KINGSTONS HOUSE ENVISAGED BASEMENT CONSTRUCTION SEQUENCE

Size: px
Start display at page:

Download "KINGSTONS HOUSE ENVISAGED BASEMENT CONSTRUCTION SEQUENCE"

Transcription

1 Intended for J Document type Kingstons House Envisaged Basement Construction Sequence Date August, 2015 KINGSTONS HOUSE ENVISAGED BASEMENT CONSTRUCTION SEQUENCE

2 KINGSTONS HOUSE ENVISAGED BASEMENT CONSTRUCTION SEQUENCE Revision 01 Date 14/08/2015 Made by Grace Richardson Checked by Chris Papanastasiou Ref Kingstons House Envisaged Basement Construction Sequence Ramboll 240 Blackfriars Road SE1 8NW T +44 (0)

3 CONTENTS 1. INTRODUCTION 1 2. METHOD OF CONSTRUCTION 1 3. FURTHER CONSIDERATIONS Soil Conditions Network Rail Asset Protection Existing Building Foundations 3 APPENDICES Appendix 1 Sketches Outlining Envisaged Basement Construction Sequence Appendix 2 Outline Risk Assessment

4 1 of 3 1. INTRODUCTION The proposed development is situated on the corner of Station Road and Coombe Road in Kingston upon Thames. The site is not within a conservation area and none of the existing buildings currently on the site are statutory or locally listed. It is proposed to demolish the existing building to make way for a new mixed use development that will include a new purpose built two form early primary school and 25 residential units. This Report summarises a possible construction sequence for the basement construction at Kingstons House. The content of the Report is for the exclusive use of J and should not be used in whole or in part by any third parties without the express permission of Ramboll UK in writing. It should not be relied upon exclusively for decision making purposes and should be read in conjunction with all other relevant reports and drawings submitted as part of the planning application. The following information was provided by the architect to inform this Report: Architecture Initiative, Proposed Plans evels -1 & -2, Drawing No. KH-100 Rev D; Architecture Initiative, Proposed Plans evel 0, Drawing No. KH-101 Rev E; and Architecture Initiative, Proposed Section, Drawing No. KH-202 Rev A. An outline risk assessment highlighting the key design risks at this stage has been included in Appendix B. 2. METHOD OF CONSTRUCTION Reference should be made to the Ramboll sketch numbers sk001 and sk002 in Appendix A for an indicative construction sequence for the proposed basement. A piled wall such as a secant wall is the recommended form of construction for the basement with a reinforced concrete capping beam. This will allow for construction in most soil types and it will also provide a temporary barrier to groundwater during construction if the ground water levels are above formation level. A secant piled wall has vertical load bearing capacity which will allow the superstructure to be constructed directly above the capping beam. A concrete liner wall is likely to be required to meet the waterproofing requirements for a Grade 3 habitable basement. In the temporary condition, props will be required to support the wall until the ground and basement floor slabs have been constructed. In the permanent state the floor slabs will prop the piled wall. 3. FURTHER CONSIDERATIONS 3.1 Soil Conditions The site geology and associated soil design parameters will greatly influence the design of the piled wall in both the temporary and permanent condition. A full site investigation will need to be undertaken including a representative number of boreholes across the site to understand the soil strata and ground water levels. This information can then be used to inform the design and determine the lengths and diameters of piles required as well as the number of props and their locations in the temporary state. Wall and adjacent ground movement predictions can then be made.

5 2 of Network Rail Asset Protection Given the close proximity of the South West Trains railway line to the development, we would recommend early engagement with Network Rail to ensure that their requirements are incorporated into the scheme. The first stage of the formal ageement process with Network Rail is a Form A. This includes a summary of the analysis undertaken to justify the negligible impact on the rail tracks. Following this, if Network Rail do not believe that the works are sufficiently far from their assets, they may require further submission under Forms B & C. Since the proposed scheme is adjacent to the bottom of the slope that the rail lines sit on, the following analyses will likely be required to satisfy the Network Rail requirements regardless of the level of the basement: Slope stability analysis; Ground movement assessment of rails and other key Network Rail assets; Condition surveys before and after construction; and The above may include a requirement for monitoring before construction begins, during construction and for a certain time after construction has finished. The current scheme includes a basement which extends into both the track and slope support zones. Usually, the Network Rail guidelines advise that if a new structure is proposed within a 3:2 slope that starts 2.75m from the edge of the closest rail track or below a notional extension of an embankment then analysis will have to be carried out to demonstrate that the development will not affect the operation of the railway. Figure 1 shows an indicative line of influence from the rail tracks and the slope. New development (Kingstons House) South West Trains railway line ocation of Network Rail fence unknown ~ 2.75m 2 ine of influence of slope 3 ine of influence of rail tracks Figure 1: Indicative line of influence from Network Rail lines During construction the following should also be considered: Tower cranes cannot over-sail Network Rail land. Tower cranes will have to be overdesigned by 25% as will working platforms for mobile plant. Mobile cranes cannot work towards the railway if working within a collapse radius of the Network Rail boundary. Piling rigs must be perpendicular to the railway. A façade glare assessment may be required. Design and Method Statement submissions will be required for any element of temporary or permanent works that has potential to affect the railway.

6 3 of Existing Building Foundations The type and location of any existing foundations from the building that currently sits on the site are unknown. A full site survey will be required to understand the implications that this may have on the construction sequence. It should be noted that if there are existing foundations in the location of proposed piles, these will either have to be removed or piled through which have time and cost implications. The contractor should decide the preferred strategy if this is required.

7 1-1 APPENDIX 1 SKETCHES OUTINING ENVISAGED BASEMENT CONSTRUCTION SEQUENCE

8 Temporary propping KINGSTON HOUSE ENVISAGED BASEMENT CONSTRUCTION SEQUENCE STAGE 1 INVESTIGATIONS TO BE CARRIED OUT TO OCATE ANY EXISTING FOUNDATIONS PRIOR TO PIING AND EXCAVATION. IF THERE ARE EXISTING FOUNDATIONS IN THE PIING OCATIONS, CONTRACTOR TO DECIDE IF THE EXISTING FOUNDATIONS SHOUD BE REMOVED PRIOR TO PIING. PIING ASSUMED TO BE CARRIED OUT FROM GROUND EVE CONSTRUCT CAPPING BEAM 1 A A Indicative location of existing building. A full site investigation should be carried out to understand any clashes with the new and existing foundations. Any clashes may affect the speed of construction. Contractor to decide if existing foundations should be dug out or piled through. Indicative piled wall and capping beam over STAGE 2 EXCAVATUE TO JUST BEOW CAPPING BEAM INSTA FYING SHORES/TEMPORARY WORKS EXCAVATE TO BASEMENT FORMATION EVE 2 B B Temporary propping may be in the form of flying shores SECTION A-A SECTION B-B Capping beam constructed before excavation Indicative piled wall General Notes: 1. Sketches are schematic only and not to scale. 2. Sketches show envisaged sequence of construction. 3. Sketches should be read in conjunction with relevant design philosophy reports and architectural information. 4. Final construction sequence to be developed by the contractor. 5. All temporary works shown is indicative only. The contractor will be responsible for the design, erection and maintenance of all of the temporary works. Project Title Kingstons House Project N Sketch N sk001 Title Basement Construction Sequence Scale NTS Eng: Rev: Date: Checked GR 02 14/08/15 CP

9 KINGSTON HOUSE ENVISAGED BASEMENT CONSTRUCTION SEQUENCE STAGE 3 INSTA INTERMEDIATE PROPPING IF REQUIRED EXCAVATION COMPETED 3 STAGE 4 REMAINING FOUNDATIONS CONSTRUCTED WHERE REQUIRED. BASEMENT SAB AND CONCRETE SUBSTRUCTURE, CONSTRUCTED. INER WA INSTAED TO ENSURE WATERTIGHTNESS. PROPS REMOVED ONY ONCE GROUND FOOR SAB HAS REACHED SUFFICIENT STRENGTH. 4 STAGE 5 SUPERSTRUCTURE FRAME CONSTRUCTED 5 Superstructure frame Props dismantled and removed once ground floor slab has reached sufficient strength iner wall for water tightness Additional props may be required Allow for temporary openings in slab for removal of props Substructure frame Given the space constraints, it may be difficult to fit a rig in for the internal foundations. One possibility is to pile these at the Stage 1 from ground level. The piles can then be broken down during excavation. This will mean that temporary heave forces have to be accounted for in the pile design. If the piles are bored rather than CFA then the bores above formation could be filled with gravels rather than concrete and the steel cages hung at final cut off level to avoid breaking down the piles over the entire basement depth. General Notes: 1. Sketches are schematic only and not to scale. 2. Sketches show envisaged sequence of construction. 3. Sketches should be read in conjunction with relevant design philosophy reports and architectural information. 4. Final construction sequence to be developed by the contractor. 5. All temporary works shown is indicative only. The contractor will be responsible for the design, erection and maintenance of all of the temporary works. Project Title Kingstons House Project N Sketch N sk002 Title Basement Construction Sequence Scale NTS Eng: Rev: Date: Checked GR 02 14/08/15 CP

10 2-2 APPENDIX 2 OUTINE RISK ASSESSMENT

11 RISK ASSESSMENT (PP12.4) job title KINGSTONS HOUSE file ref. Stage / Section of works BASEMENT CONSTRUCTION METHOD Rev 1-04/06/2015 PD/PM approval The list of risks below is not intended as an exhaustive list. Hazards have been identified where they are project specific and as such hazards that a competent contractor would be expected to identify have not been listed. Design item giving rise to risk² Consequence of item giving rise to risk Residual risks - risks that cannot be designed out or those remaining Action to mitigate/reduce risk Action By Status 7 following risk assessment Activity /Element Item Cat¹ Nº P 1 A site specific Ground Investigation has not been undertaken. Delays due to unforeseen ground conditions; cost and programme implications. Impacting on foundation solution. P 2 The groundwater levels on site are unknown at present. Impact of Excessive and/or differential water uplift. potential dewatering/groundwater control measures of adjacent Delays due to unforeseen ground conditions; cost and structures/services. programme implications. Cost and program implications should remedial water retention measures be required. Impacting on foundation solution. Extensive dewatering measures may be required. P 3 South West Train railway lines. The new development is adjacent to the bottom of the sope that the rail lines sit on and also cuts through the expected line of influence of the rail tracks. Delays due to lengthy approval process with Network Rail. Network Rail may believe that the development will affect their assts and therefore ask for changes to the proposal or reject the proposal altogether. The close proximity of the rail tracks will dictate the construction methodology including type and location of piling rig and tower cranes. The close proximity will also affect the permanent design including the façade access and maintenance strategy, and possibly the building geometry. P/C 4 The location of all the existing services in the vicinity of the site is not known. Risk of damaging services beneath/surrounding the site during site investigation and construction works. Health and safety implications of unexpected service strike during excavation. iability through damage. Removal/re-routing of services will have cost and programme implications. P 5 Undiscovered buried obstructions and existing piles Increased costs due to hold up in construction program and increased costs for removing buried obstructions. Carry out a Ground Investigation to confirm the ground conditions Carry out a Ground Investigation to confirm the ground water level. Any excavation that extends below the groundwater level will require dewatering. Basement walls for levels that extend below the groundwater table will have to be formed by interconnecting embedded concrete or steel piles if required. Early engagement with Network Rail is advised to ensure that their requirements are incorporated into the scheme. A detailed immpact assessment should be carried out for both the slope stability and any additional impact on the rail tracks. Design and method statement submissions will be required for any element of temporary o parmanent works that has the potential to affect the railway. Desk study should be carried out to visually identify the locations of any services on or surrounding the site if the building footprint will extend close to service routes. Contractor to carry out survey prior to works to confirm location of services. Programme to ensure that all services at the sites are located, isolated and disconnected at meter where applicable before commencement of any works. Identification of requirements and scope of works issued to the health and safety site manager. ocation of existing piles to be investigated NR may not approve the scheme. Risk of damaging existing services Risk present until works complete. Client/ Engineer/ Contractor Client/ Engineer/ Contractor Client/ Engineer/ Contractor Client/ Engineer/ Contractor Client/ Engineer/ Contractor P 6 Existing public sewers potentially crossing the development site If public sewerage crosses the site then no build zones may be enforced around them or they may need to be diverted. Diversion agreements will need to be in place with Thames Water before any works can be undertaken. CCTV survey undertaken to confirm the exact location of all sewerage crossing the site. Public sewer diversions may be required. Client P 7 Basement waterproofing. Different waterproofing strategies have different build-up requirements, potential impact on basement size and construction. Structural engineer to assist Architect with waterproofing strategy where integral to the basement structure e.g. waterproof concrete admixture. Design Team / Client 1 (C) CDM / (P) Project / (E) Environmental ² Hazard consideration - harm to human health, construction, cost, project developments, breach of legislation/regulations or the natural environment 7 ive/close ramboll uk PP12.4 Designers Risk Assessment Rev 02/10 Risk Assessment for Basement Construction.xlsx Page 1 of 1

90 Brighton Road, Surbiton, Surrey

90 Brighton Road, Surbiton, Surrey 90 Brighton Road, Surbiton, Surrey Civil and Structural Engineering Basement Feasibility Report Mixed Use Scheme 108802-REP-002 March 2015 Contents 1. Executive Summary... 3 2. Site Description and Constraints...

More information

Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations

Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations Cambridge City Council - East Cambridgeshire District Council - Fenland District Council, Huntingdonshire

More information

BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY

BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY MURRAY SHIRE COUNCIL BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY ADOPTED: 1 May 2012 1 BUILDING OVER OR NEAR WATER AND SEWER MAINS POLICY CONTENTS 1. Objective... 2 2. Requirements for Building Near

More information

-SQA-SCOTTISH QUALIFICATIONS AUTHORITY HIGHER NATIONAL UNIT SPECIFICATION GENERAL INFORMATION

-SQA-SCOTTISH QUALIFICATIONS AUTHORITY HIGHER NATIONAL UNIT SPECIFICATION GENERAL INFORMATION -SQA-SCOTTISH QUALIFICATIONS AUTHORITY HIGHER NATIONAL UNIT SPECIFICATION GENERAL INFORMATION -Unit number- 4420798 -Unit title- CONSTRUCTION TECHNOLOGY 2: SUBSTRUCTURE AND REMEDIAL WORKS -Superclass category-

More information

A Guide to Structural Waterproofing

A Guide to Structural Waterproofing A Guide to Structural Waterproofing Part One Waterproofing Protection For Below Ground Structures 1 2012 W. R. Grace & Co Benjamin J. Brooks Table of Contents Grace Around The World Reference Material

More information

Safe & Sound Bridge Terminology

Safe & Sound Bridge Terminology Safe & Sound Bridge Terminology Abutment A retaining wall supporting the ends of a bridge, and, in general, retaining or supporting the approach embankment. Approach The part of the bridge that carries

More information

STRUCTURES. 1.1. Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.

STRUCTURES. 1.1. Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL. STRUCTURES 1. General. Critical structures may impact the integrity of a flood control project in several manners such as the excavation for construction of the structure, the type of foundation, backfill

More information

IH-635 MANAGED LANES PROJECT, SEG. 3.2

IH-635 MANAGED LANES PROJECT, SEG. 3.2 IH-635 MANAGED LANES PROJECT, SEG. 3.2 Location: Dallas, Texas Owner: Texas Department of Transportation Client: Ferrovial Agroman Construction Cost: $1 Billion Construction Completion Date: December,

More information

Temporary Works. Jan Andresen BEng CEng MIStructE HM Specialist Inspector of Health and Safety. 12 October 2012

Temporary Works. Jan Andresen BEng CEng MIStructE HM Specialist Inspector of Health and Safety. 12 October 2012 Temporary Works Jan Andresen BEng CEng MIStructE HM Specialist Inspector of Health and Safety 12 October 2012 Doing what's right isn't the problem. It is knowing what's right. Lyndon B Johnson worksafe.vic.gov.au

More information

Asset Data Dictionary Definition Document Continuous Flight Auger Piles (CFA) Uniclass Classification

Asset Data Dictionary Definition Document Continuous Flight Auger Piles (CFA) Uniclass Classification Asset Data Dictionary Definition Document Continuous Flight Auger Piles (CFA) Uniclass Classification Contents Introduction... 3 Asset Details... 3 Description... 3 Asset Tagging... 3 Attributes... 4 Data

More information

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide

More information

HIGHWAYS ASSET MANAGEMENT STRUCTURES TEAM GUIDANCE NOTE SMT/GN/03/10 TECHNICAL APPROVAL

HIGHWAYS ASSET MANAGEMENT STRUCTURES TEAM GUIDANCE NOTE SMT/GN/03/10 TECHNICAL APPROVAL HIGHWAYS ASSET MANAGEMENT STRUCTURES TEAM GUIDANCE NOTE SMT/GN/03/10 TECHNICAL APPROVAL Rev Purpose of Issue Originated Reviewed Authorised Date 0 First issue Anil Kumar Ken Duguid Stephen Pottle 21-07-2010

More information

CONTRACTORS INSURANCE SPECIFIC CONTRACT INSURANCE PROPOSAL

CONTRACTORS INSURANCE SPECIFIC CONTRACT INSURANCE PROPOSAL CONTRACTORS INSURANCE SPECIFIC CONTRACT INSURANCE PROPOSAL A FULL POLICY WORDING IS AVAILABLE ON REQUEST PLEASE COMPLETE IN CAPITAL LETTERS USING AN INK PEN AND TICK BOXES AS APPROPRIATE Where requested,

More information

Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing

Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing Brussels, 18-20 February 2008 Dissemination of information workshop 1 Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing Dr.-Ing. Bernd Schuppener, Federal Waterways Engineering

More information

Permits to Dig / Permits to Excavate / Permits to work near underground services

Permits to Dig / Permits to Excavate / Permits to work near underground services Permits to Dig / Permits to Excavate / Permits to work near underground services Aim and purpose The aim of this guidance is to identify what should be included in a permit to excavate / dig and additional

More information

CONTE NT DESIGN PROCESS. Appendix. 01 First Issue. 02 Revision A. 03 Revision B. 04 Co-ordination. 05 Panel Thicknesses. 06 Panel Surface Quality

CONTE NT DESIGN PROCESS. Appendix. 01 First Issue. 02 Revision A. 03 Revision B. 04 Co-ordination. 05 Panel Thicknesses. 06 Panel Surface Quality CONTE NT DESIGN PROCESS First Issue 02 Revision A 03 Revision B 04 Co-ordination 05 Panel Thicknesses 06 Panel Surface Quality 07 CNC Timber Processing 08 Panel Standard Sizes 09 Glulam Standard Sizes

More information

Requirements for Building Application Submission

Requirements for Building Application Submission THE DEVELOPMENT CONTROL AND PLANNING BOARD P O Box 597 Phone: 869 465-2277 Bladen Commercial Development Fax: 869 465-5842 Basseterre, St. Kitts Email: phyplskb@caribsurf.com To: Architects, Designers

More information

Demolition & Construction Management Plan

Demolition & Construction Management Plan Demolition & Construction Management Plan 72 76 Cadogan lane SW1 Demolition & Construction Management Plan Issue Date: March 2013 Contents: 1.0 Introduction 1.1 Objectives of the Plan 1.2 Project Overview

More information

COPYRIGHT. Dincel Construction System Pty Ltd

COPYRIGHT. Dincel Construction System Pty Ltd BASEMENT CONSTRUCTION Dincel Construction System Pty Ltd 101 Quarry Road ERSKINE PARK NSW 2759 PO Box 104, ST CLAIR NSW 2759 Phone: (612) 9670 1633 Fax: (612) 9670 6744 Email: construction@dincel.com.au

More information

Photo 2. View showing flour mill, machine shed, veranda and saw mill + storage shed.

Photo 2. View showing flour mill, machine shed, veranda and saw mill + storage shed. May 7,2015 KSANDER & ASSOCIATES CONSULTING PROFESSIONAL ENGINEERS 130 HUINTER STREET, UNIT 103, PETERBOROUGH, ONTARIO K9H2K8 TELEPHONE (705) 743-9221 FAX 743-0904 Ontario Region Conservation Authority

More information

CITY OF VINCENT CONSTRUCTION MANAGEMENT PLAN GUIDELINES

CITY OF VINCENT CONSTRUCTION MANAGEMENT PLAN GUIDELINES CITY OF VINCENT CONSTRUCTION MANAGEMENT PLAN GUIDELINES INTRODUCTION What is a Construction Management Plan? The City of Vincent requires careful management of construction involving excavation and retention

More information

Piling Datasheets. Continuous flight auger (CFA) Driven Rotary

Piling Datasheets. Continuous flight auger (CFA) Driven Rotary Piling Datasheets Continuous flight auger (CFA) Driven Rotary Continuous Flight Auger Piles (CFA) Technical Data Application Well suited to soft and/or water bearing ground where deep casings or bentonite

More information

Geotechnical Building Works (GBW) Submission Requirements

Geotechnical Building Works (GBW) Submission Requirements Building Control (Amendment) Act 2012 and Regulations 2012: Geotechnical Building Works (GBW) Submission Requirements Building Engineering Group Building and Construction Authority May 2015 Content : 1.

More information

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations Nathan A. Ingraffea, P.E., S.E. Associate, KPFF Consulting Engineers, Portland, Oregon, USA Abstract The use of steel sheet

More information

Re: Damages to Alaska Building from Legislative Information Office Construction

Re: Damages to Alaska Building from Legislative Information Office Construction 510 L Street Suite 200 Anchorage, AK 99501-1949 (907) 274-22362236 Phone (907) 274-25202520 Fax www.bbfm.com July 22, 2015 Jim Gottstein Alaska Building 406 G Street, Suite 206 Anchorage, AK 99501 Re:

More information

Tree Work on District of West Vancouver Property

Tree Work on District of West Vancouver Property CORPORATE POLICY Parks & Community Services File #2190-01-01 West Vancouver Property 1.0 Purpose This policy has three sections: 1.1 Section 1 ensures the safety of the residents of West Vancouver through

More information

CONTRACTORS COMBINED SUPPLEMENTARY PROPOSAL FORM THE RIGHT TOOL FOR THE JOB

CONTRACTORS COMBINED SUPPLEMENTARY PROPOSAL FORM THE RIGHT TOOL FOR THE JOB CONTRACTORS COMBINED SUPPLEMENTARY PROPOSAL FORM THE RIGHT TOOL FOR THE JOB Introduction Clause 21.2.1 In the Joint Contracts Tribunal (JCT) Standard Form of Building Contract there are a number of clauses

More information

ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057. Lecturer: Jim Cahill

ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057. Lecturer: Jim Cahill ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057 Lecturer: Jim Cahill 29 th November 2011 TABLE OF CONTENTS SUMMARY 1 MAIN BODY SECTION

More information

SECTION 02100 SITE PREPARATION

SECTION 02100 SITE PREPARATION SECTION 02100 SITE PREPARATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and General Provisions of Contract, including General Conditions and Supplementary Conditions and Division 1 through Division

More information

Building over or close to a public sewer

Building over or close to a public sewer Building over or close to a public sewer thameswater.co.uk/developerservices thameswater.co.uk/developerservices 1 Questions and answers Did you know Thames Water is legally responsible for more than 100,000

More information

Chapter 9 Remedial Measures

Chapter 9 Remedial Measures [This is an annotated version of a chapter from the US Army Corps of Engineers book, Foundations in Expansive Soils. This book is in the public domain. This document is consists of an abbreviated and annotated

More information

Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file

Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file Notation B1 = lowest level of basement slab c = cohesion E = drained Young s Modulus Eu = undrained Young s Modulus

More information

LS 2540 SEWER LATERALS AND INSPECTION TEES

LS 2540 SEWER LATERALS AND INSPECTION TEES LS 2540 SEWER LATERALS AND INSPECTION TEES A. Summary B. Submittals C. Site Information D. Sewer Pipe and Fittings E. Lateral Locations F. Lateral Installation G. Inspection Tee Installation H. Removal

More information

BUTE Department of Construction Management and Technology

BUTE Department of Construction Management and Technology BUTE Department of Construction Management and Technology 02.10.2012 Definition 1: Foundation: The structure, that transmits the load of the building to the soil Definition 2: Load bearing soil (strata):

More information

GUIDANCE NOTES FOR DEVELOPMENTS OR ENGINEERING WORKS IN THE VICINITY OF SPT SUBWAY INFRASTRUCTURE JULY 2005

GUIDANCE NOTES FOR DEVELOPMENTS OR ENGINEERING WORKS IN THE VICINITY OF SPT SUBWAY INFRASTRUCTURE JULY 2005 GUIDANCE NOTES FOR DEVELOPMENTS OR ENGINEERING WORKS IN THE VICINITY OF SPT SUBWAY INFRASTRUCTURE JULY 2005 CONTENTS 1.0 INTRODUCTION 2.0 OVERVIEW OF SPT APPROACH TO DEVEOPMENTS/WORKS IN THE VICINITY OF

More information

Challenging Skew: Higgins Road Steel I-Girder Bridge over I-90 OTEC 2015 - October 27, 2015 Session 26

Challenging Skew: Higgins Road Steel I-Girder Bridge over I-90 OTEC 2015 - October 27, 2015 Session 26 2014 HDR Architecture, 2014 2014 HDR, HDR, Inc., all all rights reserved. Challenging Skew: Higgins Road Steel I-Girder Bridge over I-90 OTEC 2015 - October 27, 2015 Session 26 Brandon Chavel, PhD, P.E.,

More information

Design and Construction of Cantilevered Reinforced Concrete Structures

Design and Construction of Cantilevered Reinforced Concrete Structures Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-68 Design and Construction of Cantilevered Reinforced Concrete Structures

More information

Uniform Construction Code (UCC) Manufactured Homes. Modular Homes. Building Permit Application Package

Uniform Construction Code (UCC) Manufactured Homes. Modular Homes. Building Permit Application Package Uniform Construction Code (UCC) Manufactured Homes (Single-Wide, Double-Wide) Modular Homes Building Permit Application Package Per the Uniform Construction Code (UCC) all structures must be built per

More information

Ground-borne Vibrations and Ground Settlements Arising from Pile Driving and Similar Operations

Ground-borne Vibrations and Ground Settlements Arising from Pile Driving and Similar Operations Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-137 Ground-borne Vibrations and Ground Settlements Arising from Pile

More information

Micropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation

Micropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation Micropiles Reduce Costs and Schedule for Merchant RR Bridge Rehabilitation Jeff R. Hill, P.E. Hayward Baker Inc. 111 W. Port Plaza Drive Suite 600 St. Louis, MO 63146 314-542-3040 JRHill@HaywardBaker.com

More information

Investigation of Foundation Failure. Step 1 - Data Collection. Investigation Steps

Investigation of Foundation Failure. Step 1 - Data Collection. Investigation Steps Foundations on Expansive Clay Soil Part 3 - Investigation of Failed Foundations Presented by: Eric Green, P.E. Structural Engineer Slide 1 Copyright Eric Green 2005 Investigation of Foundation Failure

More information

King Post Wall Information

King Post Wall Information King Post Wall Information DAWSON-WAM specialise in the installation of piled retaining wall systems including steel sheet piling, concrete piled walls and king post walls. This document is our guide to

More information

Standard terms and conditions

Standard terms and conditions Standard terms and conditions INTRODUCTION For the provision of a water service (Water Supply, Wastewater and Drainage) Under Section 73(2)(a) of the Water Services Act 2012, landowners may be entitled

More information

EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS

EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS NMP 1.4 EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS Index Purpose... 2 Application... 2 Referral Agency... 2 Associated Requirements... 2 Referenced Standards...2 Definitions...

More information

ENTRY FORM. DVASE 2013 Excellence in Structural Engineering Awards Program

ENTRY FORM. DVASE 2013 Excellence in Structural Engineering Awards Program ENTRY FORM DVASE 2013 Excellence in Structural Engineering Awards Program PROJECT CATEGORY (check one): Buildings under $2M Buildings Over $100M Buildings $2M-$10M Other Structures Under $5M Buildings

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering

More information

Amendment to OPSS 415 (Nov 2008) Construction Specification for Pipeline and Utility Installation by Tunnelling

Amendment to OPSS 415 (Nov 2008) Construction Specification for Pipeline and Utility Installation by Tunnelling Engineering and Construction Services Division Standard Specifications for Sewers and Watermains TS 415 April 2013 Amendment to OPSS 415 (Nov 2008) Construction Specification for Pipeline and Utility Installation

More information

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT City of Swartz Creek 8083 Civic Drive Swartz Creek, MI 48473 810-635-4464 Fee Received: $ Date: / / Receipt No: Demolition Permit (including Right of

More information

SECTION 15 FLOODPLAIN MANAGEMENT

SECTION 15 FLOODPLAIN MANAGEMENT SECTION 15 15.1 Purpose Certain areas of the City of Gardiner, Maine, are subject to periodic flooding, causing serious damages to properties within these areas. Relief is available in the form of flood

More information

Uncovered Decks & Porches

Uncovered Decks & Porches Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed

More information

Guide to Carrying Out Engineering Works within Road Structure Safety Zone and Engineering Activity on Land adjoining Public Streets

Guide to Carrying Out Engineering Works within Road Structure Safety Zone and Engineering Activity on Land adjoining Public Streets Guide to Carrying Out Engineering Works within Road Structure Safety Zone and Engineering Activity on Land adjoining Public Streets January 2011 Edition All rights reserved. No part of this publication

More information

How to Estimate the Cost of Support of Excavation for Foundation Installation. CPE Candidate No. 0113013. May 15, 2013

How to Estimate the Cost of Support of Excavation for Foundation Installation. CPE Candidate No. 0113013. May 15, 2013 How to Estimate the Cost of Support of Excavation for Foundation Installation CPE Candidate No. 0113013 May 15, 2013 1 How to Estimate the Cost of Support of Excavation for Foundation Installation Table

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

HOUSE BUILDING DIGEST

HOUSE BUILDING DIGEST HOUSE BUILDING DIGEST (Construction Specifications-Foundations) Creating Enabling Environment for Affordable Housing for All This is an attempt by BMTPC to provide useful but often ignored information

More information

FLOOD DAMAGE PREVENTION ORDINANCE

FLOOD DAMAGE PREVENTION ORDINANCE FLOOD DAMAGE PREVENTION ORDINANCE SECTION 1.0 STATUTORY AUTHORIZATION, FINDINGS FO FACT, PURPOSE, AND OBJECTIVES 1.1 STATUTORY AUTHORIZATION The Legislature of the State of Washington has in RCW delegated

More information

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE

APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE JURISDICTION OF ALBERTA TRANSPORTATION 1.0 Application Procedures 2.0

More information

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County Building Permit Application Packet The purpose of Building Codes is to establish the minimum requirements to safe guard the public health, safety and general welfare through structural strength, means

More information

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development 7 SPECIFICATIONS There is currently no Irish specification for construction of drainage works, or water supply works. There are several publications that give guidance on drainage works, such as the Building

More information

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request

More information

DESIGNING STRUCTURES IN EXPANSIVE CLAY

DESIGNING STRUCTURES IN EXPANSIVE CLAY DESIGNING STRUCTURES IN EXPANSIVE CLAY A GUIDE FOR A RCHITECTS AND E NGINEERS Table of Contents 1. Introduction Page 1 2. Common Foundation Systems Page 2 3. Drilled Piers Page 3 a. Skin Friction Piers

More information

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Federation of Piling Specialists July 2010

Federation of Piling Specialists July 2010 Examples of Hazards associated with Piling and Diaphragm Walling Works and how these might be managed within the design phase of a project (neither exhaustive nor exclusive) This list of examples has been

More information

DEMOLITION PERMIT CHECKLIST* B.H.M.C. Section 10-3-4201

DEMOLITION PERMIT CHECKLIST* B.H.M.C. Section 10-3-4201 GEORGE CHAVEZ, City Building Official DAVID YELTON, Building Inspection Manager NESTOR OTAZU, Community Preservation Manager BUILDING & SAFETY DIVISION 455 North Rexford Drive, 1 st Floor Beverly Hills,

More information

USE OF MICROPILES IN TEXAS BRIDGES. by John G. Delphia, P.E. TxDOT Bridge Division Geotechnical Branch

USE OF MICROPILES IN TEXAS BRIDGES. by John G. Delphia, P.E. TxDOT Bridge Division Geotechnical Branch USE OF MICROPILES IN TEXAS BRIDGES by John G. Delphia, P.E. TxDOT Bridge Division Geotechnical Branch DEFINITION OF A MICROPILE A micropile is a small diameter (typically less than 12 in.), drilled and

More information

720 Contour Grading. General. References. Resources. Definitions

720 Contour Grading. General. References. Resources. Definitions 720 Contour Grading General Contour grading directs water to a desired point, prevents erosion, provides noise deflection, provides visual fit of the facility into the landscape, and protects desirable

More information

Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013

Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013 Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013 Alan Baxter Westminster City Council s Residential Basement Report Prepared for Westminster City

More information

Transmission Foundations Case History : Helical piles Hydro One Networks Inc.

Transmission Foundations Case History : Helical piles Hydro One Networks Inc. Transmission Foundations Case History : Helical piles Hydro One Networks Inc. www.hubbellpowersystems.com Late in 2008, an aerial patrol discovered three 500kV towers with partially-collapsed foundations

More information

Elevating Your House. Introduction CHAPTER 5

Elevating Your House. Introduction CHAPTER 5 CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,

More information

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are: When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory

More information

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing 1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize

More information

Civil Engineering and Architecture (CEA) Detailed Outline

Civil Engineering and Architecture (CEA) Detailed Outline Civil Engineering and Architecture (CEA) Detailed Outline Unit 1: Overview of Civil Engineering and Architecture (23 days) Lesson 1.1: History of Civil Engineering and Architecture 1. Many features of

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION

CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION CONCRETE FLOOR SLAB & CASTING BED CONSTRUCTION General 7 www.meadowburke.com 877-518-7665 MB1109 CONCRETE FLOOR SLAB AND CASTING BED CONSTRUCTION Quality Construction Begins at Ground Level Everything

More information

SIKA AT WORK THE KAENG KRACHAN ELEPHANT HOUSE AT ZURICH ZOO

SIKA AT WORK THE KAENG KRACHAN ELEPHANT HOUSE AT ZURICH ZOO SIKA AT WORK THE KAENG KRACHAN ELEPHANT HOUSE AT ZURICH ZOO SIKA SYSTEMS FROM BASEMENT TO ROOF BASEMENT TO ROOF SOLUTIONS FOR ELEPHANT HOUSE AT ZURICH ZOO PROJECT DESCRIPTION The Kaeng Krachan Elephant

More information

How To Build A Luxury Apartment Complex In London

How To Build A Luxury Apartment Complex In London Post Tensioning Awards 2009 Project Summary Type of structure Location Architects Structural Engineer Residential with leisure suites including Swimming pool, Cinema, Virtual Golf, Wine Cellars, and Parking

More information

Excavation Procedure. MIDGA Reviewed: 07/29/14 Effective: 06/20/09 Supersedes: Original Preparer: Owner: Approver: Safety Safety Safety

Excavation Procedure. MIDGA Reviewed: 07/29/14 Effective: 06/20/09 Supersedes: Original Preparer: Owner: Approver: Safety Safety Safety Procedure No.: SOP-0203 Page: 1 of 5 Preparer: Owner: Approver: Safety Safety Safety 1. PURPOSE The purposes of this procedure is to ensure safe excavation, reduce the potential of damaging underground

More information

Outlet stabilization structure

Outlet stabilization structure Overview of Sedimentation and Erosion Control Practices Practice no. 6.41 Outlet stabilization structure Erosion at the outlet of channels, culverts, and other structures is common, and can cause structural

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

September 2007. September 2013. Consulting Structural and Civil Engineers. 100 St John Street London EC1M 4EH. info @ akt-uk.com www.akt-uk.

September 2007. September 2013. Consulting Structural and Civil Engineers. 100 St John Street London EC1M 4EH. info @ akt-uk.com www.akt-uk. Consulting Structural and Civil Engineers 100 St John Street London EC1M 4EH T +44 (0) 20 7250 7777 F +44 (0) 20 7250 7555 info @ akt-uk.com www.akt-uk.com 3290 A031234 The 196-222 Joseph Kings Bloggs

More information

IALN11006400 /05 01 19.06.13. FAO: The Planning Department The Royal Borough of Windsor and Maidenhead Town Hall, St. Ives Road Maidenhead SL6 1RF

IALN11006400 /05 01 19.06.13. FAO: The Planning Department The Royal Borough of Windsor and Maidenhead Town Hall, St. Ives Road Maidenhead SL6 1RF IALN11006400 /05 01 19.06.13 FAO: The Planning Department The Royal Borough of Windsor and Maidenhead Town Hall, St. Ives Road Maidenhead SL6 1RF Dear Sir / Madam Re: 12/02994 BCA Sports Hall Condition

More information

Milan M5 metro extension the construction of Lotto station

Milan M5 metro extension the construction of Lotto station Milan M5 metro extension the construction of Lotto station Giuseppe LUNARDI, Rocksoil S.p.A., Italy giuseppe.lunardi@rocksoil.com Luca MANCINELLI, Rocksoil S.p.A., Italy, luca.mancinelli@rocksoil.com Massimiliano

More information

Federation of Piling Specialists

Federation of Piling Specialists Federation of Piling Specialists COMPANY NAME CONTRACT NAME TENDER REF SCHEDULE OF ATTENDANCES AND FACILITIES TO BE PROVIDED BY THE CLIENT TO A STEEL SHEET PILING SPECIALIST For the purposes of this document

More information

Settlement of Precast Culverts Under High Fills; The Influence of Construction Sequence and Structural Effects of Longitudinal Strains

Settlement of Precast Culverts Under High Fills; The Influence of Construction Sequence and Structural Effects of Longitudinal Strains Settlement of Precast Culverts Under High Fills; The Influence of Construction Sequence and Structural Effects of Longitudinal Strains Doug Jenkins 1, Chris Lawson 2 1 Interactive Design Services, 2 Reinforced

More information

Interim Advice Note 105/08 Implementation of Construction (Design and Management) 2007 And the withdrawal of SD 10/05 and SD 11/05

Interim Advice Note 105/08 Implementation of Construction (Design and Management) 2007 And the withdrawal of SD 10/05 and SD 11/05 Interim Advice Note 105/08 Implementation of Construction (Design and Management) 2007 And the withdrawal of SD 10/05 and SD 11/05 IAN 105/08 1 of 7 Jan 2008 1. Introduction The Construction (Design and

More information

STANDARD AND SPECIFICATIONS FOR STORM DRAIN INLET PROTECTION

STANDARD AND SPECIFICATIONS FOR STORM DRAIN INLET PROTECTION STANDARD AND SPECIFICATIONS FOR STORM DRAIN INLET PROTECTION Design Criteria Drainage Area The drainage area for storm drain inlets shall not exceed one acre. The crest elevations of these practices shall

More information

Series 600: Earthworks

Series 600: Earthworks Series 600: Volume 4 home page 1 General Where the Contractor has obligations in respect of classification of earthworks materials then these obligations include sampling and testing in accordance with

More information

Property Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT

Property Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT Property Inspection 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT March 2013 This document has been prepared for the benefit of Clint Marston. No liability is accepted by this company

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section

More information

Sample Drawing Package for One and Two Family Dwelling Applications

Sample Drawing Package for One and Two Family Dwelling Applications Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx

More information

University Arms Hotel, Cambridge

University Arms Hotel, Cambridge Traffic Management Plan For University Arms Hotel, Cambridge Prepared By: James Batterbee Number: M1342 / Rev B Date: 29 th August 2014 CONTENTS: (1) INTRODUCTION (2) VEHICLE ACCESS & EGRESS AND PEDESTRIAN

More information

Gas Meter Clearances and Service Installation Requirements

Gas Meter Clearances and Service Installation Requirements March 2016 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE's Customer Construction Services 1 888 321 7779 or visit PSE.com/CustomerConstruction

More information

Quality Control and Quality Assurance Guide

Quality Control and Quality Assurance Guide Quality Control and Quality Assurance Guide Bridge Division, Design Section October 2013 Table of Contents Chapter 1 About this Guide... 3 Chapter 2 Goals and Objectives... 5 Chapter 3 Participants...

More information

GUIDELINES FOR DESIGNERS BUILDING AND CONSTRUCTION WORKS WITHIN PROXIMITY TO CORPORATION SERVICES

GUIDELINES FOR DESIGNERS BUILDING AND CONSTRUCTION WORKS WITHIN PROXIMITY TO CORPORATION SERVICES CUSTOMER SERVICES DIVISION GUIDELINES FOR DESIGNERS BUILDING AND CONSTRUCTION WORKS WITHIN PROXIMITY TO CORPORATION SERVICES September 2000 FOREWORD This document provides guidelines for the structural

More information

Supplier ID: 26421. Local Office: GLASGOW 69 Buchanan Street Glasgow G1 3HL

Supplier ID: 26421. Local Office: GLASGOW 69 Buchanan Street Glasgow G1 3HL M D & FOUNDATIONS MIDLANDS Supplier ID: 26421 MINI PILING PILING REINFORCED CONCRETE UNDERPINNING DRILLING & GROUTING SITE INVESTIGATION & PILE TESTING NATIONWIDE SPECIALIST PILING & FOUNDATION SERVICES

More information

Chapter 5.4. Waterproofing of basements and other below ground structures

Chapter 5.4. Waterproofing of basements and other below ground structures Chapter Waterproofing of basements and other below ground structures Waterproofing of basements and other below ground structures CONTENTS SCOPE DESIGN Clause Page D1 Design standards D1 2 D2 Statutory

More information

Designed and Engineered to Perform

Designed and Engineered to Perform History EARTH CONTACT PRODUCTS, L.L.C., is a family owned company, based in Olathe, Kansas. This company was built upon Don May s U.S. Patented fourth-generation Steel Piering System that has led to the

More information

CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714

CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714 CITY OF YORBA LINDA P.O. BOX 87014 CALIFORNIA 92885-8714 BUILDING DIVISION (714) 961-7120 Single Family Residential New Construction, Additions & Alterations Submittal Requirements Required agency approvals

More information

Residential Building Permits

Residential Building Permits LANE COUNTY PUBLIC WORKS Residential Building Permits LAND MANAGEMENT DIVISION 3050 N. DELTA HWY, EUGENE OR 97408 i CONTACT PHONE NUMBERS: Building Program: (541) 682-4651 Inspection Requests: (888) 299-2821

More information

The information and materials contained in this disc are provided as is and as available.

The information and materials contained in this disc are provided as is and as available. The information and materials contained in this disc are provided as is and as available. Whilst every effort is made to ensure that the information and materials provided are correct, the Land Transport

More information