Building Condition Assessment: West Lexington Street Baltimore, Maryland
|
|
- Jessica Sherman
- 8 years ago
- Views:
Transcription
1 KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc Seton Drive, Baltimore, MD Phone: ( ) Fax: (410) Building Condition Assessment: Baltimore, Maryland May 7, 2012
2 EXCUTIVE SUMMARY The roof is leaking at throughout. No leaking was observed at windows. The front wall has open mortar joints and cracked stone units. Exterior walls are structurally sound. There is no danger of failure of structural elements. Opinion of Cost: Immediate Repairs Structural Stabilization Repairs: None required None required Building Envelope Repairs: $59,000 Total: $59,000 Prepared by Kennedy, Porter and Associates, Inc. Page 1
3 STRUCTURE DESCRIPTION The building is approximately 158 x 70, with three stories over a basement. It was reportedly constructed circa The building s structure consists of brick masonry exterior walls and wood framed floors. The north face of the building finished with decorative stone. The premises are currently vacant; its most recent uses include offices and retail stores. We have reviewed available information provided to us by Baltimore City about the building. This information was limited to tax records, historic fire insurance maps and land eligibility reports provided by CHAP. INSPECTION OBSERVATIONS Building was inspected by the joint venture of EBA Engineering, Inc. and Kennedy, Porter and Associates, Inc. on May 2, Our inspection was visual in nature, and was limited to accessible structural elements. Façades were inspected from grade using binoculars. Roofs were accessible and were included in our inspection program. No finishes were removed and no probes were made to determine structural conditions. Figures 1 and 2 show general exterior conditions and photograph locations. The structure is in overall fair to good condition. Observed deficiencies are summarized as follows: Roof Appurtenances Roof Framing The roof is generally flat, and is covered with a membrane roofing system. There are many penetrations through the roof for mechanical equipment (see Photo 1and 2). Steel dunnage supporting mechanical equipment over the roof is in generally fair condition. Paint is peeling throughout and minor corrosion was observed. The upper stair well roof exhibits membrane deterioration and is not able to repel water (see Photo 3). The roofing membrane has generally failed throughout. Active leaks were noted in the fifth floor ceiling below. Standing water was noted against the south parapet near the building s middle. Water damage from leakage was observed along the south wall at two locations (one east of the elevator and over the stair tower (see Photo 3). At these locations, wood plank roof sheathing has been damaged and will require replacement (see Photo 4). Wood roof rafters have minor deterioration. Floor Framing Water damage continues down to the third and second floor framing. Wood plank sub-floor is damaged and leaks in these areas. The second floor southwest corner area exhibits partial failure due to heavy loads imposed on deteriorating floor framing (see Photo 5). Prepared by Kennedy, Porter and Associates, Inc. Page 2
4 Foundations There are numerous areas that exhibit water damage throughout the third, second, and first floors (see Photos 6-9). No signs of differential settlement, bowing or cracking were observed in the masonry foundation walls (see Photo 10). There are several reinforced concrete beams that exhibit wide horizontal cracks (see Photos 11-14). There are several loose and broken treads in the basement level stair well (see Photo 15). The concrete basement slab exhibits uplift, cracking and settlement in two locations (see Photos 16-18). Interior Bearing Walls Interior walls were concealed by finishes, but no signs of distress, such as settlement or cracking, were noted in these finishes (see Photo 19). South Elevation The south façade consists of common brick. There are step cracks in the brick and mortar joints at the top portions of the wall (see Photos 20 and 21). The cracking at the east end continues horizontally into the east façade plastered finish (see Photos 21 and 22). There are areas of missing brick and deteriorating mortar at the base of the wall, with concrete spalling located along an exit door threshold ( see Photos 23 and 24). Rear (East) Elevation The east elevation consists of common brick. The brick is in generally satisfactory condition, although there are random areas of spalled bricks (see Photo 9). The steel fire escape at this façade is in generally fair condition. Left (North) Elevation The North elevation features three recessed entries. The second and third stories have decorative stone work finishes that exhibit numerous cracks and deteriorating mortar. Several of these locations exhibit vegetation growth (see Photo 25-29). There are two fractured parapet cap stones at the east and west portions of the north wall (see Photos 30 and 31). Interior leakage above the north store front framing in building 219 was observed during the time of inspection thru deteriorated members (see Photo 32). All window and door sashes, lintels, frames, and sills exhibit moderate to severe paint failure. Prepared by Kennedy, Porter and Associates, Inc. Page 3
5 Recommendations: Our recommendations below refer to structural elements of the building only. These are based on conditions observed at the time of our inspection. Our Engineer s Opinion of Probable Cost included with the repair recommendations is schematic in nature, consistent with the level of detail provided in our general repair recommendations. Immediate Repairs These repairs are required to be performed immediately on an emergency basis in order to prevent an imminent collapse or because the noted conditions pose a safety risk to the general public. - None required Structural Stabilization Repairs These should be scheduled as soon as possible. These recommendations require action to prevent accelerated deterioration of the structure, or in order to prevent the development of dangerous conditions in the future. - None required Building Envelope Repairs These repairs should be performed in order to maintain the building s longevity and ensure its continued usability, in part or in whole. - Patch roofing system $8,000 - Repoint open mortar joints at front façade $36,000 - Repair cracked stone units at front façade $15,000 Total $59,000 Prepared by Kennedy, Porter and Associates, Inc. Page 4
6 Figure 1: West Elevation Prepared by Kennedy, Porter and Associates, Inc. Page 5
7 20 21 Figure 2: North Elevation Prepared by Kennedy, Porter and Associates, Inc. Page 6
8 Photo 1: Roof Condition Looking North Photo 2: Roof Condition Looking South Prepared by Kennedy, Porter and Associates, Inc. Page 7
9 Photo 3: Deteriorating Roof Membrane Photo 4: Water Damage in Third Floor Ceiling at South Wall Prepared by Kennedy, Porter and Associates, Inc. Page 8
10 Photo 5: Collapsed Second Floor in Southwest Room Photo 6: Typical Water Damage in Floor Ceiling Prepared by Kennedy, Porter and Associates, Inc. Page 9
11 Photo 7: Typical First Floor Ceiling Photo 8: Water Damage in First Floor Framing Prepared by Kennedy, Porter and Associates, Inc. Page 10
12 Photo 9: Water Damage in Second Floor Framing Photo 10: Typical Basement Foundation Wall Prepared by Kennedy, Porter and Associates, Inc. Page 11
13 Photo 11: Cracking Concrete Beam in Basement Level Ceiling Photo 12: Cracking Concrete Beam in Basement Level Ceiling Prepared by Kennedy, Porter and Associates, Inc. Page 12
14 Photo 13: Cracking Concrete Beam in Basement Level Ceiling Photo 14: Cracking Concrete Beam in Basement Level Ceiling Prepared by Kennedy, Porter and Associates, Inc. Page 13
15 Photo 15: Broken Basement Steps Photo 16: Spalling Concrete Basement Slab Prepared by Kennedy, Porter and Associates, Inc. Page 14
16 Photo 17: Spalling Concrete Basement Slab Photo 18: Spalling Concrete Basement Slab Prepared by Kennedy, Porter and Associates, Inc. Page 15
17 Photo 19: Typical Condition of Interior Bearing Walls Photo 20: Cracking in West corner of South Façade Prepared by Kennedy, Porter and Associates, Inc. Page 16
18 Photo 21: Cracking in East corner of South Façade Photo 22: Cracking in West Elevation Prepared by Kennedy, Porter and Associates, Inc. Page 17
19 Photo 23: Deteriorating Mortar at Base of South Wall Photo 24: Spalling Concrete at Base of South Wall Prepared by Kennedy, Porter and Associates, Inc. Page 18
20 Photo 25: Cracked Stone Lintel in North Façade Photo 26: Deteriorating Mortar in North Facade Prepared by Kennedy, Porter and Associates, Inc. Page 19
21 Photo 27: Deteriorating Mortar in North Facade Photo 28: Cracked Stone Lintel in North Facade Prepared by Kennedy, Porter and Associates, Inc. Page 20
22 Photo 29: Cracked Stone Lintel in North Facade Photo 30: Crack in Parapet Cap Stone Prepared by Kennedy, Porter and Associates, Inc. Page 21
23 Photo 31: Crack in Parapet Cap Stone Photo 32: Interior North Face Water Damage at Window Lintel Prepared by Kennedy, Porter and Associates, Inc. Page 22
Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More information201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE
STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,
More informationSECTION 3 ONM & J STRUCTURAL ANALYSIS
Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION
More informationSTRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA
STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael
More information423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT
Urgent Needs II City of Baltimore No. 1099 423 NORTH HOWARD ST. 423 North Howard Street (circa 1880) is a multi-story building constructed second in row south of Franklin Street and between the vacant
More informationSlavic Village Building Condition Review
Slavic Village Building Condition Review Slavic Village Development May 8, 2015 Page 1 EXECUTIVE SUMMARY City Architecture was commissioned by Slavic Village Development to review five existing facilities
More informationExterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
More informationSTRUCTURAL ASSESSMENT
STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha
More informationEngineers, Civil Structural Survey
Engineers, Civil Structural Survey 317 STREET 0 6 3 6 0 886-1966 886-9165 FAX. September 1 1 Mr. Alan Bergren City Manager City of Norwich Broadway, Floor Norwich, 06360 Re: Limited Structural Condition
More informationPELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007
PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT November 2007 PURPOSE OF INVESTIGATION Determine possible locations of moisture intrusion into and through facade. Determine cause of horizontal and vertical
More informationEAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
More informationFacility Assessment for. 11801 East Main Street, Huntley, IL
Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested
More informationReference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls
Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto
More informationREQUEST FOR PROPOSALS FOR: THE PURCHASE AND RENOVATION OF ADJOINING PROPERTIES AT 200/240 SOUTH 16 TH STREET ORD, NEBRASKA BY:
REQUEST FOR PROPOSALS FOR: THE PURCHASE AND RENOVATION OF ADJOINING PROPERTIES AT 200/240 SOUTH 16 TH STREET ORD, NEBRASKA BY: THE COMMUNITY DEVELOPMENT AGENCY OF THE CITY OF ORD JULY 2014 A. STATEMENT
More informationBuilding Foundation and Structure
Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original
More informationBROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208
BROWNSVILLE STRUCTURES STUDY July 2012 Prepared by LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 TABLE OF CONTENTS I. SUMMARY OF BUILDING ANALYSIS.. 1 II. INDIVIDUAL BUILDING
More informationOctober 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.
117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This
More informationBuilding Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
More informationStructural Assessment Report
Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive
More information14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102
Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We
More information48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.
Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two
More informationGarver Feed Mill Condition Evaluation
Garver Feed Mill Condition Evaluation OUTLINE Brick masonry overview Condition assessment & methodology Project overview Existing conditions Stabilization Probable costs Summary BRICK MASONRY OVERVIEW
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More information29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York
Due Diligence Report New York, New York Prepared for Mr. On February 8, 2010 P a g e 1 Table of Contents PAGE 3.. GENERAL INFORMATION PAGE 4 FILINGS PERMITS AND ENCUMBRANCES PAGE 6. CORE AND SHELL PAGE
More informationCertification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
More informationSchool Construction Authority Architecture & Engineering
SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following
More informationMay 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,
PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced
More informationCZAR Engineering, L.L.C.
CZAR Engineering, L.L.C. Lamont H. Czar, P.E. Phone: (609) 653-9445 5014 Fernwood Avenue Fax:(609)653-2015 Egg Harbor Township, New Jersey 08234 www.czarengineering.com May 3, 2013 Craig Dothe, Architect
More informationPage & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
More informationA0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET
POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET
More informationFoundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:
A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.
More informationRe: Damages to Alaska Building from Legislative Information Office Construction
510 L Street Suite 200 Anchorage, AK 99501-1949 (907) 274-22362236 Phone (907) 274-25202520 Fax www.bbfm.com July 22, 2015 Jim Gottstein Alaska Building 406 G Street, Suite 206 Anchorage, AK 99501 Re:
More informationArchitectural Condition Survey
Architectural Condition Survey Santa Fe Railroad / AMTRAK Depot, Lawrence. Kansas for the City of Lawrence, 2002 Survey: (student) PI: William Carswell, Associate Dean, School of Architecture, University
More informationBUNKER HILL ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1970 BUILDING AREA 98,200 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 387 WARD 5 PROPOSED PROGRAM CAPACITY 750 Site Plan BUNKER HILL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationMemorandum. July 16, 2008. To: Plan Commission City of Madison
Memorandum July 16, 2008 To: Plan Commission City of Madison From: Marc Schellpfeffer Engberg Anderson Re: Structural/Architectural Assessment of Homes for Proposed Demolition Findorff Yards Office Lofts
More informationPhotos showing the change in condition from 2006 to 2012 are located in Appendix A.
January 27, 2012 Ms. Theresa Gallavan Economic Development Director City of Lompoc 100 Civic Center Plaza Lompoc, California 93436 RE: Lompoc Theater Limited Visual Condition Assessment Dear Theresa: Representatives
More informationMarch 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202
Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request
More informationHEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationOTTAWA CIVIC CENTRE & NORTH SIDE STANDS LANSDOWNE PARK FRANK CLAIR STADIUM STRUCTURAL ADEQUACY REPORT 2007
OTTAWA CIVIC CENTRE & NORTH SIDE STANDS at LANSDOWNE PARK FRANK CLAIR STADIUM STRUCTURAL ADEQUACY REPORT 2007 for CITY OF OTTAWA REAL PROPERTY ASSET MANAGEMENT prepared by ADJELEIAN ALLEN RUBELI LIMITED
More informationSisal Composite Ltd. Apparel 4 Ltd. JM Knit Ltd. Natun Para, Hemayetpur, Savar, Dhaka-1340 (23.789416N,90.266135E)
Revision: issue 1 Date: 11 June 2014 Sisal Composite Ltd. Apparel 4 Ltd. JM Knit Ltd. Natun Para, Hemayetpur, Savar, Dhaka-1340 (23.789416N,90.266135E) 24 th May 2014 Structural Inspection Report Observations
More informationLighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
More informationSTRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA
STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box 144003 835 College Avenue, Building MS-3 Kentfield, California
More informationSelf-Home Inspection Checklist
To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional
More informationCONSERVATION MAINTENANCE WORKSHEET Universal Checklist
3.1 SITE 1 Concrete curbs Check for cracks, spalling, growth from joints X 2 Stone curbs Check for cracks, spalling, growth from joints X 3 Concrete walkways Look for uneven surfaces, ponding, growth from
More informationBUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
More informationMEMORANDUM. General: Foundation:
MEMORANDUM State of Alaska Department of Transportation and Public Facilities Central Region - Division of Construction and Operations Public Facilities Branch TO: Jennifer Murrel DATE: August 19, 2010
More informationProject Report. Structural Investigations Hotel del Sol Yuma, Arizona
Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,
More informationDRAPER ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1953 BUILDING AREA 54,000 SF CURRENT PROGRAM CAPACITY 250 ENROLLMENT 2008 84 WARD 8 PROPOSED PROGRAM CAPACITY 325 Site Plan DRAPER - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationFoundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training
Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline
More informationHow To Prevent Water Damage To A Home
Having inspected about 800 homes in the last four years, I have seen a lot of problems with many homes. Most of these problems are minor; however, there are some problems that are quite serious. One of
More informationFoundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
More informationPROFESSIONAL ENGINEERING INSPECTIONS, INC.
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More information17,280 square feet Overview:
CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The
More informationVision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationMark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
More informationChapter 5. In-depth Building Analyses and Recommendations. Planning Study for Downtown Revitalization City of Martinsville
75-77 East Washington Street In-depth Building Analyses and Recommendations Chapter 5 In-depth Building Analysis Overview Four of the nineteen downtown buildings selected for façade assessments and recommendations
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More informationHistoric Preservation Certification Application Part 2 343-345 Main Street West South Haven, Vermont NPS Project No. 12345
Exterior Features 1 site and drainage 2 foundation 3 wood siding and trim 4 exterior doors 5 windows / storm windows 6 porches front and rear 7 chimneys 8 roofing Interior Features 9 frame 10 basement
More informationGuernsey s Structural Engineering Experience
Guernsey s Structural Engineering Experience Foundation Settlement Issues: Trinity Valley Electric Cooperative, Kaufman, TX: Analyzed their headquarters facility for issues with soil movement that was
More informationCONDITION OF QUALITY ITEMS
CONDITION OF QUALITY ITEMS FOUNDATION Always look for moisture problems and any bulges or irregularities in the walls. Lines on the walls or floors may indicate water problems. Have these been cured? If
More informationPRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com
PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com June 17, 2015 Ms. Kimberley Heaton McCarthy Supervising Planner Building and Safety
More informationName of course: Residential Construction Site Management (RCSM) Level 1
Name of course: Residential Construction Site Management (RCSM) Level 1 Core (required courses) or Optional (elective course): Required Delivery Method: This is an online course only with no classroom
More informationRepair and Rehabilitation of Nehru Memorial College of K.V.G. Group of Institutions at Mangalore - A Case Study
Repair and Rehabilitation of Nehru Memorial College of K.V.G. Group of Institutions at Mangalore - A Case Study Surresh Chandra Pattanaik ab, E. Gopal Krishnan b and Mohan Kumar c a School of Civil Engineering,
More informationREBUILDING WOOD TRUSSES WITH STEEL. Despite a major renovation
REBUILDING WOOD TRUSSES WITH STEEL Moisture damage to structural elements required an innovative solution to preserve a historic structure By Ethan Buell, P.E., and David Carroll, P.E. Despite a major
More informationSaint Cloud Business Center
Saint Cloud Business Center 14 7th Avenue North Saint Cloud, MN 56303 For Sale Located on 7th Avenue in the heart of downtown across from the Court House Square. A large professional reception area with
More informationNational Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067
Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com
More informationHow Façade Ordinances Affect Your Historic Building
How Façade Ordinances Affect Your Historic Building Carolyn L. Searls Simpson Gumpertz & Heger 12 May 2015 www.sgh.com Copyright Materials This presentation is protected by US and International Copyright
More informationProperty Condition Assessment
Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar
More information~iffiui ~ Bridge Condition Survey. Inspection Date: 21 May 2003 District: San Angelo County: Tom Green Highway:
Texas Depadment of Transpo,tation Bridge Condition Survey Inspection Date: 21 May 2003 District: San Angelo County: Tom Green Highway: Irving Street Facility Name: Lone Wolf Bridge Structure Number: B00315-031
More informationLighthouse Engineering, L.L.C.
Wednesday, August 20, 2014 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website:
More informationASHULIA APPARELS LTD. Client Summary Report
Revision : Issue 1 Date: 18 March 2014 ASHULIA APPARELS LTD Samad Mansion, Sec # 6, Block # kha, Road No# 1, Plot #14, Shenpara Parbata, Mirpur, Dhaka (23.8065N,90.3683E) 4th March 2014 Client Summary
More informationDate: March 7, 2006 Report for [removed]
Date: March 7, 2006 Report for [removed] The Preservation Resource Center Of New Orleans, in conjunction the National Trust for Historic Preservation, has conducted a condition survey of your property.
More informationBernie Nimer, Dave Seton Mayfair Hotel Development Corporation
SITE INVESTIGATION REPORT NO. S1r1 PROJECT: The Mayfair Hotel PROJECT NO: 140565 ATTN: Bernie Nimer, Dave Seton Mayfair Hotel Development Corporation PREPARED BY: Cory Zurell, PhD, P.Eng. DATE: 13 April
More informationHow to Identify, Evaluate & Repair Shrinkage Cracks in Poured Concrete
How to Identify, Evaluate & Repair Shrinkage Cracks in Poured Concrete What is concrete shrinkage cracking, how and where does it occur? Are concrete floor cracks a structural problem? How to recognize
More informationHISTORIC PRESERVATION COMMISSION ADMINISTRATIVE APPROVAL ISSUED JULY - SEPTEMBER 2014 DATE PROJECT ADDRESS PROJECT DESCRIPTION
HISTORIC PRESERVATION COMMISSION ADMINISTRATIVE APPROVAL ISSUED JULY - SEPTEMBER 2014 DATE PROJECT ADDRESS PROJECT DESCRIPTION 07/02/14 212A King George Street Remove existing picket fence from side yard
More informationD Sample Notices to Property Owners, Sample Affidavits, and Other Material
D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully
More informationHome Inspection Report
Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector
More informationPhoto 2. View showing flour mill, machine shed, veranda and saw mill + storage shed.
May 7,2015 KSANDER & ASSOCIATES CONSULTING PROFESSIONAL ENGINEERS 130 HUINTER STREET, UNIT 103, PETERBOROUGH, ONTARIO K9H2K8 TELEPHONE (705) 743-9221 FAX 743-0904 Ontario Region Conservation Authority
More informationbout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
More informationEstimated Cost of Repair
1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:
More informationWebsite. King County Council District # WA State Legislative District # Date Incorporated. Federal Tax ID. WA State UBI#
Address Shipping Address Phone Information removed for privacy Fax Website Email Information removed for privacy King County Council District # WA State Legislative District # Date Incorporated Information
More informationHow To Find Out What Happened To Slave Housing
Slave Housing Data Base Building Name: Presquisle Brick Duplex 2 (northern building) Evidence Type: Extant Site ID: Historical Site Name: City or Vicinity: County: Culpeper State: Virginia UTM: Easting:
More informationCABIN A Restored & Preserved 1850 Slave Cabin
CABIN A Restored & Preserved 1850 Slave Cabin Cabin A has been restored and preserved to reflect its original 1850 construction and utilization as a slave cabin. This cabin had the most intact architectural
More informationTITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
More informationPROPERTY East Wetumpka Commercial Historic District (Boundary Increas NAME: e)
REQUESTED ACTION: UNITED STATES DEPARTMENT OF THE INTERIOR NATIONAL PARK SERVICE EVALUATION/RETURN SHEET NOMINATION PROPERTY East Wetumpka Commercial Historic District (Boundary Increas NAME: e) MULTIPLE
More informationGUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES
GUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES PAGE 13 DESIGN GUIDELINES The following design guidelines have been developed to guide appropriate design in the Downtown
More informationArticle 5: Building Regulations
Article 5: Building Regulations Division 37: Additional Building Regulations for Archaic Materials and Methods of Construction (Added Additional Building Regulations for Archaic Materials and Methods of
More informationFire Alarm And System Description. Automatic Sprinkler System Description. Fire Suppression Equipment. Fire and Evacuation Drills
Building Name: Maddox Hall Year Built: 1985 Occupancy: Residence Hall Capacity: 152 Construction Type: Reinforced concrete slab, CMU walls, flat roof concrete slab. Building Name: Wright Hall Year Built:
More informationRoof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
More informationWEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204
WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 Structural Inspection Report Client: CSArch Architecture Engineering Construction Management 19 Front Street, Newburgh,
More informationGeneral Earthquake Damage Inspection Checklist
A. GENERAL INFORMATION 1. Street Address of Property: City: State: Zip: 2. Property Owner s Name: 3. Date of inspection: 4. Inspector s Name: B. BUILDING SITE INSPECTION 5. Utility Service Safety: IMPORTANT
More informationChapter 11: Demolition
City of Independence Chapter 11: Demolition In this chapter you will find: Demolition Mothballing Treatment Types of Demolition By Neglect and Recommended Corrective Measures DEMOLITION Photograph on cover
More informationHarris Hydraulics Laboratory Pumphouse Fall Guard Addendum to the Historic Resources Addendum
Harris Hydraulics Laboratory Pumphouse Fall Guard Addendum to the Historic Resources Addendum University of Washington James Cary, Architect pc 8 May 2013 1. INTRODUCTION Background The University of Washington
More informationHAMILTON SCHOOL. 1401 Brentwood Parkway, N.E., Washington, DC INITIAL YEAR BUILT 1968 BUILDING AREA
INITIAL YEAR BUILT 1968 BUILDING AREA 187,700 SF CURRENT PROGRAM CAPACITY N/A ENROLLMENT 2008 129 WARD 5 PROPOSED PROGRAM CAPACITY N/A Site Plan HAMILTON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More information5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net LIMITATIONS AND DISCLAIMERS
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Court Richmond, Texas Mr. Foundation Concerns INSPECTION DATE:
More informationGOOD NEWS BUT NOT ALWAYS
GOOD NEWS BUT NOT ALWAYS The prospective homebuyer and homeowner in the Amarillo area are indeed fortunate. Typically, he has a wide choice of type home, size, and location for wide ranges of pricing.
More informationG. Common Defects in Buildings - Leakage
F. Common Defects in Buildings - Structural 32. Recently, some concrete chips have fallen from the ceiling in my kitchen. There are rusty steel bars and the area in question measures about 300 x 400mm.
More informationBTC. Building Technology Consultants, PC 1845 E. Rand Road, Suite L-100 Arlington Heights, Illinois 60004 Main: (847) 454-8800, Fax: (847) 454-8801
BTC Structural Engineer Hpreicher@btcpc.com Patrick E. Reicher is a Structural Engineer at Building Technology Consultants, PC. 6BREGISTRATIONS Licensed Structural Engineer (SE), Illinois Certified Construction
More information