SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

Size: px
Start display at page:

Download "SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)"

Transcription

1 SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for the Air Cooled Packaged Units including associated ductwork covered by this Contract. The Services shall be carried out at the intervals stated below unless otherwise stated in the Equipment and Pricing Schedule. 2.0 MINIMUM STANDARD The minimum standards for periodic inspection and servicing shall be as stated below and in accordance with the requirements of the current editions of: Fire and Rescue Service Act Building Act and Building Fire Safety Regulations BCA Building Code of Australia QDC MP 6.1 Maintenance of Fire Safety Installations AS 1851 Maintenance of Fire Protection Systems and Equipment AS/NZS 3788 Pressure equipment - In-service inspection AS 3873 Pressure equipment - Operation and maintenance AS/NZS Air-handling and water systems of buildings Microbial control Part 2: Operation and maintenance HB 40 The Australian Refrigeration and Air-conditioning Code of Good Practice 3.0 MINIMUM QUALIFICATIONS The Contractor shall ensure that it has the appropriate licences issued by the Queensland Building Services Authority to perform the services under the Contract and must provide evidence to the satisfaction of the Principal. The Contractor shall also ensure that persons who carry out required tests, services or make logbook entries are qualified in Refrigeration, Air Conditioning and Mechanical Services, with: a) Expertise in the servicing and repair of packaged air conditioning units b) Accreditation in the handling of Ozone Depleting Substances The Contractor shall hold valid licences issued under the Ozone Protection and Synthetic Greenhouse Gas Management Act 1989 as follows: National Refrigerant Trading Authorisation in the name of the company undertaking the work of the Contract. National Refrigerant Handling licence in the name of each employee of the company who is likely to handle refrigerants in undertaking the work of the Contract. The above licences shall be produced upon request by the Principal's Representative. 4.0 REFRIGERANT MANAGEMENT All maintenance and work practices are to be in accordance with The Australian Refrigeration and Air-conditioning Code of Good Practice (HB 40). All refrigerant usage is to be recorded. Whilst undertaking servicing, maintenance and repairs to equipment of this Contract, service personnel shall take all necessary precautions to ensure that no refrigerant is released to the atmosphere. All refrigerant is to be recovered using an approved recovery unit. It is the responsibility of the Contractor to provide a suitable recovery unit for the installations of the Contract. Document: TSW00010 Date Issued: Page 1 of 7

2 All clean recovered refrigerant may be re-used. The Contractor shall ensure that the re-use of recovered refrigerant does not cause any system malfunction due to unacceptable contamination. Recovered contaminated refrigerant shall not be re-used. 5.0 MAINTENANCE REQUIREMENTS AND FREQUENCY Perform all the service requirements as detailed below: 5.1 Refrigeration Compressors 1 Measure suction and discharge pressures. 2 Check all safeties and pressure gauges. 3 Ensure the unloading mechanism and controls are functioning correctly. 4 Inspect and record oil level and pressure including crankcase heater condition. 5 Inspect compressor motor coupling and / or pulleys and belts where applicable. 6 Test for and repair refrigerant and oil leakage. 7 Check for undue noise and vibration. 8 Measure and record motor amperage. Compare with nameplate rating. 9 Change sequence switch and ensure correct operation. 10 Clean compressor, base and motor casing. 11 For open compressors take an oil sample from each compressor and analyse for acid, moisture, etc. If an oil change is required, liaise with the principal's representative regarding approval. 12 Check compressor motor terminals for hot connections, undertake resistance test of windings and record readings. 13 Check operation efficiency of suction discharge valves. 5.2 Air Cooled Condensers 1 Check operation and condition of fans including fan cycling operation for head pressure modulating. 2 Check efficiency of condenser operation by reading compressor discharge pressure and report any abnormal function. 3 Clean condenser coils by hosing with water. 4 Report abnormal high noise level. Document: TSW00010 Date Issued: Page 2 of 7

3 5 Treat and paint corrosion as necessary. 6 Measure motor amperage and compare ratings. 7 Change lead-lag sequence on fan motors and calibrate head pressure modulating device. 8 Comb all condenser fins straight. 9 Supply and replace all belts on belt drive units. 10 Report on overall condition and indicate when replacement required. 5.3 Air Handling Unit and Air Filters 1 Clean and flush condensate trays and drains. Ensure drain is running free. Leave tray dry. 2 Inspect cooling and heating (if fitted) coils: Comb fins straight and clean coils as required, using biodegradable, non-toxic, water-based odour-free foaming detergent. Provide MSDS prior to the first service or on request. Rinse coils thoroughly with clean water after applying detergents. 3 Check air filters (dry media): Check integrity of filter seals to ensure there is no air bypass. Check that restraining brackets hold the filter frames securely and that the filter media is securely fastened. Repair filter handles and frames as required. Record pressure-drop across filters. If pressure-drop is excessive, report the circumstances to the principal s representative for further instructions. Note: supplying washable filter media and/or washing existing filter media are not acceptable. If removing dirty filter media from site, take care to avoid soiling floor coverings and other furnishings etc. Fans are to be turned off while filters are being inspected and/or changed. After completing the work, ensure the fans are turned on and operable. Remove filter debris from the chamber and leave clean and tidy. Document: TSW00010 Date Issued: Page 3 of 7

4 4 Check unit and seals for air leakage. 5 Check panels, doors and fastenings for security and air leaks. Repair any air leaks. 6 Check that insulation is clean and secure. Repair as required. 7 Check that all automatic volume control dampers and linkages are fully operable. Lubricate, using a dry lubricant, as required. 8 Check that all automatic volume control dampers seal tight when closed. 9 Check and record air on coil, air off coil, room, return air and outside air temperatures. 10 Check complete unit for corrosion or deterioration. 5.4 Fans and Motors Supply or Return Air used in Day-To-Day Operation Item 1 Obstructions Check there are no physical obstructions likely to impede performance. 2 Noise, Check motor and all bearings for noise, overheating and overheating and vibration excessive vibration. 3 Flexible Check flexible connections, where fitted, for leaks, tearing connections or fraying. 4 Fan belts (wear) Check fan belts for wear. 5 Guards and Check for satisfactory condition. other safety features 6 Bearings Check lubrication of bearings and lubricate as required. 7 Couplings Check couplings for tightness. 8 Fan belts Check for correct tension. (tension) 9 Fan blades Clean fan blades and scrolls. 10 Pulley wheels Check pulley wheels and couplings for alignment. and couplings 11 Casing guards Check casing, guards and impeller for corrosion. and impeller 12 Fan belts Supply and replace all drive belts. 13 Electrical Check electrical connections, isolators and terminal box. Document: TSW00010 Date Issued: Page 4 of 7

5 5.5 Ductwork 1 Check ductwork for air leakage. Repair minor leaks. 2 Check external insulation for retainment. Repair as required. 3 Check and clean all fresh air intakes, return air grilles, exhaust outlets and air relief transfer grilles. 4 Report severe deterioration of ductwork, insulation, dampers, heater banks and any build up of impurities. 5 Check integrity of flashing at external penetrations. 6 Check that all automatic terminal units are fully operable and that linkages are free to move. 7 Check that manual volume control dampers are correctly positioned and are freely adjustable. 8 Check and clean the following: Ductwork in the vicinity of moisture producing equipment. Drainage facilities associated with moisture producing equipment. Air terminal units, including air registers. Steam and spray humidifiers, including line strainers, valves, sparge pipes, spray nozzles and other components discharging moisture into the airstream. 5.6 Air conditioning controls Item no. Service item 1 Check for burnt wiring. 2 Check all fuses. 3 Check all meters for correct operation. 4 Check all contactors for correct operation. 5 Ensure all relays are secure. 6 Test all run and fault lights. Supply and replace faulty switchboard/panel lights. 7 Ensure all cable duct covers are in place and secure. 8 Ensure all control covers are in place and secure. 9 Clean inside of switchboard/control panel. 10 Check operation of air compressor and drain vessel where applicable. 11 Check staging controls for correct operation. Report short cycling to Principal s Representative. Document: TSW00010 Date Issued: Page 5 of 7

6 Item no. Service item 12 Check all temperatures and adjust if required. 13 Ensure all room thermostat covers are in place and secure. 14 Check set points of all controls for accuracy - recalibrate as required. 15 Ensure safety controls and devices are controlling at the recommended value. 16 Test all manual over-ride switches. 17 Test operation of all test switches. 5.7 System Shutdown (where applicable) Item 1 Full simulation Fully simulate a fire/smoke situation from any device such as a sprinkler, thermal or smoke detector, to effect shut-down of all air conditioning and mechanical ventilation systems not required to operate in fire mode (see clause of AS 1851). Check all systems required to shut down are not operating. 5.8 Pressure Vessels - Internal And External Inspection (where applicable) The minimum standards for periodic inspection and servicing shall be as stated below and in accordance with the current requirements of AS\NZS Inspections are required for vessels that contain either: 1) Group 1 refrigerants 1 when the vessel has pv > 200MPa.L 2 ; or 2) Any refrigerant from Group A2, A3 and B External Inspections 1 Inspect external surfaces of vessel for pitting. 2 Inspect external surfaces of vessel for cracks or splitting. 3 Inspect vessel for distortion or bulging. 4 Inspect vessel for corrosion. Repair as required. 1 Refer AS/NZS Group A1 refrigerants include R22, R123, R 134a and R4xx blends. Group B2 includes R717 (Ammonia) and Groups A2 and A3 contain the flammable refrigerants Propane, butane etc 2 Where p = design pressure of vessel in MPa (mega-pascals) and V=water volume of vessel in litres Document: TSW00010 Date Issued: Page 6 of 7

7 Remove all deposits and debris build-up from and around vessel. 6 Inspect condition of welds. 7 Inspect condition of all sockets, studs and flanges. 8 Inspect access panels for damage and sealing integrity. 9 Inspect vessel for leaks Internal Inspections 1 Inspect internal surfaces of vessel for pitting. 2 Inspect internal surfaces of vessel for cracks or splitting. 3 Inspect vessel for distortion or bulging. 4 Remove all deposits from vessel. 5 Inspect access panels for damage and sealing integrity. 6 Inspect vessel for leaks after reinstatement of access panels General 1 Supply a complete and concise report on each internal and external inspection. 2 Contact the Principal s Representative if further work is required. 3 On completion of inspection the Contractor shall fix an aluminium tag (business card size) to the equipment. The tag shall indicate the contractor s name, the Date Tested and the Next Test Date for both internal and external inspections. Document: TSW00010 Date Issued: Page 7 of 7

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient

More information

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

Action Plan Template HVAC Page 1

Action Plan Template HVAC Page 1 Action Plan Template HVAC Page 1 Once Establish expected HVAC system efficiency - Write down the expected efficiency of HVAC systems to use as a baseline - Add this information to maintenance plan documentation

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013. Issued by: NH Liquor Commission. PO Box 503, Concord, NH 03302

REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013. Issued by: NH Liquor Commission. PO Box 503, Concord, NH 03302 REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013 Issued by: NH Liquor Commission PO Box 503, Concord, NH 03302 This Page intentional left blank TABLE OF CONTENTS EXHIBITS...

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering

More information

A Guide to Trouble-Free Cooling Towers

A Guide to Trouble-Free Cooling Towers A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic

More information

Training Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test

Training Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test APTA STANDARDS DEVELOPMENT PROGRAM RECOMMENDED PRACTICE American Public Transportation Association 1666 K Street, NW, Washington, DC, 20006-1215 APTA BTS-BMT-RP-001-10 Approved October, 2010 APTA Bus Maintenance

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

Boiler and Burner Cleaning and Servicing Specifications

Boiler and Burner Cleaning and Servicing Specifications Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service

More information

HVAC Preventative Maintenance Basics. Presented by Mike Crawley

HVAC Preventative Maintenance Basics. Presented by Mike Crawley HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow

More information

Terms of Reference Air Handling Unit (HVAC System) Cleaning

Terms of Reference Air Handling Unit (HVAC System) Cleaning Terms of Reference Air Handling Unit (HVAC System) Cleaning Introduction General cleaning of the air handling units is currently undertaken by the Mechanical Division staff composing of 3 personnel. Cleaning

More information

Preventive Maintenance. Learning Objectives: Howdy! Learning Objectives Cont:

Preventive Maintenance. Learning Objectives: Howdy! Learning Objectives Cont: Preventive Maintenance Fountain of Youth for HVAC Successful Learning Environment Bonus Strategies James D. McClure, P.E. Action Planning Guide As you listen to this presentation, use the chart in your

More information

First irst Co. Products

First irst Co. Products First irst Co. Products Recommended Maintenance Program PM1193 FIRST OPERATIONS,LP - P.O. Box 270969 - Dallas, Texas 75227 - www.firstco.com Table of Contents Introduction... 3 General Precautions... 3

More information

3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com

3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor

More information

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

THREE. Heating and Cooling

THREE. Heating and Cooling THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,

More information

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved. 3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

REFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR

REFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR REFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR Sub.: Day-to-Day operation contract & maintenance for 2 X 40 TR &1 X 20 TR DX type Central AC Plant of Netaji Auditorium of IIT Kharagpur Ref.: IIT/RAC/Netaji/OC

More information

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE

More information

MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE

MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE Faculty are required to have the outline submitted to the Academic Affairs Office. The course outline is the form used for approval of new courses

More information

Maintenance for Energy Efficiency

Maintenance for Energy Efficiency Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS

FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS To be used in conjunction with the Fire Protection Association Australia FPS4-2000: Agreement

More information

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1

More information

SL280UHV SERIES GAS FURNACE WARNING

SL280UHV SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and

More information

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport. ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS

More information

MIDLAND COLLEGE SYLLABUS DEMR 1323 AUTOMOTIVE HEATING AND AIR CONDITIONING 2-4

MIDLAND COLLEGE SYLLABUS DEMR 1323 AUTOMOTIVE HEATING AND AIR CONDITIONING 2-4 Course Description: Text, References and Supplies: Course Goals/Objectives: Theory of automotive air conditioning and heating systems. Emphasis on the basic refrigeration cycle and diagnosis and repair

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

HEATER, AIR CONDITIONING AND VENTILATION

HEATER, AIR CONDITIONING AND VENTILATION 55-1 GROUP 55 HEATER, AIR CONDITIONING AND VENTILATION CONTENTS GENERAL DESCRIPTION 55-2 HEATER AND AIR CONDITIONING SYSTEM 55-4 HEATER CONTROL 55-6 A/C-ECU 55-7 A/C COMPRESSOR 55-9 CONDENSER 55-9 DUCT

More information

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC & hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

PC1130 Electric Air Compressor

PC1130 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

Split Air Conditioner

Split Air Conditioner Split nditioner plit itsplit ir onditioner Split Split Split Split Split User s WNER'S 'S ER'S For s: AWI/AWO-21HPR1 Delta AWI/AWO-25HPR1 Delta AWI/AWO-32HPR1 Delta AWI/AWO-53HPR1 Delta AWI/AWO-65HPR1

More information

ENGINE COOLING SYSTEM

ENGINE COOLING SYSTEM ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

STATEMENT OF WORK FOR MAINTENANCE OF AIR CONDITIONERS

STATEMENT OF WORK FOR MAINTENANCE OF AIR CONDITIONERS STATEMENT OF WORK FOR MAINTENANCE OF AIR CONDITIONERS 1) SCOPE: The successful bidder (Contractor) is responsible to perform periodic routine preventive maintenance and repair of all accepted air conditioner

More information

Competency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6

Competency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6 Table of Contents (MEC 6)... 1 Function: Operate Vessel Machinery and Systems... 1 Diesel engines.... 1 Operational procedures.... 3 Operate and monitor a vessel s engines and auxiliary equipment.... 4

More information

Heat Pump Water Heater IOM Manual

Heat Pump Water Heater IOM Manual Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump

More information

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00 RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls

More information

FOXAIR 60/50 ALL MODELS

FOXAIR 60/50 ALL MODELS FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

PC1131 Electric Air Compressor

PC1131 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

Six Monthly Servicing of Fire Extinguisher on Commercial Vessels.

Six Monthly Servicing of Fire Extinguisher on Commercial Vessels. Marine Safety Notice to Industry Number: 34 Date of Issue: 17 January 2012 Six Monthly Servicing of Fire Extinguisher on Commercial Vessels. This Notice to Industry is to clarify the requirements for the

More information

USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide

USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide GUIDE EQUIPMENT TYPE & TASKS FREQUENCY A-1 Air Dryer 1. Lubricate valves and replace packing, if necessary 2. Check

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

Home Maintenance Checklist

Home Maintenance Checklist Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your

More information

How to Maintain an Air Conditioner

How to Maintain an Air Conditioner How to Maintain an Air Conditioner by Fix-It Club How to Troubleshoot a Central Air Conditioning System Publications International, Ltd. Central air conditioners are made up of two separate components:

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around

More information

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and

More information

Elements Elements describe the essential outcomes.

Elements Elements describe the essential outcomes. AURETU005 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. Retrofit and modify air conditioning and HVAC systems This unit describes the performance outcomes

More information

10 tips for getting more reliability from your air-conditioning system [reliability]

10 tips for getting more reliability from your air-conditioning system [reliability] 10 tips for getting more reliability from your air-conditioning system [reliability] A guide for installers, specifiers, contractors and architects February 2010 10 tips for getting more reliability from

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

Preventative Maintenance Plan. Guide. The Simple, Smart Way To Properly Care For Home Systems And Appliances.

Preventative Maintenance Plan. Guide. The Simple, Smart Way To Properly Care For Home Systems And Appliances. Preventative Maintenance Plan Guide The Simple, Smart Way To Properly Care For Home Systems And Appliances. Protect. Prevent. Preserve. Prolong. What AHS Preventative Maintenance Plans Can Do For Your

More information

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions

More information

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace) UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system

More information

Chapter 7 Hydraulic System Troubleshooting

Chapter 7 Hydraulic System Troubleshooting Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06 A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

AABC Specifications for Testing and Balancing HVAC Systems

AABC Specifications for Testing and Balancing HVAC Systems AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL

More information

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump

MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

SYSTEM Inverter Air Conditioners

SYSTEM Inverter Air Conditioners OPERATION MANUAL SYSTEM Inverter Air Conditioners MODEL Ceiling Suspended type FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU Read these instructions carefully before installation. Keep this manual in a handy place

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information

INVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl.

INVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. INVOICE DATE: May 11, 2005 CLIENT: The Buyer DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. TOTAL FEE: $ See Schedule Tom Villani Hallmark Inspection

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning NORSOK STANDARD H-001 Rev. 4, Nov. 2001 Heating, ventilation and air-conditioning This NORSOK standard is developed by NTS with broad industry participation. Please note that whilst every effort has been

More information

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6

More information

Pump Maintenance - Repair

Pump Maintenance - Repair Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

Australian/New Zealand Standard

Australian/New Zealand Standard Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The

More information

Acumen Enterprises, Inc.

Acumen Enterprises, Inc. Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter

More information