the size of the floorplate. Underfloor fan terminals typically range in height from 8 in. (203 mm) to as much as 16 in. (406 mm) for large cooling-and-heating units. For larger floorplates, the size of the stub-ductwork (typically limited to 22 in. [559 mm] wide to fit between the RAF pedestals) may pose a height constraint. Design Phase: Ductwork and Air Handlers A UFAD system requires some special consideration of the ductwork. In the room, the return-air intake should be sized for a maximum of 500 fpm (2.5 m/s) and be located above the occupied zone. Air moving any faster will disrupt the stratification effect necessary for a properly designed UFAD system. Combination fire/smoke/control-zone dampers (FSDs) should be those specifically designed for modulating control. As with overhead systems, it is important to take into account the effect of air velocities on noise. It is recommended that air velocity entering the supply airway be limited to a maximum of 1,500 fpm (7.6 m/s) to reduce noise. On the other end of the noise spectrum, it should be noted that noise levels of UFAD systems are typically lower than overhead systems. For this reason, engineers may want to consider adding sound masking in low-occupancy areas for acoustic privacy. 6 The air-handling device will be responsible for providing some or all of the minimum ventilation requirement. So, the minimum airflow requirement for each device should be displayed on the mechanical schedule. The air-handling device also should be equipped with some sort of reheat capability, so it can handle the higher supplyair temperatures (SAT) about 60 F (16 C) versus 55 F (13 C) required by these systems without creating a humidity problem in the occupied spaces. In most cases, it is best to use one primary air-handling unit with a return-air bypass (see Figure 4). The typical face-and-bypass arrangement is not the same as the return-air bypass and will result in unacceptably high humidity levels. Other, more expensive reheat methods include modulating hot-gas, run-around heat pipes, or using as many as three fans (not including a return or relief fan) to supply air to perimeter zones. Design Phase: Control Systems Controls for an UFAD system are similar to those of an overhead VAV system, except the SAT is designed for a minimum of 60 F dry bulb 3, and the static pressure (SP) differential pressure between the airway and the occupied space is nominally designed for 0.05 in. w.g. (0.012 kpa). Some manufacturers may recommend higher airway SP (up to 0.10 in. w.g. [0.025 kpa]). However, this will increase uncontrolled leakage, theoretically by more than 40%. At light loads, the SAT is typically reset upward, and SP downward, to prevent overcooling and to maximize free-cooling (economizer) hours. Night set-back should be minimized to maintain proper building control, and morning warm-up will not work because of the thermal effects of the building slab. The control sequence also should have the ability to lower the off-coil temperature, based on the level of underfloor RH, in order to prevent condensation and maintain comfortable humidity levels in the space. Be aware that UFAD components use a number of different types of controls. By working with component manufacturers, design engineers can secure sequences of operation for the diffusers, actuators and fan-powered units necessary for proper zone control. O c t o b e r A S H R A E J o u r n a l 4 1

4 Construction Phase During the construction phase, contractors must be aware that the floor slab, ceiling, walls and column enclosures are the structure of the supply and return airways, and they must act to preserve the integrity of the airways. This means informing all trades of their responsibility with respect to sealing the airways. To ensure proper installation and operation of the underfloor system, here is a typical sequence of interior construction that takes place only after final design-layout drawings have been issued. Install and finish all fire-rated demising walls. Install ceilings and ceiling systems. Complete the floor slabs, sealing them as dictated by building codes and project specifications, and checking to be certain they are level. Mark the RAF pedestal-support-grid layout on the floor slab, being certain the grid lines match up with the main supply and branch ductwork. Install and prepare all fan-powered units, diffusers, and any associated ductwork before the RAF is installed. Install pressure-control dampers and FSDs, fan-terminal ductwork, and branch ductwork while the RAF is being installed to ensure proper room for the ductwork. Clean and vacuum the slab before cabling is installed. A clean airway prevents dust from being blown throughout the space during startup. Install all wiring systems on the slab and coordinate the systems with the floor-pedestal marks. Set up a workstation to install the UFAD terminals in the RAF panels, expediting the installation of floor pedestals, panels, and PVD boxes. Overlay the wiring (preferably plugand-play cabling) on the UFAD drawings. Unique tag numbers are often unnecessary for the UFAD drawings, because typically only a few types of diffusers and fan terminals are used. Install the RAF pedestals and panels, including those with UFAD terminals and PVD boxes. It is recommended that diffusers or control items not be installed along known partition lines or under furniture. Install diffusers in the correct orientation on floor panels and panels in the RAF to ensure airflow patterns match the drawings. In larger floorplates, i.e., when the diffusers are located within 15 ft (4.6 m) of the supply duct, install the diffusers with the inlet facing away from the air supply to avoid a velocity effect from the ductwork. (However, some diffusers have inlets on all sides and do not allow this.) Orient directional grilles to provide the desired airflow pattern. At the perimeter, airflow should be directed along and/or away from the exterior walls, while grilles in the interior should create an outwards circular pattern. An outward pattern allows for the greatest amount of induction and is recommended for initial installment, even if occupants change the pattern once the building is in use. Construct partition walls on the top of the RAF, covering Advertisement formerly in this space. 4 2 A S H R A E J o u r n a l a s h r a e. o r g O c t o b e r

5 Return Air High-Efficiency Filters Damper Outside Air Dampers Filters Cooling Coil Supply Fan Supply Air Figure 4: Air-handling unit with return-air bypass. the floor and any openings or air-distribution terminals to keep construction debris from entering the floor airway. Apply finishes to the walls. Remove the covering from the RAF and vacuum. Lay carpet on the RAF panels. Install furniture. Ensure all plug-and-play cable connections are properly connected and engaged in mating connectors. (This can be accomplished earlier, when the RAF is installed, depending on the sequence of the trades.) Vacuum all construction debris in the diffusers. (This is not necessary if diffuser protective sheets were used earlier.) Commission the mechanical systems. Advertisement formerly in this space. Commissioning Phase Following the construction phase, the UFAD system is commissioned, which should include an airway-leakage test and an airflow test. Begin by testing each primary supply fan to check for minimum airflow with all diffusers closed or at the minimum stop. If uncontrolled leakage (leakage not coming through the diffusers and not what is expected through the floor) is too high, the leakage needs to be found and corrected, and the primary supply fan must be retested. The leakage test itself should be repeated every few years or after any remodeling that includes reconfiguring the UFAD system. An airflow/sp test determines that the system can provide adequate air to all diffusers. Typically, test one diffuser per zone and verify that the zone controllers are functioning properly (based upon the predefined sequence of operation). Balancing the diffusers is necessary only on ducted diffusers (often used along the perimeter). Educate Building Occupants on UFAD After commissioning, building owners and occupants assume responsibility for the optimal operation of the UFAD system. The owner or facility manager should secure a complete set of as-built drawings, establishing the grid system and lo- O c t o b e r A S H R A E J o u r n a l 4 3

6 cating all UFAD components and controls. This grid system needs to be revised whenever changes are made to the UFAD system. It is also important for the owner to train maintenance people to operate the UFAD system. Begin by providing them with applicable service manuals that explain the operation and maintenance of the system, and review the manuals with them. Pay special attention to the impact of room-temperature stratification on comfort and control, as well as the control functions to reset the RH, supply-air temperature and floor SP as needed. If applicable, any control options should be explained, such as providing a pocket digital assistant as a maintenance tool. Finally, it is important to inform the building occupants about the UFAD system. Stress with them the importance of periodically vacuuming the underfloor airway as well as cleaning up spills. Explain the benefits of the system to them, including comfort, improved IAQ, flexibility, and energy efficiency. Point out the location of the diffusers and the availability of individual diffusers to meet special needs. Identify the location of thermostats and sensors for individual work areas or zones, their functions and how to use them, and provide contact information to register comfort complaints. Buildings with UFAD may require more thought during the design phase, especially when designers are working on their first building with UFAD. However, if best practices are carefully followed and the proper coordination occurs on the UFAD job, then the process can be smoother, shortening the construction cycle, ensuring a successful commissioning process, and ultimately securing the advantages in system flexibility, IAQ, and energy efficiency that are contributing to the rapid growth of UFAD. References 1. Bauman, F Underfloor Air Distribution Design Guide. American Society of ing, Refrigerating, and Air-Conditioning Engineers, Inc. 2. Webster, T., F. Bauman, J. Reese. 2002b. Underfloor air distribution: thermal stratification. ASHRAE Journal, May. 3. YORK International. 1999, YORK Modular Integrated Terminals: Convection Enhanced Ventilation Technical Manual. 4. Webster, T., R. Bannon, D. Lehrer Teledesic Broadband Center Field Study. Center for the Built Environment, University of California, Berkeley. April. 5. Bauman, F., P. Pecora, T. Webster How low can you go? Air flowperformance of low-height under-floor plenums. Center for the Built Environment, University of California, Berkeley. October. 6. Tate Raised Access Floors and Office Acoustics. Tate Technical Bulletin #235. Advertisement formerly in this space. 4 4 A S H R A E J o u r n a l a s h r a e. o r g O c t o b e r

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering

Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Challenges and Failures in Green Building Design Using Under-Floor Air Distribution Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Agenda UFAD Overview Challenges / Failures Steps for a Successful

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

Dehumidification Design

Dehumidification Design Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible

More information

Center for the Built Environment UC Berkeley

Center for the Built Environment UC Berkeley Center for the Built Environment UC Berkeley Peer Reviewed Title: Analysis of a hybrid UFAD and radiant hydronic slab HVAC system Author: Raftery, Paul, National University of Ireland Galway Lee, Kwang

More information

MULTIZONE APPLICATION OF SOLUTION UNITS

MULTIZONE APPLICATION OF SOLUTION UNITS MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages

More information

UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS

UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS UNDER FLOOR AIR DISTRIBUTION (UFAD) SOLUTIONS OVERHEAD SYSTEM UFAD SYSTEM ...... - A product of AirFixture USA I DON T CARE ZONE B R E A T H I N G Z O N E W E L L M I X E D CONSTANT VOLUME DIFFUSER WITH

More information

AIR DISTRIBUTION FOR COMFORT AND IAQ

AIR DISTRIBUTION FOR COMFORT AND IAQ AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant

More information

UNDERFLOOR AIR DISTRIBUTION

UNDERFLOOR AIR DISTRIBUTION FINAL REPORT NCEMBT-080801 UNDERFLOOR AIR DISTRIBUTION AN EXPERIMENTAL COMPARISON OF AIR DIFFUSION PERFORMANCE BETWEEN UNDERFLOOR AIR DISTRIBUTION AND CONVENTIONAL OVERHEAD AIR DISTRIBUTION SYSTEMS AUGUST

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

Galina Stankevica. Master of Science in Engineering and ICT

Galina Stankevica. Master of Science in Engineering and ICT Commissioning of the HVAC-plant in a large office building designed with an underfloor ventilation system including input into what should be emphasized when evaluating the total system is to be done.

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

Flexibility, Efficiency In San Antonio Arena

Flexibility, Efficiency In San Antonio Arena 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not

More information

Design Options for HVAC Distribution Systems

Design Options for HVAC Distribution Systems Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)

More information

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic

More information

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2 providing insights for today s hvac system designer Engineers Newsletter volume 42 2 Understanding Single-Zone VAV Systems Single-zone variable-air-volume (VAV) is not a new concept, but due to new energy

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History

Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems Ryan R. Hoger, LEED AP 708.670.6383 ryan.hoger@tecmungo.com History VAV systems came into favor for mid and large size

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Residential Duct Systems for New and Retrofit Homes

Residential Duct Systems for New and Retrofit Homes Residential Duct Systems for New and Retrofit Homes Why it is important to properly design and install high quality, efficient ducted air systems? The efficiency of air distribution systems has been found

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

Active & Passive Beams

Active & Passive Beams Active & Passive Beams Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building and service the

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Air Conditioning Contractors of America

Air Conditioning Contractors of America Air Conditioning Contractors of America WHO IS ACCA???? Industry Manuals Residential D, J, S, H, RS, T, P A manual J load calculation is a measurement of how much heating and cooling capacity a home will

More information

Performance Rating of Room Fan- Coils

Performance Rating of Room Fan- Coils ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS

More information

LITERATURE REVIEW OF FLEXIBLE AND ADAPTIVE HVAC DISTRIBUTION SYSTEMS FOR OFFICE BUILDINGS. Xin Yu and Theodore F. Smith

LITERATURE REVIEW OF FLEXIBLE AND ADAPTIVE HVAC DISTRIBUTION SYSTEMS FOR OFFICE BUILDINGS. Xin Yu and Theodore F. Smith LITERATURE REVIEW OF FLEXIBLE AND ADAPTIVE HVAC DISTRIBUTION SYSTEMS FOR OFFICE BUILDINGS Xin Yu and Theodore F. Smith Department of Mechanical Engineering The University of Iowa Iowa City, Iowa 52242

More information

underfloor air distribution

underfloor air distribution hospitals fire rated woodgrains energy solutions Redefine your comfort zone. www.titus-hvac.com Table of Contents products UnderFloor Air Distribution Products... 4 overview Application Guide... 8 Introduction

More information

Dual Maximum VAV Box Controls

Dual Maximum VAV Box Controls ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How

More information

Design Options For HVAC Distribution System

Design Options For HVAC Distribution System PDHonline Course M147 (4 PDH) Design Options For HVAC Distribution System Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution.

SECTION EG. Engineering Guide Air Distribution. Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. SECTION EG Air Distribution Please refer to the Price Engineer s HVAC Handbook for more information on Air Distribution. Space Air Diffusion AIR DISTRIBUTION ENGINEERING GUIDE Proper selection of air diffusion

More information

L EED & G r e e n B u i ldi ngs

L EED & G r e e n B u i ldi ngs L EED & G r e e n B u i ldi ngs A P P L I C AT I O N G U I D E contents 3 - General 3 - Introduction 3 - Leadership in Energy & Environment 3 - Purpose 3 - LEED Rating System 4 - Energy & Atmosphere 4

More information

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

engineers newsletter air distribution Cold Air Makes Good $ense Benefits of Cold Air How Cold Is Cold?

engineers newsletter air distribution Cold Air Makes Good $ense Benefits of Cold Air How Cold Is Cold? engineers newsletter providing insights for today s hvac system designer air distribution Cold Air Makes Good $ense from the editor Since 1995, the Engineers Newsletter has examined various aspects of

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client Order of Magnitude Mechanical Estimating Justin Apprill, P.E. Topics for Today Estimate Goals A Concept for Accurate Conceptual Estimating HVAC Systems Common System Types and Rules of Thumb Pricing Example

More information

Raised Floor Data Centers Prepared for the Future

Raised Floor Data Centers Prepared for the Future Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The

More information

Noise in the Classroom

Noise in the Classroom ASHRAE JOURNAL Copyright 2000, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission of ASHRAE Journal. This article may not be copied nor distributed

More information

Acoustic Design Practices for Sustainable Buildings

Acoustic Design Practices for Sustainable Buildings Acoustics 2008 Geelong, Victoria, Australia 24 to 26 November 2008 Acoustics and Sustainability: How should acoustics adapt to meet future demands? Acoustic Design Practices for Sustainable Buildings Danny

More information

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA.

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP)

Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP) Lee, K.S., Xue, G., Jiang, Z., and Chen, Q. 0. Thermal environment in indoor spaces with under-floor air distribution systems:. Impact of design parameters (5-RP), HVAC&R Research, 8(6), 8 9. Thermal environment

More information

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA. 1. There is verbiage in the hazardous material report referring to a state licensed abatement contractor. Within the recommendations part of the report (page 64 of 111 of the specification pdf) is the

More information

SECTION 15936 AIR INLETS AND OUTLETS

SECTION 15936 AIR INLETS AND OUTLETS SECTION 15936 AIR INLETS AND OUTLETS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers. 3. Grilles. 4. Louvers. 5. Lowered Penthouses. 6. Gravity Roof Hoods. 7. Gravity Roof

More information

HVAC Characteristics. Test Space HVAC Characteristics

HVAC Characteristics. Test Space HVAC Characteristics HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,

More information

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY

SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Building Performance Solutions HVAC Design Guide, 2007

Building Performance Solutions HVAC Design Guide, 2007 Building Performance Solutions HVAC Design Guide, 2007 HVAC sizing, system design, layout, and installation shall be sized according to (Air Conditioning Contractor of America), ACCA manual J8, 8 th edition,

More information

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

THREE. Heating and Cooling

THREE. Heating and Cooling THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,

More information

HVAC SYSTEMS ACOUSTICAL, COST & ENERGY STUDY

HVAC SYSTEMS ACOUSTICAL, COST & ENERGY STUDY HVAC SYSTEMS ACOUSTICAL, COST & ENERGY STUDY Prepared for the Los Angeles Unified School District Facilities Services Division June 6, 2005 By Maroko & Shwe, Inc., Professional Engineers With Schaffer

More information

AIR LEAKAGE TEST REPORT EPA REGION 8 HEADQUARTERS, DENVER, CO

AIR LEAKAGE TEST REPORT EPA REGION 8 HEADQUARTERS, DENVER, CO AIR LEAKAGE TEST REPORT EPA REGION 8 HEADQUARTERS, DENVER, CO Fred Bauman, Tom Webster, and Darryl Dickerhoff Center for the Built Environment (CBE) University of California, Berkeley August 2008 ACKNOWLEDGMENTS

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved. 3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning

More information

Radiant Panels and Chilled Sails. www.price-hvac.com

Radiant Panels and Chilled Sails. www.price-hvac.com Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)

More information

Suspended ceiling or open plenum?

Suspended ceiling or open plenum? CI/SfB (35) Xy 04/2015 Suspended ceiling or open plenum? Making the right choice. Recent studies illustrate the positive impact of suspended ceilings on life cycle costs, fire safety and the acoustic environment.

More information

Tate s Wire & Cable Solution

Tate s Wire & Cable Solution Access Floors Tate s Wire & Cable Solution A Flexible & Sustainable Management System Access Flooring to the Power of Your company will discover complete flexibility and reconfiguration capability 2 Creating

More information

Riverside City College. Math & Science Building HVAC Investigation. May 23, 2013

Riverside City College. Math & Science Building HVAC Investigation. May 23, 2013 May 23, 2013 Prepared by: P2S Engineering, Inc. 5000 East Spring St, Eighth Floor Long Beach, CA 90815 T 562.497.2999 F 562.497.2990 www.p2seng.com Table of Contents Executive Summary... 2 Background...

More information

Terms of Reference Air Handling Unit (HVAC System) Cleaning

Terms of Reference Air Handling Unit (HVAC System) Cleaning Terms of Reference Air Handling Unit (HVAC System) Cleaning Introduction General cleaning of the air handling units is currently undertaken by the Mechanical Division staff composing of 3 personnel. Cleaning

More information

Rev. No. 0 January 5, 2009

Rev. No. 0 January 5, 2009 ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January

More information

Printing and Publishing Energy Savings Guide

Printing and Publishing Energy Savings Guide Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand

More information

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained). CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement

More information

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Integrated Solar Radiant Systems

Integrated Solar Radiant Systems Integrated Solar Radiant Systems William Shady PE President Topics Radiant heating Indoor air quality Radiant Cooling Project Photos Questions and answers The goal for our clients Healthy Comfort Why Radiant

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

FIRE DAMPER APPLICATION GUIDE

FIRE DAMPER APPLICATION GUIDE FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire

More information

SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)

SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following

More information

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly

More information

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work? engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort

More information

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

energydesignresources design brief

energydesignresources design brief energydesignresources design brief UNDERFLOOR AIR DISTRIBUTION AND ACCESS FLOORS Underfloor air distribution and access floor systems can provide Summary Underfloor air distribution and access floor systems

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information