High Speed Fuses. High Speed Fuses

Size: px
Start display at page:

Download "High Speed Fuses. High Speed Fuses"

Transcription

1 Section Contents Page General Applications North American fuses & accessories DFJ - High speed Class J fuse Square Body fuses & accessories BS 88 fuses & accessories Ferrule fuses & accessories High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

2 General Applications Rated Voltage The AC voltage rating of Cooper Bussmann fuses is given in volts rms. Fuses tested to IEC are tested at 5% above their rated voltage. British Style BS 88 fuses are tested at 10% above its rated voltage. UL recognition tests are performed at the rated voltage. Rated Current Rated current is given in amps rms. Cooper Bussmann fuses can continuously carry the rated current. Power Factor For other power factor values, the total clearing integral can be calculated as a multiple of the clearing integrals, the correction factor K and the correction factor X. X Melting Characteristic The melting 10 characteristic shows the virtual 10 melting time in 3 seconds as a function of the 10 prospective current in amperes rms. 10 The fuses are 1 specially constructed for 10 short-circuit 0 protection against high level fault 10 1 currents. Loading and operation of 10 the fuse in the noncontinuous/dashed 10 3 section of the melt curve must be avoided. The curve can also be read Prospective Current In Amperes RMS as the real melting time as a function of the RMS value of the pre-arc current. Virtual Pre-Arcing Time In Seconds Clearing Integrals The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) K E g Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Cut-Off Current A fuse operation relating to short-circuits only. When a fuse operates in its current-limiting range, it will clear a shortcircuit in less than 1 cycle. Also, it will limit the instantaneous Peak Let-Through Current A B COS U L Eg Kp I 0.1 b % Prospective Current in Amps RMS peak let-through current to a value substantially less than that obtainable in the same circuit if that fuse were replaced 9 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

3 General Applications with a solid conductor of equal impedance. A asymmetrical current B symmetrical current Parallel Connection When fuses are connected in parallel it is recommended that the applied voltage does not exceed 0.9 U N (the rated voltage of the fuse). This is due to the fact that the energy released within the fuses may be unevenly shared between the parallel connected barrels. When fuses are connected in parallel, one must take into account that the current sharing is not necessarily equal. And it must be checked, that the maximum load current is not exceeded. Series Connection Fuses in series may not equally divide the applied voltage. It is recommended that series connected fuses should only be operated at fault currents that yield melting times less than 10 ms and a recovery voltage per fuse of less than or equal to 0.9 U N (the rated voltage of the fuse). Mounting Guidance The recommendations below have to be followed when mounting a Cooper Bussmann fuse with end plate threaded holes. 1. Screw in studs: 5 N m Max, 3 N m Min. Attachment of the fuse to bussbar by means of nut and washer: Thread Torque (N m)* Configuration Max Min , M , M , M *1 N m = lb-ft Overloads The design of Cooper Bussmann fuses is such that they can be operated under rather severe operating conditions imposed by overloads (any load current in excess of the maximum permissible load current). In applications, there will be a maximum overload current, Imax, which can be imposed on the fuse with a corresponding duration and frequency of occurrence. Time durations fall into two categories: 1. Overloads longer than one second. Overloads less than one second termed impulse loads. The following table gives general application guidelines which, in the expression Imax < (% factor) x I t. I t is the melting current corresponding to the time t of the overload duration as read from the time-current curve of the fuse. The guidelines in the table below determine the acceptability of the selected fuses for a given I max. Frequency of Occurrence Overloads (> 1 sec) Impulse Loads (< 1 sec) Less than once per month I max < 80% x I t I max < 70% x I t Less than twice per week I max < 70% x I t I max < 0% x I t Several times per day I max < 0% x I t When impulse loads are an intrinsic/normal parameter of the load current either as single pulse or in trains of pulses or when their level is higher than the melting current at 0.01 seconds (per time-current curve), contact Cooper Bussmann for application assistance. In addition to the parameters set forth in the preceding table, the RMS value of the load current as calculated for any period of 10 minutes or more should not exceed the maximum permissible load current. Furthermore, it is important that a fuse should not be applied in the non-continuous/dashed portion of the associated time-current curve. Any time-current combination point which falls in the non-continuous/dashed portion of the time-current curve is beyond the capability of the fuse to operate properly. DC Operation Depending upon the short-circuit time constant and the magnitude of the prospective short-circuit current, the dc voltage at which a fuse can be applied may be less than its ac rating. Long time constants require a lower dc voltage. Conversely, however, higher available prospective shortcircuit currents result in faster fuse openings and thus permit a fuse to be operated at a higher DC voltage. Consult Cooper Reduction Factor Bussmann for additional information and application assistance when 1.0 fuses have to operate under DC conditions. 0.9 Load Current Versus Conductor Cross Section (IEC cross section) Reduction of permissible load current when the conductor cross section is less than that given in IEC Publication 9-1 & valid for Cooper Bussmann high speed fuses. Application Assistance If you have application problems or need a fuse outside our standard program, please contact the nearest Cooper Bussmann representative. Phone numbers are shown on the back cover. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

4 North American Fuses Introduction North American Contents Catalog Amp Number Volts Range Page DFJ FWA FWA FWX FWH KAC KBC FWP FWJ Accessories Fuse Bases 113 North American Fuse Ranges Amps Volts AC DC X X X X X X X X X X X X X General Information Cooper Bussmann offers a complete range of North American blade and flush-end style fuses and accessories. Their design and construction were optimized to provide: Low energy let-through (I t) Low watts loss Superior cycling capability Low arc voltage Excellent DC performance North American style fuses provide an excellent solution for medium power applications. While there are currently no published standards for these fuses, the industry has standardized on mounting centers that accept Cooper Bussmann fuses. Voltage Rating All Cooper Bussmann North American style fuses are tested at their rated voltage. Cooper Bussmann should be consulted for applications exceeding those values. Accessories External and internal open fuse indication is available for selected portions of the North American line. Fuse blocks are available for most applications. 9 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

5 Drive Fuse High Speed Fuses DFJ Class J Time-Current Characteristic Curves Average Melt Specifications Description: High speed, current-limiting fuse. The Cooper Bussmann Drive Fuse will provide maximum protection for AC and DC drives and controllers and meet NEC branch circuit protection requirements. The Drive Fuse has the lowest I t of any branch circuit fuse to protect power semiconductor devices that utilize diodes, GTOs, SCRs and SSRs. Dimensions: See page 15 for Class J dimensions. Construction: Melamine tube with silver fuse element. Ratings: Volts 00Vac (or less), 50Vdc (or less) Amps 1-00A IR 00kA RMS Sym., 100kA DC Agency Information: CE, Std. 8-8, Class J, UL Listed, Guide JDDZ, File E73, CSA Certified, Class 1-0, File Current Limitation Curves High Speed Fuses Features and Benefits Easily coordinated with existing and new variable speed drives and electric controllers. Standard Class J dimensions allowing the use of readily available fuse blocks, holders, and switches. Allows the lowest let-thru energy of any branch circuit overcurrent protective device. Typical Applications Protection of ac & dc drives Equipment using power semi-conductor devices Catalog Numbers (Amps) DFJ-1 DFJ-15 DFJ-70 DFJ-5 DFJ- DFJ-0 DFJ-80 DFJ-50 DFJ-3 DFJ-5 DFJ-90 DFJ-300 DFJ- DFJ-30 DFJ-100 DFJ-350 DFJ-5 DFJ-35 DFJ-110 DFJ-00 DFJ- DFJ-0 DFJ-15 DFJ-50 DFJ-8 DFJ-5 DFJ-150 DFJ-500 DFJ-10 DFJ-50 DFJ-175 DFJ-00 DFJ-1 DFJ-0 DFJ-00 Data Sheet: 108 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

6 North American FWA 130V: A FWA Specifications Description: North American style flush-end high speed fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: 130Vac Amps: A IR: 00kA RMS Sym. Agency Information: CE, UL Recognized on A fuses Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Dimensions (in) Catalog Number Fig. B C D Thread Depth FWA-1000AH-000AH Tapped x 1 FWA-500AH-3000AH Tapped 1-0 x 1 FWA-000AH Tapped 1-0 x 1 1mm = / 1 = 5.mm Fig. 1: A K Fig. : 000A Eg Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current Catalog Numbers I t (A Sec) Catalog Rated Current Clearing Watts Numbers RMS-Amps Pre-arc at 130V Loss FWA-1000AH FWA-100AH FWA-1500AH FWA-000AH FWA-500AH FWA-3000AH FWA-000AH Watts loss provided at rated current. See accessories on page 113. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Kp U L 50 E g I 0.1 b % Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters D B C B C Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

7 North American FWA 130V: A FWA A: 130V FWA-1000AH FWA-100AH FWA-1500AH FWA-000AH FWA-500AH FWA-3000AH FWA-000AH Virtual Pre-Arcing Time In Seconds High Speed Fuses Prospective Current In Amps RMS 10 5 Peak Let-Through Current 10 FWA-000AH FWA-3000AH FWA-500AH FWA-000AH FWA-1500AH FWA-100AH FWA-1000AH Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

8 North American FWA 150V: A FWA Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: 150Vac/dc Amps: A IR: 100kA Sym. (70-00A) 00kA Sym. ( A) (70-800A) 80Vdc (70-00A) Agency Information: CE, UL Recognized Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Dimensions (in) Fig. 1: 70-00A K ) ) ) A Range ) 70-00A Range 150 Eg 0.15 Arc Voltage This curve gives the peak arc voltage, U L, which may 300 appear across the fuse during its operation as a 00 function of the applied working voltage, E g, (rms) at a power factor of 15%. 100 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Number RMS-Amps Pre-arc at 150V Loss FWA-70B FWA-80B FWA-100B FWA-15B FWA-150B FWA-00B FWA-50B FWA-300B FWA-350B FWA-00B FWA-500A FWA-00A FWA-700A FWA-800A FWA-1000A Watts loss provided at rated current. See accessories on page 113. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Kp U L 50 E g I 0.1 b % Fig. : A Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters mm = / 1 = 5.mm Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

9 North American FWA 150V: A FWA A: 150V FWA-500A FWA-00A FWA-700A FWA-800A FWA-1000A Virtual Pre-Arcing Time In Seconds FWA-70A FWA-80A FWA-100A FWA-15A FWA-150A High Speed Fuses 10 3 FWA-00A FWA-50A FWA-300A FWA-350A FWA-00A Prospective Current In Amps RMS 10 Peak Let-Through Current 10 FWA-00A FWA-350A FWA-300A FWA-50A FWA-00A FWA-150A FWA-100A FWA-80A FWA-70A Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

10 North American FWX 50V: A FWX Specifications Description: North American style stud-mount and flush-end fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: 50Vac/dc Amps: A IR: 00kA RMS Sym. Agency Information: CE, UL Recognized & CSA Component Acceptance on A fuses (0kA Electrical Characteristics Total Clearing I t The total clearing I t at rated 0.5 voltage and at power factor of 15% are given in the 0.3 electrical characteristics. 0. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). K 1) ) Eg ) A Range ) A Range Dimensions (in) Tapped Amp Thread Range Fig. A B C D E F G H J Depth x x 1 1mm = / 1 = 5.mm A D E C Fig. 1: A J A Fig. : A A Fig. 3: A D Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical char acteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current U L ) 300 ) E g ) A Range ) A Range 1.0 Kp Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Number RMS-Amps Pre-arc at 50V Loss FWX-35A FWX-0A FWX-5A FWX-50A FWX-0A FWX-70A FWX-80A FWX-90A FWX-100A FWX-15A FWX-150A FWX-175A FWX-00A FWX-5A FWX-50A FWX-75A FWX-300A FWX-350A FWX-00A FWX-50A FWX-500A FWX-00A FWX-700A FWX-800A FWX-1000AH FWX-100AH FWX-1500AH FWX-100AH FWX-000AH FWX-500AH Watts loss provided at rated current. See accessories on page I 0.1 b % F G B C B C Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters H 10 B Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

11 North American FWX 50V: A FWX A: 50V 10 FWX A(H): 50V 10 Virtual Pre-arcing Time In Seconds FWX-35A FWX-0A FWX-0A FWX-70A FWX-100A FWX-150A FWX-00A FWX-350A FXW-00A FWX-500A FWX-00A FWX-800A Prospective Current In Amps RMS Virtual Pre-Arcing Time In Seconds FWX-1000AH FWX-100AH FWX-1500AH FWX-100AH FWX-000AH FWX-500AH High Speed Fuses B FWX-800A FWX-00A FWX-00A FWX-300A FWX-00A Prospective Current In Amps RMS Peak Let-Through Current A FWX-150A FWX-100A FWX-70A FWX-0A FWX-5A FWX-35A Peak Let-Through Current FWX-500AH FWX-000AH FWX-100AH FWX-1500AH FWX-100AH FWX-1000AH Prospective Short-Circuit Current Symmetrical RMS Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 359 Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

12 North American FWH 500V: A FWH Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustration. Ratings: Volts: 500Vac/dc Amps: A IR: 00kA Sym. 500Vdc Agency Information: CE, UL Recognition & CSA Component Acceptance on A only (50kA IR@500Vdc). UL Recognition on A only, CSA Component Acceptance: A. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Fig. 1: A G F Fig. : A A D E C K 1) ) J ) A Range ) A Range Dimensions (in) Amp Range Fig. A B C D E F G H J See Drawing 1mm = / 1 = 5.mm B H 500 Eg Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, Ib, in % of the rated current. Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Numbers RMS-Amps Pre-arc at 500V Loss FWH-35B FWH-0B FWH-5B FWH-50B FWH-0B FWH-70B FWH-80B FWH-90B FWH-100B FWH-15B FWH-150B FWH-175B FWH-00B FWH-5A FWH-50A FWH-75A FWH-300A FWH-35A FWH-350A FWH-00A FWH-50A FWH-500A FWH-00A FWH-700A FWH-800A FWH-1000A FWH-100A FWH-100A FWH-100A Watts loss provided at rated current. See accessories on page 113. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Superior cycling capability Data Sheet: U L ) 00 1) E g 500 Kp 1) & A Range ) 5-800A Range I 0.1 b % Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

13 North American FWH 500V: A FWH 35-00A(B) & A(A): 500V 10 FWH A: 500V FWH-35B FWH-0B FWH-5B FWH-50B FWH-0B FWH-70B FWH-80B FWH-90B FWH-100B FWH-15B FWH-150B FWH-175B FWH-00B FWH-900A FWH-1000A FWH-100A FWH-100A FWH-100A Virtual Pre-Arcing Time In Seconds FWH-300A FWH-00A FWH-500A FWH-00A FWH-800A High Speed Fuses Prospective Current In Amps RMS 10 5 FWH-100A FWH-100A FWH-100A FWH-1000A Prospective Current In Amps RMS 10 5 B Peak Let-Through Current Peak Let-Through Current FWH-800A FWH-00A FWH-500A FWH-00A FWH-300A FWH-50A FWH-00B FWH-150B FWH-15B FWH-100B FWH-80B FWH-0B FWH-50B FWH-0B FWH-35B Prospective Short-Circuit Current Symmetrical RMS A Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Data Sheet: 30 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

14 North American KAC 00V: A KAC Specifications Description: North American style stud-mount fuses. These 00V fuses are supplied as replacements only. For new installations, Cooper Bussmann recommends the 700V FWP Series fuse. Dimensions: See Dimensions illustrations. Ratings: Volts: 00Vac Amps: A IR: 00kA RMS Sym. Agency Information: CE, UL Recognition on 1-00A only. Catalog Numbers (Amps) KAC-1 KAC-5 KAC-175 KAC- KAC-30 KAC-00 KAC-3 KAC-35 KAC-5 KAC- KAC-0 KAC-50 KAC-5 KAC-5 KAC-300 KAC- KAC-50 KAC-350 KAC-7 KAC-0 KAC-00 KAC-8 KAC-70 KAC-50 KAC-9 KAC-80 KAC-500 KAC-10 KAC-90 KAC-00 KAC-1 KAC-100 KAC-700 KAC-15 KAC-110 KAC-800 KAC-17.5 KAC-15 KAC-1000 KAC-0 KAC-150 See accessories on page 113. Features and Benefits Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications Power converters/rectifiers Reduced voltage starters Dimensions (in) Amp Range Fig. A B1 B B3 C D E F G H 1-30A A A A A A A mm = / 1 = 5.mm Fig. 1: 1-30 & A A B1 C G D F H Fig. : 35-00A A B B3 C G D E F H Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

15 North American KBC 00V: A KBC Specifications Description: North American style stud-mount and flush-end fuses. These 00V fuses are supplied as replacements only. For new installations, Cooper Bussmann recommends the 700V FWP Series fuse. Dimensions: See Dimensions illustrations. Ratings: Volts: 00Vac Amps: A IR: 00kA RMS Sym. Agency Information: CE, UL Recognition on 35-00A only. Catalog Numbers (Amps) KBC-35 KBC-100 KBC-300 KBC-0 KBC-110 KBC-350 KBC-5 KBC-15 KBC-00 KBC-50 KBC-150 KBC-50 KBC-0 KBC-175 KBC-500 KBC-70 KBC-00 KBC-00 KBC-80 KBC-5 KBC-800 KBC-90 KBC-50 See accessories on page 113. Features and Benefits Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications Power converters/rectifiers Reduced voltage starters High Speed Fuses Dimensions (in) Amp Range Fig. A B C D E F G H I 35-0A A See Drawing A A A A 3 See Drawing 1mm = / 1 = 5.mm Fig. 1: 35-0 and A E A B C D H F G Fig. : A I Fig. 3: 800A / " - / " Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

16 North American FWP 700V: 5-100A FWP Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: 700Vac/dc Amps: 5-100A IR: 00kA RMS Sym. Agency Information: CE, UL Recognition & CSA Component Acceptance on 5-800A Total Clearing I t 1.5 K The total clearing I t at rated 1.0 voltage and at power factor of 15% are given in the electrical ) characteristics. For other 0.5 voltages, the clearing I t is found by multiplying by 1) 0.3 correction factor, K, given as 0. a function of applied working voltage, E g, (rms) ) ) A Range ) 15-00A Range 3) A Range Dimensions (in) Amp Range Fig. A B C D E F G H I See Drawing See Drawing 1mm = / 1 = 5.mm Fig. 1: 5-800A A D E C B F G J H Fig. : A Fig. 3: 100A Eg Arc Voltage This curve gives the peak arc 1. voltage, U L, which may appear across the fuse during its operation as a 8 function of the applied working voltage, E g, (rms) at 5 a power factor of 15%. Power Losses 3 Watts loss at rated current is given in the electrical characteristics. The curve 1.0 allows the calculation of the 0.8 power losses at load 0. currents lower than the rated 0.5 current. The correction factor, 0. K p, is given as a function of 0.3 the RMS load current, I b, in 0. % of the rated current. 0.1 I b Catalog Numbers % Rated I t (A Sec) Catalog Current Clearing Watts Numbers RMS-Amps Pre-arc at 700V Loss FWP-5B FWP-10B. 0 FWP-15B FWP-0B FWP-5B FWP-30B FWP-35B FWP-0B FWP-50B FWP-0B FWP-70B FWP-80B FWP-90B FWP-100B FWP-15A FWP-150A FWP-175A FWP-00A FWP-5A FWP-50A FWP-300A FWP-350A FWP-00A FWP-50A FWP-500A FWP-00A FWP-700A FWP-800A FWP-900A FWP-1000A FWP-100A Watts loss provided at rated current. See accessories on page 113. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Superior cycling capability Data Sheet: 7001 U L 1) ) E g ) 15-00A Range ) & A Range Kp Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

17 North American FWP 700V: 5-100A FWP 5-30A(B): 700V 10 FWP A(B) & A(A): 700V 10 Virtual Pre-Arcing Time In Seconds FWP-5B FWP-10B FWP-15B FWP-0B FWP-5B FWP-30B Prospective Current In Amps RMS Virtual Pre-Arcing Time In Seconds FWP-35B FWP-0B FWP-50B FWP-0B FWP-70B FWP-80B FWP-90B FWP-100B FWP-700A FWP-800A FWP-900A FWP-1000A FWP-100A Prospective Current In Amps RMS High Speed Fuses FWP-100A FWP-1000A FWP-800A FWP-700A FWP-30B FWP-5B Peak Let-Through Current 10 FWP-0B FWP-15B FWP-10B FWP- 5B Peak Let-Through Current Prospective Short-Circuit Current FWP-100B FWP-70B FWP-0B FWP-50B FWP-0B FWP-35B Prospective Short-Circuit Current Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

18 North American FWP 700V: 5-100A FWP A: 700V FWP-150A FWP-00A FWP-300A FWP-00A FWP-00A Virtual Pre-Arcing Time In Seconds Prospective Current Current In In Amperes Amps RMS RMS 10 5 B 10 Peak Let-Through Current FWP-00A FWP-00A FWP-300A FWP-00A FWP-150A A Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

19 North American FWJ 1000V: A FWJ Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustration. Ratings: Volts: 1000Vac Amps: A IR: 5kA (35-00A) 100kA (50-000A) 800Vdc (35-00A, 50-00A) Agency Information: CE, UL Recognition File E91958 on 35-00A only. Total Clearing I t 1.5 The total clearing I K t at rated 1.0 voltage and at power factor of 15% are given in the electrical characteristics. For other 0.5 voltages, the clearing I t is found by multiplying by 0.3 correction factor, K, given as 0. a function of applied working voltage, E g, (rms) Dimensions (in) Amp Range Fig. A B C D E F G H I mm = / 1 = 5.mm Fig. 1: A A D E C Eg H Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current Kp U L E g I b % Catalog Numbers Rated It (A Sec) Catalog Current Clearing Watts Numbers RMS-Amps Pre-arc at 1000V Loss FWJ-35A FWJ-0A FWJ-50A FWJ-0A FWJ-70A FWJ-80A FWJ-90A FWJ-100A FWJ-15A FWJ-150A FWJ-175A FWJ-00A FWJ-50A FWJ-300A FWJ-350A FWJ-00A FWJ-500A FWJ-00A FWJ-800A FWJ-1000A FWJ-100A FWJ-100A FWJ-100A FWJ-1800A FWJ-000A Watts loss provided at rated current. See accessories on page 113. High Speed Fuses G F J B Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Data Sheet: 7007 Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

20 North American FWJ 1000V: A FWJ 35-00A: 1000V Virtual Pre-Arcing Time In Seconds FWJ-0A FWJ-50A FWJ-0A FWJ-70A FWJ-80A FWJ-90A FWJ-100A FWJ-15A FWJ-150A FWJ-175A Prospective Current In Amps RMS FWJ-00A FWJ-50A FWJ-300A FWJ-350A FWJ-00A FWJ-500A FWJ-00A FWJ A: 1000V Virtual Pre-Arcing Time In Seconds FWJ-800A FWJ-1000A FWJ-100A FWJ-100A FWJ-100A FWJ-1800A FWJ-000A Prospective Prospective Current Current In Amperes in AmpsRMS Data Sheet: Peak Let-Through Current FWJ-000A FWJ-1800A FWJ-100A FWJ-100A FWJ-150A FWJ-1000A FWJ-00A FWJ-800A FWJ-00A FWJ-500A FWJ-350A FWJ-300A FWJ-50A FWJ-00A FWJ-175A FWJ-150A FWJ-15A FWJ-100A FWJ-90A FWJ-80A FWJ-70A FWJ-0A FWJ-50A FWJ-0A Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

21 North American Fuse Accessories Fuse Bases (Blocks) Modular Style Cooper Bussmann offers a comprehensive line of fuse bases that provide the user with design and manufacturing flexibility. Two identical half bases make up a Cooper Bussmann modular fuse base. These split units can be panel mounted any distance apart to accommodate any length fuse. Stud Type (Not sold in pairs) The simpler design is the C58 Series modular fuse base. With this design, the fuse terminal and cable (with termination) are mounted on the same stud, minimizing labor needed for installation. The stud type base is available in the configuration shown in the table below. Catalog Max Fuse Stud Stud Dia. Number Amp Rating Height (in) & Threads C C C C C C58 Series Stud Type High Speed Fuses Connector Type Cooper Bussmann also offers a modular style fuse base that utilizes a tin-plated connector (for wire termination and heat dissipation) and a plated-steel stud (for fuse mounting). The connector type fuse base is available in the configurations shown below. Consult Cooper Bussmann for additional product details. Modular Max Max Fuse Data Sheet Base Style Voltage Amp Rating Number 1BS BS BS BS BH-0xxx BH-1xxx BH-xxx BH-3xxx Refer to page 75 for BH style holders. BS Style Connector Type Fixed Center Base Style Cooper Bussmann offers a comprehensive line of fixed mount style fuse bases under the trademark TRON rectifier fuse blocks. The cable and fuse connections are similar to the stud type fuse base both are mounted on the same stud. Consult Cooper Bussmann for complete product details. Fixed Center Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

22 Square Body Fuses Introduction Square Body Contents Page Application Information Volts (IEC/UL) Size Class Fuse Style Page ar DIN ,00 ar Flush End Contact ar DIN ar DIN ar Flush End Contact /700 1*, 1,, 3 ar US Style 1-17 ar French Style ar Fuse Curves *,, 3 ar DIN ar Flush End Contact , ar Flush End Contact , 1,, 3 ar DIN ar DIN ar DIN ar Flush End Contact *, 1,, 3 ar US Style ar Fuse Curves ar Flush End Contact ar Flush End Contact ar DIN /1300 1*, 1,, 3 ar Flush End Contact 1-13 ar US Style 1-15 ar Fuse Curves 1-17 ar Flush End Contact ar Flush End Contact ar Flush End Contact 173 DC Fuses Accessories Page Indicator System 185 Fuse Bases 18 Square Body Fuse Ranges Amps Volts AC DC X X General Information Designed and tested to: IEC 09: Part UL Recognized Cooper Bussmann offers a complete range of square body style fuses and accessories. Their unique design and construction provide: Minimal energy let-through (I t) Low operating temperature Low watts loss Square body style fuses are a very attractive solution for high power applications which require a compact design with superior performance. The construction and design of square body style fuses make it easy for Cooper Bussmann to manufacture custom products. Our cataloged offering provides only a sample of the wide variety of product which is available. Each square body style fuse is available with a number of different end fittings. Options include: DIN 3 53 DIN 3 0 Flush End (Metric/US) French Style US Style Voltage Rating All Cooper Bussmann square body style fuses are tested to IEC 09: Part. This standard requires a test voltage which is 5% higher than the rated voltage. In North America, fuses are required to clear only their rated voltage. Accessories Square Body style fuses are available with three different open fuse indicator systems. Options include visual indication and indication utilizing a microswitch. Fuse blocks are also available for most applications. 11 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

23 Square Body Applications Maximum Permissible Load Current The rated current value of Cooper Bussmann fuses is based on the ambient temperature in the space immediately below the fuse of 0 C. The following graph gives correction factors (k) for a range of temperatures ( 0 C to +80 C). Maximum permissible continuous load currents can be calculated by applying the following formula: I b I n k ( V) x K b where I b = Maximum permissible continuous load current I n = Rated current of fuse k = Temperature correction factor v = Velocity of cooling air in m/s (max. 5 m/s). K b = Fuse load constant k Temperature Correction Curve C The maximum permissible continuous load current Ib of a fuse can be checked empirically (i.e., by satisfying the formula below) by making simple voltage and temperature measurements under actual operating conditions after the fuse has been installed in its operating location and loaded at the calculated Ib value: E ( t) N E 1 where E 1 = Voltage drop across fuse after 5 seconds E = Voltage drop across fuse after hours t = Air temperature at start of test ( C) N = Constant Fuse Rated Voltage (IEC) N High Speed Fuses Body Cross Section Standard fuse program includes barrels with different cross sections. Size Maximum Cross-section (mm) Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

24 Square Body Applications Example Application of Square Body High Speed Fuses Subject to Overload and Impulse Loading Select a short-blade indicating fuse with indicator/adapter to permit the use of a single-pole microswitch for remote indication and determine if the fuse selected will meet the following application parameters. 170M39 (00A) Application Parameters Load Currents Expected Load Type Duration Frequency of Occurrence Amps (1) Normal Continuous 300A () Overload 0 Seconds Once Per Hour 500A (3a) 10 Seconds -3 Times Per Week (3b) Overload 0 Seconds (max.) Once Per Month 700A () Impulse 0.5 Seconds Less Than Once Per Month 1100A Voltage Data (5) Voltage Applied to Fuse During Fault Conditions 00V (+10%) Temperature Data () Temperature Inside Cubicle in Which Fuse is Located (Natural Convection Cooling Only) 0 C Thyrister Data (7) Thyrister Peak Voltage Withstand 1000V (8) Thyrister I t Withstand at 10 Milliseconds* 90,000A s *Note: The I t withstand of the thyrister may be given for other impulse durations (i.e., 1.5 ms, 3.5 ms, or 8.3 ms); however, the stated fuse I t is valid for all impulse durations of 10 ms or less. Time In Seconds A Profile Line A Application Procedure Step Procedure Remarks (1) Select a short-blade fuse to permit 1.1 Taking into consideration only the mounting of microswitch 170H009 continuous load current and ambient temperature, from Table on page 17 tentatively select fuse 170M39 00A, 90V). () Determine I t (total clearing) at 0V..1 See Table, page 17. Note I t is 105,000A s at rated voltage of 90V.. From the figure on page 1, note that correction factor K = 0.5. OK.3 I t 0V K = I t 0V 105, = 8,50 (3) Determine maximum arc voltage 3.1 From the figure on page 1, note that at 0V maximum voltage at 0V is 900V OK () Determine maximum permissible.1 Per page 115 data, continuous load current I b. I b = I n k ( V) K b I b = 00A 0.8 (1 + 0) 1 I b = 30A (5) Plot a line profile showing the 5.0 Calculate I max per Table, expected load and overload currents. High Speed Fuse Application Guide Determine that overload and impulse page 1, for each overload and impulse load currents do not exceed their load. maximum permissible values. (Item ) 5.1 I max < 0% I t 500A < 0% 950A OK 500A < 570A (Item 3a) 5. I max < 0% I t 700A < 0% 130A OK 700A < 780A (Item 3b) 5.3 I max < 70% I t 700A < 70% 1150A OK 700A < 805A (Item ) 5. I max < 70% I t 1100A < 70% 1800A OK 1100A < 10A The tentatively selected fuse 170M39 with microswitch 170H009 meets all application parameters; no further selection would be necessary Current In Amperes Calculation of Watt Loss From the Table on page 17, watt loss at 00 amps is 0 watts. The continuous load current of 300A is 75% of rated current (00A). From page 1, the correction factor K p = 0.5. Watt Loss 75% = Watt Loss 100% K p = 0W 0.5 = 30 watts Special Fuses Other high speed fuses are available from Cooper Bussmann with voltage ratings of 380 to 10,000V and current ratings up to 10,000A in a single unit configuration. Fuses can be supplied with open fuse, pin indicators. Various types of microswitches are also available (see page 185). 11 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

25 Square Body DIN V/700V (IEC/UL): 10-00A 90V/700V (IEC/UL) 10-00A Specifications Description: Square body DIN 3-53 stud mount high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac (IEC) 700Vac (UL) Amps: 10-00A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. UL Recognition/CSA Component Acceptance on Size 000. Total Clearing I t The total clearing I 1.5 t at K rated voltage and at power 1.0 factor of 15% are given in the electrical characteristics. For other 0.5 voltages, the clearing I t is 0. found by multiplying by 0.3 correction factor, K, given as a function of applied 0. E g working voltage, E g, (rms) Dimensions (mm) Type -U/80, -/80, -TN/80 Size D E F G H K mm = / 1 = 5.mm 5 Indicator * Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters U L E g K p % For Other Voltage Ratings in This Body Style See page 1 (1000V) Dimensions (mm) Type 00B/0, 00BTN/0 1mm = / 1 = 5.mm I b High Speed Fuses M8 D K G Max E H F 8 * Indication for Size 00 fuses is a red pin. Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800) Indicator 117

26 Square Body DIN V/700V (IEC/UL): 10-00A Catalog Numbers Catalog Numbers -TN/80 00BTN/0 -U/80 -/80 Type T 00B/0 Type T Rated I t (A Sec) Without Visual Indicator Visual Indicator Current Clearing Watts Indicator Indicator for Micro Indicator for Micro Size RMS-Amps Pre-arc at 0V Loss 170M M M M M M M M M M M M M M13 170M M M M M M13 170M M M M M M13 170M M M M M M M M M M M M M M M M M13 170M M M08 170M58 170M M M09 170M59 170M M M10 170M0 170M M M11 170M1 170M M M1 170M 170M71 170M M13 170M3 170M M M1 170M 170M71 170M M15 170M5 170M M M1 170M 170M71 170M M17 170M7 170M M M18 170M8 170M M M19 170M9 170M M M0 170M70 170M70 170M M1 170M71 170M71 170M Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see page Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

27 Square Body Size 000, 00 90V/700V (IEC/UL): 10-00A Size A: 90V Size A: 90V 10 10A 1A 0A 5A 3A 0A 50A 3A 80A 100A 15A 10A 00A 50A 315A 10 5A 3A 0A 50A 3A 80A 100A 15A 10A 00A 50A 315A 350A 00A A A Virtual Pre-Arcing Time In Seconds A Virtual Pre-Arcing Time In Seconds A High Speed Fuses x10 1x Prospective Current In Amps RMS 1x10 1x Prospective Current in Amps RMS Peak Let-Through Current 10 B 315A 50A 00A 10A 15A 100A 80A 3A 50A 0A 3A 5A 0A 1A 10A Peak Let-Through Current 10 B 00A 350A 315A 50A 00A 10A 15A 100A 80A 3A 50A 0A 3A 5A A A x10 1 1x Prospective Short-Circuit Current Symmetrical RMS x10 1 1x Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

28 Square Body DIN V (IEC/UL): A 90V (IEC/UL) A Specifications Description: Square body DIN 3 0 blade style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac Amps: A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Dimensions (mm) DIN 000 Type T 1mm = / 1 = 5.mm 5 Max Indicator Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

29 Square Body DIN V (IEC/UL): A Catalog Numbers Catalog Numbers DIN Type T Rated I t (A Sec) Indicator Current Clearing Watts for Micro Size RMS-Amps Pre-arc at 0V Loss 170M1558D M1559D M150D M151D M15D M153D M15D M155D M15D M157D M158D M159D M1570D M1571D M157D Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages Rated Current The rated current of this fuse range has been given with copper conductors that have a current density of 1.3 A/mm (IEC 09-). For conductor cross section according to IEC 09-1, the fuses with a rated current higher than 15A must be derated. Please contact Cooper Bussmann for application assistance. Size A: 90V High Speed Fuses Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

30 Square Body DIN V/700V (IEC/UL): 0-000A 90V/700V (IEC/UL) 0-000A Specifications Description: Square body DIN 3 53 stud-mount high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac (IEC) 700Vac (UL) Amps: 0-000A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Consult Cooper Bussmann for UL Recognition/CSA Component Acceptance status. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) K ) 1) ) Rated voltage 00V ) Rated voltage 550V Dimensions (mm) Size A B B** C C** D*** E H 1* **Valid for fuses type -/110, -TN/110. ***Microswitch. 1mm = / 1 = 5.mm Type -/80, -TN/80, -/110, -TN/110. E g Arc Voltage U L This curve gives the peak arc voltage, U L, which 9 may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. 3 Power Losses E g Watts loss at rated current 1.0 is given in the electrical 0.8 Kp characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is 0. given as a function of the RMS load current, I b, in % 0.1 I b of the rated current % Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For Other Voltage Ratings in This Body Style See pages 1 (1000V) and 10 (150V/1300V) Type -KN/80, -KN/110 C A C A H H 11 D 11 D E B E B E E 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

31 Square Body DIN V/700V (IEC/UL): 0-000A Catalog Numbers Catalog Numbers -/80 -TN/80 -KN/80 -TN/110 -KN/110 Visual Type T Type K -/110 Type T Type K I t (A Sec) Watts Indicator Indicator Visual Indicator Indicator Rated Current Clearing Indicator for Micro for Micro for Micro for Micro -KN/80 Size RMS-Amps Pre-arc at 0V Loss 170M M M M M M M M M M M M M M M M M M M M M M M M M M30 170M M31 170M31 170M M M M M M M M M30 170M M31 170M31 170M M M M M M M M M30 170M M31 170M31 170M3 1* M M M M M M M M M M M M M M M M M M M M M M M30 170M M M M M M31 170M M30 170M M31 170M M3 170M M M M M M33 170M M M M M M08 170M M M M M M09 170M M M00 170M M10 170M10 170M M M01 170M M11 170M11 170M M01 170M0 170M11 170M1 170M1 170M M M03 170M M13 170M13 170M M01 170M0 170M11 170M1 170M1 170M M M05 170M M15 170M15 170M M01 170M0 170M11 170M1 170M1 170M M M07 170M M17 170M17 170M M M08 170M M18 170M18 170M M M09 170M M19 170M19 170M M M M M M M M M M M M M M M M M M M M M M M M M M M50 170M M51 170M51 170M M M M M M M M M50 170M M51 170M51 170M M M M M M M M M50 170M M51 170M51 170M M M M M M M M M M M M M M M M M M08 170M M M M M M09 170M M M00 170M M10 170M10 170M M M01 170M M11 170M11 170M M01 170M0 170M11 170M1 170M1 170M M M03 170M M13 170M13 170M M01 170M0 170M11 170M1 170M1 170M M M05 170M M15 170M15 170M M01 170M0 170M11 170M1 170M1 170M M M07 170M M17 170M17 170M M M08 170M M18 170M18 170M M M09 170M M19 170M19 170M M00 170M M10 170M M0 170M M01 170M M11 170M M1 170M Rated voltage (IEC) 00V. Rated voltage (IEC) 550V. Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see pages 130 and 131. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

32 Square Body Flush End Contact 90V/700V (IEC/UL): 0-000A 90V/700V (IEC/UL) 0-000A Specifications Description: Square body flush end contact high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 90Vac (IEC) 700Vac (UL) Amps: 0-000A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Consult Cooper Bussmann for UL Recognition / CSA Component Acceptance Status. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) K ) 1) E g ) Rated voltage 00V. ) Rated voltage 550V Arc Voltage This curve gives the peak U L 10 arc voltage, U L, which 9 may appear across the 8 fuse during its operation as a function of the applied working voltage, 7 5 E g, (rms) at a power factor of 15%. E g Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters K p I 0.1 b % For Other Voltage Ratings in This Body Style See pages 18 (1000V) and 1 (150V/1300V) Dimensions (mm) Type -B/-, -BKN/-, -G/-, -GKN/- Size A B D E F F** (in) G H 1* M UNC-B 5 ø M UNC-B 8 ø M 8-1 UNC-B 10 ø M UNC-B 10 ø30 **Valid for fuses type -G/- & -GKN/-. NB: B = 5 for: Size, A Size 3, A 1mm = / 1 = 5.mm B D E A E F H 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800) G

33 Square Body Flush End Contact 90V/700V (IEC/UL): 0-000A Catalog Numbers Catalog Numbers -BKN/- -GKN/- -B/- Type K -G/- Type K Rated I t (A Sec) Visual Indicator Visual Indicator Current Clearing Watts Indicator for Micro Indicator for Micro Size RMS-Amps Pre-arc at 0V Loss 170M M M M M M M M M M30 170M M M M31 170M M M31 170M3 170M M M M33 170M M M31 170M3 170M M M M35 170M M M31 170M3 170M M35 1* M M37 170M M M M38 170M M M M39 170M M M30 170M M M M31 170M M M M3 170M37 170M35 170M M33 170M M M M08 170M58 170M M M09 170M59 170M M M10 170M0 170M M M11 170M1 170M M M1 170M 170M51 170M M13 170M3 170M M M1 170M 170M51 170M M15 170M5 170M M M1 170M 170M51 170M M17 170M7 170M M M18 170M8 170M M M19 170M9 170M M M M M M M M M M M M50 170M M M M51 170M M M51 170M5 170M M M M53 170M M M51 170M5 170M M M M55 170M M M51 170M5 170M M M M57 170M M M M58 170M M M08 170M58 170M M M09 170M59 170M M M10 170M0 170M M M11 170M1 170M M M1 170M 170M51 170M M13 170M3 170M M M1 170M 170M51 170M M15 170M5 170M M M1 170M 170M51 170M M17 170M7 170M M M18 170M8 170M M M19 170M9 170M M M0 170M70 170M50 170M M1 170M71 170M51 170M Rated voltage (IEC) 00V. Rated voltage (IEC) 550V. Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see pages 130 and 131. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

34 Square Body US Style 90V/700V (IEC): 0-000A 90V/700V (IEC) 0-000A Specifications Description: Square body US style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac (IEC) 700Vac (UL) Amps: 0-00A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Consult Cooper Bussmann for UL Recognition/ CSA Component Acceptance status. Total Clearing I t The total clearing I t at rated 1.5 voltage and at power factor 1.0 of 15% are given in the electrical characteristics. For other voltages, the clearing I 0.5 t is found by multiplying by 0. correction factor, K, given as 0.3 a function of applied working voltage, E g, (rms). 0. Dimensions (mm) Type -FU/-, -FKE/-, FU/115-, -FKE/115 Size A B B** C1 C1** C C** D E H I 1* **Valid for fuses type -FU/115 & -FKE/115. 1mm = / 1 = 5.mm K ) 1) ) Rated voltage 00V. ) Rated voltage 550V Arc Voltage U This curve gives the peak L 10 arc voltage, U L, which 9 may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. E g 3 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Kp 0.1 I b % For Other Voltage Ratings in This Body Style See pages 150 (1000V) and 1 (150V/1300V) B A D E C1 C E I H 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

35 Square Body US style 90V/700V (IEC): 0-000A Catalog Numbers Catalog Numbers -FKE/- -FKE/115 -FU/- Type K -FU/115 Type K Rated I t (A Sec) Without Indicator Without Indicator Current Clearing Watts Indicator for Micro Indicator for Micro Size RMS-Amps Pre-arc at 0V Loss 170M M M M M M M M M M30 170M M M M31 170M M M31 170M3 170M M M M33 170M M M31 170M3 170M M M M35 170M M M31 170M3 170M M37 1* M M37 170M M M M38 170M M M M39 170M M M30 170M M M M31 170M M M M3 170M37 170M37 170M M33 170M M M M08 170M58 170M M M09 170M59 170M M M10 170M0 170M M M11 170M1 170M M M1 170M 170M71 170M M13 170M3 170M M M1 170M 170M71 170M M15 170M5 170M M M1 170M 170M71 170M M17 170M7 170M M M18 170M8 170M M M19 170M9 170M M M M M M M M M M M M50 170M M M M51 170M M M51 170M5 170M M M M53 170M M M51 170M5 170M M M M55 170M M M51 170M5 170M M M M57 170M M M M58 170M M M08 170M58 170M M M09 170M59 170M M M10 170M0 170M M M11 170M1 170M M M1 170M 170M71 170M M13 170M3 170M M M1 170M 170M71 170M M15 170M5 170M M M1 170M 170M71 170M M17 170M7 170M M M18 170M8 170M M M19 170M9 170M M M0 170M70 170M70 170M M1 170M71 170M71 170M Rated voltage (IEC) 00V. Rated voltage (IEC) 550V. Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see pages 130 and 131. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

36 Square Body French Style 90V/700V (IEC/UL): A 90V/700V (IEC/UL) A Specifications Description: Square body French style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac (IEC) 700Vac (UL) Amps: A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total Clearing I t 1.5 The total clearing I t at K rated voltage and at power 1.0 factor of 15% are given in the electrical characteristics. For other 0.5 voltages, the clearing I t is 0. found by multiplying by 0.3 correction factor, K, given as a function of applied 0. E g working voltage, E g, (rms) Arc Voltage U This curve gives the peak L 10 arc voltage, U L, which 9 may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. E g 3 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Kp 0.1 I b % Dimensions (mm) Type -E/-, -EKN/- Size A B C D E H I J 1* mm = / 1 = 5.mm C A H I J E D B E 18 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

37 Square Body French Style 90V/700V (IEC/UL): A Catalog Numbers Catalog Numbers -E/ -EKN/- Type T Type K Rated It (A Sec) Indicator Indicator Current Clearing Watts For Micro for Micro Size RMS-Amps Pre-arc at 0V Loss 170M M M M M M M M M M M M M M M M335 1* M M M M M M M M339 A 00 A M M M M M M M M M M M M M31 170M M M M31 170M M M M31 170M M M M M M M M M M M M M M M M M M M M M x10 170M531 1x10 170M M M358 Prospective Current 500 In Amperes RMS Virtual Pre-Arcing Time In Seconds 00A 50A 500A 550A 30A 700A 800A 900A 1000A 1100A 150A 170M M M M M M M31 170M M M M31 170M M M M31 170M M M M M Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see pages 130 and 131. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

38 Square Body Size 1*, 1 90V/700V (IEC/UL): 0-000A Size 1* 0-30A: 90V Size A: 90V 10 00A 50A 315A 350A 00A 50A 500A 550A 30A 700A 800A 900A 10 A A Virtual Pre-Arcing Time In Seconds x10 1x Prospective Current In Amps RMS Peak Let-Through Current B 550A 30A 50A 500A 350A 00A 50A 315A 00A 10A 100A 15A 3A 80A 50A 0A Peak Let-Through Current B 900A 700A 800A 550A 30A 50A 500A 350A 00A 315A 50A 00A A A x10 1x Prospective Short-Circuit Current Symmetrical RMS x10 1x amp fuse is derated to 550V (IEC). Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

39 Square Body Size, 3 90V/700V (IEC/UL): 0-000A Size A: 90V Size A: 90V 10 00A 50A 500A 550A 30A 700A 800A 900A 1000A 1100A 150A A 550A 30A 700A 800A 900A 1000A 1100A 150A 100A 1500A 100A 1800A 000A A A A A Virtual Pre-Arcing Time In Seconds Virtual Pre-Arcing Time In Seconds High Speed Fuses x10 1x Prospective Current In Amps RMS 1x10 1x Prospective Current In Amps RMS 10 B 10 B Peak Let-Through Current A 1000A 1100A 800A 900A 30A 700A 500A 550A 00A 50A Peak Let-Through Current A 000A 1500A 150A 100A 100A 1000A 1100A 800A 900A 30A 700A 500A 550A A A x 1x Prospective Short-Circuit Current Symmetrical RMS x 1x Prospective Short-Circuit Current Symmetrical RMS 1800A fuse is derated to 00V (IEC). 000A fuse is derated to 550V (IEC). Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

40 Square Body DIN V/700V (IEC/UL): A 90V/700V (IEC/UL) A Specifications Description: Square body DIN 3 0 blade style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac (IEC) 700Vac (UL) Amps: A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For Full Range Fuses in This Body Style See page 10 Dimensions (mm) Type DIN 1*, DIN, DIN 3 Size A B D E F H 1* mm = / 1 = 5.mm A Indicator H D F B E 13 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

41 Square Body DIN V/700V (IEC/UL): 0-00A Catalog Numbers Catalog Numbers DIN Type T Rated I t (A Sec) Indicator Current Clearing Watts for Micro Size RMS-Amps Pre-arc at 0V Loss 170M3808D M3809D M3810D M3811D M381D M3813D M381D M3815D M381D 1* M3817D M3818D M3819D M83D M8D M85D M8D M87D M5808D M5809D M5810D M5811D M581D M5813D M581D M580D M581D M5817D M808D M809D M810D M811D M81D M813D M81D M89D M855D M8555D M855D M8557D Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see page 13. Size 1* 0-30A: 90V High Speed Fuses Rated Current The rated current of this fuse range has been given with copper conductors that have a current density of 1.3 A/mm (IEC 09-). For conductor cross section according to IEC 09-1, the fuses must be derated. Please contact Cooper Bussmann for application assistance. Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

42 Square Body DIN V/700V (IEC/UL): A Size A: 90V Size A: 90V Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

43 Square Body Flush End Contact 90/700V (IEC/UL): A 90V (IEC) A Specifications Description: Square body flush end contact high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 90Vac Amps: A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) K 1) E g ) Rated voltage 500V Arc Voltage This curve gives the peak U L 10 arc voltage, U L, which 9 may appear across the 8 fuse during its operation as a function of the applied working voltage, 7 5 E g, (rms) at a power factor of 15%. E g Power Losses Watts loss at rated 1.0 current is given in the 0.8 K p electrical characteristics. 0. The curve allows the 0.5 calculation of the power 0. losses at load currents 0.3 lower than the rated current. The correction 0. factor, K p, is given as a function of the RMS load current, I b, in % of the 0.1 I b rated current % Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability High Speed Fuses Dimensions (mm) Type B/-, BKN/-, G/-, GKN/- Size F (in) G B M10 10 deep 33 G 1-13 UNC-B 10 deep 38 1mm = / 1 = 5.mm Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For Other Voltage Ratings in This Body Style See pages 15 (1000V) and 18 (150V) F Ø 105 G Ø Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

44 Square Body Flush End Contact 90V (IEC): A Catalog Numbers Catalog Numbers -BKN/- -GKN/- -B/- Type K -G/- Type K Rated Current RMS I t (A Sec) Watts Loss Visual Indicator Visual Indicator Norm. Liquid Clearing Norm. Liquid Indicator for Micro Indicator for Micro Size Cool. Cool. Pre-arc at 0V Cool. Cool. 170M M M M M M M M M M M M M M M M M70 170M M M M M M M M70 170M M M M M M M M70 170M M M Rated voltage (IEC) 500V. Watts loss provided at rated current. Liquid Cool. = Liquid cooling. Temperature on the terminals not to exceed 0 C. Microswitch indicator ordered separately. See accessories on pages Size A: 90V 1000A 150A 100A 100A 000A 00A 500A 3000A 3500A 000A B Virtual Pre-Arcing Time In Seconds A A Peak Let-Through Current A 000A 3500A 500A 3000A 000A 00A 100A 100A 1000A 150A x 1x Prospective Short-Circuit Current Symmetrical RMS 000A fuse is derated to 500V (IEC) x10 1x Prospective Current in Amps RMS 13 Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

45 Square Body Flush End Contact Size 3, 0V (IEC): A 0V (IEC) A Specifications Description: High speed square body fuses, for the protection of the power rectifier section of the equipment. Dimensions: See dimensions illustration. Ratings: Volts: 0Vac Amps: A IR: 300kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total clearing I t Arc Voltage Size 3 Size This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses High Speed Fuses Size 3 Size The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Size 3 Size Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Low watts loss Superior cycling capability Typical Applications Power converters/rectifiers Reduced voltage starters For Other Voltage Ratings in This Body Style See pages 157 (1000V) and 171 (150V) Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

46 Square Body Flush End Contact Size 3, 0V (IEC): A Catalogue Number -BU/55 -BKE/55 -BKN/55 -GU/55 -GKE/55 -GKN/55 Rated Rated I t (A Sec) Watt Fuse Visual Type K Type K Visual Type K Indicator Indicator (V) RMS-Amp Pre-arc at 0V (W) Type K Voltage Current Clearing Loss Size Indicator Indicator Indicator Indicator 170M M M M M M , , M M M M M M ,000 35, M80 170M M M90 170M90 170M ,000 1,050, M81 170M M M91 170M91 170M ,000 1,350, M8 170M90 170M88 170M9 170M9 170M ,000 1,50, M83 170M M M93 170M93 170M ,000,150, M8 170M90 170M88 170M9 170M9 170M ,000 3,050, M85 170M M M95 170M95 170M ,000,00, M8 170M90 170M88 170M9 170M9 170M ,000 5,00, M87 170M M M97 170M97 170M ,50,000 8,350, M88 170M M M98 170M98 170M ,50,000 15,500, M89 170M M M99 170M99 170M ,50,000 1,000, M M M M M M ,000,000 7,500, Data Sheet: 170K3 Catalog Numbers: Fuse Size -BU/0 without Indicator Catalogue Number -BKN/0 Type K Indicator -GU/0 without Indicator -GKN/0 Type K Indicator Rated Voltage (V) Rated Current RMS-Amp I t (A Sec) Clearing at Pre-arc 0V 170M M M M M M M M M M M M M M M M M71 170M71 170M70 170M M M M M M71 170M71 170M70 170M M M M M M71 170M71 170M70 170M M M M M M M M M M M M M Watts Loss (W) A 500V Data Sheet: 170K33 Size Dimensions (mm): Type BU/55, -BKE/55, -BKN/55, -GU/55, -GKE/55, -GKN/55 Size 3 Dimensions (mm): Type BU/55, -BKE/55, -BKN/55, -GU/55, -GKE/55, -GKN/55 Size 3G 3B A x M10 3 /8 1UNC-B Size BKN GKN A x3 M1 x3 1 / 1UNC-B 138 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

47 Square Body Flush End Contact Size 3, 0V (IEC): A Size A: 0V Size A: 0V High Speed Fuses Prospective Current in Amps RMS Prospective Current in Amps RMS Data Sheet: Available upon request Data Sheet: Available upon request Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

48 Square Body DIN V (IEC): A Class gr Full Range Fuses 90V (IEC) A Specifications Description: Square body DIN 3 0 blade style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac (IEC) Amps: A IR: 300kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Electrical Characteristics Total clearing I t 1,0 The total clearing I t at rated voltage and at power 0,5 factor of 15% are given in 0, the electrical 0,3 characteristics. For other voltages, the clearing I t is 0, found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). 1,5 K Eg Arc Voltage 3 U,5 L This curve gives the peak arc voltage, U L, 1,8 1, which may appear 1, 1, across the fuse during its operation as a 8 function of the applied 7 working voltage E g, 5 (rms) at a power factor of 15%. 3 Eg Power Losses Watts loss at rated current 1,0 K p 0,8 is given in the electrical 0,7 characteristics. The curve allows the calculation of the power losses at load currents lower than the 0, 0,5 0, 0,3 rated current. The 0, correction factor, K p, is 0,15 given as a function of the RMS load current, I b, in % Ib 0,1 of the rated current % Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For Operating Class ar Fuses in This Body Style See page 13 Dimensions (mm) Type DIN 00, DIN 1, DIN, DIN 3 Size A B Max D Max E F Min H mm = = 5. mm 10 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

49 Square Body DIN V (IEC): A Class gr Full Range Fuses Catalog Numbers Catalog Numbers Type T RMS I t (A Sec) Indicator Amp Clearing Watts For Micro Size Rating* Pre-arc at 00V Loss 170M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M *The RMS amp rating of this fuse range is given with open fuse bases connected to copper conductors according to IEC 09, Part 1, table 10. When used in enclosed fuse bases/ disconnects, derating factors have to be observed. Please contact Cooper Bussmann for application assistance. Watts loss provided at rated current. Microswitch ordered separately. See accessories on page For fuse curves see pages 1 and 13. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

50 Square Body Size 00, 1 90V (IEC): A Class gr Full Range Fuses Size A: 90V Size A: 90V Virtual Pre-arcing Time In Seconds 10 1s A 3A 0A 10A 0A 5A 1A 10A 100A 3A 15A 80A Virtual Pre-arcing Time In Seconds 10 1s A 15A 80A 50A 10A 100A 3A 50A 350A 00A 315A Prospective Current In Amp RMS 10-5x x10 Prospective Current In Amp RMS Peak Let-Through Current In Amperes A 15A 100A 80A 3A 50A 0A 3A 5A 0A 1A 10A Peak Let-Through Current In Amperes A 350A 315A 50A 00A 10A 15A 100A 80A 3A 50A x Amp 10 5 Prospective Short-Circuit Current Symmetrical RMS x Amp 10 5 Prospective Short-Circuit Current Symmetrical RMS 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

51 Square Body Size, 3 90V (IEC): A Class gr Full Range Fuses Size 00-30A: 90V Size A: 90V Virtual Pre-arcing Time In Seconds 10 1s A 50A 00A 315A 350A 550A 50A 30A 500A Virtual Pre-arcing Time In Seconds 10 1s A 800A 30A 500A 00A 50A 700A 550A High Speed Fuses Prospective Current In Amp RMS Prospective Current In Amp RMS Peak Let-Through Current In Amperes A 550A 500A 50A 100A 350A 315A 50A 00A Peak Let-Through Current In Amperes A 700A 30A 550A 00A 50A 00A 350A x Amp 10 Prospective Short-Circuit Current Symmetrical RMS x Amp 10 Prospective Short-Circuit Current Symmetrical RMS Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

52 Square Body DIN V (IEC): 0-315A 1000V (IEC) 0-315A Specifications Description: Square body DIN 3 53 stud-mount high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 1000Vac (0-50A) 900Vac (315A) Amps: 0-315A IR: 150kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multi-plying by correction factor, K, given as a function of applied working voltage, E g, (rms). 1,5 1,0 0,5 0, 0,3 0, K *Rated voltage 900V Dimensions (mm) Type 00TN/80 00/80 Size Max A B C D Max E F G H 00/ TN/ mm = / 1 = 5.mm * Eg Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters 3,5 1,8 1, 1, 1, U L Eg ,0 K p 0,8 0,7 0, 0,5 0, 0,3 0, 0,15 Ib 0, % For Other Voltage Ratings in This Body Style See page 117 (90V/700V) 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

53 315A * High Speed Fuses Square Body DIN V (IEC): 0-315A Catalog Numbers Catalog Numbers 00/80 00TN/80 I t (A Sec) Visual Type T Rated Clearing Indicator for Indicator for Rated Current at Rated Watts Micro Micro Size Voltage RMS Amps Pre-arc Voltage Loss 170M80 170M M M M80 170M M M M80 170M M M M M M M M M M M M81 170M M M M81 170M M M Watts loss provided at rated current. Microswitch ordered separately. See accessories on page Size A: 1000V Virtual Pre-arcing Time In Seconds s A 5A 0A 3A 35A 50A 3A 80A 100A 15A 10A 00A 50A High Speed Fuses Prospective Current In Amp RMS Peak Let-Through Current In Amperes A 50A 00A 10A 15A 100A 80A 3A 50A 0A 35A 3A 5A 0A x Amp 10 5 Prospective Short-Circuit Current symmetrical Symmetrical RMS RMS * 315A fuse is derated to 900V Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

54 Square Body DIN V (IEC): A 1000V (IEC) A Specifications Description: Square body mount high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 1000Vac. Amps: A IR: 150kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). 1,5 1,0 0,5 0, 0,3 0, K Eg *Rated voltage 900V Dimensions (mm) Type KN/110 Size A B C Max D1 E G H I 1*KN/ KN/ KN/ KN/ Type TN/110 Size A B C Max D E G H I 1*TN/ TN/ TN/ TN/ mm = / 1 = 5.mm Type-KN/110 * Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Type-TN/110 3,5 1,8 1, 1, 1, U L Eg ,0 K p 0,8 0,7 0, 0,5 0, 0,3 0, 0,15 0,1 Ib % For Other Voltage Ratings in This Body Style See pages 1 (90V/700V) and 10 (150V/1300V) 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

55 Square Body DIN V (IEC): A Catalog Numbers Catalog Numbers -KN/110 -TN/110 Rated I t (A Sec) Type K Type T Current Clearing Indicator for Indicator for Rated RMS at Rated Watts Micro Micro Size Voltage Amps Pre-arc Voltage Loss 170M M M39 170M M M M M M M M M398 1* M M M M M M M M M M M95 170M M9 170M M97 170M M98 170M M99 170M M M M M M97 170M M M M97 170M M59 170M M M M M M M M M M M M M M M M M M M M81 170M M M M81 170M M M M M M M M80 170M M81 170M M8 170M M83 170M M8 170M M85 170M M8 170M M87 170M Watts loss provided at rated current. Microswitch ordered separately. See accessories on page For fuse curves see pages 15 and 153. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

56 Square Body Flush End Contact 1000V (IEC): A 1000V (IEC) A Specifications Description: Square body flush end contact high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 1000Vac. Amps: A IR: 150kA (Est. 300kA) RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). 1,5 1,0 0,5 0, 0,3 0, K Eg *Rated voltage 900V * Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters 3,5 1,8 1, 1, 1, U L Eg ,0 K p 0,8 0,7 0, 0,5 0, 0,3 0, 0,15 0,1 Ib % Dimensions (mm) Type BKN/- and GKN/- Size A B Max D E F F* (in) Min G H 1*BKN/75+GKN/ M UNC-B 5 ø17.5 1BKN/75+GKN/ M UNC-B 8 ø0 BKN/75+GKN/ M 8 1 UNC-B 10 ø 3BKN/75+GKN/ M UNC-B 10 ø30 3BKN/90+GKN/ M UNC-B 10 ø30 * Valid for fuses type GKN/-. 1mm = / 1 = 5.mm For Other Voltage Ratings in This Body Style See pages 1 (90V/700V) and 1 (150V/1300V) 18 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

57 Square Body Flush End Contact 1000V (IEC): A Catalog Numbers Catalog Numbers -BKN/- -GKN/- I t (A Sec) Type K Type K Rated Clearing Indicator for Indicator for Rated Current at Rated Watts Micro Micro Size Voltage RMS-Amps Pre-arc Voltage Loss 170M M M M M M M M M M M M39 1* M M M M M M M M M M M M M95 170M M M M95 170M M M M95 170M M M M M M M M90 170M M M M M M M M M M M M M M M M M M M M M M M M M M80 170M M M M80 170M M M M80 170M M M M M M M M M M M M81** 170M851** M813** 170M8513** **Overall length is 90mm, for all other fuses the overall length is 75mm. Watts loss provided at rated current. Microswitch ordered separately. See accessories on page For fuse curves see pages 15 and 153. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

58 Square Body US style 1000V (IEC): A 1000V (IEC) A Specifications Description: Square body US style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 1000Vac. Amps: A IR: 150kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). 1,5 1,0 0,5 0, 0,3 0, K Eg *Rated voltage 900V Dimensions (mm) Type FKE/115 Size B C1 C D E H I 1*FKE/ FKE/ FKE/ FKE/ mm = / 1 = 5.mm * Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters 3,5 1,8 1, 1, 1, U L Eg ,0 K p 0,8 0,7 0, 0,5 0, 0,3 0, 0,15 Ib 0, % For Other Voltage Ratings in This Body Style See pages 1 (90V/700V) and 1 (150V/1300) 150 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

59 Square Body US style 1000V (IEC): A Catalog Numbers Catalog Numbers -FKE/115 Type K Rated I t (A Sec) Indicator for Current Clearing Watts Micro Size RMS-Amps Pre-arc at 1000V Loss 170M M M M M M353 1* M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M85* * 185 * Rated voltage 900V. Watts loss provided at rated current. Microswitch ordered separately. See accessories on pages For fuse curves see pages 15 and 153. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

60 Square Body Size 1*, V (IEC): A Size 1* 50-00A: 1000V Size A: 1000V Virtual Pre-arcing Time In Seconds 1s A 80A 50A 3A 350A 50A 10A 100A 00A 315A 00A Virtual Pre-arcing Time In Seconds 10 1s A 00A 50A 315A 350A 30A 500A 00A 550A 50A x x10 Prospective Current In Amp RMS Prospective Current In Amp RMS Peak Let-Through Current In Amperes 10 00A 350A 315A 50A 00A 10A 100A 15A 80A 30A 50A Peak Let-Through Current In Amperes 10 30A 550A 500A 50A 00A 350A 315A 00A 50A 10A x Amp 10 Prospective Short-Circuit Current Symmetrical RMS x Amp 10 Prospective Short-Circuit Current Symmetrical RMS 15 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

61 Square Body Size, V (IEC): A Size A: 1000V Size A: 1000V Virtual Pre-arcing Time In Seconds 10 1s A 315A 50A 350A 00A 700A 550A 500A 800A 30A Virtual Pre-arcing Time In Seconds 10 1s A 350A 00A 550A 50A 500A 900A 700A 30A 800A 100A* 1100A 150A 1000A High Speed Fuses Prospective Current In Amp RMS Prospective Current In Amp RMS Peak Let-Through Current In Amperes A 700A 30A 550A 500A 50A 00A 315A 350A 50A Peak Let-Through Current In Amperes A* 1100A 150A 1000A 900A 800A 700A 30A 550A 500A 50A 00A 350A 315A x Amp 10 Prospective Short-Circuit Current Symmetrical RMS x Amp 10 Prospective Short-Circuit Current Symmetrical RMS * 100A fuses are derated to 900V Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

62 Square Body Flush End Contact Size 1000V (IEC): A 1000V (IEC) A Specifications Description: Square body DIN 3 0 blade style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 1000Vac (IEC) Amps: A IR: 15kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Electrical Characteristics Total clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For Other Voltage Ratings in This Body Style See pages 135 (90V/700V) and 18 (150V) Catalog Numbers Catalog Number -BKN/95 -SBKN/90 Rated Rated I t (A Sec) Watt Fuse Type K Type K Voltage Current Clearing Loss Size Indicator Indicator (V) RMS-Amp Pre-arc at 1000V (W) 170M M M73 170M M M M M M M M70 170M M M Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

63 Square Body Flush End Contact Size 1000V (IEC): A Flush End Contact - Size 1000V : A Dimensions (mm): Type BKN/95 High Speed Fuses Type SBKN/95 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

64 Square Body Flush End Contact Size 1000V (IEC): A Size A: 0V Prospective Current in Amps RMS Data Sheet: Available upon request 15 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

65 Square Body Flush End Contact Size 1000V (IEC): A 1000V (IEC) A Specifications Description: High speed square body fuses, for the protection of the power rectifier section of the equipment. Dimensions: See dimensions illustration. Ratings: Volts: 1000Vac Amps: A IR: 300kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Total clearing I t Arc Voltage A A This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses High Speed Fuses A A The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) A A Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Low watts loss Superior cycling capability Typical Applications Power converters/rectifiers Reduced voltage starters For Other Voltage Ratings in This Body Style See pages 137 (0V) and 171 (150V) Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

66 Square Body Flush End Contact Size 1000V (IEC): A Catalog Numbers Fuse Size Cat. Number -BKN/85 Type K Indicator Rated Voltage (V) Rated Current RMS-Amp I t (A Sec) Clearing at Watt Loss (W) Pre-arc 1000V 170M M M M M M M M Data Sheet: 170K750, 170K851 Dimensions (mm): 158 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

67 Square Body Flush End Contact Size 1000V (IEC): A Size A: 1000V Size A: 1000V High Speed Fuses Prospective Current in Amps RMS Prospective Current in Amps RMS Data Sheet: Available upon request Data Sheet: Available upon request Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

68 Square Body DIN V/1300V (IEC/UL): A 150V/1300V (IEC/UL) A Specifications Description: Square body DIN 3 53 stud-mount high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 150Vac (IEC) 1300Vac (UL) Amps: A IR: 100kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Consult Cooper Bussmann for UL Recognition/CSA Component Acceptance status. Total Clearing I t The total clearing I t at rated voltage and at K power factor of 15% are 0.5 given in the electrical 0. characteristics. For other 0.3 voltages, the clearing I t is found by multiplying by 0. correction factor, K, given as a function of E g 100 applied working voltage, Dashed lines ( ) apply to the following amperages:. E g, (rms). Size Amps. 1* 00A A A A Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters U L 5 E 3 g Kp I b % For Other Voltage Ratings in This Body Style See pages 1 (90V/700V) and 1 (1000V) Dimensions (mm) Type -/110, -TN/110 Size A B D** E H 1* **Microswitch. 1mm = / 1 = 5.mm 108 A Dimensions (mm) Type -KN/110 Size A B D E H 1* mm = / 1 = 5.mm C A H D E E 11 B D E 11 B H E 10 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

69 Square Body DIN V/1300V (IEC/UL): A Catalog Numbers Catalog Numbers -TN/110 -KN/110 -/110 Type T Type K Rated I t (A Sec) Visual Indicator Indicator Current Clearing Clearing Watts Indicator for Micro for Micro Size RMS-Amps Pre-arc at 1000V at 150V Loss 170M M M M M M M M M M M M M31 170M M M M M33 1* M31 170M M M M M M31 170M M M M M M M M M M M M M M M10 170M M M11 170M M M1 170M19 170M M13 170M M M1 170M19 170M M15 170M M M1 170M19 170M M17 170M M M M M M M M M M M M M M M51 170M M M M M M51 170M M M M M M51 170M M M M M M M M M M M M M M M M M M M M M10 170M M M11 170M M M1 170M19 170M M13 170M M M1 170M19 170M M15 170M M M1 170M19 170M M17 170M M M18 170M M M19 170M M M M00 170M M M01 170M Rated voltage (IEC) 1100V. Rated voltage (IEC) 150V. Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see pages 1 and 17. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

70 Square Body Flush End Contact 150V/1300V (IEC/UL): A 150V/1300V (IEC/UL) A Specifications Description: Square body flush end contact high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 150Vac (IEC) 1300Vac (UL) Amps: A IR: 100kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Consult Cooper Bussmann for UL Recognition/CSA Component Acceptance status. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Dimensions (mm) Type -BKN/-, -GKN/- Size Type A B D E F F** (in) G H 1* BKN + GKN/ M UNC-B 5 Ø17 1* BKN/ M8 5 Ø17 1 BKN + GKN/ M UNC-B 8 Ø0 1 BKN/ M8 8 Ø0 BKN + GKN/ M 8-1 UNC-B 10 Ø BKN/ M10 10 Ø BKN + GKN/ M 8-1 UNC-B 10 Ø 3 BKN + GKN/ M UNC-B 10 Ø30 3 BKN/ M1 10 Ø30 3 BKN + GKN/ M UNC-B 10 Ø30 **Valid for fuses type -GKN/-. 1mm = / 1 = 5.mm K 0. E g Dashed lines ( ) apply to the following amperages:. Size Amps. 1* 00A A A A D E Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters B A U L 5 E 3 g Kp I b % For Other Voltage Ratings in This Body Style See pages 1 (90V/700V) and 18 (1000V) E F H G 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

71 Square Body Flush End Contact 150V/1300V (IEC/UL): A Catalog Numbers Catalog Numbers -BKN/75 -BKN/80 -BKN/90 -GKN/75 -GKN/90 Rated Type K Type K Type K Type K Type K Current I t (A Sec) Indicator Indicator Indicator Indicator Indicator RMS- Clearing Clearing Watts for Micro for Micro for Micro for Micro for Micro Size Amps Pre-arc at 1000V at 150V Loss 170M M M M M M M M30 170M M M31 170M M M3 170M M M33 170M393 1* M M3 170M M M35 170M M M3 170M M M37 170M M M M38 170M M M39 170M M M0 170M M M1 170M M39 170M 170M M M3 170M M39 170M 170M M M5 170M M39 170M 170M M M7 170M M M M M M M M M50 170M M M51 170M M M5 170M M M53 170M M M5 170M59 170M M M M55 170M M M M M5 170M59 170M M M M57 170M M M M M58 170M M M M M M M M M M M M M M30 170M50 170M M31 170M51 170M M3 170M5 170M M33 170M53 170M M3 170M5 170M9 170M59 170M M35 170M55 170M95 170M M M3 170M5 170M9 170M59 170M M37 170M57 170M97 170M M M38 170M58 170M98 170M M M39 170M59 170M99 170M M M M M M Rated voltage (IEC) 1100V. Rated voltage (IEC) 1000V. Rated voltage (IEC) 150V. Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see pages 1 and 17. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

72 Square Body US Style 150V/1300V (IEC/UL): A 150V/1300V (IEC/UL) A Specifications Description: Square body US style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 150Vac (IEC) 1300Vac (UL) Amps: A IR: 100kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Consult Cooper Bussmann for UL Recognition/CSA Component Acceptance status. Electrical Characteristics Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) Dimensions (mm) Type -FU/115, -FKE/115 Size B C1 C D E H I 1* mm = / 1 = 5.mm K 0. E g Dashed lines ( ) apply to the following amperages:. Size Amps. 1* 00A A A B Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters U L Kp E g I b % A For Other Voltage Ratings in This Body Style See pages 1 (90V/700V) and 150 (1000V) A D E C1 C E I H 1 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

73 Square Body US Style 150V/1300V (IEC/UL): A Catalog Numbers Catalog Numbers -FKE/115 -FU/115 Type K Rated I t (A Sec) Without Indicator Current Clearing Clearing Watts Indicator for Micro Size RMS-Amps Pre-arc at 1000V at 150V Loss 170M M M M M M M M M39 170M M M373 1* M39 170M M M M39 170M M M M88 170M M89 170M M90 170M M91 170M M9 170M M93 170M M9 170M M95 170M M9 170M M97 170M M M M M M M M M M59 170M M M M59 170M M M M59 170M M M M M M M M M M88 170M M89 170M M90 170M M91 170M M9 170M M93 170M M9 170M M95 170M M9 170M M97 170M M98 170M M99 170M M M M M Rated voltage (IEC) Rated voltage (IEC) 1000V. UL Recognition at 1000V. Watts loss provided at rated current. Microswitch indicator ordered separately. See accessories on pages For fuse curves see pages 1 and 17. High Speed Fuses Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

74 Square Body Size 1*, 1 150V/1300V (IEC/UL): A Size 1* 50-00A:150V Size A: 150V 10 10A 00A 50A 315A 350A 00A 50A 500A 550A 30A 10 A Virtual Pre-Arcing Time In Seconds A x10 1x Prospective Current In Amp RMS Peak Let-Through Current B 00A 350A 315A 50A 00A 10A 15A 100A 80A 3A 50A Peak Let-Through In Amperes B 30A 500A 550A 00A 50A 315A 350A 50A 00A 10A A A x10 1x Prospective Short-Circuit Current Symmetrical RMS x10 1x Prospective Short-Circuit Current Symmetrical RMS 30A fuse is derated to 1100V (IEC). Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

75 Square Body Size, 3 150V/1300V (IEC/UL): A Size A: 150V Size A: 150V 10 50A 80A 315A 350A 00A 50A 500A 550A 30A 700A 800A 900A 1000A 10 A Virtual Pre-Arcing Time In Seconds A High Speed Fuses x10 1x Prospective Current In Amp RMS 10 5 B 1000A 800A 900A 30A 700A 500A 550A 00A 50A 315A 350A 50A 80A 10 5 B 100A 150A 1000A 1100A 800A 900A 30A 700A 500A 550A 00A 50A 315A 350A Peak Let-Through Current 10 Peak Let-Through Current 10 A A x10 1x Prospective Short-Circuit Current Symmetrical RMS x10 1x Prospective Short-Circuit Current Symmetrical RMS A fuses are derated to 1100V (IEC) A fuses are derated to 1100V (IEC). Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

76 Square Body Flush End Contact Size 150V (IEC): A 150V (IEC) A Specifications Description: High speed square body fuses, for the protection of the power rectifier section of the equipment. Dimensions: See dimensions illustration. Ratings: Volts: 150Vac (IEC) Amps: A IR: 15kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Electrical Characteristics Total clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For Other Voltage Ratings in This Body Style See pages 135 (90V/700V) and 15 (1000V) Catalog Numbers Catalog Number -BKN/105 -SBKN/105 Rated Rated I t (A Sec) Watt Fuse Type K Type K Voltage Current Clearing Loss Size Indicator Indicator (V) RMS-Amp Pre-arc at 150V (W) 170M M M M M77 170M M M M M M M M M M M Data Sheet: 170K0, 170K 18 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

77 Square Body Flush End Contact Size 150V (IEC): A Flush End Contact - Size 150V (IEC) / A Dimensions (mm): Type BKN/105 High Speed Fuses 10. Type SBKN/105 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

78 Square Body Flush End Contact Size 150V (IEC): A Size A: 150V Size A: 150V Prospective Current in Amps RMS Prospective Current in Amps RMS Data Sheet: Available upon request Data Sheet: Available upon request 170 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

79 Square Body Flush End Contact Size 3 150V (IEC/UL): A 150V (IEC) A Specifications Description: High speed square body fuses, for the protection of the power rectifier section of the equipment. Dimensions: See dimensions illustration. Ratings: Volts: 150Vac (IEC) Amps: A IR: 15kA RMS Sym. Agency Information: CE, Designed and tested to IEC 09: Part, UL Recognized. Electrical Characteristics Total clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters High Speed Fuses Catalog Numbers Fuse Size -BU/75 without Indicator -BKE/75 Type K Indicator Catalog Number -BKN/75 Type K Indicator -BU/80 without Indicator -BKE/80 Type K Indicator For Other Voltage Ratings in This Body Style See pages 137 (0V) and 157 (1000V) -BKN/80 Type K Indicator Rated Voltage (V) Rated Current RMS-Amp I t (A Sec) Clearing at Pre-arc 150V 170M M M M77 170M79 170M M M M M M M M M M M M M M M M M M M M78 170M80 170M M M M M78 170M80 170M M M M M81 170M83 170M M M M Watts Loss (W) A 1000V Data Sheet: 170K38 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

80 Square Body Flush End Contact Size 3 150V (IEC/UL): A Flush End Contact - Size 3 150V (IEC) / A Size A: 150V Dimensions (mm): Prospective Current in Amps RMS 17 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

81 Square Body Flush End Contact Size V-000V: A 1000V (IEC) A Specifications Description: High speed square body fuses, for the protection or isolation for components such as diodes, silicon controlled rectifiers (SCRs), Gate torn-off Thyristors (GTOs) and IGBTs. Dimensions: See dimensions illustration. Ratings: Volts: Vac (IEC) Amps: A IR: 300kA RMS Sym. estimated, 197kA tested Agency Information: Consult Cooper Bussmann. [email protected] High Speed Fuses Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications AC and DC drives High power converters/rectifiers Diemensions - mm (in) This dimension drawing is an example of the range of size 5 fuses available. Contact Cooper Bussmann for available parts and technical information. For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

82 Square Body DC Fuses 750Vdc: 3-500A 750Vdc 3-500A Specifications Description: High speed fuses, for the protection of DC circuits in equipment. Dimensions: See dimensions illustration. Ratings: Volts: 750Vdc Amps: 3-500A IR: 750Vdc IR: 100kA, L/R = 100 ms. 1000Vdc IR: 100kA, L/R = 0 ms Agency Information: Consult Cooper Bussmann. Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Catalog Numbers Fuse Size Catalog Numbers -BK/130 -EK/- Rated Voltage (Vdc) Rated Current RMS-Amp Watt Loss (W) 170E E E E * 170E E E E E E E E E E E E E E E E E E Data Sheet: Size 1*: 170K30 Size 1: 170K3 Size : 170K3 Size 3: 170K3 Microswitch: 170H009, 170H307 (gold) 17 For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

83 Square Body DC Fuses 750Vdc: 3-500A Square Body DC Fuses 750Vdc / 3-500A (mm): Type BK/130 High Speed Fuses Size/Type A B D 1* BK/ BK/ BK/ BK/ Type EK/- Size/Type A B C D E F G H I J 1* EK/ EK/ EK/ EK/ For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

84 Square Body DC Fuses 750Vdc: 3-500A Square Body DC Fuse 3-10A: 750V Square Body DC Fuse 00-50A: 750V Prospective Current in Amps RMS Prospective Current in Amps RMS Data Sheet: Available upon request Data Sheet: Available upon request 17 For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

85 Square Body DC Fuses 750Vdc: 3-500A Square Body DC Fuse 50-00A: 750V Square Body DC Fuse 500A: 750V High Speed Fuses Prospective Current in Amps RMS Prospective Current in Amps RMS Data Sheet: Available upon request Data Sheet: Available upon request For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

86 Square Body DC Fuses 100Vdc: 10-0A 100Vdc 10-0A Specifications Description: High speed fuses that provides superior protection in light and heavy harsh DC traction applications as 100Vdc and below circuits, and as DC link/power converters. Dimensions: See dimensions illustration. Ratings: Volts: 100Vdc Amps: 10-0A IR: 100Vdc = 100kA L/R: 15 ms. Agency Information: Consult Cooper Bussmann. Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Catalog Numbers Fuse Type SKN / 10 Cat. Numbers -SKNB/10 Rated Rated Max I t (A 1000Vdc Watts Type K Voltage Current Loss Indicator (Vdc) RMS-Amp L/R = 15ms L/R = 5ms (W) 170F F F F F F Data Sheet: 170K550 Microswitch: 170H009, 170H307 (gold) Dimensions (mm): 178 For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

87 Square Body DC Fuses 100Vdc: 10-0A Square Body DC Fuse 10-0A: 100V High Speed Fuses Prospective Current in Amps RMS Data Sheet: Available upon request For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

88 Square Body DC fuses 000Vdc: 10-15A 000Vdc 10-15A Specifications Description: High speed fuses for the protection of DC circuits in equipment. Dimensions: See dimensions illustration. Ratings: Volts: 100Vdc Amps: 10-0A IR: 100Vdc = 100kA L/R: 15 ms. Agency Information: Consult Cooper Bussmann. Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Catalog Numbers Fuse Type Cat. Number -SKN/ Type K Indicator Rated Voltage (Vdc) Rated Current RMS-Amp Watt Loss (W) 170E E E E *SKN/ 170E E E E E Fuse Type Cat. Number -SKN/ Type K Indicator Rated Voltage (Vdc) Rated Current RMS-Amp Watt Loss (W) 170E E E E *SKN/ 170E E E E E Vdc / 10-15A Dimensions (mm): Data Sheet: 170K538 Microswitch: 170H039, 170H3030 (gold) Data Sheet: 170K900 Microswitch: 170H039, 170H3030 (gold) 180 For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

89 Square Body DC fuses 000Vdc: 10-15A Square Body DC Fuses 10-80A: 000V Square Body DC Fuses 0-15A: 000V High Speed Fuses Prospective Current in Amps RMS Prospective Current in Amps RMS Data Sheet: Available upon request Data Sheet: Available upon request For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

90 Square Body DC Fuses 000Vdc: 0-50A 000Vdc 0-50A Specifications Description: High speed fuses for the protection of DC circuits in equipment. Dimensions: See dimensions illustration. Ratings: Volts: 000Vdc Amps: 0-50A IR: 0kA L/R: 5 ms. Agency Information: Consult Cooper Bussmann. Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage E g. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Features and Benefits Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Catalog Numbers Fuse Type Cat. Numbers -SKN/39 Type K Indicator Rated Voltage (Vdc) Rated Current RMS-Amp Watts Loss (W) 170E E E E *SKN/39 170E E E E E E SKN/39 170E E E //SKN/39 170E E E For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

91 DC Fuses 000Vdc: 0-50A DC Fuses 000Vdc / 0-50A Dimensions (mm): Type 1*SKN/39 High Speed Fuses Type SKN/39 Type //SKN/39 For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

92 Square Body DC Fuses 000Vdc: 0-50A Square Body DC Fuses 0-15A: 000V Square Body DC Fuses 10-50A: 000V Prospective Current in Amps RMS Prospective Current in Amps RMS Data Sheet: Available upon request Data Sheet: Available upon request 18 For detailed information, visit the Electrical IEC section at Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

93 Square Body Fuse Accessories Indicator Systems Typower ZILOX fuses are available with three different indicator systems. 1. Visual Indicator The indicator situated in one cover plate is clearly visible as soon as the fuse has operated. The minimum voltage for operating the indicator is 0V.. Type T Indicator The indicator is situated on one cover plate with a cover plate tag to accommodate an auxiliary switch. The minimum voltage for operating the indicator is 0V. A special low voltage indicator (1.5V) is available on request. 3. Type K Indicator This indicator is situated on the fuse body. It is covered by an adapter for snap-on mounting of an auxiliary switch. The operating voltage of the indicator is 1.5V. As a matter of safety, the factory mounted adapter must not be removed from the fuse. Microswitch The Typower ZILOX fuses with either type T indicator or type K indicator can be equipped with a microswitch for remote electrical indication of fuse operations. All micro-switches have one normally open and one normally closed contact. Ratings are A, 50Vac. High Speed Fuses.3 x 0.8mm.8 x 0.5mm Indicator Microswitch Lugs Lugs Type 170H035 X T 170H03 X T 170H037 X T 170H038 X T 170H009 X K DIN 3 53 DIN 3 0 French Style Flush End US Style Size Type T Type K Type T Type K Type T Type K Type T Type K Type K H03 170H03 170H H H H H H037 1* 170H H H H03 170H H H H H H H H H03 170H H H H H H H H H03 170H H H H H H H H H03 170H03 170H H H H H H H H H009 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

94 Square Body Fuse Accessories Fuse Bases (Blocks) DIN 3 53 Fuse Bases For the Typower ZILOX fuses according to DIN 3 53, the following fuse bases are available: 170H300 Catalog Max Amp Center Number Volts Rating Distance 170H mm 170H mm 170H mm 170H mm The fuse bases rated 150A can also be used for the fuses with higher rated current if the maximum load current is derated according to the table below: Fuse Amp Max Amp Load Rating In Fuse Base Fixed Center Max Max. Fuse Fuse Base Style Volts Amp Rating Size 170H , H ,000 UL Recognized to UL H1013 Universal Fuse Bases For the Typower ZILOX fuses according to DIN 3 53, French style and North American style, the following fuse bases are available: Modular Max Max. Fuse Base Style Volts Amp Rating Data Sheet 1BS BS BS BS BH-0xxx BH-1xxx BH-xxx BH-3xxx Modular fuse bases are UL Recognized to UL 51 and meet the spacing requirements of UL 37. Contact your Cooper Bussmann sales representative for more complete ordering information. DIN 3 0 Fuse Bases Size Part Number SB00-D 1*, 1 SB1-D,3 SB-D 1BS Series Example 18 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

95 British BS 88 Fuses High Speed Fuses Introduction British BS 88 Contents Fuse Volts Amp Range Page Accessories Indicator System & Fuse Bases 195 British BS 88 Fuse Ranges Amps Vac Vdc General Information Designed and tested to: BS 88: Part IEC 9: Part UL Recognized Cooper Bussmann offers the industry s widest range of British style semiconductor fuses and accessories. Cooper Bussmann British style products use innovative arc quenching techniques and high grade materials to provide: Minimal energy let-through (I t) Excellent DC performance Good surge withstand profile British style fuses are typically found in equipment manufactured in the United Kingdom or British Commonwealth countries. However, North American manufacturers have begun to specify British style fuses particularly in UPS applications at 0V or less to take advantage of their size, performance and cost benefits. Voltage Rating All Cooper Bussmann British style fuses are tested to IEC 9: Part. This standard requires a test voltage which is 5% higher than the rated voltage. In North America, fuses are required to clear only their rated voltage. Accessories Trip-indicator fuses are available for use in parallel with the main fuse. Indicator fuses can be attached to the associated fuselink, or mounted separately in panel-mounted fuseclips. In addition, a push-on adapter and microswitch attachment are available, to provide remote indication. Fuse blocks are also available for most applications. Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

96 British BS 88 0V: -900A LCT, LET, LMT, LMMT Specifications Description: BS 88 style stud-mount fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 0Vac/150Vdc Amps: -900A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to: BS 88 Part, IEC 9 Part, UL Recognized. All fuses above have been tested at 318Vac. Consult Cooper Bussmann for specific UL Recognition status. 1. Total Clearing I t K 1. The total clearing I t at rated 1. voltage and at power factor 1.0 of 15% are given in the electrical characteristics. For 0.8 other voltages, the clearing 0. 1) I t is found by multiplying by 0. correction factor, K, given as 0. a function of applied working ) E g voltage, E g, (rms) Dimensions (mm) Fig. 1: LCT mm = / 1 = 5.mm Fig. 3: LMT Fig. : LET ) LCT ) LET, LMT, LMMT Fig. : LMMT Arc Voltage 750 This curve gives the peak arc voltage, U L, which may appear across the 500 fuse during its operation as a function of the applied working voltage, 50 E g, (rms) at a power factor of 15%. Power Losses ) LCT Watts loss at rated current ) LET, LMT, LMMT is given in the electrical 1.0 Kp characteristics. The curve 0.8 allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. 0.1 I b Catalog Numbers % Rated I t (A Sec) Catalog Current Clearing Clearing Watts Numbers Type RMS-Amps Pre-arc at 10V at 0V Loss LCT LCT LCT LCT LCT LCT LET LET LET LET LET LET LET LET LET LET LETa LMT LMT LMT LMT LMT LMT LMT LMT LMMT LMMT LMMT LMMT LMMT LMMT LMMT Watts loss provided at rated current. Note: 7LET, 10LET, 1LET and 1LET are available for replacement purposes on existing equipment. See accessories on page 195. U L 1) ) E g Data Sheet: Indicator (Optional) Features and Benefits Excellent cycling capability Excellent DC performance Low arc voltage and low energy let-through (I t) Typical Applications DC common bus AC and DC drives Power converters/rectifiers Reduced voltage starters Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

97 British BS 88 0V: -900A LCT -0A: 0V LET 5-180A: 0V Virtual Pre-Arcing Time In Seconds LCT 10LCT 1LCT 1LCT 0LCT Virtual Pre-Arcing Time In Seconds LET 3LET 35LET 50LET 3LET 80LET 100LET 15LET 10LET 180LETa High Speed Fuses Prospective Current In Amps RMS Prospective Current In Amps RMS Data Sheet: Data Sheet: Peak Let-Through Current LMMT 800LMMT 710LMMT 30LMMT 50LMT 00 & 500LMMT 355LMT 315LMT 50LMT 180LET 00LMT 10LET & LMT 15 & 100LET 80LET SYMMETRICAL FAULT FULLY ASYMMETRICAL FAULT LCT 1LCT 1LCT 10LCT LCT Prospective Short-Circuit Current Symmetrical RMS 3LET 50LET 35LET 3LET 5LET Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

98 British BS 88 0V: -900A LMT 10-50A: 0V Virtual Pre-Arcing Time In Seconds LMT 00LMT 50LMT 315LMT 355LMT 00LMT 50LMT Prospective Current In Amps RMS LMMT A: 0V Virtual Pre-Arcing Time In Seconds Prospective Current In Amps RMS 00LMMT 500LMMT 30LMMT 710LMMT 800LMMT 900LMMT Data Sheet: Data Sheet: Peak Let-Through Current LMMT 800LMMT 710LMMT 30LMMT 50LMT 00 & 500LMMT 355LMT 315LMT 50LMT 180LET 00LMT 10LET & LMT 15 & 100LET 80LET SYMMETRICAL FAULT FULLY ASYMMETRICAL FAULT LCT 1LCT 1LCT 10LCT LCT Prospective Short-Circuit Current Symmetrical RMS 3LET 50LET 35LET 3LET 5LET Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

99 British BS 88 90V: -710A CT, ET, FE, EET, FEE, FM, FMM, MT, MMT Specifications Description: BS 88 style stud-mount fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 90Vac/500Vdc Amps: -710A IR: 00kA RMS Sym. Agency Information: CE, Designed and tested to: BS 88 Part, IEC 9 Part, UL Recognized. MT and MMT 350Vdc (IEC) rating. Consult Cooper Bussmann for UL Recognition status. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) K 1) ) ) CT, ET, EET, FE, FEE, MT, MMT ) FM, FMM E g Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, Ib, in % of the rated current. Features and Benefits Excellent cycling capability Excellent DC performance Low arc voltage and low energy let-through (I t) Low watts loss Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Kp U L E g ) CT ) ET, FE, EET, FEE, FM, FMM I 0.1 b % 1) ) High Speed Fuses Dimensions (mm) Fig. 1: CT 5.5 Fig. : ET, FE 7.1 Fig. 3: EET, FEE Fig. : FM, MT Fig. 5: FMM, MMT A A mm = / 1 = 5.mm Data Sheet: Figs. & 5 A Dimensions Type A FM 80-85mm FMM 80-85mm MT 85mm MMT 85mm Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

100 British BS 88 90V: -710A Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Clearing Watts Numbers Type RMS-Amps Pre-arc at 15V at 0V Loss CT CT CT CT CT CT ET ET ET ET ET 5ET ET ET ET FE FE FE FE FE FE FE FE FE FE EET EET EET 10EET EET FEE FEE FEE FEE 10FEE FEE FEE FM FM FM FM FM FM FM FM FMM FMM FMM FMM 550FMM FMM FMM MT MT MT MT MT MT MT MT MMT MMT MMT MMT MMT MMT MMT 00MMT MMT MMT MMT MMT MMT Watts loss provided at rated current. Note: FC, 8ET, 1ET, 15ET, 0ET, 5EET and 75EET are available for replacement purposes on existing equipment. See accessories on page 195. CT -0, ET 5-80A: 90V Virtual Pre-Arcing Time In Seconds Peak Let-Through Current CT 10CT 1CT 1CT 0CT 5ET 3ET 35ET 0ET 5ET 5ET 3ET 80ET Prospective Current In Amps RMS 710MMT 30MMT 50MMT 500MMT 50MMT 315MT 355MT 00MMT 80MT 355MMT 50MT 315MMT 80MMT 00MT 180MT 5MMT 10MT 00MMT 180MMT 0CT 1CT 1CT 10CT CT 80ET 3ET 5ET 5ET 0ET 35ET 3ET 5ET Prospective Short-Circuit Current Symmetrical RMS 10EET 10EET 110EET 90EET 19 Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

101 British BS 88 90V: -710A EET 90-10A, MT A: 90V MMT A: 90V Virtual Pre-Arcing Time In Seconds EET 110EET 10EET 10EET Data Sheet: Prospective Current In Amps RMS 10MT 180MT 00MT 50MT 80MT 315MT 355MT Virtual Pre-Arcing Time In Seconds MMT 00MMT 5MMT 80MMT 315MMT 355MMT Data Sheet: MMT 50MMT 500MMT 50MMT 30MMT 710MMT Prospective Current In Amps RMS High Speed Fuses MMT 30MMT 50MMT 500MMT 50MMT 315MT 355MT 00MMT 80MT 355MMT 50MT 315MMT 80MMT 00MT 180MT 5MMT 10MT 00MMT 180MMT Peak Let-Through Current CT 1CT 1CT 10CT CT 80ET 3ET 5ET 5ET 0ET 35ET 3ET 5ET 10EET 10EET 110EET 90EET Prospective Short-Circuit Current Symmetrical RMS Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

102 British BS 88 90V: -710A FE A & FM A: 90V FEE A & FMM A: 90V Virtual Pre-Arcing Time In Seconds FE 0FE 5FE 50FE 3FE 71FE 80FE 90FE 100FE Prospective Current In Amps RMS 180FM 00FM 0FM 50FM 80FM 315FM 350FM Virtual Pre-Arcing Time In Seconds FEE 10FEE 10FEE 10FEE 180FEE FEE FMM 50FMM 500FMM 550FMM 30FMM 700FMM Prospective Current In Amps RMS FMM 30FMM 550FMM 500FMM FM 315FM 80FM 50FM 5FM 00FM 180FM 50FMM 00FMM Peak Let-Through Current FE 90FE 80FE 71FE 3FE 50FE 5FE 0FE 35FE Peak Let-Through Current FEE 180FEE 10FEE 10FEE 10FEE Prospective Short-Circuit Current Symmetrical RMS 100FEE Data Sheet: Data Sheet: Prospective Short-Circuit Current Symmetrical RMS 19 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

103 British BS 88 Fuse Accessories Indicator System Trip-Indicators Trip-indicators are available for use in parallel with the main fuse. They can either be attached to the associated fuse or mounted separately in panel mounted fuse clips, reference CL1. A push-on adapter and microswitch attachment is available for use with the trip indicator to give the facility of remote indication, reference MAI. Fuse ratings of 0A and below cannot usually accommodate a trip-indicator. When a trip-indicator is to be attached to the main fuse an accessory pack comprising a pair of mounting clips and an appropriate trip indicator would be required. The clips are snapped onto the fuse end caps and the indicator is pressed into clips as shown. Electrical Specifications Type TI500 TI700 Maximum RMS Voltage Maximum Peak Voltage Maximum DC Voltage Cold Resistance (ohms) Maximum permissible steady-state current 1.5A 1.5A Interrupting Capacity (RMS Symm.) 100, ,000 Pre-Arcing I t 3 3 Fuse Indicator Kits RMS For use Kit. Ref. Details Volts with Fuse Ref. EC-50 Fuse Mount 50 LET MC50 Indicator Kits 50 LMT & LMMT EC-00 (Includes one 0 FE, FEE & ET MC00 indicator 0 FM & FMM MC700 and two clips) 700 MT & MMT CL1 Panel Mount Clips CL1 Panel mount fuse clips are available for mounting a trip-indicator when mounting directly on the fuse is impractical. Order part number CL1. Trip-Indicator Dimensions - mm C 1 B E0.8 A Ref. Dim. A (mm) RMS Volts TI TI TI TI TI TI TI TI CL1 Panel Mount Clip Dimensions - mm Trip Indicator D.8 F B.35 High Speed Fuses Microswitch Adapter MAI We offer a microswitch, complete with adapter for securing the indicator. The microswitch is provided with double pole, single throw contacts, having both a normally open and a normally closed position. A special material has been employed in the construction of the adapter to provide reliable operation in the range of temperatures associated with standard operating conditions and during fuse operation. Microswitch and Adapter Type MAI Terminal Arrangement Dimensions in mm NO NC NC NO Current Rating: AC 50/0Hz resistive 50V RMS AC 50/0Hz resistive 17V RMS DC, resistive 110Vdc DC, resistive 30Vdc Maximum Working Voltage: Contact-to-contact (RMS) Contact-to-contact (RMS) Maximum DC Volts: A A 0.7A DC A DC 1000V 1500V 110V DC Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

104 Ferrule fuses Table of Contents Basic Catalog Amp Number Volts Range Page FWA FWX FWH FWC FWP 90V/ FWK FWJ FWL/FWS 150/1500/ Accessories Fuse Holders 1 Ferrule Fuse Ranges Volts Amps AC DC X X X X X X 00-3 X X 700 ( x 58mm) X 700 (1 x 51mm) 1-50 X X X X X X (800Vdc) X X (1000Vdc) X X (1000Vdc) X X (1000Vdc) General Information Cooper Bussmann offers a full line of ferrule style (cylindrical clip-mounted) fuses, designed and tested to meet standards and requirements in various locations around the world. Their unique design and construction provide: Superior cycling capability Low energy let-through (I t) Ferrule fuses provide an excellent solution for small UPS, small ac drives and other low power applications where space is at a premium. Voltage Rating All Cooper Bussmann ferrule fuses except 90V have been tested at their rated voltage. The 90V ferrule fuse has been tested to the IEC 09 standard, which requires clearing at the rated voltage +5%. Accessories Ferrule fuses may be mounted in fuseclips, fuse holders, fuse blocks or fused switches. A variety of products are available. Please consult Cooper Bussmann Application Engineering to discuss your requirement. 19 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

105 Ferrule FWA 150V: 5-0A FWA 5-30A (10 x 38mm) 35-0A (1 X 51mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 150Vac/dc Amps: 5-0A IR: 100kA Sym. Agency Information: CE, UL Recognition Total Clearing I t The total clearing I t at 1.5 K rated voltage and at power 1.0 factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is 0.5 1) found by multiplying by 0.3 correction factor, K, given 0. ) as a function of applied working voltage, E g, (rms) Dimensions - in (mm) Amp Dimensions Range A B C (38.1) (9.5) 0.0 (10.3) (50.8) 0.5 (15.9) (0.) A ) 5-30A Range ) 35-0A Range 150 C Eg Arc Voltage This curve gives the peak arc voltage, U L, which 300 may appear across the fuse during its operation as a function of the 00 applied working voltage, E g, (rms) at a power factor 100 of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Catalog Numbers I t (A Sec) Rated Catalog Current Clearing Watts Numbers Size RMS-Amps Pre-arc at 150V Loss FWA-5A10F FWA-10A10F. 1.7 FWA-15A10F 10 x 38mm FWA-0A10F ( 13 3 x 1 1 ) FWA-5A10F FWA-30A10F FWA-35A1F FWA-0A1F x 51mm FWA-5A1F ( 13 1 x ) FWA-50A1F FWA-0A1F Watts loss provided at rated current. See accessories on page 1. U L Kp 50 E g I 0.1 b % High Speed Fuses Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks B Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

106 Ferrule FWA 150V: 5-0A FWA 5-30A: 150V (10 x 38mm) FWA 35-0A: 150V (1 x 51mm) Virtual Pre-Arcing Time In Seconds FWA-5A10F FWA-10A10F FWA-15A10F FWA-0A10F FWA-5A10F FWA-30A10F Prospective Current In Amps RMS Virtual Pre-Arcing Time In Seconds FWA-35A1F FWA-0A1F FWA-5A1F FWA-50A1F FWA-0A1F Prospective Current In Amps RMS Peak Let-Through Current FWA-30A10F FWA-5A10F FWA-0A10F FWA-15A10F FWA-1A10F FWA-10A10F FWA-5A10F Peak Let-Through Current FWA-0A1F FWA-50A1F FWA-5A1F FWA-0A1F FWA-35A1F Prospective Short-Circuit Current Symmetrical RMS Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

107 Ferrule FWX 50V (UL): 1-50A FWX (1 x 51mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 50Vac/dc Amps: 1-50A IR: 00kA RMS Sym. 50Vdc Agency Information: CE, UL Recognition 1-50A & CSA Component Acceptance: 5-30A Electrical Characteristics Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Dimensions - mm (inches) 50.8 (.000") K 1) Eg (0.10") ) 1.3 (0.53") Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Number Size RMS-Amps Pre-arc at 50V Loss FWX-1A1F 1 FWX-A1F FWX-3A1F 3 FWX-A1F FWX-5A1F 1 x 51mm FWX-10A1F ( 9 1 x ). 3. FWX-15A1F FWX-0A1F FWX-5A1F FWX-30A1F FWX-50A1F Watts loss provided at rated current. (50Vdc/Interrupting rating 50kA) UL Recognition & CSA Component Acceptance on 5 through 30A only. Consult Cooper Bussmann for additional ratings. See accessories on page 1. Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters U L ) 300 ) E g Kp I 0.1 b % High Speed Fuses Data Sheet: 7000 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

108 Ferrule FWX 50V (UL): 1-50A FWX 1-30A: 50V (1 x 51mm) Prospective Current In Amps RMS Prospective Current In Amps RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

109 Ferrule FWH 500V: A FWH ( x 3mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 500Vac Amps: A IR: 50kA at 0% pf (0.5-0A) 0kA at 0% pf (5-30A) Agency Information: CE, UL Recognition A, CSA Component Acceptance: 0.5-7A Opening Times Amp Ratings 150% 00% 300% > 30 min < 30 min 10 sec < 30 min < 30 min 10 sec Dimensions - mm (inches) 31.8 (1.5") 3. (0.15"). (0.5") Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Numbers Size RMS-Amps Pre-arc at 500V Loss FWH-.50AF 0.5* FWH-.500AF 0.5* FWH-001AF 1* FWH-00AF * FWH-3.15AF 3.15* FWH-005AF 5* FWH-.30AF x 3mm.3* FWH-007AF ( 1 x 1 1 ) 7* FWH-010AF 10** FWH-1.5AF 1.5** FWH-015AF 15** FWH-01AF 1** FWH-00AF 0** FWH-05AF 5** 1 35 FWH-030AF 30** *300% minimum opening current at rated voltage. **00% minimum opening current at rated voltage. Consult Cooper Bussmann for DC ratings. See accessories on page 1. Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters High Speed Fuses Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

110 Ferrule FWH 500V: A FWH 0.5-7A: 500V ( x 3mm) FWH 10-30A: 500V ( x 3mm) 10 FWH-00AF FWH-3.15AF FWH-005AF FWH-.30AF FWH-007AF 10 Virtual Pre-Arcing Time In Seconds FWH-.50AF FWH-.500AF FWH-001AF x Prospective Current In Amps RMS Data Sheet: Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

111 Ferrule FWH 500V: 1-30A FWH (1 x 51mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 500Vac/dc Amps: 1-30A IR: 00kA RMS Sym. Agency Information: CE, UL Recognition 1-30A & CSA Component Acceptance: 5-30A. Total Clearing I t The total clearing I t at rated 1.5 voltage and at power factor 1.0 of 15% are given in the electrical characteristics. For other voltages, the clearing 0.5 I t is found by multiplying by correction factor, K, given as 0.3 a function of applied working 0. voltage, E g, (rms). Dimensions - mm (inches) 50.8 (.000") 15.5 (0.10") K (0.53") 500 Eg Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Numbers Size RMS-Amps Pre-arc at 500V Loss FWH-1A1F 1 FWH-A1F FWH-3A1F 3.3 FWH-A1F FWH-5A1F FWH-A1F 1 x 51mm FWH-10A1F ( 9 1 x ). 13 FWH-1A1F 1 FWH-15A1F FWH-0A1F 0 9 FWH-5A1F FWH-30A1F Watts loss provided at rated current. See accessories on page 1. Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters.0 1. U L E g Kp I 0.1 b % High Speed Fuses Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

112 Ferrule FWH 500V: 1-30A FWH 1-30A: 500V (1 x 51mm) 10 Virtual Pre-Arcing Time In Seconds FWH-5A1F FWH-10A1F FWH-15A1F FWH-0A1F FWH-5A1F FWH-30A1F Prospective Current In Amps RMS 10 Peak Let-Through Current 10 FWH-30A1F FWH-5A1F FWH-0A1F FWH-15A1F FWH-10A1F FWH-5A1F Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

113 Ferrule FWC 00V: -3A FWC (10 x 38mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 00Vac/dc Amps: -3A IR: 00kA RMS Sym. 700Vdc (-5A) Agency Information: CE, UL Recognition: -3A. UL Recognition: -5A Total Clearing I t 1.5 K The total clearing I t at rated 1.0 voltage and at power factor of 15% are given in the electrical characteristics. For 0.5 other voltages, the clearing I t is found by multiplying by 0.3 correction factor, K, given as 0. a function of applied working voltage, E g, (rms) Dimensions - mm (inches) 38.1 (1.500") 9.5 (0.375") (0.0") Eg Arc Voltage This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Numbers Size RMS-Amps Pre-arc at 00V Loss FWC-A10F FWC-8A10F FWC-10A10F FWC-1A10F 10 x 38mm FWC-1A10F ( 13 3 x 1 1 ) FWC-0A10F FWC-5A10F FWC-30A10F FWC-3A10F Watts loss provided at rated current. See accessories on page 1. Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters.0 1. U L E g Kp I 0.1 b % High Speed Fuses Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

114 Ferrule FWC 00V: -3A FWC -3A: 00V (10 x 38mm) 10 Virtual Pre-Arcing Time In Seconds FWC-A10F FWC-8A10F FWC-10A10F FWC-1A10F FWC-1A10F FWC-0A10F FWC-5A10F FWC-30A10F & FWC-3A10F Prospective Current In Amps RMS 10 FWC-30A10F & FWC-3A10F FWC-5A10F FWC-0A10F FWC-1A10F Peak Let-Through Current 10 FWC-1A10F FWC-10A10F FWC-8A10F FWC-A10F Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

115 Ferrule FWP 90V/700V (IEC/UL): 1-50A, Striker Optional FWP (1 x 51mm) Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustrations. Ratings: Volts: 90Vac (IEC) 700Vac (UL) 800Vdc (5-50A) Amps: 1-50A IR: 00kA RMS Sym. Agency Information: CE, UL Recognition, CSA Component Acceptance for versions without indicator only. Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms). Dimensions - mm (inches) Without Striker With Striker ) 0. ) K E g (.000") 1.3 (0.53") 1) 5-30A Range ) 3-50A Range 15.5 (0.10") 59 (.33") 51 (.00") FWP with striker option. 13 (0.511") 1.3 (0.53") Arc Voltage 1. This curve gives the peak 1. arc voltage, U L, which 10 may appear across the 3 9 fuse during its operation 8 as a function of the 7 applied working voltage, E g, (rms) at a power factor 5 of 15%. Power Losses 3 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current U L E g I b % Catalog Numbers Rated I t (A Sec) Catalog Current Minimum Clearing At Watts Numbers Size RMS-Amps Melting Rated Voltage Loss Without Striker FWP-1A1Fa 1 FWP-A1Fa FWP-.5A1Fa.5 FWP-3A1Fa 3 FWP-A1Fa FWP-5A1Fa 1 x 51mm FWP-10A1Fa ( 9 1" x ") FWP-15A1Fa FWP-0A1Fa FWP-5A1Fa FWP-30A1Fa FWP-3A1Fa FWP-0A1Fa FWP-50A1Fa With Striker FWP-10A1FI FWP-15A1FI FWP-0A1FI 1 x 51mm FWP-5A1FI ( 9 1 x ) FWP-30A1FI FWP-3A1FI FWP-0A1FI FWP-50A1FI Watts loss provided at rated current. See accessories on page 1. Kp High Speed Fuses 5 (0.197") Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through ( I t) Low watts loss in a compact size Used with finger-safe holders/blocks Data Sheet: 7005 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

116 Ferrule FWP 90V/700V (IEC/UL): 1-50A, Striker Optional Without Striker FWP 5-50A: 0V/700V (1x 51mm) 10 Virtual Pre-Arcing Time In Seconds FWP-5A1F FWP-10A1F FWP-15A1F FWP-0A1F FWP-5A1F FWP-30A1F FWP-3A1F FWP-0A1F FWP-50A1F Prospective Current In Amps RMS 10 FWP-50A1F FWP-0A1F FWP-3A1F FWP-30A1F FWP-5A1F Peak Let-Through Current 10 FWP-0A1F FWP-15A1F FWP-10A1F FWP-5A1F Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

117 Ferrule FWP 90V/700V (IEC/UL): 0-100A, Striker Optional FWP ( x 58mm) Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustration. Ratings: Volts: 90Vac (IEC) 700Vac (UL) Amps: 0-100A IR: 00kA RMS Sym. 500Vdc Agency Information: CE, UL Recognition Total Clearing I t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I t is found by multiplying by correction factor, K, given as a function of applied working voltage, E g, (rms) Dimensions - mm (inches) Without Striker K E g (.83") 15.0 (0.591") FWP with striker option.. (0.875") Arc Voltage U This curve gives the peak L 10 arc voltage, U L, which 9 may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. E g 3 Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p, is given as a function of the RMS load current, I b, in % of the rated current. Catalog Numbers Rated I t (A Sec) Catalog Current Minimum Clearing At Watts Numbers Size RMS-Amps Melting Rated Voltage Loss Without Striker FWP-0AFa FWP-5AFa FWP-3AFa x 58mm FWP-0AFa ( 7 8" x 9 3") FWP-50AFa FWP-3AFa FWP-80AFa FWP-100AFa 100* With Striker FWP-0AFI FWP-5AFI FWP-3AFI x 58mm FWP-0AFI ( 7 8" x 9 3") FWP-50AFI FWP-3AFI FWP-80AFI FWP-100AFI 100* *IEC/UL Voltage rating 90/700 Kp I 0.1 b % High Speed Fuses With Striker 5 (0.197"). (0.87") (.598") 58 (.83") 1 (0.30" Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Data Sheet: 700 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

118 Ferrule FWP 90V/700V (IEC/UL): 0-100A, Striker Optional Without Striker FWP 0-100A: 0V/700V ( x 58mm) FWP-50AF FWP-3AF FWP-80AF FWP-100AF Virtual Pre-Arcing Time In Seconds FWP-0AF FWP-5AF FWP-3AF FWP-0AF Prospective Current In Amps RMS 10 FWP-100AF FWP-80AF FWP-3AF FWP-50AF Peak Let-Through Current FWP-0AF FWP-3AF FWP-5AF FWP-0AF Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

119 Ferrule FWK 750V: 5-0A FWK 5-30A (0 x 17mm 35-0A (5 x 1mm) Specifications Description: Ferrule style high speed fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: 750Vac 750Vdc (Time constant = 10-15mS) Amps: 5-0A IR: 5kA RMS Sym. Agency Information: CE Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Numbers Size RMS-Amps Pre-arc at 750Vdc FWK-5A0F FWK-8A0F FWK-10A0F FWK-15A0F 0 x 17mm x 5 ) FWK-0A0F ( FWK-5A0F FWK-30A0F FWK-35A5F FWK-0A5F 5 x 1mm FWK-50A5F (1 x 5 3 ) FWK-0A5F Recommended fuseholders for 0x17, CH17-1, -, -3 Recommended fuseclips for 0x17, 1A1837 Recommended fuseclips for 5x1, A High Speed Fuses Dimensions - mm (inches) Fig. 1: 5-30A 17.0 (5.000") 0.5 (0.807") Fig. : 35-0A 1.0 (0.30") 1.05 (5.75") 5. (1") 0. (0.813") Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

120 Ferrule FWK 750V: 5-0A FWK 750V: 5-30A (0 x 17mm) 35-0A (5 x 1mm) 10 Virtual Pre-Arcing Time In Seconds ±1 FWK-5A0F FWK-8A0F FWK-10A0F FWK-15A0F FWK-0A0F FWK-5A0F FWK-30A0F FWK-0A5F FWK-50A5F FWK-0A5F 10 ± x10 ± Prospective Current In Amps RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

121 Ferrule FWJ 1000V: 0-30A FWJ (1 x 7mm) Arc Voltage 000 Specifications Description: Ferrule style high speed fuses. Dimensions: See dimensions illustration. Ratings: Volts: 1000Vac/800Vdc Amps: 0-30A IR: 5kA RMS Sym. 800Vdc Agency Information: CE, UL Recognized Total Clearing I t 1.5 K The total clearing I t at 1.0 rated voltage and at power factor of 15% are given in the electrical 0.5 characteristics. For other voltages, the clearing I t is 0.3 found by multiplying by 0. correction factor, K, given 0.15 as a function of applied 00 working voltage, E g, (rms). Dimensions - mm (inches).7 (.") Eg 1.5 (0.571") This curve gives the peak arc voltage, U L, which may appear across the fuse during its operation as a function of the applied working voltage, E g, (rms) at a power factor of 15%. Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, I b, in % of the rated current Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Numbers Size RMS-Amps Pre-arc at 1000V Loss FWJ-0A1F 1 x 7mm FWJ-5A1F ( 9 1 x 5 8 ) FWJ-30A1F Watts loss provided at rated current. See accessories on page 1. Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Kp U L E g I 0.1 b % High Speed Fuses 15.9 (0.5") Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Fuseclips: Catalog Number: 5591 (see data sheet 13) Data Sheet: 7008 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

122 Ferrule FWJ 1000V: 0-30A FWJ 0-30A: 1000V (1 x 7mm) Virtual Pre-Arcing Time In Seconds FWJ-0A1F FWJ-5A1F FWJ-30A1F Prospective Current In Amps RMS 10 Peak Let-Through Current 10 FWJ-30A1F FWJ-5A1F FWJ-0A1F Prospective Short-Circuit Current Symmetrical RMS Data Sheet: Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

123 Ferrule FWS/FWL 1000Vdc: -30A FWS -15A (0 x 17mm) FWL 0-30A (0 x 17mm) Specifications Description: Ferrule style full range fuses. Dimensions: See dimensions illustrations. Ratings: Volts: 100Vac (FWL 0-30A) 100Vac (FWS 8-15A) 100Vac (FWS -A) 1000Vdc (FWL/FWS -30) Amps: -30A IR: 5kA RMS Sym. 1000Vdc Agency Information: CE, IEC 0077 Catalog Numbers Rated I t (A Sec) Catalog Current Clearing Watts Numbers Size RMS-Amps Pre-arc at 1000Vdc Loss FWS-A0F FWS-A0F FWS-8A0F 0 x 17mm FWS-10A0F ( 13 1 x 5 ) FWS-1A0F FWS-15A0F FWL-0A0F x 17mm FWL-5A0F ( x 5 ) FWL-30A0F ADD I to catalog number for indicating version. Enclosed finger-safe fuse holder CH17 Open style fuse block 530-OP See accessories on page 1. Watts loss provided at rated current. Dimensions - mm (inches) Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I t) Low watts loss in a compact size Used with finger-safe holders/blocks Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Traction aux circuits Capacitor protection FWL/FWS -30A: 1000Vdc -30A (0 x 17mm) High Speed Fuses 17.0 (5.000") 0.5 (0.807") 1.0 (0.30") Indicating Version Dimensions - mm (inches) 8.0 (0.315") 17.0 (5.000") 0.5 (0.807").0 Data Sheet: (0.30").0 (0.079") Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

124 Ferrule Fuse Accessories Fuse Holders Specifications Catalog Symbol: CH Series Description: DIN rail mount fuse holders Agency Information: culus/curus/ce North American 10 x 38 Class CC: Listed UL 8, Guide IZLT, File E1853, Certified CSA Std. C. No. 39, Class 5 01, File 735 North American 10 x 38 Midget: Recognized UL 8, Guide IZLT, File E1853, Certified CSA Std. C. No. 39, Class 5 01, File 735 European: 10 x 38 IEC 9--1, 1 x 51 IEC 9--1, x 58 IEC 9--1 Features and Benefits Finger-safe design - No exposed contacts DIN rail mount (35mm) - Fits standard mounting rails Optional open fuse indication lights tells fuse status at a glance Handle/fusepuller easily installs and removes fuses Available in single and multi-pole configurations Wire ready lugs and spade terminal connections save installation time CE marking Available up to 1000Vdc PLC device available for remote monitoring Fuse Blocks Specifications Catalog Symbol: J70100, J7003 Description: Fuse blocks for x 58mm & 1 x 51mm fuses. Ratings: Volts: 700Vac Amps: 3-100A Withstand: 00kA RMS Sym. Agency Information: CE, UL Recognized, Guide IZLT, File E1853 Flammability Rating: UL 9V0 Catalog Numbers Catalog Fuse Max Wire Numbers Size Amps Poles Size Terminations J7003-CR 1x51 3 # Box Lug w/ J7003-3CR 3 3 # Retaining Clip Box Lug w/ J CR # Retaining Clip J70100-CR x # J CR # Typical Applications Switchboard panel, control consoles, small motors, transformers, and similar applications Recommended Cooper Bussmann Fuse Types Class CC North American Class CC Fuses - LP-CC, FNQ-R, KTK-R 10 x 38 North American Midget Fuses - FNQ, KTK, AGU, BAF, BAN, FNM, FWA, FWC, PV & DCM 1 x 51 Fuses - FWX, FWH, FWP & NON x 58 Fuses - FWP See pages 57 and 58 for CH Series fuse holder information. Data Sheet: Data Sheet: 111 Courtesy of Steven Engineering, Inc.-30 Ryan Way, South San Francisco, CA Main Office: (50) Outside Local Area: (800)

British BS 88 Fuses. Introduction

British BS 88 Fuses. Introduction British BS 88 Introduction British BS 88 Contents Fuse Volts Amp Range Page 0-900 188-190 90-791-19 Accessories Indicator System & Fuse Bases 195 British BS 88 Fuse Ranges Amps Vac Vdc -900 0 150-710 90

More information

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES The Edison British Style semiconductor protection fuses include a 660VAC line utilizing new filler technology. These new fuses have greatly reduced peak let-through current and energy under fault conditions

More information

PSC SQUARE BODY 690/700 Volt SEMICONDUCTOR PROTECTION FUSES

PSC SQUARE BODY 690/700 Volt SEMICONDUCTOR PROTECTION FUSES PSC SQUARE BOY Ferraz Shawmut 690/700V PSC fuse-links provide maximum flexibility in equipment design and ultimate protection for today s power conversion equipment. These square body fuse-links are available

More information

Photovoltaic System Overcurrent Protection

Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Photovoltaic System Overcurrent Protection Introduction Solar Photovoltaic (PV) systems have, over the last fifty years, evolved into a mature, sustainable and

More information

Fuses for Semiconductor Protection - Cylindrical Fuses. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits

Fuses for Semiconductor Protection - Cylindrical Fuses. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits Fuses for Semiconductor Protection - Cylindrical Fuses SIBA cylindrical Ultra-Rapid fuses are available in six different sizes They can be ordered with an integral striker for blown fuse indication or

More information

BETA Protecting SITOR Semiconductor Fuses

BETA Protecting SITOR Semiconductor Fuses BETA Protecting SITOR Semiconductor Fuses /2 Product overview /3 /17 SITOR, cylindrical fuse design /22 SILIZED, NEOZED and DIAZED design Siemens ET B1 /2008 Product overview Overview Devices Page Field

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

CONDUCTOR SHORT-CIRCUIT PROTECTION

CONDUCTOR SHORT-CIRCUIT PROTECTION CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating

More information

Solar Circuit Protection Application Guide. Complete and reliable solar circuit protection

Solar Circuit Protection Application Guide. Complete and reliable solar circuit protection Solar Circuit Protection Application Guide Complete and reliable solar circuit protection Introduction Benefits of Eaton s Circuit Protection Solutions Complete and Reliable Circuit Protection for Photovoltaic

More information

Circuit Protection. Copper Cable Limiters (600Vac) Copper/Aluminum Cable Limiters (250Vac)

Circuit Protection. Copper Cable Limiters (600Vac) Copper/Aluminum Cable Limiters (250Vac) Catalog Number UCL (25XX 75XX) 600Vac or Less Catalog Number UCLA 250Vac or Less Catalog AC Volts Number* Rating Cable Size Cable Terminals Available UCL25XX (1) 600 250MCM T = crimp tube UCL35XX (1) 600

More information

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules. Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting

More information

IEC 60269 gg & am STANDARD LOW VOLTAGE FUSE

IEC 60269 gg & am STANDARD LOW VOLTAGE FUSE IEC 60269 gg & am STANDARD LOW VOLTAGE FUSE. INTRODUCTION 2. INTRODUCTION TO THE IEC 60269 STANDARD 3. COMPARISON OF THE TIME CURRENT CURVES OF DIFFERENT FUSE TYPES 3.. Comparison of IEC and UL fuses 3.2.

More information

Solar circuit protection application guide. Complete and reliable solar circuit protection

Solar circuit protection application guide. Complete and reliable solar circuit protection Solar circuit protection application guide Complete and reliable solar circuit protection Introduction Benefits of Eaton s circuit protection solutions Complete and reliable circuit protection for photovoltaic

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable. Technical Data:

Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable. Technical Data: Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable Catalogue Symbol: Class of Operation: Fuse Size: NIT (amp rating) NET (amp rating) TIA (amp rating) TIS

More information

GS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks

GS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks GE Power Controls GS Semiconductor fuselinks TYPE GS Semiconductor Fuselinks Technical information Full GS range of fuselinks are designed to the requirements of IEC269 -IV (1986) Precise Pre-determined

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

Fuse Selection Method Module 2. Date of the presentation

Fuse Selection Method Module 2. Date of the presentation Fuse Selection Method Module 2 Date of the presentation Fuse Selection When selecting LV fuses certain important information must be known. 1.System Voltage This is the voltage of the system or distribution

More information

Power Distribution & Terminal Blocks

Power Distribution & Terminal Blocks Power Distribution & Terminal Section Contents Page Selection table for SCCR PDBs & Power terminal blocks................................ 294 Power distribution blocks Series PDBFS enclosed, with high

More information

NH DIN Dual Indication Fuse Links Class gg/gl, 690Vac, 2 to 800 Amps, Sizes 000 to 4 NH Series

NH DIN Dual Indication Fuse Links Class gg/gl, 690Vac, 2 to 800 Amps, Sizes 000 to 4 NH Series Description: A range of Class gg/gl square bodied industrial fuse links for a variety of applications. Packaging: MOQ: 3 (size 000 to 3) MOQ: 1 (size 4) Catalogue Symbol: Class of Operation: (amp)nhg(size)b-690

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

ABB Fuses Competitive Advantages

ABB Fuses Competitive Advantages GPMM Tomasz Komalski 2009 ABB Fuses Competitive Advantages May 14, 2009 Slide 1 Basic comments ABB is a global manufacturer of both current limiting and expulsion (non-current limiting) fuses for medium

More information

Bimetallic Overload Relay Specifications

Bimetallic Overload Relay Specifications Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Guidelines on the Short Circuit Current Rating for Industrial Control Panels usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A

More information

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 FUSES Catalogue CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 INTRODUCTION The main function of current limiting fuses is to protect electrical apparatus, such as distribution transformers, motors

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Protection from Short-circuit

Protection from Short-circuit Protection from Short-circuit Back-up Fuse-Link with ÜLA (controlled power dissipation) Test device for tripping device Special version with threat High-voltage Fuse-Link for voltage transformers (HSW)

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Technical data UNIBLOCK UBSF 180 625

Technical data UNIBLOCK UBSF 180 625 Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

instabus KNX / EIB System System E F G H

instabus KNX / EIB System System E F G H Product name: Uninterruptible power supply (USV) 640 ma Design: REG (rail-mounted device) Article-no.: 1079 00 ETS search path: Gira Giersiepen / system components / power supply / power supply 640mA DRA

More information

40.3. Control Relays and Timers

40.3. Control Relays and Timers .3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited

More information

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is

More information

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140) 9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity

More information

Rotary Disconnect Switch Specifications

Rotary Disconnect Switch Specifications Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

IEC and British Standard Fuses

IEC and British Standard Fuses IEC and British Standard Fuses Section Contents Page Application Data...7-8 CSA Type P and Type D fuses (CDS, CDN & PON)............................9 Tron HRC Form II Class C fuses (CGL Form II Class C)..........................

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses 14x51 & 22x58 URC / URD - 600 to 690 VAC EXTREMELY BREAKING CAPACITY RATING FUSES: PROTECTION OF POWER SEMI CONDUCTORS COMPLYING WITH IEC STANDARD 60269.1 AND 4 600-690 V AC VOLTAGE RATING ar-class ACCORDING

More information

Features. Applications. Truth Table. Close

Features. Applications. Truth Table. Close ASSR-8, ASSR-9 and ASSR-8 Form A, Solid State Relay (Photo MOSFET) (0V/0.A/0Ω) Data Sheet Description The ASSR-XX Series consists of an AlGaAs infrared light-emitting diode (LED) input stage optically

More information

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050 Extract from the online catalog DEK-REL- 24/1/SEN Order No.: 2964050 Relay terminal block for sensor, with soldered-in miniature relays, contact (AgNi+Au): small to medium loads, 1 N/O contact, input voltage

More information

Cable Plug acc. to DIN EN 175301-803, Form A

Cable Plug acc. to DIN EN 175301-803, Form A Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with

More information

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

Medium voltage products. Fuses

Medium voltage products. Fuses Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...

More information

Bussmann series Third rail fuse links application guide. Leadership in fusible circuit protection solutions

Bussmann series Third rail fuse links application guide. Leadership in fusible circuit protection solutions Bussmann series Third rail fuse links application guide Leadership in fusible circuit protection solutions Eaton s Bussmann business has over 100 years of experience in the design and manufacture of fuse

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Talon and Talon SR User Manual

Talon and Talon SR User Manual Talon and Talon SR User Manual Brushed DC motor controller Version 1.3 Cross the Road Electronics, LLC www.crosstheroadelectronics.com Cross The Road Electronics, LLC Page 1 4/2/2013 Device Overview Clear,

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog 2004 Class 601 CONTENTS Description..............................................Page INTRODUCTION.............................................

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components

More information

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5 AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation

More information

Capacitive Prox E2K-X

Capacitive Prox E2K-X Capacitive Prox Threaded, Cylindrical Sensor Detects Metallic and Non-metallic Objects Permits non-contact detection of metallic and non-metallic objects such as glass, wood, water, oil and plastic Allows

More information

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00 Soft Starter Three Phase General Purpose Soft Starters Type RSGD Soft starting and soft-stopping of 3-phase squirrel cage motors 45mm wide IP20 housing Operational Voltage: RSGD40 (220-400V), RSGD60 (220-600V)

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357

PLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357 Series Features: Color coding and pin configuration makes it physically impossible to mate plugs and receptacles of different voltages and current ratings (per IEC 60 309-2). Interlocked switch mechanism

More information

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

Renewable energy. Inverters - Socomec G-1. Load break switches (Isolators) - Socomec G-2. Fuses - df G-3. Fuse bases.

Renewable energy. Inverters - Socomec G-1. Load break switches (Isolators) - Socomec G-2. Fuses - df G-3. Fuse bases. G Product page Inverters - Socomec G-1 Load break switches (Isolators) - Socomec G-2 Fuses - df G-3 Fuse bases Surge protection - df G-3 - Wohner G-5 - CPT G-4 - Dehn G-5 Connectors - Wieland G-6 Cable

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output Forced current sharing at parallel operation Power OK signal

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

Data Sheet. Electro-mechanical counters Hengstler 800 series

Data Sheet. Electro-mechanical counters Hengstler 800 series Data Pack D Issued March 00 504897 Data Sheet Electro-mechanical counters Hengstler 800 series The 800 series totalising and predetermining batch counters, manufactured by Hengstler, is available from

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Solid State Relays Industrial, 1-Phase ZS w. LED Types RS 23, RS 40, RS 48

Solid State Relays Industrial, 1-Phase ZS w. LED Types RS 23, RS 40, RS 48 Solid State Relays Industrial, 1-Phase ZS w. LED Types RS 23, RS 0, RS 8 Zero switching AC Solid State Relay Direct copper bonding (DCB) technology in 25A and 0A types LED indication Clip-on IP 20 protection

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information