Property Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT

Size: px
Start display at page:

Download "Property Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT"

Transcription

1 Property Inspection 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT March 2013

2 This document has been prepared for the benefit of Clint Marston. No liability is accepted by this company or any employee or sub-consultant of this company with respect to its use by any other person. Quality Assurance Statement and Revision History Revision Date Inspected By Prepared and Reviewed By Status Milton Hayward Project Manager Graeme Johnson Structural Lead CPEng MIPENZ Approved Viden Consulting Engineers Ltd PO Box Hornby, 8442 Christchurch New Zealand Tel: Web:

3 Contents Executive Summary Introduction Inspection Structural Form General Detailed Findings Summary... 4 Appendix A Site Location... 5 Appendix B Site Plan... 6 Appendix C Site Photos... 7

4 Executive Summary Viden Group Engineers have been engaged to conduct a structural inspection of 83A Ascot Avenue, North New Brighton, Christchurch. The purpose of the inspection and this report are to ascertain and document the extent of any structural damage caused through the recent seismic events in Canterbury, covering the period September 2010 to March A detailed visual inspection of the main structural elements of the house has been conducted, with a review of the structural condition and integrity as may be typical for a house of this age, material and construction. No review of the original design documentation, compliance with building code clauses B1/B2, or building consent has been undertaken as part of the inspection and this subsequent report. In addition, it should be noted that assessment of the baseline capacity of the structure is beyond the scope of this report. Further to this, Viden has not made any assessment of the structural stability or building safety in connection with future aftershocks or earthquakes which have the potential to damage the building. This report is limited by the restricted ability to carry out inspections due to coverings of many elements and no destructive testing has been undertaken. The report does not address defects that are not reasonably discoverable on visual inspection, including defects in inaccessible places. Visual inspection of the property at 83A Ascot Avenue has revealed signs of moderate structural damage attributable to the recent Canterbury earthquake sequence. The foundations are out of level and exceed recommended tolerances, although the general condition of the perimeter foundation suggests the foundations will respond well to re-levelling. In general, repairs should be undertaken to reinstate the house to its pre earthquake level. Provided appropriate repairs and replacement of the damaged internal bracing elements (plasterboard) are carried out in accordance with the available guidelines, it is expected that the dwelling will be safe to occupy in the interim. The original inspection and this subsequent report are carried out in accordance with the ACENZ Short Form Model Conditions for Engagement of Consulting Engineers, copies available at the following web address. ( 1. Introduction Viden Group conducted a structural inspection of the 83A Ascot Avenue property for the current owner on the 23 rd of March (Figure 1) The land was visually inspected and compared along with the Tonkin and Taylor detailed land reports and zoning maps for Christchurch. This has identified the house lying with the Green Zone Technical Category 3 which is described as being generally suitable to be repaired and rebuilt on but with moderate to significant land damage possible from future significant earthquakes (CERA and Department of Building and Housing Information Sheet October For houses in this technical category that have suffered foundation damage, site-specific geotechnical investigation and specific engineering design may be necessary for repair or rebuilding of those elements.

5 2. Inspection 2.1 Structural Form 83A Ascot Avenue is characterised as a timber framed single story residential dwelling with brick veneer cladding typical of modern house construction in New Zealand. It is assumed that this dwelling was designed and built in accordance with the governing codes of practice at the time of construction. No original engineering or building documentation has been reviewed as part of this report. 2.2 General The house is a single story residence. The gravity system consists of a corrugated profiled metal roof supported on timber trusses spanning between external and internal load-bearing walls. The ceiling is lined with plasterboard supported from timber joists spanning between external and internal load-bearing walls. The walls are timber framed, with internal plasterboard cladding and external brick cladding. The walls transmit loads vertically to the slab-on-grade concrete foundation. Residential construction of this type is typically detailed to use ceiling lining as a horizontal diaphragm, transferring lateral loads to the vertical resisting elements (walls) which transmit the load into the foundation. The lateral load transfer capacity of the walls is provided through panel action of the plasterboard lining, with the timber framing behind acting as compression and tension chords and detailed accordingly for hold-down. Founded on a concrete slab-on-grade, the house structure relies on adequate vertical bearing capacity and lateral resistance of the soil on which the pad is constructed. The ability of the concrete slab foundation to transmit lateral loads into the ground is typically a function of the vertical area of the sides of the slab or thickenings and the embedment into the soil, and friction interaction between the underside of these elements and the soil beneath. An attached internal access double garage forms part of the structure with vertical structure comprising profiled metal roofing spanning over timber framing which spans between an external timber wall and the timber framing of the house. The floor is a concrete slab-on-grade and the external walls are clad with brick. The east (rear) wall of the garage is a 150mm filled block fire wall being less than 1 meter from the boundary line. The house is defined as a Type C2 structure in table 2.1 of the DBH s Guide: Revised guidance on repairing and rebuilding houses affected by the Canterbury earthquake sequence (Dec 2012) and Appendix C (April 2012). Hereafter referred to as the DBH Guide. 2.3 Detailed Findings The section surrounding the building showed considerable evidence of liquefaction at the time of inspection, particularly at the street frontage and eastern wall of the garage as well as residual liquefaction dust on the garage floor on the south facing wall where maximum slab settlement had occurred. No ground Fissures were seen. There was evidence of movement in the driveway and footpaths. (Figure 4, Figure 5, Figure 6).

6 The house has differentially settled to the south. Floor levels were taken through the house using a digital spirit level which showed slopes in the order of 0.2% east/west and 1.6% north/south (Figure 7, Figure 8, Figure 9). Further to this, a levelling survey was undertaken through the house using a gas level and the readings are shown on the floor plan (Figure 2 ). This survey showed that the house had settled in the order of 210mm from north to south. This relatively uniform settlement is likely caused by a loss of bearing capacity following the liquefaction. The settlement is predominantly towards the southern garage end of the house, clearly seen by the liquefaction line still on the external brickwork and the excavations still evident (Figure 10). The level of settlement in the slab over the house footprint inclusive of the garage falls in the order of 210mm North/South and 20-30mm east/west mm settlement over the floor plan is a performance criteria referenced in the DBH guide for which foundation re-levelling is required (DBH Guide Table 2.3). Therefore, based on current DBH Table 2.3 guide, re-levelling of the foundation is likely required as a minimum. The slab gradients actually exceed this criteria indicating a foundation rebuild may be required, as indicated by table 2.3 of the DBH guide. In its current state, it is expected that in the event of further significant seismic events, the foundation would not perform as designed and therefore incremental increases to the damage may be expected. It should also be noted that since the house is sited on land zoned as TC3, specific engineering design or direction may be required prior to repairs and pending any requirements for Building Consent. It was not possible to visually inspect the full concrete slab foundation inside the house due to floor coverings. However in the vinyl areas of the kitchen and the bathroom/toilet and ensuite, no cracks or movements were discernible in the slab. No obvious vertical or lateral movement was suggested in the carpet contour. No cracks were seen in the external perimeter concrete footing at any point where it was exposed for inspection. The exposed garage concrete slab-on-grade foundation is cracked along the central machine cut joint. (Figure 11). The garage has at least one smaller crack (Figure 12) that is in the order of 1-2mm in width. As above, the DBH guide suggests that cracks of this magnitude should be repaired. Most of the entire garage was covered in the occupant s belongings and was not able to be inspected. A reasonable quantity of liquefaction dust was observed along the inside front (south) wall on the garage. The external brick cladding is generally in acceptable structural condition. There is minor stepped cracking in the order of 1-2mm in width around window frames which are typically high stress areas (Figure 13, Figure 14). Further to this, a gap has opened up between the brick cladding and the garage door framing in the order of 10mm (Figure 15). These cracks do not significantly reduce the structural capacity of the house and can be remediated in due course in order to promote and maintain durability and weather-tightness. The verticality of the external cladding is within acceptable limits, and the cladding appeared secure with the framing behind. (Figure 16) There is significant damage to the internal plasterboard linings throughout the house particularly in the lounge, living room and kitchen areas. This damage is typical of many houses in Christchurch following the recent earthquakes and typically comprises 0.5-1mm wide cracks around high stress areas such as windows frames, door frames and plasterboard joins (Figure 17, Figure 18, Figure 19 ). These cracks do not significantly reduce the structural capacity of the house and can be remediated in due course in accordance with the recommendations found in the DBH guide.

7 The timber roof framing was visually inspected from the access hatch in hallway. The timber structural members are in acceptable condition and showed no signs of structural damage attributable to recent Canterbury earthquake events. Nail plates on the timber trusses and connections inspected were in good condition and no evidence of significant movement or permanent deformation was noted (Figure 20, Figure 21). 3. Summary The property at 83A Ascot Avenue shows evidence of structural damage as a result of the recent Canterbury earthquake sequence. There is movement and differential settlement of foundations and moderate damage to internal lining. Besides minor stepped fractures in the external brick cladding, the external veneer is in acceptable condition. Although the current guidance from the Department of Building and Housing suggest the foundation may require rebuilding, given the good condition of the concrete perimeter foundation the dwelling may respond well to re-levelling using injection techniques. As the house is sited on land zoned as TC3, specific engineering design or direction may be required to secure a Building Consent relating to foundation repairs or rebuilding. Provided appropriate repairs and replacement of the damaged internal bracing elements (plasterboard) are carried out in accordance with the available guidelines, it is expected that the dwelling will be safe to occupy in the interim.

8 Appendix A Site Location Figure 1 - Site location

9 Appendix B Site Plan Figure 2 - Site layout with floor levels (indicative only - not to scale)

10 Appendix C Site Photos Figure 3 - General view Figure 4 Lateral movement in driveway slabs.

11 Figure 5 - Movement between concrete driveway slabs up to 30mm Figure 6 Lateral movement between paving and floor slab, East wall

12 Figure 7 East/West benchtop level Figure 8 North/ South benchtop Level

13 Figure 9 North/South Kitchen floor level Figure 10 Excavation and liquefaction line at front of garage

14 Figure 11 - Crack to Central cut joint in garage floor slab

15 Figure 12 - Crack through garage slab (1-2mm) Figure 13 Stepped cracking of west elevation

16 Figure 14 Stepped cracking on east elevation Figure 15 Movement between brick veneer and garage door framing

17 Figure 16 Front wall of garage Figure 17 Stress cracking in living room wall

18 Figure 18 - Major horizontal joint failure in kitchen/living area Figure 19- Typical stress fractures in most rooms from 100mm to 600mm long

19 Figure 20 - Timber trusses show no sign of stress, all nail plates firm and undisturbed. Figure 21- Roof trusses in good condition

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

FOUNDATION TECHNICAL CATEGORY 3 (TC3) AUGUST 2012

FOUNDATION TECHNICAL CATEGORY 3 (TC3) AUGUST 2012 FOUNDATION TECHNICAL CATEGORY 3 (TC3) AUGUST 2012 Building and Housing has published technical guidance for foundation repairs and reconstruction for residential properties in green zone Foundation Technical

More information

Development of Guidance Information for the Repair and Rebuilding of Houses Following the Canterbury Earthquake Series

Development of Guidance Information for the Repair and Rebuilding of Houses Following the Canterbury Earthquake Series Development of Guidance Information for the Repair and Rebuilding of Houses Following the Canterbury Earthquake Series Graeme J Beattie (1) 1. Principal Structural Engineer, BRANZ Ltd, Private Bag 50908,

More information

Technical categories and your property

Technical categories and your property Technical categories and your property Information about residential green zone technical categories December 2011 Outline of land assessments Assessment of the land is undertaken by a range of organisations

More information

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:

Foundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for: A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.

More information

19.1 Overview...19.1 19.2 Repair or replace...19.1 19.3 Relevelling... 19.3

19.1 Overview...19.1 19.2 Repair or replace...19.1 19.3 Relevelling... 19.3 GUIDANCE E CONTENTS Part E: Repairing and rebuilding multi-unit residential buildings Contents 17. Introduction 17.1 17.1 Background...17.1 17.2 Scope...17.2 17.3 General principles...17.4 17.4 Regulatory

More information

EARTHQUAKE UPDATE. Your claim settlement options. Starting repairs and rebuilding. The good news... PERSONAL INSURANCE DECEMBER 2011

EARTHQUAKE UPDATE. Your claim settlement options. Starting repairs and rebuilding. The good news... PERSONAL INSURANCE DECEMBER 2011 EARTHQUAKE UPDATE PERSONAL INSURANCE DECEMBER 2011 Welcome to our December Customer Update. Many people have told us that they found the information in the November Update helpful which is really good

More information

Date, Time and Place: Presented by: Presented to: 22 August 2013, 0900 hrs, Pier 1 The Embarcadero, San Francisco

Date, Time and Place: Presented by: Presented to: 22 August 2013, 0900 hrs, Pier 1 The Embarcadero, San Francisco Date, Time and Place: 22 August 2013, 0900 hrs, Pier 1 The Embarcadero, San Francisco Presented by: Nick Rogers, Mike Jacka, Kate Williams, Sjoerd van Ballegooy and Rick Wentz, Tonkin & Taylor International

More information

Regarding the compliance of repairs to a foundation slab of a house at 137 Centaurus Road, St Martins, Christchurch

Regarding the compliance of repairs to a foundation slab of a house at 137 Centaurus Road, St Martins, Christchurch Determination 2015/016 Regarding the compliance of repairs to a foundation slab of a house at 137 Centaurus Road, St Martins, Christchurch 1. The matter to be determined 1.1 This is a determination under

More information

Sample Drawing Package for One and Two Family Dwelling Applications

Sample Drawing Package for One and Two Family Dwelling Applications Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx

More information

How To Build A Foundation For A Building Site In Creeper Island

How To Build A Foundation For A Building Site In Creeper Island GUIDANCE C CONTENTS Part C: Assessing, repairing and rebuilding foundations in TC3 Contents 11. Introduction to TC3 11.1 Overview... 11.1 11.2 General principles... 11.2 11.3 Scope... 11.4 11.4 Future

More information

4.1 General...4.1 4.2 Local repairs (TC1 and TC2)...4.1 4.3 Re-levelling floors (TC1 and TC2)...4.6

4.1 General...4.1 4.2 Local repairs (TC1 and TC2)...4.1 4.3 Re-levelling floors (TC1 and TC2)...4.6 GUIDANCE A CONTENTS Part A: Technical guidance Contents 2. Foundation assessment criteria and approaches 2.1 Typical dwelling foundation types...2.1 2.2 Assessing foundation damage...2.2 2.3 Indicator

More information

Cecil Courts BE 1047 EQ2 Detailed Engineering Evaluation Quantitative Assessment Report

Cecil Courts BE 1047 EQ2 Detailed Engineering Evaluation Quantitative Assessment Report Christchurch City Council Cecil Courts BE 1047 EQ2 Detailed Engineering Evaluation Quantitative Assessment Report Christchurch City Council Cecil Courts Quantitative Assessment Report 16 Cecil Place and

More information

Part C: Assessing, repairing and rebuilding foundations in TC3 Contents

Part C: Assessing, repairing and rebuilding foundations in TC3 Contents C 2. FOUNDATION CONTENTS Part C: Assessing, repairing and rebuilding foundations in TC3 Contents 11. Introduction to TC3 11.1 Overview... 11.1 11.2 General principles... 11.2 11.3 Scope... 11.4 11.4 Future

More information

Centennial Recreation and Sport Centre, Christchurch Post Earthquake Preliminary Damage Inspection

Centennial Recreation and Sport Centre, Christchurch Post Earthquake Preliminary Damage Inspection Report Centennial Recreation and Sport Centre, Christchurch Post Earthquake Preliminary Damage Inspection Prepared for Christchurch City Council (CCC) By Beca Carter Hollings & Ferner Ltd (Beca) 20 July

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA

STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box 144003 835 College Avenue, Building MS-3 Kentfield, California

More information

Re: Damages to Alaska Building from Legislative Information Office Construction

Re: Damages to Alaska Building from Legislative Information Office Construction 510 L Street Suite 200 Anchorage, AK 99501-1949 (907) 274-22362236 Phone (907) 274-25202520 Fax www.bbfm.com July 22, 2015 Jim Gottstein Alaska Building 406 G Street, Suite 206 Anchorage, AK 99501 Re:

More information

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri Determination 2009/103 The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri 1. The matters to be determined 1.1 This is a determination under Part 3 Subpart 1 of the

More information

Sisal Composite Ltd. Apparel 4 Ltd. JM Knit Ltd. Natun Para, Hemayetpur, Savar, Dhaka-1340 (23.789416N,90.266135E)

Sisal Composite Ltd. Apparel 4 Ltd. JM Knit Ltd. Natun Para, Hemayetpur, Savar, Dhaka-1340 (23.789416N,90.266135E) Revision: issue 1 Date: 11 June 2014 Sisal Composite Ltd. Apparel 4 Ltd. JM Knit Ltd. Natun Para, Hemayetpur, Savar, Dhaka-1340 (23.789416N,90.266135E) 24 th May 2014 Structural Inspection Report Observations

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering

More information

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline

More information

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael

More information

Residential Inspection Guidelines

Residential Inspection Guidelines Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against

More information

4B-2. 2. The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.

4B-2. 2. The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections. Shear Walls Buildings that use shear walls as the lateral force-resisting system can be designed to provide a safe, serviceable, and economical solution for wind and earthquake resistance. Shear walls

More information

HOME INSURANCE ASSESSMENT

HOME INSURANCE ASSESSMENT m pl e HOME INSURANCE ASSESSMENT Sa Street Address, Suburb File. 0000 Date. December 2014 Street Address, Suburb Page 1 of 8 File. 0000 Date. December 2014 Client Name Street Address Suburb HOME INSURANCE

More information

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr. 117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This

More information

6 RETROFITTING POST & PIER HOUSES

6 RETROFITTING POST & PIER HOUSES Retrofitting Post & Pier Houses 71 6 RETROFITTING POST & PIER HOUSES by James E. Russell, P.E. 72 Retrofitting Post & Pier Houses Retrofitting Post & Pier Houses 73 RETROFITTING POST AND PIER HOUSES This

More information

Structural Assessment Report

Structural Assessment Report Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive

More information

Guidance for building in toe slump areas of mass movement in the Port Hills (Class II and Class III)

Guidance for building in toe slump areas of mass movement in the Port Hills (Class II and Class III) November 2013 Guidance for building in toe slump areas of mass movement in the Port Hills (Class II and Class III) Supplementary guidance to Guidance on repairing and rebuilding houses affected by the

More information

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022

Steve Brinkman Alain Pinel Realtors 167 S San Antonio Road Los Altos, CA 94022 RE: Foundation Inspection for 162 Del Monte Ave. Los Altos, CA 94022 M G C O N S T R U C T O R S & E N G I N E E R S, I N C. I N S P E C T O R S E N G I N E E R S B U I L D E R S C A L I F O R N I A E N G I N E E R I N G A N D B U I L D I N G L I C E N S E A / B 6 4 2 0

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Wednesday, August 20, 2014 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website:

More information

Timber Frame Construction

Timber Frame Construction Timber Frame Construction Introduction Design and Detailing What is timber? Failure modes History of timber frame construction Forms of timber frame construction Live and dead loads Wind loads Roof construction

More information

Statement of evidence of Brett Gilmore (Engineering)

Statement of evidence of Brett Gilmore (Engineering) Before the Independent Hearings Panel at Christchurch under: in the matter of: the Resource Management Act 1991 and the Canterbury Earthquake (Christchurch Replacement District Plan) Order 2014 Submissions

More information

Your home: the next steps

Your home: the next steps Your home: the next steps Property Address Pack Delivery Date Practical Completion Date Defects Liability Period Finishes Moving Forward Contains useful general guidance for what to do now your earthquake

More information

Elevating Your House. Introduction CHAPTER 5

Elevating Your House. Introduction CHAPTER 5 CHAPTER 5 Elevating Your House Introduction One of the most common retrofitting methods is elevating a house to a required or desired Flood Protection Elevation (FPE). When a house is properly elevated,

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information

A RESIDENTIAL PROPERTY LOCATED AT xxxxxxxxxxxxxx, PASADENA, TX 77505

A RESIDENTIAL PROPERTY LOCATED AT xxxxxxxxxxxxxx, PASADENA, TX 77505 REPORT # SFR12- DATE OF INSPECTION: xx/xx/xxxx (04:30PM) A RESIDENTIAL PROPERTY LOCATED AT xxxxxxxxxxxxxx, PASADENA, TX 77505 FOR MR. & MRS. xxxxxxxxxxxxxx (CLIENT) BY: JITENDRA M. VARMA, Licensed Professional

More information

Housing New Zealand. Technical Report on the Results of Foundation Repair Trials Conducted following the Canterbury Earthquakes

Housing New Zealand. Technical Report on the Results of Foundation Repair Trials Conducted following the Canterbury Earthquakes Housing New Zealand Technical Report on the Results of Foundation Repair Trials Conducted following the Canterbury Earthquakes Compiled by Housing New Zealand in partnership with Southern Response Earthquake

More information

423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT

423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT Urgent Needs II City of Baltimore No. 1099 423 NORTH HOWARD ST. 423 North Howard Street (circa 1880) is a multi-story building constructed second in row south of Franklin Street and between the vacant

More information

8.1 Insurance requirements...8.1 8.2 Regulatory requirements...8.3 8.3 Seismicity considerations... 8.12 8.4 Flood risk and floor levels... 8.

8.1 Insurance requirements...8.1 8.2 Regulatory requirements...8.3 8.3 Seismicity considerations... 8.12 8.4 Flood risk and floor levels... 8. GUIDANCE CONTENTS Part : Technical information Contents 8. Insurance and regulatory requirements 8.1 Insurance requirements...8.1 8.2 Regulatory requirements...8.3 8.3 Seismicity considerations... 8.12

More information

Guidance on Detailed Engineering Evaluation of Nonresidential buildings

Guidance on Detailed Engineering Evaluation of Nonresidential buildings Guidance on Detailed Engineering Evaluation of Nonresidential buildings Part 3 Technical Guidance Section 5 Foundations Draft Prepared by the Engineering Advisory Group Read in Conjunction with Sections

More information

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide

More information

Canterbury earthquake update

Canterbury earthquake update Canterbury earthquake update Important information for NZI customers Please file this somewhere safe so you can refer to it throughout the claims process. July 2011 Earthquake update We ve recommenced

More information

National Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067

National Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section

More information

Structural Audit of Buildings

Structural Audit of Buildings International Journal of Civil Engineering Research. ISSN 2278-3652 Volume 5, Number 4 (2014), pp. 411-416 Research India Publications http://www.ripublication.com/ijcer.htm Structural Audit of Buildings

More information

Simpson Engineering A state licensed engineering firm F-1607

Simpson Engineering A state licensed engineering firm F-1607 Simpson Engineering A state licensed engineering firm F-1607 4126 Allencrest 13901 Midway Lane, Dallas, Road, Texas Ste.102-136 75244 Telephone: 214-351-1637 Dallas, - Fax: TX 214-351-1639 75244-4388 Telephone:

More information

Hunter College school of Social Work Thesis Proposal

Hunter College school of Social Work Thesis Proposal Fall 2009 Hunter College school of Social Work Thesis Proposal To analyze how energy efficiency can be implemented using facade and green roof redesign. It ties structural engineering concepts with existing

More information

DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES

DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES WBCA 403 DESIGNERS GUIDE TO DOMESTIC CONSERVATORIES A guide to assist those intending to install or who are involved in installing conservatories. Includes information about: conservatory and component

More information

GUIDE TO SETTLEMENT OF CANTERBURY FLAT LAND CLAIMS

GUIDE TO SETTLEMENT OF CANTERBURY FLAT LAND CLAIMS GUIDE TO SETTLEMENT OF CANTERBURY FLAT LAND CLAIMS April 2013 i Introduction This guide focuses on repair methods for some of the types of land damage that occurred on flat residential land as a result

More information

THE GUIDE FOR CANTERBURY BUILDERS BELOW-FLOOR WORK

THE GUIDE FOR CANTERBURY BUILDERS BELOW-FLOOR WORK TE GUIDE FOR CANTERBURY BUILDERS BELOW-FLOOR WORK [Your new best friend] About this booklet This booklet, Below-Floor Work, and its companion booklet Above-Floor Work, are for builders and others wanting

More information

Lighthouse Engineering, L.L.C.

Lighthouse Engineering, L.L.C. Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Engineering Evaluation

More information

PLEASE REFER TO YOUR INDIVIDUAL QUOTE

PLEASE REFER TO YOUR INDIVIDUAL QUOTE STANDARD INCLUSIONS AND EXCLUSIONS SECONDARY DWELLING 16/04/2014 PLEASE REFER TO YOUR INDIVIDUAL QUOTE Inclusions Super Structure: Timber Frames including Roof Trussing and Framing, Internal and External

More information

Chapter 2 Basis of design and materials

Chapter 2 Basis of design and materials Chapter 2 Basis of design and materials 2.1 Structural action It is necessary to start a design by deciding on the type and layout of structure to be used. Tentative sizes must be allocated to each structural

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

Chapter 9 Remedial Measures

Chapter 9 Remedial Measures [This is an annotated version of a chapter from the US Army Corps of Engineers book, Foundations in Expansive Soils. This book is in the public domain. This document is consists of an abbreviated and annotated

More information

Repairing and rebuilding multi-unit residential buildings

Repairing and rebuilding multi-unit residential buildings Introduction The Ministry of Business, Innovation and Employment (MBIE) has released technical guidance on repairing and rebuilding multi-unit residential buildings in Canterbury. The guidance applies

More information

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We

More information

Chapter. Restoration of Damaged Structures

Chapter. Restoration of Damaged Structures 5 Chapter Restoration of Damaged Structures Bringing back a damaged structure to its pre-earthquake state and original strength is called restoration. This is the first step of building rehabilitation.

More information

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination

National Council of Examiners for Engineering and Surveying. Principles and Practice of Engineering Structural Examination Structural Effective Beginning with the April 2011 The structural engineering exam is a breadth and exam examination offered in two components on successive days. The 8-hour Vertical Forces (Gravity/Other)

More information

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California 94103. Prepared By Project Structural Conditions Survey and Seismic Vulnerability Assessment For SFCC Civic Center Campus 750 Eddy Street San Francisco, California 94109 Prepared For San Francisco Community College District

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection PB301 July 2009 Lightweight Building Solutions Bushfire Protection www.boral.com.au/bushfireprotection Attached or adjacent within 6m roofed structures such as garages, carports, verandas and the like,

More information

D Sample Notices to Property Owners, Sample Affidavits, and Other Material

D Sample Notices to Property Owners, Sample Affidavits, and Other Material D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully

More information

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Melbourne balcony Assessments

Melbourne balcony Assessments Balcony Assessment Melbourne balcony Assessments Address: SAMPLE Date: Assessor: Luke O Neill Registered Builder DBL-C 31305 Assessment Guidelines This is an assessment of balcony and elements as presented

More information

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No.

Report on Sanctuary/Chancel Crawl Space Inspection. St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove. Project No. Report on Sanctuary/Chancel Crawl Space Inspection St. John in The Wilderness, 2896 Old Lakeshore Road Bright s Grove Project No. E112056 1. Background St. John in the Wilderness (SJITW) is considering

More information

PROFESSIONAL ENGINEERING INSPECTIONS, INC.

PROFESSIONAL ENGINEERING INSPECTIONS, INC. PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

Energy Company Obligation (ECO): Technical Monitoring Questions

Energy Company Obligation (ECO): Technical Monitoring Questions Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified

More information

REQUEST FOR QUALIFICATIONS FROM FOUNDATION REPAIR CONTRACTORS BROOMFIELD DEPOT FOUNDATION REHABILITATION PROJECT

REQUEST FOR QUALIFICATIONS FROM FOUNDATION REPAIR CONTRACTORS BROOMFIELD DEPOT FOUNDATION REHABILITATION PROJECT Project Description and Scope The City and County of Broomfield, Colorado (Broomfield) hereby solicits this Request for Qualifications (RFQ) to prequalify and shortlist up to five (5) foundation repair

More information

PRE-PURCHASE INSPECTION REPORT

PRE-PURCHASE INSPECTION REPORT PRE-PURCHASE INSPECTION REPORT PREPARED FOR: PROPERTY ADDRESS: Waiheke Island DATE: 21 November 2012 Page 1 of 13 (a) This is a report of a visual only, non-invasive inspection of the areas of the building

More information

Rebuild with confidence A guide for homeowners in Canterbury

Rebuild with confidence A guide for homeowners in Canterbury Rebuild with confidence A guide for homeowners in Canterbury BUILD IT RIGHT CANTERBURY The groundwork for good decisions. Disclaimer: This document is a guide only. It should not be used as a substitute

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

EARTHQUAKE DESIGN OF BUILDINGS

EARTHQUAKE DESIGN OF BUILDINGS GAP.2.0.9 A Publication of Global Asset Protection Services LLC EARTHQUAKE DESIGN OF BUILDINGS INTRODUCTION Buildings in many areas of the world are susceptible to damage from moderate to severe earthquakes.

More information

dpd 316 Seattle Permits Tip www.seattle.gov/dpd Subject-to-Field-Inspection (STFI) Permits Projects that Qualify as STFI

dpd 316 Seattle Permits Tip www.seattle.gov/dpd Subject-to-Field-Inspection (STFI) Permits Projects that Qualify as STFI dpd Department of Planning and Development Tip 316 Seattle Permits part of a multi-departmental City of Seattle series on getting a permit Subject-to-Field-Inspection (STFI) Permits Updated June 3, 2015

More information

Basic Requirements for Residential Plan Review _

Basic Requirements for Residential Plan Review _ Basic Requirements for Residential Plan Review _ Below you will find the basic requirements for your plan submittal. General: Drawn to scale Plan Size minimum: 9 x 12 Designer, Engineer, or Architect name,

More information

5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net LIMITATIONS AND DISCLAIMERS

5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net LIMITATIONS AND DISCLAIMERS 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Court Richmond, Texas Mr. Foundation Concerns INSPECTION DATE:

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:

When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are: When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory

More information

The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma

The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma Bart B. Barrett, B.S., P.E.1 Kerry S. Lee, M.B.A., P.E., M. ASCE2 Erik L. Nelson, Ph.D., P.E., M. ASCE3

More information

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,

More information

TECHNICAL RECOMMENDATION

TECHNICAL RECOMMENDATION TECHNICAL RECOMMENDATION NO: 9 DESIGN OF LIGHT TIMBER FRAMED WALLS AND FLOORS FOR FIRE RESISTANCE Peter Collier Contents Design of Light Timber Framed Walls and Floors for Fire Resistance Relevance Acceptance

More information

Chapter 3 FOUNDATIONS AND FOUNDATION WALLS

Chapter 3 FOUNDATIONS AND FOUNDATION WALLS Chapter 3 FOUNDATIONS AND FOUNDATION WALLS This chapter discusses foundations and foundation walls constructed using the two most common foundation materials concrete and masonry. Although the IRC permits

More information

Chapter. Earthquake Damage: Types, Process, Categories

Chapter. Earthquake Damage: Types, Process, Categories 3 Chapter Earthquake Damage: Types, Process, Categories Earthquakes leave behind a trail of damage and destruction. People s lives are affected by the loss of loved ones, destruction of property, economic

More information

How To Repair A House

How To Repair A House Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

STANDARD OPEN PATIO COVER

STANDARD OPEN PATIO COVER STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist

More information

Leaky Homes Financial Assistance Package (FAP) Repair plan example

Leaky Homes Financial Assistance Package (FAP) Repair plan example LEAKY HOMES FINANCIAL ASSISTANCE PACKAGE FACT SHEET Repair Plan Example - June 2014 Page 1 Leaky Homes Financial Assistance Package (FAP) Repair plan example Introduction This repair plan example is intended

More information

CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST

CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all

More information

symptoms of a faulty foundation

symptoms of a faulty foundation symptoms of a faulty foundation How does drought impact your home's foundation? For many Texas families, their home becomes the single largest investment and also the family fortune. The home's foundation

More information

Worked Example 2 (Version 1) Design of concrete cantilever retaining walls to resist earthquake loading for residential sites

Worked Example 2 (Version 1) Design of concrete cantilever retaining walls to resist earthquake loading for residential sites Worked Example 2 (Version 1) Design of concrete cantilever retaining walls to resist earthquake loading for residential sites Worked example to accompany MBIE Guidance on the seismic design of retaining

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

Timber Decks. Technical Note. March 2007

Timber Decks. Technical Note. March 2007 Timber Decks Technical Note. March 2007 This Technical Note contains general information for residential timber decks and floor frame structures for veranda s, patios etc which are exposed to the weather.

More information

inimi ing damage and repair osts to manufa tured omes during an eart ua e

inimi ing damage and repair osts to manufa tured omes during an eart ua e inimi ing damage and repair osts to manufa tured omes during an eart ua e Prepared for T e Department of Housing and Urban Development Offi e of Poli y Development and eesear by t e National Conferen e

More information