Red Phase Instruments Australia Earth Systems Paper
|
|
- Neil Barton
- 7 years ago
- Views:
Transcription
1 Red Phase Instruments Australia Earth Systems Paper This document is intended as a guide to Red Phase Instruments IEarth Systems testing products and as a supplement to a visual or power point presentation. The information garnered in this document is assumed to be correct at the time of printing and the author bares no responsibility for obvious omissions or mistakes. Much of the technical documentation, labeling, drawings and or explanations are produced and interpreted by the author however reference is also made to associated papers and material from which some of this information has been sourced and it is with the sincerest of apologies to those whose papers and publications are not fully covered in the reference list but on whom some of this paper may be based.. Patrick Stankovic October 2015
2 WHY PERFORM EARTH TESTING? The integrity of earthed systems which support large electrical infrastructures such as substations, transmission towers and large industrial installations have to be periodically monitored to check if they comply with safety levels established in standards and regulations. This testing is critical. It establishes the ability of an earthed system to divert as much unwanted electrical energy, (brought about by an electrical fault), into the earth and away from equipment and personnel inside and outside of an earthed complex. The most common of these faults is a current fault which can be imposed on an earthed system by a broken high voltage cable, equipment insulation failure, a lightning strike or any other event which allows the flow of high currents away from their intended path and into the earthed system. To establish if an earthed system complies with safety levels, operators rely on equipment which can perform a simulated high power, albeit lower level, of current fault simulation. Appreciable levels of current fault simulation can only be achieved with powerful current injection systems such as the Red Phase Instruments, 2kVA and 8kVA current injection systems. OFF FREQUENCY TESTING Traditional current injection methods required high current to be used at base frequencies of 50Hz or 60 Hz in order to overcome system noise. Red Phase Earth Test equipment generates selectable off frequency injection current that is very near load frequency. This off frequency signal is precisely filtered down to 0.1Hz using a tuneable or frequency selective multimeter which can recover the signal cleanly, noise and interference free. TEST CAPABILITIES To examine the flow of currents and resultant potentials developed though-out an Earthed system during a fault, operators use Red Phase Earth test equipment to measure: EPR, Earth Potential Rise Step Potential Touch Potential Surface Potential distribution Current Branching Soil Resistivity Bonded Earth testing KEY FEATURES Smaller, lighter, safer and faster than conventional high power methods. Tough and durable. Continuous power at 2kVA or 8kVA at up to 40⁰C ambient. Live testing:- tests can be made while an earthed system such as a substation is in service. Immune to system noise High accuracy in voltage, current and impedance measurements. STANDARDS COMPLIANCE Using Red Phase current injection equipment is the truest way to test if earthed systems comply with international standards such as: IEEE IEEE DIN VDE 0101 Cenelec HD637S1
3 EARTH TESTING SET UP The most effective method of measuring the surface potential variations or EPR across an earthed electrical system is to perform a current injection test or CIT. A current injection test comprises two earthed systems, a connecting circuit between them and a current source. The generated current source does not contribute to the EPR, however the return path current generated as a consequence of the current injection will. When performing a CIT the most practical method used to measure EPR is the Fall of Potential Method or FoPM described in the IEEE 81 standard and other sources. The FoPM essentially requires the measure and plot of the V/I = R ratio as a function of the potential probe distance. When the plot begins to level out this is taken to be the grid EPR or impedance. WHICH FALL of POTENTIAL METHOD to use? When selecting which Fall of Potential Method to use the most important factor which must be taken into account is the inductive influence of the injection line on the potential line. Small high resistance earth systems generally don t incur substantive inductive coupling issues and are quite easy to test with small inexpensive, and at times battery operated equipment. The restrictions on the injection and potential cable positions is not so critical. However, when it comes to medium to large low impedance earthing systems, the cable layout, current injection points and choice of FoPM become important factors in correct EPR determination. Hence cable layout planning is very important. An example of inductive influence on layout is shown in Figures 3, 4 and 5 FoPM is a 4 point test method but subsets such as the 3 point test, MER correction method or the Slope method are also effective in some applications. Basic CIT Set Up Figure 1 EPR Plot Figure 2
4 CIT FoPM LAYOUT - Small earth / grounding systems Figure 3 CIT FoPM LAYOUT - Medium to large earthed systems Figure 4 CIT FoPM LAYOUT - Medium to large earthed systems Figure 5 CIT FoPM LAYOUT - Ideal Steup Figure 6
5 STEP & TOUCH Measurements With an established FoPM set up the operator can take a number of step and touch test points in and around an earthed complex such as a substation with a frequency selective multi-meter tuned to the injection frequency. Test points can must be taken at points such as a substation's equipment, its barriers and fence line perimeter. Step Measurement setup SURFACE POTENTIAL DISTRIBUTION Surface potential distribution is a key factor that can reveal the true state of a grounding system. During a FoPM setup operators can measure the generated surface voltages at equidistant points across an earthed system. A plot representing the measured points can easily uncover equi-potential zones and high risk areas. This kind of measurement begins with an operator laying out a grid onto a map of the earthed system where the earthed point of injection is taken as the centre. One end of the frequency selective multimeter is connected to the injection point while the other end is connected to a probe/stake which is inserted into equi-distant points in the grid and consecutive measurements are taken moving away from the centre or point of injection. Main Earth Grid Remote Earth Yellow dots are the potential measurement points Touch measurement setup The surface potential measurements can then be transferred to a voltage against distance graph to help the operator identify which areas of the earthed grid may indicate localized problems. V Poor grounding Localized grounding issue Even grounding distribution Distance Better modelling software can reproduce a 3D potential contour map of the earthed surface uncovering regions of uncertainty in grid integrity which may pose a danger to personnel and equipment.
6 CURRENT BRANCH MEASUREMENTS During a FoPM setup the operator may also perform current branch measurements on current bearing structures to determine the amount of current coming into or leaving a grid or earthed system under test. ELEMENTS OF A RED PHASE INJECTION SYSTEM Solid State Injection unit(s) Frequency selectable current injection instrument with a user interface for selecting injection frequency and current level. Coupling Transformer A multi-tap transformer which isolates the current injection unit from direct ground connection and also provides a corresponding injection selection tap. Frequency Selective Multimeter A multimeter specifically tuned to the current injection frequency selected by the solid state current injection unit.
GroundRod AC Substation Earthing Tutorial
1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities
More informationEarthing Guidance Notes
Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head
More informationSubstation Grounding Study Specification
Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number
More informationEMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC) http://www.iec.
EMC STANDARDS The EMC standards that a particular electronic product must meet depend on the product application (commercial or military) and the country in which the product is to be used. These EMC regulatory
More informationEARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
More informationVideo Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
More informationCrosstalk effects of shielded twisted pairs
This article deals with the modeling and simulation of shielded twisted pairs with CST CABLE STUDIO. The quality of braided shields is investigated with respect to perfect solid shields. Crosstalk effects
More informationHarmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
More informationSingle Channel Loop Detector
Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop
More informationEMC Basics. Speaker : Alain Lafuente. Alain.lafuente@we-online.com
EMC Basics Speaker : lain Lafuente lain.lafuente@we-online.com WHT IS EMC? 2 CE Marking With the formation of the single European market, standardization was required to remove technical barriers to trade.
More informationEarth Ground Resistance
Principles, testing methods and applications Diagnose intermittent electrical problems Avoid unnecessary downtime Learn earth ground safety principles Earth Ground Resistance Why Ground, Why Test? Why
More informationCoaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note
Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax
More informationGrounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
More informationTypical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
More informationDesigning the NEWCARD Connector Interface to Extend PCI Express Serial Architecture to the PC Card Modular Form Factor
Designing the NEWCARD Connector Interface to Extend PCI Express Serial Architecture to the PC Card Modular Form Factor Abstract This paper provides information about the NEWCARD connector and board design
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationGUIDE FOR TESTING POWER TRANSFORMERS
GUIDE FOR TESTING POWER TRANSFORMERS Routine test 11/11/02 Pagina 1 di 10 INDEX Introduction... 3 1 Dielectric tests Separate-source voltage withstand test... 4 2 Induced voltage test... 5 3 Voltage ratio
More informationGrounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
More informationCurrent Probes, More Useful Than You Think
Current Probes, More Useful Than You Think Training and design help in most areas of Electrical Engineering Copyright 1998 Institute of Electrical and Electronics Engineers. Reprinted from the IEEE 1998
More informationHigh Voltage Power Supplies for Analytical Instrumentation
ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply
More informationAssessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria
Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria Abstract Gabriel A. Adegboyega and Kehinde O. Odeyemi Department of Electrical and Electronic
More informationCHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationNexus Technology Review -- Exhibit A
Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.
More informationwww.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
More informationSES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy
SES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy A Center of Excellence, Where Experts are Created and Certified 1 SES: Training You and Your Staff to Carry
More informationApplication-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template
Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister jens.baumeister@omicron.at Date
More informationLightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
More informationLightning Protection Introduction
Lightning Protection Introduction Structural lightning protection design considerations BS 6651 (Protection of structures against lightning) clearly advises strict adherence to the provision of a conventional
More informationLab 3 - DC Circuits and Ohm s Law
Lab 3 DC Circuits and Ohm s Law L3-1 Name Date Partners Lab 3 - DC Circuits and Ohm s Law OBJECTIES To learn to apply the concept of potential difference (voltage) to explain the action of a battery in
More informationTRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
More informationWhite Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
More informationDET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com DET3 Contractor Series 3-Terminal DET3 Contractor Series 2 and 3 point testing
More informationELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES
ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES The purpose of this lab session is to experimentally investigate the relation between electric field lines of force and equipotential surfaces in two dimensions.
More informationBroadband over Power Line (BPL) Test Procedures and Equipment Authorization
Broadband over Power Line (BPL) Test Procedures and Equipment Authorization Andy Leimer Equipment Authorization Branch Federal Communications Commission Office of Engineering and Technology Laboratory
More informationVisual System Simulator White Paper
Visual System Simulator White Paper UNDERSTANDING AND CORRECTLY PREDICTING CRITICAL METRICS FOR WIRELESS RF LINKS Understanding and correctly predicting cellular, radar, or satellite RF link performance
More informationGROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
More informationPre-Compliance Test Method for Radiated Emissions of Automotive Components Using Scattering Parameter Transfer Functions
PreCompliance Test Method for Radiated Emissions of Automotive Components Using Scattering Parameter Transfer Functions D. Schneider 1*, S. Tenbohlen 1, W. Köhler 1 1 Institute of Power Transmission and
More informationSiemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring
Siemens Integrated Substation Condition Monitoring System Circuit Breaker Monitoring System Description Introduction The Circuit Breaker Monitor [CBM] is only one example of the way that the Substation
More informationBSA Technical Information
BSA Technical Information Electrical Isolation of Co-Located Horizontally and Vertically Stacked Antennas Introduction: Service providers are facing rapidly increasing pressure from zoning boards to co-locate
More informationBS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
More informationCONSTANT CURRENT REGULATOR INDUPERM TYPE CCR 951. Standarddescription of CONSTANT CURRENT REGULATOR TYPE CCR 951.
Standarddescription of TYPE CCR 951 List of contents: A. General Description B. General Data's and Functions C. CCR Working Principle D. Specifications Page 1 of 9 pages A. General Description. Induperm
More informationEMI and t Layout Fundamentals for Switched-Mode Circuits
v sg (t) (t) DT s V pp = n - 1 2 V pp V g n V T s t EE core insulation primary return secondary return Supplementary notes on EMI and t Layout Fundamentals for Switched-Mode Circuits secondary primary
More informationGenerator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
More informationEverything you need for protection scheme testing
Power System Simulator for Testing Protection Relays and Schemes Everything you need for protection scheme testing The is the only instrument with the high power, flexibility and software to perform full
More informationInterfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13
Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified
More informationANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line
International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit
More informationGrounding and Shield Termination. Application Note 51204
Grounding and Shield Termination Application Note 51204 DEFINITIONS This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this
More informationTROUBLESHOOTING RECEIVERS
TROUBLESHOOTING RECEIVERS The four methods of troubleshooting are: 1. Circuit Disturbance 2. Signal Substitution 3. Signal Tracing 4. Measurement of Circuit Parameters Definition of Terms: Circuit Disturbance
More informationTHE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.
THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies
More informationCurrent Monitoring Kit QUICK START GUIDE
Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...
More informationECEN 1400, Introduction to Analog and Digital Electronics
ECEN 1400, Introduction to Analog and Digital Electronics Lab 4: Power supply 1 INTRODUCTION This lab will span two lab periods. In this lab, you will create the power supply that transforms the AC wall
More informationApplication Note: PCB Design By: Wei-Lung Ho
Application Note: PCB Design By: Wei-Lung Ho Introduction: A printed circuit board (PCB) electrically connects circuit components by routing conductive traces to conductive pads designed for specific components
More informationNOKIA 32 SUPPORT GUIDE FOR INSTALLING NOKIA 32
NIA 32 SUPPORT GUIDE FOR INSTALLING NIA 32 CONTENTS 1. INTRODUCTION...1 2. INSTALLATION...1 2.1 INSTALLATION ENVIRONMENT...1 2.2 CONNECTING NIA 32 TERMINAL AND PBX / TELEPHONE SET...1 2.3 CONNECTING NIA
More informationBalanced vs. Unbalanced Audio Interconnections
Revised 7/2/08 Balanced vs. Unbalanced Audio Interconnections In discussing the characteristics and performance of various interconnect systems; two points should be kept in mind. Balance is defined in
More informationTrial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
More informationELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
More informationDET3 Contractor Series
DET3 Contractor Series 3-Terminal 2 and 3 point testing ART (Attached Rod Technique) testing capability User selectable test voltage (25/50 V) Choice of digital or analog display Warning indicators prevent
More informationCurrent Monitoring Kit
Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added
More informationThe electrical field produces a force that acts
Physics Equipotential Lines and Electric Fields Plotting the Electric Field MATERIALS AND RESOURCES ABOUT THIS LESSON EACH GROUP 5 alligator clip leads 2 batteries, 9 V 2 binder clips, large computer LabQuest
More informationStrength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines
Strength and Durability for Life CORROSION CONTROL The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines Last Revised: May 2016 Sharing of rights-of-way by AC power lines and buried
More informationInductors in AC Circuits
Inductors in AC Circuits Name Section Resistors, inductors, and capacitors all have the effect of modifying the size of the current in an AC circuit and the time at which the current reaches its maximum
More informationTelecommunication Line Protectors
TN CR 0025 Telecommunication Line s 1.1 The nature of telecom surges The telecom services considered in this report are transported on twisted pair. Each service has two wires, or lines, sometimes called
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationWORLDWIDE. GW400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION
ORLDIDE G400k SERIES MAINTENANCE MANUAL PROVEN PERIMETER PROTECTION GEOQUIP LIMITED Kingsfield Industrial Estate, Derby Road irksworth, Matlock, Derbyshire, DE4 4BG Tel : 01629 824891 Fax : 01629 824896
More information12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
More informationMOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD
MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH
More informationRLC Series Resonance
RLC Series Resonance 11EM Object: The purpose of this laboratory activity is to study resonance in a resistor-inductor-capacitor (RLC) circuit by examining the current through the circuit as a function
More informationAn Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware
for CAT 6A Connecting Hardware Written by: Antoine Pelletier Engineer, Global Cabling Products Intertek www.intertek-etlsemko.com 1-800-WORLDLAB Introduction The telecommunication industry recently achieved
More informationWorld Leader in HV Testing Technology
World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------
More informationBasic voltmeter use. Resources and methods for learning about these subjects (list a few here, in preparation for your research):
Basic voltmeter use This worksheet and all related files are licensed under the Creative Commons ttribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
More informationUNDERGROUND TELECOMMUNICATIONS CABLES ACROSS PRIVATE LAND
FACT SHEET TELEPHONE 0800 327 646 I WEBSITE WWW.FEDFARM.ORG.NZ UNDERGROUND TELECOMMUNICATIONS CABLES ACROSS PRIVATE LAND BACKGROUND The Rural Broadband Initiative envisages substantially improved broadband
More informationCUSTOMER REQUIREMENTS AT POWER SUBSTATIONS
CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0
More informationMEASUREMENT UNCERTAINTY IN VECTOR NETWORK ANALYZER
MEASUREMENT UNCERTAINTY IN VECTOR NETWORK ANALYZER W. Li, J. Vandewege Department of Information Technology (INTEC) University of Gent, St.Pietersnieuwstaat 41, B-9000, Gent, Belgium Abstract: Precision
More informationEMI in Electric Vehicles
EMI in Electric Vehicles S. Guttowski, S. Weber, E. Hoene, W. John, H. Reichl Fraunhofer Institute for Reliability and Microintegration Gustav-Meyer-Allee 25, 13355 Berlin, Germany Phone: ++49(0)3046403144,
More information162 CB CABLE TRACER. Filter Probe & Tone Generator INSTRUCTION MANUAL
162 CB CABLE TRACER Filter Probe & Tone Generator INSTRUCTION MANUAL INDEX PAGE 1. INTRODUCTION... 1 2. FILTER PROBE... 1-3 3. TONE GENERATOR... 3-6 4. SPECIFICATION... 7-8 5. MAINTENANCE... 8 1. INTRODUCTION
More informationSeparation of power and information technology cabling
Technical bulletin Separation of power and information technology cabling Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based on the current
More informationAPPLICATION NOTES POWER DIVIDERS. Things to consider
Internet Copy Rev A Overview Various RF applications require power to be distributed among various paths. The simplest way this can be done is by using a power splitter/divider. Power dividers are reciprocal
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
More informationMODEL 2202IQ (1991-MSRP $549.00)
F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR
More informationTechnical Description. Transistor D.C. Chopper Controller Type GS 24 S
Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine
More informationProduct brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity
More informationUNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com hott@ieee.org Page 2 THE BASIC
More informationrigel 288 Electrical Medical Safety Analyser Key Features Applications
rigel 288 Electrical Medical Safety Analyser Key Features Versatile Test in Accordance with the leakage requirements of IEC/EN 60601-1, AAMI and NFPA, IEC 62353 (VDE 0751-1) using separate IEC 60601 and
More informationUser Guide. www.burntec.com. 4 wire Earth Resistance Tester Model GRT300
User Guide 4 wire Earth Resistance Tester Model GRT300 Introduction Congratulations on your purchase of Extech s 4 Wire Earth Resistance Tester. The Model GRT300 has been designed and tested according
More informationPROTECTION AGAINST ELECTRIC SHOCK by John Ware
16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created
More informationTest & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
More informationE-Option Multi-taps Conditioning at the Tap
E-Option Multi-taps Conditioning at the Tap (actual size) Introduction Traditional Cable Television Systems had long been associated with one-way downstream signal transmissions that provide video services
More informationPower surges can also be generated by equipment in your facility such as:
Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement
More informationRadiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
More informationFRAX 150 Sweep Frequency Response Analyzer
FRAX 150 n Highest dynamic range and accuracy in the industry n Built-in PC with powerful backlit screen for use in direct sunlight n Highest possible repeatability by using reliable cable practice and
More informationElectrical safety requirements in DC distribution systems
Electrical safety requirements in DC distribution systems PAUL J.L.AN TICHELEN, DOMINIQUE WEYEN ITO Boeretang 200, 2400 Mol BELGIUM Abstract: This paper focuses on the safety requirements for the DC bus
More informationUltraFED IIB. 30 MHz Far-End Device
COMMUNICATIONS TEST AND MEASUREMENT SOLUTIONS UltraFED IIB 30 MHz Far-End Device Key Benefits Faster and more accurate than a single-ended test Eliminate driving to change line conditions Remotely set
More informationAN-3 SEVEN KEY CONSIDERATIONS BEFORE YOU START YOUR SLIC OR FXS PHONE LINE INTERFACE DESIGN
AN-3 SEVEN KEY CONSIDERATIONS BEFORE YOU START YOUR SLIC OR FXS PHONE LINE INTERFACE DESIGN By Joe Randolph Introduction The conventional 2-wire analog phone line that telephone companies provide to residential
More informationTechnical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
More informationAMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
More informationAC-DC Converter Application Guidelines
AC-DC Converter Application Guidelines 1. Foreword The following guidelines should be carefully read prior to converter use. Improper use may result in the risk of electric shock, damaging the converter,
More informationCONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE
CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE Closing date for submission of representations: 30 th Sep 2014, 5 pm 18 AUG 2014 ENERGY MARKET AUTHORITY 991G Alexandra Road #01-29
More informationOperating instructions Diffuse reflection sensor with background suppression O1D101 O1D104 706114 / 00 01 / 2012
Operating instructions Diffuse reflection sensor with background suppression O1D101 O1D104 706114 / 00 01 / 2012 Contents 1 Preliminary note 3 1.1 Symbols used 3 1.2 Warning signs used 3 2 Safety instructions
More informationApplication Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
More information