Bulletin 1489 Circuit Breakers. Selection Guide

Size: px
Start display at page:

Download "Bulletin 1489 Circuit Breakers. Selection Guide"

Transcription

1 Bulletin 1489 s Selection Guide

2

3 Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable options for selective applications IP2x Finger-Protection (Front) North America certifications: UL 489, CSA C22.2 No. 5 International standards: CE Marked, and IEC (VDE) standards for worldwide acceptance Ratings: UL/CSA max. 480Y/277V AC up to 14 ka interrupt rating; IEC max. 240/415V AC A interrupt rating 48V DC rating, 96V DC 2-pole series A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position) Trip curves: C and D Time delay (D Characteristic) for high inrush currents during inductive start-ups such as motors, transformers and power supplies Superior shock and vibration resistance capabilities helps to prevent nuisance tripping Mounts on DIN Rail Wire connect, line and load (reversible) Optional terminals for ring lug terminals Table of Contents Specifications Description... 3 Product Selection... 9 Approximate Dimensions Standards Compliance UL 489 CSA C22.2 No. 5 EN/IEC Certifications UL Listed CSA Certified CE Marked VDE Certified Industrial s for North American Applications The Bulletin 1489-A line includes: UL 489, CSA C22.2 No V AC A 480V/277V AC A Miniature for EN/IEC Applications EN/IEC V AC A SWD ( A) Switching Duty for fluorescent lighting applications HACR 1-pole 48V DC A 2-pole (series) 96V DC A 48V DC A Description Bulletin 1489-A s for Branch Circuit protection are available in 1-, 2-, and 3-pole construction and are rated A at 240V AC and A at 480Y/277V AC for North American applications (UL 489 and CSA C22.2 No. 5). The circuit breakers also have a 1-pole 48V DC, 2-pole (series) 96V DC rating. For EN\IEC applications the products are rated 415V AC, 48V AC A. Thermal Magnetic s The Bulletin 1489-A Thermal Magnetic s are generalpurpose devices suitable for the majority of industrial, inverse time circuit breaker applications. They combine thermal and magnetic trip actions and provide accurate overload and short-circuit protection for conductors and connected equipment. Application Information Selection of a Bulletin 1489 circuit breaker with appropriate circuit protection includes consideration of: Circuit Voltage Circuit Frequency Available Short Circuit Current Continuous Current Rating Application Considerations Special Operating Conditions The following discussion is based upon National Electric Code and UL requirements. Similar considerations are appropriate for Canadian applications. Features Designed manufactured and listed to UL 489 (CSA 22.2 No. 5) Thermal-magnetic protection All ratings are HACR rated up to 14 ka Interrupting rating Finger safe design (front) DIN Rail mounting Line and load wire connections Optional ring terminal connections (convertible) Circuit Voltage The Bulletin 1489-A circuit breakers are rated by voltage class. Applications should not exceed the listed voltage and current range (see Table 1). Circuit Frequency The Bulletin 1489-A circuit breakers may be applied to frequencies of 50 Hz and 60 Hz without derating. For applications above 60 Hz, contact Rockwell Automation with specific application information for the derating of the circuit breakers. Available Short Circuit Current The Bulletin 1489-A circuit breakers should only be applied in those applications in which the available short-circuit (or fault) current is less than or equal to 10 ka...14 ka (US/Canada) and 15 ka (IEC). Table 1. Voltage and Current Ranges Region Max. Voltage Current Range [A] EN/IEC Regions 415V AC V DC V AC North America (UL Y/277V AC & CSA C22.2 No. 5) 1-pole 48V DC pole 96V DC Publication 1489-SG001D-EN-P 3

4 Bulletin 1489-A Description, Continued Continuous Current Rating Standard current ratings are: 0.5, 1, 1.5, 2, 3, 4, 5, 6, 7, 8, 10, 15, 16, 20, 25, 30, 32, 35, and 40 A. The Bulletin 1489-A circuit breakers are rated in RMS amperes at a 40 C (104 F) ambient temperature per the UL 489 (CSA 22.2 No. 5) standard. This temperature is generally used as the average temperature within an industrial enclosure. If a circuit breaker is applied in a temperature that exceeds the 40 C (104 F) ambient, then the circuit breaker should be derated. For IEC standard, the products carry an ambient rating of 30 C. Follow standard IEC application considerations for temperature rating in different ambient temperatures. The characteristic trip curves are shown on page 7. The trip bands shown for each breaker represent current tripping limits for a circuit breaker and are within the limits established by UL. For a specific current at 40 C (104 F), a circuit breaker will open ("clear the circuit") automatically at some total time that will be within the "Minimum" and "Maximum" time shown on the curves. For example, page 7 shows that a one-pole, 15 A, Bulletin 1489-A circuit breaker trips in not less than 10 s and not more than 120 s on a 30 A current. Because the UL standard defines this time spread, users should not specify exact tripping time. The lower current portion of the curves (upper left) depict the time to trip due to thermal action and reflect overload protection of the wire and connect load. The higher current portion of the curves (lower right) depicts the trip due to magnetic action of the circuit breaker and reflects protection due to short circuit level currents. following the guidelines for an Inverse Time. References: NEC and UL 489. Also see CEC and appropriate Canadian Standards. 2) Transformer Protection Bulletin 1489-A circuit breakers may be used for transformer protection following the guidelines established. References: NEC 450 and UL 489. Also see CEC and appropriate Canadian Standards. 3) Heater Load, Lighting, and Other Load Protection Bulletin 1489-A circuit breakers may be used for protection of heater loads, lighting loads, and other loads following the guidelines established. References: NEC Article 31 and UL 508A. Also see CEC and appropriate Canadian Standards. Coordinated Overcurrent Protection Where an orderly shutdown is required to minimize the hazards to personnel and equipment, a system of coordination based upon the faulted or overloaded circuit is isolated by selective operation of only the overcurrent protective device closest to the overcurrent condition. The user should select devices that meet this requirement. References: NEC Also see CEC. Application Considerations The following is a discussion of application considerations related to North American applications. When applying product to IEC regional requirements, follow IEC practices and guidelines. The selection of a specific ampere rating for a specific application is dependent on the type of load and duty cycle and is governed by the National Electric Code (Canadian Electric Code) and UL/CSA. In general, the codes require that overcurrent protection is at the current supply and at points where wire sizes are reduced. In addition, the codes state that conductors be protected according to their current carrying capacity. There are specific situations that require application consideration, such as motor circuit, and guidelines for the selection for transformer protection. The Bulletin 1489-A circuit breakers are non 100 percent rated as defined by UL 489, para As such, the circuit breaker's rating should be loaded to no more than 80% if used with continuous loads. Line and load may be reversed. The Bulletin 1489 circuit breaker may be bottom fed. Branch Circuits: Bulletin 1489-A circuit breakers may be used to protect branch circuits. A branch circuit is the wiring portion of a system extending beyond the final overcurrent device protecting the circuit. Guidelines established in NEC, CEC, UL, and CSA should be used to determine the specific device. For example: 1) Motor Branch Circuit Bulletin 1489-A circuit breakers are not horsepower rated because they are able to safely interrupt currents far in excess of the locked rotor value for a selected motor. This ability is recognized in the codes and standards and is also established by the UL and CSA tests described in UL 489 and CSA C22.2 No. 5 standards. The size of a Bulletin 1489 circuit breaker should be determined HACR Rating Bulletin 1489-A s are rated as Heating, Air Conditioning and Refrigeration circuit breakers as defined by UL 489, paragraph 6.7 and may used in this type of application. SWD Rating The Bulletin 1489 breakers ( A) are rated as SWD and as such may be applied to switch fluorescent lighting loads up to their current and voltage maximum. Current Limiting Bulletin 1489-A s are rated as current limiting circuit breakers as defined by UL 489, paragraph 8.6. The Bulletin 1489-A line features the ability to achieve short circuit interruptions far more effectively than conventional breakers. In conventional circuit breakers, the short circuit interruption time required is approximately one or two half cycles of an AC sine wave. When the contacts open, the resulting arc continues to burn until the current level passes through zero. The arc may re-ignite because of the insufficient width of the contact gap. The current that flows until the arc is extinguished produces a heating effect proportional to the I2t value (let-through-energy) of the fault current. The Bulletin 1489-A device is designed to substantially reduce the amount of let-through-current and the resulting let-through-energy that can damage protected components. The Bulletin 1489 has the ability to interrupt short circuit current within the first half cycle of the fault. Limiting let-through current and energy will protect against the harmful effects of overcurrent and is focused primarily on avoiding the following: Excessive Heat Mechanical Damage Both of these factors are proportional to the square of the current. Thermal energy is proportional to the square of the RMS value and magnetic forces are proportional to the square of the peak value. The most effective way to provide protection is to substantially limit let-through-energy. This provides the following advantages 4 Publication 1489-SG001D-EN-P

5 Bulletin 1489-A Description, Continued Far less damage at the location of the short circuit. Fast electric separation of a faulty unit from the system, especially power supplies connected in parallel that are switched off when the voltage of the power bus drops below a certain level. Far less wear on the miniature circuit breaker itself. This means more safe interruptions. Better protection of all components in the short circuit path. Far wider range of selective action when used with an upstream protective device. (No nuisance shut downs from feeder line interruptions, causing a blackout in all connected branches.) The following values are applicable to the whole product range with frequency of 50/60 Hz. The values were derived from worst case V AC testing of: D trip 40 A, 240V 10 ka D trip 32 A, 480Y/277V 10 ka D trip 20 A, 480Y/277V 14 ka Current-Limiting at 240V / 10 ka1p, 2p, 3p I²t = 43 ka²s and Ipeak = 6.2 ka Current-Limiting at 480Y/277V / 10 ka 1p, 2p, 3p I²t = 60 ka²s and Ipeak = 6.2 ka Current-Limiting at 480Y/277V / 14 ka 1p, 2p, 3p I²t = 65 ka²s and Ipeak = 7.5 ka Bulletin 1489-A Ambient Temperature Derating The standard tripping characteristic for Bulletin 1489-A is Type C. Type C has a magnetic trip activated at 5 10 times the rated current of the circuit breaker. The reference temperature for the thermal tripping characteristics is 40 C. The Type C characteristic will suit most applications. In rare occurrences when the Type C characteristic does not fully meet the application, the following additional magnetic trip characteristic is available: Type D allows for transients approximately twice as high as the standard Type C. Use the following table and graph to determine the current rating for the breaker if the ambient is significantly different than 40 C. Bulletin 1489-A Ambient Temperature Derating Calibration Temperature 40º C (UL) Application below 0º C is for non-condensing atmosphere Device Marked Current Rating 40 C Ambient Temperature ( C) Care should be taken for application below 0 C. These devcies are not certified to operate correctly in the presence of ice. All other specifications for standard Bulletin 1489-A products remain unchanged. The ambient temperature derating applies to applications of the device as an IEC Miniature (MCB), following and as Circuit Breaker to UL489/CSA 22.2 No 5.. Ambient temperature refers to the free air temperature in contact with the 1489 device Publication 1489-SG001D-EN-P 5

6 Bulletin 1489-A Description, Continued Ambient Temperature Graph Load Factor K T [I/I n ] Influence of Ambient Temperature (T) on Load-Carrying Capacity Ambient Temperature T [ C] Maximum load I at Ambient Temperature T: L I L (T) = I n K T (T) The 1489-A circuit breaker can function over a wide temperature range ( C). Operation in ambient temperatures below 0 C is based on a non condensing atmosphere (no ice). Use the graph above or contact your local Rockwell Automation sales office or Allen-Bradley distributor to determine the correction factor based upon ambient circuit breakers. They are available in 1-, 2-, and 3- pole configurations for connection of multiple circuit breakers. Lock-out Attachment A sturdy lock-out attachment may be added to a circuit breaker. This lock-out may be padlocked so that the circuit breaker is locked in the off position. Shunt Trip A shunt trip may be added to a circuit breaker to allow the device to be tripped from a remote source. One version is for tripping voltages of V AC (12 60V DC) and another for tripping voltages of V AC ( V DC). Auxiliary Contacts An auxiliary contact module may be added to a circuit breaker to provide pilot duty contacts to indicate the position of circuit breaker, off or on. This contact changes state when the circuit breaker is operated either manually or electrically. Signal Contacts A signal/auxiliary contact module may be added to a circuit breaker to provide auxiliary contact information off and on and signal contact pilot duty contacts. With signal contacts, the contacts change state only when the circuit breaker changes state from On to Off because of an electrical operation. The module contains one signal contact, form C contact (N.O. and N.C contact with common) and one auxiliary contact (N.O. and N.C contact with common). Terminals Standard wire (cable) connection The standard configuration of the Bulletin 1489-A is with terminals suitable for connection of stranded copper wire of the wire size #18 8 AWG ( mm2). Strip length for the termination is 0.5 in. (12 mm). Terminals are shipped in the open position for ease of installation. Optional Ring Termination For the Bulletin 1489-A circuit breakers, an optional terminal configuration (suffix R) is available for use with a ring terminal. This configuration is shipped so that the terminal screw may be unscrewed and withdrawn for the insertion of the ring terminal at proper connection point. The screw is then retightened to provide proper wire termination. This unique terminal may be field converted to open the wire termination to allow standard wire termination of the converted terminal. Bus Bars For the Bulletin 1489-A circuit breakers, UL Recognized bus bars and UL Listed feeder terminals are available for group connection of 6 Publication 1489-SG001D-EN-P

7 Time-Current Characteristic Bulletin 1489 Type C and D Ambient Temperature 40 C Bulletin 1489-A Description, Continued Tripping characteristic acc. to UL Conventional non-tripping current I = 1.0 I (T=40 C) nt Conventional tripping current I = 1.35 I : t < 1 h (T=25 C) t N N N 2.0 I : t = s (T=25 C) instantaneous tripping acc. to IEC Type C: 5 I : t > N 0.1 s 10 I : t < 0.1 s N t [sec] Type D: 10 I : t > N 0.1 s 20 I : t < 0.1 s N C 4 5 D I / I N Publication 1489-SG001D-EN-P 7

8 Bulletin 1489-A Catalog Number Explanation Bulletin 1489 Cat. No. Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid catalog number A 1 C 005 R a b c d e b Poles Code Description 1 1-Pole 2 2-Pole 3 3-Pole Trip Curve Code Trip Curve B Trip Curve B C Trip Curve C D Trip Curve D a Body Style Code Description A Standard configuration, AC Device D Standard configuration, DC Device c d Rated Current (I n ) Code Current [A] Code blank R e Factory Modifications Description Standard Terminal Ring Terminal 8 Publication 1489-SG001D-EN-P

9 Product Selection Bulletin 1489-A AC Miniature s Bulletin Pole AC Miniature s No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] 1 415V AC, 48V DC C D 277V AC, 48V DC 240V AC, 48V DC 277V AC, 48V DC 240V AC, 48V DC Standard Wire Configuration Cat. No. Bulletin 1489-A Product Selection Ring Terminal Configuration Cat. No A1C A1C005R A1C A1C010R A1C A1C015R A1C A1C020R A1C A1C030R A1C A1C040R A1C A1C050R A1C A1C060R A1C A1C070R A1C A1C080R A1C A1C100R A1C A1C130R A1C A1C150R A1C A1C160R A1C A1C200R A1C A1C250R A1C A1C300R A1C A1C320R A1C A1C350R A1C A1C400R A1D A1D005R A1D A1D010R A1D A1D015R A1D A1D020R A1D A1D030R A1D A1D040R A1D A1D050R A1D A1D060R A1D A1D070R A1D A1D080R A1D A1D100R A1D A1D130R A1D A1D150R A1D A1D160R A1D A1D200R A1D A1D250R A1D A1D300R A1D A1D320R A1D A1D350R A1D A1D400R Publication 1489-SG001D-EN-P 9

10 Bulletin 1489-A Product Selection Bulletin 1489-A 2-Pole AC Miniature s No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] 2 415V AC C D 480Y/277V AC, 96V DC 240V AC, 96V DC 480Y/277V AC, 96V DC 240V AC, 96V DC Standard Wire Terminal Cat. No. Ring Terminal Configuration Cat. No A2C A2C A2C A2C010R A2C A2C015R A2C A2C020R A2C A2C030R A2C A2C040R A2C A2C050R A2C A2C060R A2C A2C070R A2C A2C080R A2C A2C100R A2C A2C130R A2C A2C150R A2C A2C160R A2C A2C200R A2C A2C250R A2C A2C300R A2C A2C320R A2C A2C350R A2C A2C400R A2D A2D005R A2D A2D010R A2D A2D015R A2D A2D020R A2D A2D030R A2D A2D040R A2D A2D050R A2D A2D060R A2D A2D070R A2D A2D080R A2D A2D100R A2D A2D130R A2D A2D150R A2D A2D160R A2D A2D200R A2D A2D250R A2D A2D300R A2D A2D320R A2D A2D350R A2D A2D400R 10 Publication 1489-SG001D-EN-P

11 Bulletin 1489-A Product Selection Bulletin 1489-A 3-Pole AC Miniature s No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] 3 415V AC C D 480Y/277V AC 240V AC 480Y/277V AC 240V AC Standard Wire Terminal Cat. No. Ring Terminal Configurations Cat. No A3C A3C005R A3C A3C010R A3C A3C015R A3C A3C020R A3C A3C030R A3C A3C040R A3C A3C050R A3C A3C060R A3C A3C070R A3C A3C080R A3C A3C100R A3C A3C130R A3C A3C150R A3C A3C160R A3C A3C200R A3C A3C250R A3C A3C300R A3C A3C320R A3C A3C350R A3C A3C400R A3D A3D005R A3D A3D010R A3D A3D015R A3D A3D020R A3D A3D030R A3D A3D040R A3D A3D050R A3D A3D060R A3D A3D070R A3D A3D080R A3D A3D100R A3D A3D130R A3D A3D150R A3D A3D160R A3D A3D200R A3D A3D250R A3D A3D300R A3D A3D320R A3D A3D350R A3D A3D400R Publication 1489-SG001D-EN-P 11

12 Bulletin 1489-A Accessories Miniature Accessories Description CSA/UL Certifications IEC Compliance CE EN/IEC Max. Volt. UL/CSA Max. Volt. Connection Cat. No. Lockout Attachment Yes Yes 1489-AALOA Auxiliary Contact, 2 sets, each are Form C, 1 N.O. & 1 N.C. Auxiliary/Signal Contact, each are Form C, 1 N.O. & 1 N.C Auxiliary Contact, Feed Through, 1 N.O. & 1 N.C. Yes Yes Yes Yes Yes Yes 3 A, 250V AC (AC13) 0.5 A, 110V DC 3 A, 250V AC (AC13) 0.5 A, 110V DC 3 A, 250V AC (AC13) 0.5 A, 110V DC 2 A, 240V AC 0.5 A, 110V DC 2 A, 240V AC 0.5 A, 110V DC 2 A, 230V AC 0.5 A, 110V DC Cable Cable Cable 1489-AAHH AAHS ABH12 Shunt Trip Module Yes Yes Shunt Trip Module Yes Yes V AC V DC V AC 12 60V DC V AC V DC V AC 12 60V DC Use of auxiliary or signal contact limits the 1489-A circuit breaker to a maximum voltage of 240V AC for UL/CSA applications. Use of this auxiliary contact allows application of the 1489-A circuit breaker to full rating of 480Y/ 277V AC for UL/CSA applications. Cable Cable 1489-AASTA AASTA2 Bulletin 1489-A Bus Bar Description No. of Poles No. of Phases Pkg Qty. Number of s Cat. No AACL AACL AACL AACL206 Bus Bar AACL AACL AACL AACL AACL318 UL Recognized (E300325), CE Marked Bulletin 1489 Bus Bar Accessories Description No. of Poles Pkg Qty. Wire Range Cat. No. Terminal Lug 1-pole for circuit breaker termination 10 Protective Cover for Unused Termination #14 2 AWG mm AACLT35 3-pole set (may be separated) AACLPS 12 Publication 1489-SG001D-EN-P

13 Bulletin 1489-A Specifications Number of Poles 1, 2, and 3 Standards Certifications HACR Rating (USA/Canada) UL 489 CSA C22.2 No. 5 EN/IEC UL Listed (File Number E197878) CSA Certified, VDE Certified, MCB, CE Marked SWD Rating (USA/Canada) Yes ( A) Calibration Temperature UL/CSA: 40 C EN/IEC: 30 C Rated Interrupting Capacity Rated Tripping Current Degree of Protection Dielectric Strength Shock Vibration Normal Operating Environment Yes EN/IEC - Icu: A UL/CSA (See Below) Trip Curve Rated Current (In) Interrupt Rating (UL/CSA) C Curve D Curve A 10,000 A A 14,000 A A 10,000 A A 10,000 A A 14,000 A A 10,000 A UL/CSA: A, 480Y/277V AC A, 240V AC A 48V DC 1-pole A 96V DC 2-pole EN/IEC: A, 415V AC 48V DC Finger-safe from front: -IP20 per IEC 529 from front -IP00 at wire terminals 1960V AC 25 G Half sine wave for 11 ms (3 axes) Frequency range: Hz Max. Amplitude (p-p) = in. Max. Acceleration = 5 G 2 hours each of 3 axes C ( F) (non-condensing) Bulletin 1489-A Specifications Trip Curves Shipment and Short-Term Storage Limits Wire Size Terminal Torque Recommended Wire Strip Length C curve (Inductive) I N D curve (Highly Inductive) I N C ( F) 1 wire: # AWG 2 wires: # AWG # AWG: 21 lb in. # AWG: 25 lb in. #6 AWG: 36 lb in. #2 PoziDriv 0.5 in. Publication 1489-SG001D-EN-P 13

14 Bulletin 1489-A Approximate Dimensions Bulletin 1489-A Approximate Dimensions Note: All units are in millimeters unless indicated. Dimensions are not intended for manufacturing purposes. Catalog Number Line/Load Terminal Style Access Hole Dia. in Housing (mm) Terminal Screw Head Diam (mm) Comment: Terminal Screw Type Without R Suffix With R Suffix Cable Ring Lug Non-Removable #2 8 Removable PoziDrive Note: Dimensions are in millimeters (mm). 14 Publication 1489-SG001D-EN-P

15 Bulletin 1489-A Approximate Dimensions Terminal Screw/Clamp Mounting Screws 1489-AAHH3 & 1489-AAHS ABH12 Publication 1489-SG001D-EN-P 15

16 Bulletin 1489-A Approximate Dimensions 1489-AAST1, 1489-AAST AACL106 Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL Publication 1489-SG001D-EN-P

17 Bulletin 1489-A Approximate Dimensions Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL118 Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL206 Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL212 Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL218 Publication 1489-SG001D-EN-P 17

18 Bulletin 1489-A Approximate Dimensions Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL306 Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL312 Surfaces Nominally Flush (in the same plane) Maximum 1.5 (out of plane) 1489-AACL , 5 Cat 1489-AACLT35 Ser. A See instruction sheet IEC: 2,5-35mm² UL: #14-2 AWG.56 In E mm UL489 71, 6 31, 3 16, AACLT35 3, , 6 17, B L A C K P R I NT I N G 1489-AACLPS 18 Publication 1489-SG001D-EN-P

19 Bulletin 1489-D Overview/Description Bulletin 1489-D s Specially designed for higher voltage DC circuits with a permanent magnet to direct the arc into the arc splitters. Field-mountable options for selective applications IP2x Finger-Protection (Front) North America certifications: UL 489, CSA C22.2 No. 5 International standards: CE Marked for IEC standards for worldwide acceptance 10 ka interrupt rating UL/CSA 1 pole: max. 125V DC, 2 pole: max. 250V DC IEC 1 pole: max. 250V DC, 2 pole: max. 500V DC A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position) Trip curves: C Superior shock and vibration resistance capabilities helps to prevent nuisance tripping Mounts on DIN Rail Wire connect, follow polarity requirements Table of Contents Specifications Description Product Selection Approximate Dimensions Standards Compliance UL 489 CSA C22.2 No. 5 EN/IEC Certifications UL Listed CSA Certified CE Marked Industrial s for North American Applications Field mountable options for selective applications IP2x Finger-Protection (Front) North America certifications: UL 489, CSA 22.2 No. 5 International standards: CE Marked for IEC standards for worldwide acceptance 10 ka interrupt rating UL/CSA 1 pole: max. 125V DC, 2 pole: max. 250V DC IEC 1 pole: max. 250V DC, 2 pole: max. 500V DC A positively trip-free mechanism (breaker operation cannot be defeated by holding the handle in the ON position) Trip curves: C Superior shock and vibration resistance capabilities helps to prevent nuisance tripping Mounts on DIN Rail Wire connect, line and load (reversible) Follow polarity requirements. The Bulletin 1489-D line includes: UL 489, CSA C22.2 No. 5 1 pole, 125V DC, A 2 pole, 250V DC, A Miniature for EN/IEC Applications EN/IEC pole, 250V DC, A 2 pole, 500V DC, A Description Bulletin 1489-D s for Branch Circuit protection are available in 1- and 2-pole construction and are rated A at 125V DC and A at 250V DC for North American applications (UL 489 and CSA C22.2 No. 5).. For EN\IEC applications the products are rated 1-pole: A, 250V DC, and 2-pole: A, 500V DC. Thermal Magnetic s The Bulletin 1489-D Thermal Magnetic s are generalpurpose devices suitable for the majority of industrial, inverse time circuit breaker applications. They combine thermal and magnetic trip actions and provide accurate overload and short-circuit protection for conductors and connected equipment. Features Designed manufactured and listed to UL 489 (CSA 22.2 No. 5) Thermal-magnetic protection up to 10 ka Interrupting rating Finger safe design (front) DIN Rail mounting Line and load wire connections Follow polarity requirements Application Information Selection of a Bulletin 1489-D circuit breaker with appropriate circuit protection includes consideration of: Circuit Voltage Available Short Circuit Current Continuous Current Rating Application Considerations Special Operating Conditions Regional Certifications The following discussion is based upon National Electric Code and UL requirements. Similar considerations are appropriate for Canadian and IEC applications. Circuit Voltage The Bulletin 1489-D circuit breakers are rated by voltage class. Applications should not exceed the listed voltage and current range (see Table 1). Available Short Circuit Current The Bulletin 1489-D circuit breakers should only be applied in those applications in which the available short-circuit (or fault) current is less than or equal to 10 ka. Table 1. Voltage and Current Ranges Region EN/IEC Regions North America (UL 489 & CSA C22.2 No. 5) Current Range Max. Voltage [A] 1-pole 250V DC pole 500V DC pole 125V DC pole 250V DC Publication 1489-SG001D-EN-P 19

20 Bulletin 1489-D Description Continuous Current Rating Standard current ratings are: 2, 3, 4, 5, 6, 7, 8, 10, 15, 16, 20, 25, 30, 32, 35, and 40 A. The Bulletin 1489-D circuit breakers are rated in amperes at a 40 C (104 F) ambient temperature per the UL 489 (CSA 22.2 No. 5) standard. This temperature is generally used as the average temperature within an industrial enclosure. If a circuit breaker is applied in a temperature that exceeds the 40 C (104 F) ambient, then the circuit breaker should be derated. For IEC standard, the products carry an ambient rating of 30 C. Follow standard IEC application considerations for temperature rating in different ambient temperatures. The characteristic trip curve is shown on page 22. The trip bands shown for each breaker represent current tripping limits for a circuit breaker and are within the limits established by UL. For a specific current at 40 C (104 F), a circuit breaker will open ("clear the circuit") automatically at some total time that will be within the "Minimum" and "Maximum" time shown on the curves. For example, page 21 shows that a one-pole, 15 A, Bulletin 1489 circuit breaker trips in not less than 10 s and not more than 120 s on a 30 A current. Because the UL standard defines this time spread, users should not specify exact tripping time. The lower current portion of the curves (upper left) depict the time to trip due to thermal action and reflect overload protection of the wire and connect load. The higher current portion of the curves (lower right) depicts the trip due to magnetic action of the circuit breaker and reflects protection due to short circuit level currents. Application Considerations The following is a discussion of application considerations related to North American applications. When applying product to IEC regional requirements, follow IEC practices and guidelines. The selection of a specific ampere rating for a specific application is dependent on the type of load and duty cycle and is governed by the National Electric Code (Canadian Electric Code) and UL/CSA. In general, the codes require that overcurrent protection is at the current supply and at points where wire sizes are reduced. In addition, the codes state that conductors be protected according to their current carrying capacity. There are specific situations that require application consideration, such as motor circuit, and guidelines for the selection for transformer protection. The Bulletin 1489-D circuit breakers are non 100 percent rated as defined by UL 489, para As such, the circuit breaker's rating should be loaded to no more than 80% if used with continuous loads. Polarity Positive and negative connection many not be reversed. Branch Circuits Bulletin 1489 circuit breakers may be used to protect branch circuits. A branch circuit is the wiring portion of a system extending beyond the final overcurrent device protecting the circuit. Guidelines established in NEC, CEC, UL, and CSA should be used to determine the specific device. Coordinated Overcurrent Protection Where an orderly shutdown is required to minimize the hazards to personnel and equipment, a system of coordination based upon the faulted or overloaded circuit is isolated by selective operation of only the overcurrent protective device closest to the overcurrent condition. The user should select devices that meet this requirement. References: NEC Also see CEC. Determining Ratings The tripping characteristic for Bulletin 1489-D is Type C. Type C has a magnetic trip activated at 7 15 times the rated current of the circuit breaker. The reference temperature for the thermal tripping characteristics is 40 C. The Type C characteristic will suit most applications. Use the following table and graph to determine the current rating for the breaker if the ambient is significantly different than 40 C. Bulletin 1489-D Ambient Temperature Derating Calibration Temperature 40º C (UL) Application below 0º C is for non-condensing atmosphere Device Marked Current Rating 40 C Care should be taken for application below 0 C. These devcies are not certified to operate correctly in the presence of ice. All other specifications for standard Bulletin 1489-A products remain unchanged. The ambient temperature derating applies to applications of the device as an IEC Miniature (MCB), following and as Circuit Breaker to UL489/CSA 22.2 No 5.. Ambient temperature refers to the free air temperature in contact with the 1489 device 20 Publication 1489-SG001D-EN-P

21 Bulletin 1489-D Description Ambient Temperature Graph Load Factor K T [I/I n ] Influence of Ambient Temperature (T) on Load-Carrying Capacity Ambient Temperature T [ C] Maximum load I at Ambient Temperature T: L I L (T) = I n K T (T) The 1489-D circuit breaker can function over a wide temperature range ( C). Operation in ambient temperatures below 0 C is based on a non condensing atmosphere (no ice). Use the graph above or contact your local Rockwell Automation sales office or Allen-Bradley distributor to determine the correction factor based upon ambient temperature. Terminals Standard wire (cable) connection The standard configuration of the Bulletin 1489 is with terminals suitable for connection of stranded copper wire of the wire size #18 8 AWG ( mm2). Strip length for the termination is 0.5 in. (12 mm). Terminals are shipped in the open position for ease of installation. Lock-out Attachment A sturdy lock-out attachment may be added to a circuit breaker. This lock-out may be padlocked so that the circuit breaker is locked in the off position. Shunt Trip A shunt trip may be added to a circuit breaker to allow the device to be tripped from a remote source. One version is for tripping voltages of V AC (12 60V DC) and another for tripping voltages of V AC ( V DC). Auxiliary Contacts An auxiliary contact module may be added to a circuit breaker to provide pilot duty contacts to indicate the position of circuit breaker, off or on. This contact changes state when the circuit breaker is operated either manually or electrically. Signal Contacts A signal/auxiliary contact module may be added to a circuit breaker to provide auxiliary contact information off and on and signal contact pilot duty contacts. With signal contacts, the contacts change state only when the circuit breaker changes state from On to Off because of an electrical operation. The module contains one signal contact, form C contact (N.O. and N.C contact with common) and one auxiliary contact (N.O. and N.C contact with common). Publication 1489-SG001D-EN-P 21

22 Bulletin 1489-D Description Time Current Curve 1- and 2-Pole Time-Current Characteristic UL Tripping Characteristic acc. to UL conventional non-tripping current I nt = 1.0 n I conventional tripping current I = 1.35 n I : t < 1 h t I n : t = s Tripping time t [sec] I n : t > 0.1 s 15 I n : t < 0.1 s C I/I 22 Publication 1489-SG001D-EN-P

23 Bulletin 1489 Cat. No. Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid catalog number. Bulletin 1489-D Catalog Number Explanation D 1 C 020 a b c d e a Body Style Code Description A Standard configuration, AC Device D Standard configuration, DC Device b Poles Code Description 1 1-Pole 2 2-Pole c Trip Curve Code Trip Curve C Trip Curve C d Rated Current (I n ) Code Current [A] Code blank R e Factory Modifications Description Standard Terminal Ring Terminal (available on 1489-A only) Publication 1489-SG001D-EN-P 23

24 Bulletin 1489-D Product Selection Product Selection Bulletin 1489-D, 1-Pole DC Miniature s No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] Standard Wire Configuration Cat. No C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C C 125 V DC D1C400 Bulletin 1489-D, 2-Pole AC Miniature s No. of Poles EN/IEC Maximum Voltage Trip Curve UL/CSA Max. Volt. Rated Current [A] Standard Wire Configuration Cat. No V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C VDC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C V DC C 250V DC D2C Publication 1489-SG001D-EN-P

25 Miniature Accessories Description CSA/UL Certifications IEC Compliance CE EN/IEC Max. Volt. UL/CSA Max. Volt. Connection Cat. No. Lockout Attachment Yes Yes 1489-AALOA Auxiliary Contact, 2 sets, each are Form C, 1 N.O. & 1 N.C. Auxiliary/Signal Contact, each are Form C, 1 N.O. & 1 N.C Auxiliary Contact, Feed Through, 1 N.O. & 1 N.C. Yes Yes Yes Yes Yes Yes 3 A, 250V AC (AC13) 0.5 A, 110V DC 3 A, 250V AC (AC13) 0.5 A, 110V DC 3 A, 250V AC (AC13) 0.5 A, 110V DC 2 A, 240V AC 0.5 A, 110V DC 2 A, 240V AC 0.5 A, 110V DC 2 A, 230V AC 0.5 A, 110V DC Cable Cable Cable Bulletin 1489-D Accessories/Specifications 1489-AAHH AAHS ABH12 Shunt Trip Module Yes Yes Shunt Trip Module Yes Yes V AC V DC V AC 12 60V DC V AC V DC V AC 12 60V DC Cable Cable 1489-AASTA AASTA2 Bulletin 1489-D Specifications Number of Poles 1, and 2 Standards Certifications UL 489 CSA C22.2 No. 5 EN/IEC UL Listed (File Number E197878) CSA Certified, VDE Certified, MCB, CE Marked SWD Rating (USA/Canada) Yes ( A) Calibration Temperature UL/CSA: 40 C EN/IEC: 30 C Rated Interrupting Capacity Rated Tripping Current EN/IEC - Icu: A UL/CSA 10kA UL/CSA: A, 1-pole 125 VAC A, 2-pole 250 VAC EN/IEC: A, 1-pole 250 VAC A, 2-pole 500 VAC Degree of Protection Dielectric Strength Shock Vibration Normal Operating Environment Trip Curves Shipment and Short-Term Storage Limits Wire Size Terminal Torque Recommended Wire Strip Length Finger-safe from front: -IP20 per IEC 529 from front -IP00 at wire terminals 1960V AC 25 G Half sine wave for 11 ms (3 axes) Frequency range: Hz Max. Amplitude (p-p) = in. Max. Acceleration = 5 G 2 hours each of 3 axes C ( F) (non-condensing) C curve (Inductive) I N C ( F) 1 wire: # AWG 2 wires: # AWG # AWG: 21 lb in. # AWG: 25 lb in. #6 AWG: 36 lb in. #2 PoziDriv 0.5 in. Publication 1489-SG001D-EN-P 25

26 Bulletin 1489-D Approximate Dimensions Bulletin 1489-D Approximate Dimensions Note: All units are in millimeters unless indicated. Dimensions are not intended for manufacturing purposes. 26 Publication 1489-SG001D-EN-P

27 Bulletin 1489-D Approximate Dimensions w/clamp Mounting Screws 1489-ABH AAHH3 & 1489-AAHS AAST1, 1489-AAST2 Publication 1489-SG001D-EN-P 27

28 Allen-Bradley and Rockwell Automation are trademarks of Rockwell Automation, Inc. Publication 1489-SG001D-EN-P December 2010 Supersedes Publication 1489-SG001C-EN-P June 2010 Copyright 2010 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Bimetallic Overload Relay Specifications

Bimetallic Overload Relay Specifications Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Product Guide. Cable-in / cable-out miniature circuit breakers and supplementary protectors

Product Guide. Cable-in / cable-out miniature circuit breakers and supplementary protectors Product Guide Cable-in / cable-out miniature circuit breakers and supplementary protectors Cable-in / cable-out miniature circuit breakers and supplementary protectors Eaton offers a complete line of

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Supplementary Protectors/Miniature Circuit Breakers

Supplementary Protectors/Miniature Circuit Breakers Technical Data Supplementary Protectors/Miniature Circuit Breakers Catalog Numbers 1492-SP Series C Important User Information Solid-state equipment has operational characteristics differing from those

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors. Technical Data

Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors. Technical Data Molded Case Circuit Breakers, Motor Protection Circuit Breakers, and Motor Circuit Protectors Technical Data Table of Contents Introduction... 4 Definitions... 5 Product Range... 8 Product Line Overview...11

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

D-Line Contactors, Overload Relays and Accessories

D-Line Contactors, Overload Relays and Accessories D-Line Contactors, Overload Relays and Accessories Class 850 CONTENTS Description......................................................Page General Information...............................................

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Circuit Breakers Supplementary Protectors Manual Motor Controllers

Circuit Breakers Supplementary Protectors Manual Motor Controllers WHITE PAPER Circuit Breakers Supplementary Protectors Manual Motor Controllers Circuit Protection Methods Differentiating between Supplementary Protection, Branch Circuit Protection, and Self-Protected

More information

AP/UP, AP/MIL Series. Magnetic Circuit Protectors

AP/UP, AP/MIL Series. Magnetic Circuit Protectors AP/UP, AP/MIL Series Magnetic Circuit Protectors Introduction Poles Configurations Operating Characteristics Delay Curves Specifications Decision Tables 71 72 75 76 77 78 79 AP/UP, AP/MIL Series Hydraulic

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

Catalog. Modular DIN rail components Installation contactors

Catalog. Modular DIN rail components Installation contactors Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection

More information

System pro M compact Miniature Circuit Breaker S 200/S 200 M

System pro M compact Miniature Circuit Breaker S 200/S 200 M Data Sheet System pro M compact Miniature Circuit Breaker S 200/S 200 M 2CDC021023S0012 2CDC021038S0012 The miniature circuit breakers of the System pro M compact series S 200 and S 200 M provide state-of-the-art

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

Thermal-Magnetic Circuit Breaker 3120-...-M1-..

Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

High Speed Fuses. High Speed Fuses

High Speed Fuses. High Speed Fuses Section Contents Page General Applications........................ 9-95 North American fuses & accessories............9-113 DFJ - High speed Class J fuse...................97 Square Body fuses & accessories............

More information

Type: DILM32 10(24V50HZ) Article No.: 277247

Type: DILM32 10(24V50HZ) Article No.: 277247 Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES The Edison British Style semiconductor protection fuses include a 660VAC line utilizing new filler technology. These new fuses have greatly reduced peak let-through current and energy under fault conditions

More information

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,

More information

Terminal Blocks & Power Distribution Terminal Blocks. Make your connection

Terminal Blocks & Power Distribution Terminal Blocks. Make your connection Terminal Blocks & Power Distribution Terminal Blocks Make your connection IEC TERMINAL BLOCKS PRODUCT SPOTLIGHT Leading the industry in efficiency and productivity, the Bulletin 1492 family of IEC terminal

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog 2004 Class 601 CONTENTS Description..............................................Page INTRODUCTION.............................................

More information

Power Distribution & Terminal Blocks

Power Distribution & Terminal Blocks Power Distribution & Terminal Section Contents Page Selection table for SCCR PDBs & Power terminal blocks................................ 294 Power distribution blocks Series PDBFS enclosed, with high

More information

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140) 9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity

More information

Circuit Breaker. Description

Circuit Breaker. Description Data Bulletin 0739DB9901R11/03 Cedar Rapids, Iowa, USA International Miniature Circuit Breakers with QO Plug-on and Bolt-on Connections Class Number 0739 Retain for future use. GENERAL DESCRIPTION The

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

Technicaldata General

Technicaldata General Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description

More information

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V, Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41

More information

PREFACE. The products covered by this Guide are:

PREFACE. The products covered by this Guide are: PREFACE UL has developed the Molded-Case Circuit Breaker (MCCB) Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Rotary Disconnect Switch Specifications

Rotary Disconnect Switch Specifications Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

SMC -3 Specifications

SMC -3 Specifications Technical Data SMC -3 Specifications Bulletin Number 150 Topic Page Product Overview 2 Standards Compliance and Certifications 2 Features 3 Catalog Number Explanation 4 Wiring Diagrams 6 General Specifications

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Photovoltaic System Overcurrent Protection

Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Introduction Solar Photovoltaic (PV) systems have, over the last fifty years, evolved into a mature, sustainable and

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Data Bulletin. Circuit Breaker Characteristic Trip Curves and Coordination Class 0600 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES

Data Bulletin. Circuit Breaker Characteristic Trip Curves and Coordination Class 0600 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES Data Bulletin Bulletin No. 000DB0 August 0 Cedar Rapids, IA, USA Class 000 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES Thermal Tripping Characteristics agnetic Tripping Characteristics A coordination

More information

Remote Power Panels with Breakers

Remote Power Panels with Breakers Remote Power Panels with Breakers 8 Series Panels & Enclosures N/A N/A Remote power panels with breakers are available in two different sizes, each of which may be either surfacemounted or recess-mounted,

More information

AC1645. System pro M compact Supplementary Protectors Miniature MCCBs

AC1645. System pro M compact Supplementary Protectors Miniature MCCBs AC1645 System pro M compact Supplementary Protectors Miniature MCCBs Table of Content 1 2 3 4 5 pro M compact General information...1.1 S200 - Supplementary protectors...1.7 S200U - Miniature MCCBs...1.12

More information

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

Overcurrent Protection

Overcurrent Protection Overcurrent Protection Data Bulletin 0600DB0301 R03/12, 03/2012 0600DB0301 R03/12, 03/2012 Overcurrent Protection Table of Contents Table of Contents Section 1: Overcurrent Protection Fundamentals and

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

Miniature Circuit Breakers and Supplementary Protectors

Miniature Circuit Breakers and Supplementary Protectors Miniature Circuit Breakers and Supplementary Protectors Miniature Circuit Breakers and Supplementary Protectors. Industrial Circuit Breakers QUICKLAG............................................. QUICKLAG

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide - long al and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide range coils +0% to -30% Finger safe terminals Four-pole versions available NO + NC and

More information

Thermistor motor protection

Thermistor motor protection Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor

More information

Motor Protection Voltage Unbalance and Single-Phasing

Motor Protection Voltage Unbalance and Single-Phasing Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

General Purpose Relays Types K, R, N, and C

General Purpose Relays Types K, R, N, and C General Purpose Relays s K, R, N, and C Catalog 0CT00R/0 00 Class 0 CONTENTS Description............................................. Page R Miniature Plug-in Relays.............................. K Plug-in

More information

Solid State Timers Type F

Solid State Timers Type F Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

Technical catalogue. Modular DIN rail components Installation contactors

Technical catalogue. Modular DIN rail components Installation contactors Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

Contact expander modules

Contact expander modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Type Sealing Poles Contacts Rated voltage Model Standard d Flux-tight 4 poles oes 3PST-NO, SPST-NC 24 VDC G7SA-3A1B 3PST-NO, 3PST-NC

Type Sealing Poles Contacts Rated voltage Model Standard d Flux-tight 4 poles oes 3PST-NO, SPST-NC 24 VDC G7SA-3A1B 3PST-NO, 3PST-NC Safety Relay Slim Safety Relays Conforming to EN Standards The forcibly guided contact in the assures safe operation (EN50205 Class A, approved by VDE.) Ideal for use in safety circuits in press machinery,

More information