1 90 Brighton Road, Surbiton, Surrey Civil and Structural Engineering Basement Feasibility Report Mixed Use Scheme REP-002 March 2015

2 Contents 1. Executive Summary Site Description and Constraints Site Location, Description, and Current Use Geotechnical conditions and constraints Structural Design Existing Substructure Proposed Substructure Superstructure PROJECT TITLE: REPORT TITLE: Team Client Architect Building Services Engineering Consultant Civil and Structural Engineering Consultant PROJECT REFERENCE: REP 002 Issue and Approval Schedule: 90 Brighton Road, Surbiton, Surrey Indigo Scott Harper Downie Fairhurst GGA Civil and Structural Engineering Mixed Use Basement Feasibility Report Rev. 1.0 Name Signature Date Appendix A Basement Construction Methodology Appendix B Site Investigation & Environmental Impact Assessment Prepared by James Toon 10/03/2015 Appendix C Underground Drainage Report Reviewed by Nick McSpadden 10/03/2015 Approved by Nick McSpadden 10/03/2015 Revision Record: Rev. Date Status Description By Chk. App. A 16/03/15 Revised to suit comments JT NMcS NMcS B This report has been prepared in accordance with procedure OP/P02 of Fairhurst Quality Assurance System REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 2

3 1. Executive Summary This report covers the Civil and Structural Engineering Basement Feasibility Report for the development of a single storey basement at 90 Brighton Road, Surbiton, Surrey. The aim of this document is to convey the civil and structural issues considered for the construction of the basement. The proposed mixed use development is to construct two new blocks with the rear residential building 4 storeys and the front 3 storey building mixing commercial at ground floor and residential above. A single storey basement covering the majority of the site for underground parking and the lower level of the dwellings. The basement is accessed via a ramp to the south western corner. Investigation of local ground conditions suggest that the water table is relatively low, however some perched local groundwater may be found. The flood risk for the site is low and the localised damming effects of the basement also anticipated to be low. Green roof systems have been proposed, which will provide attenuation for the drainage of surface water from the site. This will control the flow into the existing sewer system. Foul water drainage for the residential areas of the development will be gravity discharged into the existing sewerage system above ground and pumped for the lower levels REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 3

4 2. Site Description and Constraints 2.1. Site Location, Description, and Current Use Site Location The site is located in Surbiton, Surrey. It is bordered by Brighton Road to the south and the rear gardens of properties on Andrews Square to the North. The eastern and western boundaries are the adjacent properties on Brighton Road Site History The site has been subject to a number of changes of use since 1840 when residential properties covered the site. This stayed with minor alterations until 1974 where a petrol filling station is shown for the first time. Between 1986 and 1987 the garage was developed to the current configuration and has remained largely unchanged until present day. Figure 1. Location of the site REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 4

5 2.2. Geotechnical conditions and constraints The production of the basement construction methodology has been developed in accordance with the documents required by London Boroughs for the construction of basements within inner city sites. Issues raised by the requirements of these documents are as follows: Local Geology Geological records suggest the site is underlain by London Clay. An outline description of the in-situ ground conditions can be found in Table 1 below from a site specific ground investigation for the site conducted in January 2015 and a Phase 1 Geo Environmental Risk Assessment conducted by SLR Global Environmental Solutions (refer to Appendix B). The following data was based on the boreholes dug across the plan of the site. The boreholes were dug to 6m with the London Clay not encountered, however existing borehole data held by the BGS for sites within 1000m of the site show London Clay. Stratum Depth to top of stratum (mbgl) Depth to base of stratum (mbgl) General description Slope Stability The proposed development poses no slope stability issues. The site is slopes gently to the north east and south west whilst the surrounding area slopes gently to the north west towards the River Thames. The basement construction method has been proposed to resist the temporary and permanent loads with very small movements and hence pose little risk to structures at ground level Impact on Drainage, Surface and Groundwater Flows and Levels The current development is predominantly covered by hard standing and the proposed development will therefore have limited impact on the drainage of surface water (refer later within this report). A report has been completed by Odyssey Markides in January 2015 for the Drainage Assessment and Strategy (refer to Appendix C). Within this report it is stated that all the surface water drainage will discharge under gravity into the existing connection to the Thames Water sewer network. Surface water within the basement will be pumped to the outfall via a rising main. Attenuation of the surface water will be achieved by a series of green roofs across the development. Compliance with the London Plan and the reduction of flow rates is considered within this report. Made ground Langley Silt Concrete over grey, black and brown sandy clayey gravel of flint, brick and concrete. Orange-brown clayey sand / very sandy clay. The groundwater level has been monitored as part of the ground investigation with a depth ranging between 3.841m and 5.105m below ground level. From this data it is anticipated that some groundwater will be encountered within the basement excavation that will need to be pumped out as part of the works. Hydrostatic pressures on the basement construction will be minimal with only the lower section of the basement within the water. The Odyssey Markides report notes that the encroachment of the new basement into the groundwater will be minimal and so will not affect the surrounding buildings during or after the construction. Kempton Park Gravels Dark brown sand, becoming sandy gravel with depth. The River Thames runs 350m north west of the site with no other watercourses in close proximity. London clay 6.00 Undetermined Not encountered Table 1 Summary of site specific ground conditions Impact of Temporary and Permanent Works on Integrity of Adjacent Structures There are no underground structures in the vicinity of the proposed development. A method for construction of the basement has been proposed that will limit the surface ground movements to very small amounts and so will ensure the integrity of the adjoining pavement and roadway are maintained REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 5

6 excavation of the basement area. Through the design and the construction of the basement the impact on the adjacent structures will be minimal. The Thames Water Ring Main South crosses the site (refer to figure 4). The depth of the tunnel is currently unknown and will be subject to further investigation. Works above the tunnel and exclusion zones are to be established to Thames Water prior to the commencement of the works. Figure 2 Local river courses How the Design has Assessed Geological and Hydrological Concerns The choice of walling method for the basement has been influenced by the local geology: A stable basement excavation has been designed in the temporary case; Basement walls have been designed for the permanent case; The basement water control has been designed to have minimal impact on the adjoining structures by ensuring no dewatering will occur outside the basement. Should dewatering be required then sufficient flow paths will be maintained that no significant change to the water table will occur due to the basement installation Engineering Details The principles of the structure of the basement and its construction are considered later within this document Impact on Stability of Local Buildings Below Ground The basement construction will be constructed using steel sheet piles, which have been designed to ensure that construction movements are minimised during excavation of the basement. Suitable propping in the temporary and permanent cases will be designed to ensure there is little ground movement during Impact on Existing Trees Figure 3 Thames Water Ring Main South A number of established trees cover the rear of the site. The eastern corner of the basement has been recessed, which is to avoid an established tree on the boundary that currently has a Tree Preservation Order (TPO) in place. It is not anticipated that the proposed works will have a detrimental effect on the trees, which will be monitored during the construction. An Arboricultural Impact Assessment, Arboricultural Method Statement and Tree Protection Plan has been produced by Advanced Tree Services and is available from the client on request. The NHBC document for the construction of foundations near trees will be referred to for guidance, however this is more applicable for ground level domestic buildings REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 6

7 3. Structural Design 3.1. Existing Substructure There are believed to be a number of tanks currently on the site as part of the petrol station. Some of the tanks are understood to be still in operation with the others redundant. The condition of the tanks is unknown and will be subject to further investigation. The tanks will be removed as part of an enabling works package prior to the commencement of the main works. The existing Thames Water tunnel is described in the previous section with easements and construction still to be confirmed. A build over agreement and confirmation of the depth will be required from Thames Water as well as the agreement of any temporary works above to the form the basement. Current Thames Water guidance recommends that easements to sewers are 3m from the outer wall of the sewer and is assumed to be applicable to the construction above the tunnel. It is generally accepted that vibration through construction activities are to be avoided adjacent to sewers and so the sheet piling installation will need to be confirmed as acceptable by the local authority and Thames Water. Basements to adjacent structures are currently unknown and will be subject to further investigation Proposed Substructure Figure 4 Silent piling installation machinery The advantages of this form of piling is the achievement of close proximity to adjacent structures (not applicable on all the boundaries of this site), but more importantly the minimal vibration during construction. This will have little or no impact on the adjacent residential properties and adjacent Thames Water sewer through ground based vibration. Clay soils are best suited for sheet piling with the reduction in the risk of ground obstructions (as discussed previously London clay soils have been assumed through existing borehole data). Localised obstructions can be overcome by either water jetting or pre-augering Structure The current architectural proposal is for a single storey basement accessed by a ramp to the south western corner of the site. The basement contains the lower level of each dwelling as well as parking for each residence, bin stores, bicycle stores and storage areas. The perimeter to the excavation is to be constructed using steel sheet piles that are pushed in using the silent piling technique (refer to figure 4). A trench is excavated prior to the installation of the piles along the line of the wall for the construction of the reinforced concrete capping beam after the sheets have been installed. A preliminary construction method statement has been included in Appendix A. Figure 5 Installation of the steel sheet piles Following the completion of the sheet piles the reinforced concrete capping beam can be constructed (refer to figure 6), which fulfils a number of functions, i.e. ties the head of the sheet piles and the concrete liner wall (constructed later in the process). The ground floor slab will also be tied into the capping beam REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 7

8 Figure 6 Construction of the reinforced concrete capping beam The excavation of the basement can then commence with a soil berm against the sheet pile retaining wall, which starts just below the capping beam at a 45 degree incline into the basement. Once the excavation reaches formation level then concrete thrust blocks are constructed within the ground as the base of the temporary raking props to the sheet pile wall (refer to figure 7). These blocks are required at regular centres running parallel with the wall. De-watering to the excavation will be undertaken as necessary and discharged into the local sewer network at a rate and to the agreement of Thames Water. Figure 8 Installation of raking props Once installed the remainder of the basement can be excavated to formation (refer to figure 9). Figure 9 Remainder of soil excavated Figure 7 Reduced level excavation and construction of thrust blocks Steel temporary props extend from the top of the thrust blocks to the capping beam running around the perimeter of the basement (refer to figure 8). The clutches to the sheet piles will then be welded to help against any water ingress whilst the ground is prepared for the new basement raft. Hardcore will be compacted in 150mm layers prior to the laying of a 50mm concrete blinding (refer to figure 10) and the construction of the reinforced concrete basement raft REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 8

9 Heave Ground heave occurs when the ground beneath a building expands upwards and is usually found within clay soils when they get wet or have trees or loads removed. The removal of trees causes the sub-soil to re-hydrate and expand and the extend will be dependent on the size, number and species of trees, i.e. the water demand and extent of the root system. The removal of load also causes heave with the unloading of the soil allowing the clay to swell. The effects of heave are anticipated to be low for the construction of the proposed basement and its effects will be overcome using the mass of the structure, i.e. the weight of the structure will be greater than the heaving force upwards Basement Waterproofing Figure 10 Basement raft and liner wall construction An external tanking system is proposed for the waterproofing below the basement raft running up the face of the steel sheet piles to the underside of the capping beam (refer to waterproofing section later in the report). Following the installation of the waterproofing and the completion of the raft the reinforced concrete liner walls are constructed to the perimeter to the underside of the concrete capping beam. The internal columns and the reinforced concrete ground floor completes the substructure facilitating the removal of the temporary props with the ground floor acting as the permanent prop for the top of the retaining wall. Adjacent to the rear of the properties a series of opening against the retaining wall allow light wells into the lower ground floor. In these locations the retaining wall is buttressed by concrete walls between the properties joining perpendicular. The intended use of the basement is habitable space. The requirement for residential living areas is a grade 3. These grades are what depicts the environment of the space and have been taken from the CIRIA Design Guide R139, Water Resisting Basements. Three different types of system are recognised for the waterproofing of underground structures: - 1. Type A - Tanked protection 2. Type B - Structurally integral protection 3. Type C - Drained protection The following table shows the various options for achieving the required standard: - Grade of Basement Basement Usage Performance Level Form of Protection Comments on grade Grade 1 Car Parking Plant Rooms (excluding electric equipment) Workshops Some seepage and damp patches tolerable Type B Reinforced to EC2. concrete Visible water may not be acceptable Design to EC2 Part 1 may result in crack widths unacceptable in permeable ground Groundwater should be checked for chemicals Building Regulations are more likely to require Grade 3 for workshops Figure 10 Ground floor slab construction and buttressing walls adjacent to lightwells Grade 2 Car Parking Workshops Plant Rooms (requiring drier environment) No water penetration but moisture vapour tolerable Type A or Type B Reinforced to BS8007 concrete Performance relies on good workmanship Groundwater should be checked for chemicals A high level of REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 9

10 Grade of Basement Basement Usage Performance Level Form of Protection Comments on grade Grade 3 Storage Areas supervision of all stages of construction is necessary Ventilated Residential and Working Areas Offices Restaurants Leisure Centres Dry environment Type A or Type B Reinforced concrete to BS8007 or Type C With walls and floor cavity and DPM As Grade 2 Multi element systems may be required in highly permeable ground Table 2 Basement waterproofing CIRIA Design Guide R139 Water Resisting Basements Note: Grade 4 omitted as it would not be applicable for the intended building use (i.e. generally used for book archives and mainframe computer rooms). For a grade 3 basement, a fully tanked solution is as the current proposal discussed earlier in this report. The employed systems will be very dependent on the contractor for its effectiveness as any construction defects (i.e. punctures or poor joints) would allow the penetration of water through the structure. Water could then track along the back of the wall and enter the building through any defects in the concrete. This is minimised with the concrete liner wall and drained cavity (for additional protection). Water bars and hydrophilic strips will be included at all construction joints and interfaces within the construction of the new retaining wall. Puddle flanges must be installed where the proposed services puncture the basement structure. Where sheet piles the clutches between the adjacent sheets will be welded to provide temporary protection against water ingress, however this will not be part of the permanent waterproofing strategy. One system will be constructed for the whole basement Superstructure The proposed superstructure for the development is currently being developed and is anticipated to be a reinforced concrete frame REP-002 Basement Feasibility Report Mixed Use Scheme 10/03/2015 Rev A Page 10

11 Appendix A Basement Construction Methodology

12 Appendix B Site Investigation & Environmental Impact Assessment

13 Appendix C Drainage Report

14 CIVIL ENGINEERING STRUCTURAL ENGINEERING TRANSPORTATION ROADS & BRIDGES PORTS & HARBOURS GEOTECHNICAL & ENVIRONMENTAL ENGINEERING PLANNING & DEVELOPMENT WATER SERVICES CDM COORDINATOR SERVICES Aberdeen Bristol Dundee Edinburgh Elgin Glasgow Inverness Leeds London Manchester Newcastle Sevenoaks Sheffield Taunton Watford Wellesbourne

September 2007. September 2013. Consulting Structural and Civil Engineers. 100 St John Street London EC1M 4EH. info @ akt-uk.com www.akt-uk.

September 2007. September 2013. Consulting Structural and Civil Engineers. 100 St John Street London EC1M 4EH. info @ akt-uk.com www.akt-uk. Consulting Structural and Civil Engineers 100 St John Street London EC1M 4EH T +44 (0) 20 7250 7777 F +44 (0) 20 7250 7555 info @ akt-uk.com www.akt-uk.com 3290 A031234 The 196-222 Joseph Kings Bloggs

More information

A Guide to Structural Waterproofing

A Guide to Structural Waterproofing A Guide to Structural Waterproofing Part One Waterproofing Protection For Below Ground Structures 1 2012 W. R. Grace & Co Benjamin J. Brooks Table of Contents Grace Around The World Reference Material

More information

Simplifying design and construction. Alan Tovey, Director The Basement Information Centre

Simplifying design and construction. Alan Tovey, Director The Basement Information Centre Simplifying design and construction Alan Tovey, Director The Basement Information Centre Simplifying design and construction Grades of construction Construction options Design and waterproofing issues

More information

ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057. Lecturer: Jim Cahill

ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057. Lecturer: Jim Cahill ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057 Lecturer: Jim Cahill 29 th November 2011 TABLE OF CONTENTS SUMMARY 1 MAIN BODY SECTION

More information

Proposed Construction of Basement Flood Risk Assessment. 35 Edwardes Square London W8 6HH

Proposed Construction of Basement Flood Risk Assessment. 35 Edwardes Square London W8 6HH Proposed Construction of Basement Flood Risk Assessment 35 Edwardes Square London W8 6HH 1 Introduction This FRA has been carried out in accordance with the National Planning Policy Statement (NPPF), the

More information

Chapter 5.4. Waterproofing of basements and other below ground structures

Chapter 5.4. Waterproofing of basements and other below ground structures Chapter Waterproofing of basements and other below ground structures Waterproofing of basements and other below ground structures CONTENTS SCOPE DESIGN Clause Page D1 Design standards D1 2 D2 Statutory

More information

-SQA-SCOTTISH QUALIFICATIONS AUTHORITY HIGHER NATIONAL UNIT SPECIFICATION GENERAL INFORMATION

-SQA-SCOTTISH QUALIFICATIONS AUTHORITY HIGHER NATIONAL UNIT SPECIFICATION GENERAL INFORMATION -SQA-SCOTTISH QUALIFICATIONS AUTHORITY HIGHER NATIONAL UNIT SPECIFICATION GENERAL INFORMATION -Unit number- 4420798 -Unit title- CONSTRUCTION TECHNOLOGY 2: SUBSTRUCTURE AND REMEDIAL WORKS -Superclass category-

More information

BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY

BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY MURRAY SHIRE COUNCIL BUILDING OVER OR NEAR WATER & SEWER MAINS POLICY ADOPTED: 1 May 2012 1 BUILDING OVER OR NEAR WATER AND SEWER MAINS POLICY CONTENTS 1. Objective... 2 2. Requirements for Building Near

More information

constructive solutions Fosroc total waterproofing protection of below-ground structures

constructive solutions Fosroc total waterproofing protection of below-ground structures constructive solutions Fosroc total waterproofing protection of below-ground structures Our profile Since the company s beginnings over 50 years ago, Fosroc has developed into an International leader in

More information

Basements and Deep Building Construction Policy 2014

Basements and Deep Building Construction Policy 2014 Basements and Deep Building Construction Policy 2014 APPROVAL Council / CEO 27 October 2014 VERSION NO: Version 1.0 TRIM REF: 14/67838 REVIEW 30/10/2019 RESPONSIBLE EXECUTIVE General Manager City Assets

More information

Recommendations for future developments

Recommendations for future developments C Recommendations for future developments C.1 Reducing flood risk through site layout and design C.1.1 C.1.2 Flood risk should be considered at an early stage in deciding the layout and design of a site

More information

Standards Committee T echnical Technical Conference

Standards Committee T echnical Technical Conference Standards Committee Technical Conference Agenda Overview of claims costs Years 0 2 claims and resolutions Years 3 10 claims What are we commonly seeing now? An example of what we might see in future? Summary

More information

HOUSE BUILDING DIGEST

HOUSE BUILDING DIGEST HOUSE BUILDING DIGEST (Construction Specifications-Foundations) Creating Enabling Environment for Affordable Housing for All This is an attempt by BMTPC to provide useful but often ignored information

More information

The Guide To Waterproofing An Existing Basement

The Guide To Waterproofing An Existing Basement The Guide To Waterproofing An Existing Basement John Newton & Company is the leading independent supplier of basement waterproofing and damp proofing solutions in the UK. Newton System 500 is a maintainable

More information

SikaProof A Technology

SikaProof A Technology SikaProof A Technology The fully bonded waterproofing system Keep your basements durably and securely watertight What is SikaProof A? How does it work? Where can it be used? What are the advantages of

More information

Basement Waterproofing in Existing Buildings

Basement Waterproofing in Existing Buildings A S S O C I A T I O N Basement Waterproofing in Existing Buildings A guide to protecting your home Follow us on Twitter Find us on Facebook www.property-care.org A basic understanding of Basement Waterproofing

More information

Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013

Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013 Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013 Alan Baxter Westminster City Council s Residential Basement Report Prepared for Westminster City

More information

Guidelines for Control of Water Runoff on Small Lots. Revised 6/09

Guidelines for Control of Water Runoff on Small Lots. Revised 6/09 Guidelines for Control of Water Runoff on Small Lots Revised 6/09 Table of Contents Introduction and Purpose 3 Administrative Procedures 3 Plan Submittal Requirements 3 General Design Criteria 4 Dry Wells

More information

Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing

Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing Brussels, 18-20 February 2008 Dissemination of information workshop 1 Eurocode 7 - Geotechnical design - Part 2 Ground investigation and testing Dr.-Ing. Bernd Schuppener, Federal Waterways Engineering

More information

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development 7 SPECIFICATIONS There is currently no Irish specification for construction of drainage works, or water supply works. There are several publications that give guidance on drainage works, such as the Building

More information

WEST LONDON PIPELINE AND STORAGE LIMITED AND UNITED KINGDOM OIL PIPELINES LIMITED

WEST LONDON PIPELINE AND STORAGE LIMITED AND UNITED KINGDOM OIL PIPELINES LIMITED WEST LONDON PIPELINE AND STORAGE LIMITED AND UNITED KINGDOM OIL PIPELINES LIMITED WLPS BUNCEFIELD REBUILD Flood Risk Assessment Green Lane Hemel Hempstead Hertfordshire HP2 7HZ September 2009 Prepared

More information

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations

Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations Local Authority Building Control Technical Information Note 3 Driven and In-situ Piled Foundations Cambridge City Council - East Cambridgeshire District Council - Fenland District Council, Huntingdonshire

More information

1.2 This technical note provides a preliminary investigation into the Flood Risk and provides outline drainage strategies.

1.2 This technical note provides a preliminary investigation into the Flood Risk and provides outline drainage strategies. ODYSSEY MARKIDES TECHNICAL NOTE PROJECT : CHAILEY HOUSE, BLEWBURY JOB NO. : 14-216 NOTE TITLE : PRELIMINARY FLOODING AND DRAIANGE AUTHOR : STEVEN ROOTH APPROVED : ANDREAS MARKIDES DATE : 02/09/2014 1.0

More information

building on success Trees and Basements Partial Review of the Core Strategy February 2014

building on success Trees and Basements Partial Review of the Core Strategy February 2014 building on success Trees and Basements Partial Review of the Core Strategy February 2014 Regulation 19, Town and Country Planning (Local Planning) (England) Regulations 2012. 2 Contents 1. Introduction...

More information

WATERPROOFING SikaProof -A TECHNOLOGY

WATERPROOFING SikaProof -A TECHNOLOGY SikaProof -A TECHNOLOGY content What is SikaProof -A? 6 How does it work? 8 Where can it be used? 0 What are the advantages of SikaProof -A? 2 How should it be installed? SikaProof -A system components

More information

Basement construction and waterproofing: Site investigation and preparation. good building guide

Basement construction and waterproofing: Site investigation and preparation. good building guide construction and waterproofing: Site investigation and preparation GBG 72 Part 1 good building guide Peter Trotman The requirement for building on sloping sites or increasing the area of buildings within

More information

STEPS TO CONSTRUCTING A MOISTURE-RESISTANT FOUNDATION SOURCES OF MOISTURE IN NEW CONSTRUCTION. Natural ground slope

STEPS TO CONSTRUCTING A MOISTURE-RESISTANT FOUNDATION SOURCES OF MOISTURE IN NEW CONSTRUCTION. Natural ground slope FOUNDATIONS STEPS TO CONSTRUCTING A MOISTURE-RESISTANT FOUNDATION Build a Better Home Details are critical when constructing a sound building foundation that will withstand water and control dampness.

More information

How To Build A Luxury Apartment Complex In London

How To Build A Luxury Apartment Complex In London Post Tensioning Awards 2009 Project Summary Type of structure Location Architects Structural Engineer Residential with leisure suites including Swimming pool, Cinema, Virtual Golf, Wine Cellars, and Parking

More information

Foundations and Substructures

Foundations and Substructures Ground workers handbook Foundations and Substructures Introduction The Ground Workers Handbook gives guidance to site managers and site staff on any particular issues on your site for traditional forms

More information

Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.

Civil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition. Design Guide Basis of Design This section applies to the design and installation of earthwork and backfill. Design Criteria No stockpiling of excavation materials is allowed unless the Geotechnical Engineer

More information

Designed and Engineered to Perform

Designed and Engineered to Perform History EARTH CONTACT PRODUCTS, L.L.C., is a family owned company, based in Olathe, Kansas. This company was built upon Don May s U.S. Patented fourth-generation Steel Piering System that has led to the

More information

Issue of the Guidelines on Prevention of Water Seepage in New Buildings

Issue of the Guidelines on Prevention of Water Seepage in New Buildings graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural

More information

Basement Moisture Problems

Basement Moisture Problems Foundations Foundation Purpose The purpose of a foundation is to distribute the weight of a structure securely into the ground. Engineering data regarding soil, rock and water conditions are used to design

More information

Site Grading and Drainage to Achieve High-Performance Basements

Site Grading and Drainage to Achieve High-Performance Basements Construction Technology Update No. 69 Site Grading and Drainage to Achieve High-Performance Basements By M.C. Swinton and T.J. Kesik Proper site grading and foundation drainage strategies are required

More information

CHAPTER 2 QUANTITY TAKE-OFF

CHAPTER 2 QUANTITY TAKE-OFF CHAPTER 2 QUANTITY TAKEOFF The quantity takeoff is an important part of the cost estimate. It must be as accurate as possible and should be based on all available engineering and design data. Use of appropriate

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

A guide to preventing structural damage

A guide to preventing structural damage A guide to preventing structural damage Home owners guide to planning landscaping and maintenance of foundations Structural damage can result from movement in clay soils caused by varying moisture conditions

More information

Geotechnical Building Works (GBW) Submission Requirements

Geotechnical Building Works (GBW) Submission Requirements Building Control (Amendment) Act 2012 and Regulations 2012: Geotechnical Building Works (GBW) Submission Requirements Building Engineering Group Building and Construction Authority May 2015 Content : 1.

More information

The Effects of Trees On Buildings And Their Characteristics - Part 2

The Effects of Trees On Buildings And Their Characteristics - Part 2 TECHNICAL NOTE NO. 3 TREES AND THEIR EFFECTS PART 2 Part 1 discussed tree and soil characteristics. This Part 2 will provide examples of the effects of trees on buildings with some guidance on defects

More information

K M D Hire Services, LONDON ROAD, NANTWICH, CW5 6LU

K M D Hire Services, LONDON ROAD, NANTWICH, CW5 6LU Application No: 11/2196N Location: Proposal: Applicant: Expiry Date: K M D Hire Services, LONDON ROAD, NANTWICH, CW5 6LU Extension and New Store Mr Dan Mellor 17-Aug-2011 SUMMARY RECOMMENDATION Approve

More information

GUIDANCE NOTES FOR DEVELOPMENTS OR ENGINEERING WORKS IN THE VICINITY OF SPT SUBWAY INFRASTRUCTURE JULY 2005

GUIDANCE NOTES FOR DEVELOPMENTS OR ENGINEERING WORKS IN THE VICINITY OF SPT SUBWAY INFRASTRUCTURE JULY 2005 GUIDANCE NOTES FOR DEVELOPMENTS OR ENGINEERING WORKS IN THE VICINITY OF SPT SUBWAY INFRASTRUCTURE JULY 2005 CONTENTS 1.0 INTRODUCTION 2.0 OVERVIEW OF SPT APPROACH TO DEVEOPMENTS/WORKS IN THE VICINITY OF

More information

GOOD NEWS BUT NOT ALWAYS

GOOD NEWS BUT NOT ALWAYS GOOD NEWS BUT NOT ALWAYS The prospective homebuyer and homeowner in the Amarillo area are indeed fortunate. Typically, he has a wide choice of type home, size, and location for wide ranges of pricing.

More information

Extra. Technical. November 2014 Issue 16 NHBC STANDARDS GUIDANCE AND GOOD PRACTICE. In this issue:

Extra. Technical. November 2014 Issue 16 NHBC STANDARDS GUIDANCE AND GOOD PRACTICE. In this issue: Technical Extra November 2014 Issue 16 In this issue: NHBC STANDARDS Introducing Chapter 5.4 Waterproofing of basements and other below ground structures page 3 GUIDANCE AND GOOD PRACTICE The basement

More information

DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES

DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES WBCA 403 DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES A guide to assist those intending to install or who are involved in installing conservatories. Includes information about: conservatory and component

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

Elevating Your House. Introduction CHAPTER 5

Elevating Your House. Introduction CHAPTER 5 CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,

More information

K M D Hire Services, LONDON ROAD, NANTWICH, CW5 6LU

K M D Hire Services, LONDON ROAD, NANTWICH, CW5 6LU Application No: 11/2196N Location: Proposal: Applicant: Expiry Date: K M D Hire Services, LONDON ROAD, NANTWICH, CW5 6LU Extension and New Store Mr Dan Mellor 17-Aug-2011 SUMMARY RECOMMENDATION Approve

More information

SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM

SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM Shepherd University Board of Governors June 9, 2005 Agenda Item No. 9 SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM In 1994 construction began on the Byrd Science and

More information

9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems

9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems 9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES Hunter Underground Systems 9.01 General 9.02 Surface water Drainage 9.03 Groundwater Drainage 9.04 Dispersal of Septic Tank Effluent 9.01 The use of

More information

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT City of Swartz Creek 8083 Civic Drive Swartz Creek, MI 48473 810-635-4464 Fee Received: $ Date: / / Receipt No: Demolition Permit (including Right of

More information

Chapter 2 Basis of design and materials

Chapter 2 Basis of design and materials Chapter 2 Basis of design and materials 2.1 Structural action It is necessary to start a design by deciding on the type and layout of structure to be used. Tentative sizes must be allocated to each structural

More information

DRAINAGE MANAGEMENT PLAN. HERTFORDSHIRE RESIDUAL WASTE TREATMENT PLANT Hertfordshire County Council

DRAINAGE MANAGEMENT PLAN. HERTFORDSHIRE RESIDUAL WASTE TREATMENT PLANT Hertfordshire County Council DRAINAGE MANAGEMENT PLAN HERTFORDSHIRE RESIDUAL WASTE TREATMENT PLANT Hertfordshire County Council EMPLOYER: Veolia Environmental Services (UK) Plc Veolia House 154A Pentonville Road London N1 9PE Copy

More information

R E S I D E N T I A L H O U S I N G

R E S I D E N T I A L H O U S I N G HL 252 Rev. April 1997 R E S I D E N T I A L H O U S I N G CONTROLLING EXTERNALWATER PROBLEMS FOR RESIDENCES I II III IV V Lot Drainage Gutter Water Management Foundation Waterproofing Floor Slab Waterproofing

More information

Land Disturbance, Erosion Control and Stormwater Management Checklist. Walworth County Land Conservation Department

Land Disturbance, Erosion Control and Stormwater Management Checklist. Walworth County Land Conservation Department Land Disturbance, Erosion Control and Stormwater Management Checklist Walworth County Land Conservation Department The following checklist is designed to assist the applicant in complying with the Walworth

More information

CHAPTER 6: SUBSTRUCTURE

CHAPTER 6: SUBSTRUCTURE CHAPTER 6: SUBSTRUCTURE Technical Manual V7: TS-011a-7.00-180814 CHAPTER 6: SUBSTRUCTURE CONTENTS 6.1 BASEMENTS 6.2 WALLS BELOW GROUND 6.3 DAMP PROOFING 6.4 GROUND FLOORS 89 CHAPTER 6 FUNCTIONAL REQUIREMENTS

More information

Ground-borne Vibrations and Ground Settlements Arising from Pile Driving and Similar Operations

Ground-borne Vibrations and Ground Settlements Arising from Pile Driving and Similar Operations Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-137 Ground-borne Vibrations and Ground Settlements Arising from Pile

More information

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength. INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal

More information

FLOOD DAMAGE PREVENTION ORDINANCE

FLOOD DAMAGE PREVENTION ORDINANCE FLOOD DAMAGE PREVENTION ORDINANCE SECTION 1.0 STATUTORY AUTHORIZATION, FINDINGS FO FACT, PURPOSE, AND OBJECTIVES 1.1 STATUTORY AUTHORIZATION The Legislature of the State of Washington has in RCW delegated

More information

Royal Borough of Kensington and Chelsea Residential Basement Study Report December 2012

Royal Borough of Kensington and Chelsea Residential Basement Study Report December 2012 Royal Borough of Kensington and Chelsea Residential Basement Study Report December 2012 Alan Baxter Alan Baxter Prepared by Michael Coombs Reviewed by Jim Gardiner Issued December 2012 T:\0954\0954-130\DTP

More information

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing 1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize

More information

5.0 OVERVIEW OF FLOOD DAMAGE REDUCTION MEASURES

5.0 OVERVIEW OF FLOOD DAMAGE REDUCTION MEASURES 5.0 OVERVIEW OF FLOOD DAMAGE REDUCTION MEASURES Flood damage reduction consists of two basic techniques structural and non-structural. Structural methods modify the flood and take the flood away from people

More information

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide

More information

Investigation of Foundation Failure. Step 1 - Data Collection. Investigation Steps

Investigation of Foundation Failure. Step 1 - Data Collection. Investigation Steps Foundations on Expansive Clay Soil Part 3 - Investigation of Failed Foundations Presented by: Eric Green, P.E. Structural Engineer Slide 1 Copyright Eric Green 2005 Investigation of Foundation Failure

More information

Jackson Gulch Outlet Canal Rehabilitation Project

Jackson Gulch Outlet Canal Rehabilitation Project Jackson Gulch Outlet Canal Rehabilitation Project Preliminary Budgetary Estimate for Rehabilitation February 2004 Prepared for the Mancos Water Conservancy District Jackson Gulch Reservoir 42888 County

More information

STRUCTURAL DAMAGE OF A 5-STOREY BUILDING: DIFFERENTIAL SETTLEMENT DUE TO CONSTRUCTION OF AN ADJACENT BUILDING OR BECAUSE OF CONSTRUCTION DEFECTS?

STRUCTURAL DAMAGE OF A 5-STOREY BUILDING: DIFFERENTIAL SETTLEMENT DUE TO CONSTRUCTION OF AN ADJACENT BUILDING OR BECAUSE OF CONSTRUCTION DEFECTS? STRUCTURAL DAMAGE OF A 5-STOREY BUILDING: DIFFERENTIAL SETTLEMENT DUE TO CONSTRUCTION OF AN ADJACENT BUILDING OR BECAUSE OF CONSTRUCTION DEFECTS? Ioannis Anastasopoulos National Technical University of

More information

School Construction Authority Architecture & Engineering

School Construction Authority Architecture & Engineering SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following

More information

Soils, Foundations & Moisture Control

Soils, Foundations & Moisture Control Soils, Foundations & Moisture Control Soil The top loose layer mineral and/or organic material on the surface of the Earth that serves as a natural medium for the growth of plants and support for the foundations

More information

Taylor Wimpey UK Ltd. December 2007

Taylor Wimpey UK Ltd. December 2007 Taylor Wimpey UK Ltd December 2007 QM Issue/revision Issue 1 Revision 1 Revision 2 Revision 3 Remarks Draft For Planning Date 3 August 2007 20 December 2007 Prepared by D Gooding P Barton Signature Checked

More information

EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS

EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS NMP 1.4 EXCAVATION AND PILING NEAR SEWERS, STORMWATER DRAINS AND WATER MAINS Index Purpose... 2 Application... 2 Referral Agency... 2 Associated Requirements... 2 Referenced Standards...2 Definitions...

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file

Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file Appendix A Sub surface displacements around excavations Data presented in Xdisp sample file Notation B1 = lowest level of basement slab c = cohesion E = drained Young s Modulus Eu = undrained Young s Modulus

More information

CITY OF VINCENT CONSTRUCTION MANAGEMENT PLAN GUIDELINES

CITY OF VINCENT CONSTRUCTION MANAGEMENT PLAN GUIDELINES CITY OF VINCENT CONSTRUCTION MANAGEMENT PLAN GUIDELINES INTRODUCTION What is a Construction Management Plan? The City of Vincent requires careful management of construction involving excavation and retention

More information

How To Plan For A Basement In Wandsworth

How To Plan For A Basement In Wandsworth Wandsworth Local Plan Supplementary Planning Document DRAFT Housing: Basements Section March 2015 Basements Overview of the Basements Section A. Purpose of the Guidance B. Summary of Controls Involved

More information

FOUNDATION TECHNICAL CATEGORY 3 (TC3) AUGUST 2012

FOUNDATION TECHNICAL CATEGORY 3 (TC3) AUGUST 2012 FOUNDATION TECHNICAL CATEGORY 3 (TC3) AUGUST 2012 Building and Housing has published technical guidance for foundation repairs and reconstruction for residential properties in green zone Foundation Technical

More information

ENGINEERED FOUNDATIONS. Department of Public Works Jeff Hill, PE

ENGINEERED FOUNDATIONS. Department of Public Works Jeff Hill, PE ENGINEERED FOUNDATIONS Department of Public Works Jeff Hill, PE What is an engineered foundation. A Foundation Design Developed by a Trained Professional (Engineer) Types of Foundations (All of which can

More information

EXISTING STRUCTURES 1) FAIR MARKET VALUE OF STRUCTURE(s) BEFORE IMPROVEMENT: 2) COST OF IMPROVEMENTS:

EXISTING STRUCTURES 1) FAIR MARKET VALUE OF STRUCTURE(s) BEFORE IMPROVEMENT: 2) COST OF IMPROVEMENTS: Date Received: Received By: Project/Permit Number: Fee: (To be Completed by MOA) FLOOD HAZARD PERMIT APPLICATION (Please fill out application completely; Indicate NA if necessary. Property information

More information

The Manitoba Water Services Board SECTION 022180 Standard Construction Specifications PIPE EXCAVATION, BEDDING AND BACKFILL Page 1 of 11

The Manitoba Water Services Board SECTION 022180 Standard Construction Specifications PIPE EXCAVATION, BEDDING AND BACKFILL Page 1 of 11 Page 1 of 11 Part 1 General 1.1 DESCRIPTION OF WORK.1 The work described herein shall consist of the excavation of trenches (or excavation of tunnels); the supply and placing of bedding and backfill materials;

More information

R&S. August 2014 Prepared by RandS Associated Srl. 1. Introduction

R&S. August 2014 Prepared by RandS Associated Srl. 1. Introduction Building Engineer UK Registration Board n.075077h Design and Access Statement for Application for Planning Permission for demolition of a garage and construction of an extension to an existing Victorian

More information

EARTHWORKS COMPLETION REPORT ELLEN STIRLING PARADE, ELLENBROOK. Ellenbrook, W.A. Georgiou Group Pty Ltd

EARTHWORKS COMPLETION REPORT ELLEN STIRLING PARADE, ELLENBROOK. Ellenbrook, W.A. Georgiou Group Pty Ltd EARTHWORKS COMPLETION REPORT ELLEN STIRLING PARADE, ELLENBROOK Ellenbrook, W.A. Georgiou Group Pty Ltd GEOTPERT08050AZ-AH 27 March 2013 EARTHWORKS COMPLETION REPORT ELLEN STIRLING PARADE, ELLENBROOK Ellenbrook,

More information

Use of a Reinforced Jet Grout Excavation Support System for a Major Sewer Line Repair

Use of a Reinforced Jet Grout Excavation Support System for a Major Sewer Line Repair Use of a Reinforced Jet Grout Excavation Support System for a Major Sewer Line Repair Eric M. Klein, P. E., Rummel, Klepper & Kahl, LLP, Baltimore, Maryland Kenneth B. Andromalos, P. E., Brayman Environmental,

More information

Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors

Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors Improving the flood resistance of your home Advice sheet 6: Flood-resilient This sheet provides guidance on identifying different types of floor, assessing the routes floodwater may enter, and describes

More information

Demolition & Construction Management Plan

Demolition & Construction Management Plan Demolition & Construction Management Plan 72 76 Cadogan lane SW1 Demolition & Construction Management Plan Issue Date: March 2013 Contents: 1.0 Introduction 1.1 Objectives of the Plan 1.2 Project Overview

More information

Building over or close to a public sewer

Building over or close to a public sewer Building over or close to a public sewer thameswater.co.uk/developerservices thameswater.co.uk/developerservices 1 Questions and answers Did you know Thames Water is legally responsible for more than 100,000

More information

Chapter 9 Remedial Measures

Chapter 9 Remedial Measures [This is an annotated version of a chapter from the US Army Corps of Engineers book, Foundations in Expansive Soils. This book is in the public domain. This document is consists of an abbreviated and annotated

More information

CITY OF ST. CA THARINE S. cn- Olc.4 BY-LAW NO. WHEREAS the Council of the Corporation of the City of St. Catharines, is

CITY OF ST. CA THARINE S. cn- Olc.4 BY-LAW NO. WHEREAS the Council of the Corporation of the City of St. Catharines, is ~: ~,,' " CITY OF ST. CA THARINE S BY-LAW NO. cn- Olc.4 A By-law to regulate sanitary and storm drainage. WHEREAS the Council of the Corporation of the City of St. Catharines, is authorized by the provisions

More information

SE-10 STORM DRAIN INLET PROTECTION. Objectives

SE-10 STORM DRAIN INLET PROTECTION. Objectives STORM DRAIN INLET PROTECTION SE-10 Objectives Erosion Control - EC Sediment Control - SE Tracking Control - TC Wind Erosion Control - WE Non-Storm Water Management - NS Waste and Materials Management -

More information

How to Design and Build a Fence/G traverse Bridge or Graffiti Project

How to Design and Build a Fence/G traverse Bridge or Graffiti Project Outline Project Location Project Description Project History Site Constraints Geotechnical Investigation & Soil Profile Foundation Design Process Photos Project Location Project Limits: The Grand River

More information

Action plans for hotspot locations - Ash Study

Action plans for hotspot locations - Ash Study Appendix 9 Action plans for hotspot locations - Ash Study Ash Vale North 1. Local evidence indicates the culvert could not discharge during December 2013 because the outlet was blocked on the western side

More information

FLOOD RISK AND SURFACE WATER DRAINAGE ASSESSMENT HILLHOUSE RESTORATION SITE, OFF JAMESON ROAD, THORNTON CLEVELEYS ON BEHALF OF NPL ESTATES

FLOOD RISK AND SURFACE WATER DRAINAGE ASSESSMENT HILLHOUSE RESTORATION SITE, OFF JAMESON ROAD, THORNTON CLEVELEYS ON BEHALF OF NPL ESTATES FLOOD RISK AND SURFACE WATER DRAINAGE ASSESSMENT HILLHOUSE RESTORATION SITE, OFF JAMESON ROAD, THORNTON CLEVELEYS ON BEHALF OF NPL ESTATES Integra Consulting Engineers Limited NS / 2543 Fountain House

More information

Design and Construction of Cantilevered Reinforced Concrete Structures

Design and Construction of Cantilevered Reinforced Concrete Structures Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-68 Design and Construction of Cantilevered Reinforced Concrete Structures

More information

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side

More information

Member Nation Report 2010 from Denmark.

Member Nation Report 2010 from Denmark. Member Nation Report 2010 from Denmark. The has during the year 2010 arranged 6 member meetings including two technical site visits. The first technical site visit covered the 5.3 km long Leipzig City

More information

Chapter 9: Water, Hydrology and Drainage Land West of Uttoxeter

Chapter 9: Water, Hydrology and Drainage Land West of Uttoxeter Chapter 9: Water, Hydrology and Drainage Land West of Uttoxeter ENVIRONMENTAL STATEMENT: VOLUME 1 9.1 INTRODUCTION 9.1.1 This Chapter considers the effects of the Project on surface water and groundwater

More information

Vital Earth Composting Facility Flood Risk and Drainage Statement

Vital Earth Composting Facility Flood Risk and Drainage Statement Vital Earth Flood Risk and Drainage Statement Final December 2011 Prepared for Vital Earth Ltd Revision Schedule Flood Risk and Drainage Statement December 2011 Rev Date Details Prepared by Reviewed by

More information

PROPOSAL FOR CONTRACTORS ALL RISKS

PROPOSAL FOR CONTRACTORS ALL RISKS PROPOSAL FOR CONTRACTORS ALL RISKS 1. Title of contract (If project consist of several sections, specify section(s) to be insured) 2. Location of site Country/Province/district City/town/village 3. Name

More information

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations Nathan A. Ingraffea, P.E., S.E. Associate, KPFF Consulting Engineers, Portland, Oregon, USA Abstract The use of steel sheet

More information

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE

After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE 86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is

More information

ORDINANCE NO. 2013 -

ORDINANCE NO. 2013 - ORDINANCE NO. 2013 - AN ORDINANCE OF BREVARD COUNTY, FLORIDA AMENDING CHAPTER 62, LAND DEVELOPMENT REGULATIONS SECTION 62-2891, LOT DRAINAGE, AND CHAPTER 22 BUILDINGS AND BUILDING REGULATIONS, SECTION

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information