1 A Technical Analysis: Variables That Affect The Performance Of Dry Pipe Systems James Golinveaux, Sr. Vice President, Research & Development Tyco Fire & Building Products
2
3 , A TECHNICAL ANALYSIS Variables That Affect The Performance Of Dry Pipe Systems INTRODUCTION [4] SYSTEM OPERATION AND PERFORMANCE [6] CONCEPT [6] WATER TRANSITION TIMES [7] COMPRESSION [18] SprinkFDT [19] CONCLUSION [21] ABOUT THE AUTHOR [22] [3]
4 INTRODUCTION INTRODUCTION Previously, there have not been any readily available methods for predicting the time required to deliver water to the test connection of a dry sprinkler system. The Fire Protection Engineering Handbook 1 publishes a method to calculate the trip time of a dry pipe valve, but this is only a relatively minor part of the water delivery time. Until now, a designer could never know whether his system met the 60 second water delivery criterion for dry systems with a capacity greater than 750 gallons (2839 liters) until it was installed and actually tested. If it didn t meet the criterion, it was far too late to find that out! Only when you have stood at the inspectors test valve, opened it while staring at a stopwatch, and wondered what to do when the water took 68 seconds to reach the test outlet can you appreciate the frustration of the engineers/designers task. Now, Tyco Fire & Building Products has introduced an innovative tool that permits a user to accurately simulate the acceptance trip test of dry pipe systems prior to the actual installation. Those familiar with dry pipe system designs know there are four basic factors that affect the design, installation and performance of dry pipe systems. These four principles are: 1. Air and Water Supply Pressures: a. System Air pressure The air pressure within dry system piping that keeps the dry valve closed and prevents water entering the system. This is dictated by the static water supply pressure and the dry pipe valve design. b. Static water pressure The water supply pressure at the base of the riser with no flow into the sprinkler system. This pressure dictates the system air pressure required to keep the dry pipe valve closed. c. Residual water pressure and flow The water supply pressure at a given water flow rate. Each water supply follows a unique curve in which the pressure drops as the flow rate increases. This significantly impacts the time required after the dry valve trips for a steady discharge of water from the test connection to be established. 2. System Capacity and Piping Configuration: a. Capacity Total volume of all piping on the system side of the dry pipe valve. Affects the amount of air that must be discharged from the system before steady water discharge is established at the test connection. [4]
5 INTRODUCTION b. Piping Configuration i. Tree Consists of dead-end branch lines, cross-mains, and feed main. Only the feed main, cross-main, and the one branch line with the test connection must have air displaced by water in order for water to reach the test connection. Air in the remainder of the system can be compressed into dead-end piping. This piping configuration produces the fastest water delivery times. ii. Loop Has dead-end branch lines but cross-mains are looped. Increases the amount of air that must be displaced by water in order for water to reach the test connection. iii. Grid Currently not allowed in dry systems because the air in all branch lines and cross-mains must be displaced by water in order for water to reach the test connection, resulting in very long water delivery times. 3. Size of Test Sprinkler a. The orifice size of the test sprinkler controls the rate at which air is discharged from the system piping. The rate of discharge and volume of air being discharged control the water delivery time after the dry pipe valve has been actuated. 4. Dry Pipe Valves a. Dry pipe valves have traditionally been designed as differential- pressure valves. The clapper, which holds water out of the dry system, is designed with the surface area of the airside greater than the surface area of the water side. In this way, a lower air pressure can hold back a higher water pressure, thus reducing the volume of air in the dry system that must be discharged in order for water to reach the test connection. b. Other designs of dry pipe valves include "low pressure latch type" that depend on actuators and a quick opening device to work together for the valve to function properly. This paper will concentrate on the traditional ratio valve but will discuss the latch type from time to time. [5]
6 SYSTEM OPERATION AND PERFORMANCE SYSTEM OPERATION AND PERFORMANCE To fully understand dry pipe system performance, we must look at the sequence of events that occur and the impact each has. When dry pipe sprinkler systems are trip tested for acceptance, the following events occur after the inspectors test valve is opened. 1. Air pressure begins to drop in the system as a result of the open inspectors test valve. The loss of air pressure in the system causes the dry pipe valve to trip at its designed air/water ratio, or when an optional accelerator trips the valve on loss of air pressure. 2. When the valve trips, water begins to fill the system by compressing trapped air and forcing air from the inspector s test connection. 3. Water reaches the test connection and a steady water discharge is established. With this basic understanding, let s review these steps in a little more detail to understand the effects of variables. 1. Valve Trip Time: In order for the valve to trip without an accelerator, the air pressure must drop to the point that water pressure forces the valve to open. The time required is determined by the rate at which air can be discharged from the system and the amount of air that must be discharged in order for the trip pressure to be reached. This is controlled by two factors: a. Air pressure: A higher air pressure in the system will cause a faster discharge of air at the test connection, but a larger volume of air must be discharged for the valve to reach its trip point. Conversely, lowering the initial air pressure will slow the air discharge from the system, but a smaller volume of air must discharge before the valve trips. (See Figures 1 and 2) Note that in Figure 1, the time required for a 1500-gallon (5678-liter) system to drop 5-psi (0,3 bar) from 35- psi (2,4 bar) to 30-psi (2,0 bar) is 30 seconds. The same system shown in Figure 2 shows a significant increase in time to drop the same 5-psi (0,3 bar) when the pressure drop is from 15- psi (1,0 bar) to 10-psi (0,7 bar). The time required for this system is 53 seconds. This is 23 seconds longer than the same psi drop at higher initial air pressure. b. Test orifice size: A larger orifice at the test connection will allow air to discharge more rapidly from the system. (See Figure 3) This figure clearly shows that for a given dry pipe system volume, the test orifice size can significantly change the air discharge rate. [6]
7 VALVE TRIP TIMES Air Loss in Various System Volumes 35 to 30 PSI (2,4 to 2,0 bar) 500 Gallons (1893 Liters) Gallons (4272 Liters) 1500 Gallons (5678 Liters) Pressure (psi) Time (sec) Pressure (bar) Figure 1 Air pressure vs. Time for 35-psi to 25-psi (2,4 to 1,7 bar) Pressure Drop through a K5.6 (K80) sprinkler Air Loss For Various System Volumes 15 to 10 PSI (1,0 to 0,7 bar) 500 Gallons (1893 Liters) Gallons (4272 Liters) 1500 Gallons (5678 Liters) Pressure (psi) Time (sec) Pressure (bar) Figure 2 Air pressure vs. Time for 15-psi to 10-psi (0,1 to 0,7 bar) Pressure Drop through a K5.6 (K80) sprinkler [7]
8 VALVE TRIP TIMES Air Pressure vs. Time for Various Test Orifices Single Sprinkler at Test Connection 60 PSI (4,1 bar) Start Air Pressure Gallon (4272 Liter) System Volume K25.2 (K360) K16.8 (K240) K14.0 (K200) K11.2 (K160) K8.0 (K115) K5.6 (K80) Pressure (psi) Pressure (bar) Time (sec) 0.00 Figure 3 The Effect of Test Orifice Size on the Rate of Pressure Drop in a Dry System [8]
9 VALVE TRIP TIMES c. The dry pipe valve trip pressure: Different models of dry pipe valves trip at different water to air pressure ratios. A typical ratio is 5.5:1. A system using this type valve with a static water supply of 75-psi (5,2 bar) would trip at 13.6-psi (0,9 bar) (5.5:1 = 75-psi: 13.6-psi or = 5,2 bar: 0,9 bar). The air pressure as recommended by the manufacturer would typically include a safety factor plus the compressor on-off differential settings. These are added to the trip pressure of 13.6-psi (0,9 bar) to obtain the maximum set air pressure. A Central, Gem or Star DPV-1 dry pipe valve has a 5.5:1 trip ratio, and the recommended maximum set air pressure is 39-psi (2,7 bar). This is sufficient for a static water pressure of approximately 75-psi (5,2 bar). Refer to Figure 3 for the time required to lose air pressure from a 39-psi (2,7 bar) set pressure to a 13.6-psi (0,9 bar) trip pressure, this represents a 25.4-psi (1,8 bar) loss. One can quickly see why a system as large as gallons, with a K8.0 (115 lpm/bar1/2) sprinkler, can require as much as 98 seconds ( from Figure 3) to trip due to dropping the air pressure from 39-psi (2,7 bar) to 13.6-psi (0,9 bar). For this reason, accelerators, which quickly react to the rate of pressure drop in lieu of fixed pressure are very commonly used for large dry pipe systems. Low pressure latch clapper dry pipe valves operate by use of an additional device called an actuator. The actuator operates as a simple differential device wherein loss of air pressure in the system at a greater rate than the threshold limit causes the actuator to move from its set position to an open position. This vents water from the diaphragm chamber of the main valve and releases the rod and latch that hold the clapper closed inside the main valve. Because there is no published actuation data for these valves, an actuator from another manufacturer was purchased to test the activation times. Since these actuators are designed for use with "low pressure dry pipe valves", one can expect the air movement to be slow. This is obvious as shown in Figure 3. The recommended air setting pressure of these systems varies with static water pressure and can be as low as 10-psi (0,7 bar). The performance of a 1,000-gallon (3785 liter) system with a K5.6 (80 lpm/bar1/2) inspectors test and a 100-psi (6,9 bar) static water supply was tested. A manufacturer recommended 15-psi (1,0 bar) set pressure resulted in 76 seconds to achieve full (relief) flow. As with traditional dry pipe valves, latch clapper dry pipe valves will normally require the use of an accelerator to compensate for the slow activation time. [9]
10 WATER TRANSITION TIME d. The use of an accelerator: An accelerator shortens the time required to trip a dry pipe valve since they are very sensitive to pressure changes and significantly reduce the effect of system volume. Different models of accelerators offer different performance. Products manufactured by Central, Gem and Star typically trip a dry pipe valve in 4 to 10 seconds from the opening of the inspectors test valve. Other manufacturers publish times that range from 4.5 seconds to 25 seconds. The activation time is dependent on the system volume, system configuration and test orifice size. The use of an accelerator can significantly reduce the trip time of a dry pipe valve, but has a negative impact on the water delivery time after the valve trips. The water delivery time is increased due to higher air pressure in the system when the valve trips since the accelerator will trip the valve before the air pressure in the system drops to the valve differential pressure. The combined effect, though, of a properly operating accelerator is to reduce the overall time required to deliver water to the test connection. It is very important that we not lose sight of the fact that, by their very nature as sensitive devices, accelerators require a high level of testing and maintenance in order to operate dependably. Unfortunately, history shows us that they do not always receive the required level of attention. 2. Water transition time: This is the time required after tripping of the dry pipe valve for water to displace air in system piping and begin water flow from the test orifice. Figure 4 represents a typical dry pipe system that will be used in this section. Dry pipe valve trip times are not included in this section. Water transition time is the most complex and difficult phase of dry system performance to predict. The water transition time is affected by all of the following: [10]
11 WATER TRANSITION TIME System Volume gallons (4272) Supply-Static 80-psi - Residual 60-psi gpm (5,5 bar - 4,1 bar Lpm) 20 Branch Lines, 20 Sprinklers, 10 x 10 (3m x 3m) Branch Lines - 2 (51mm) Schedule 10 Riser Nipples - 2 1/2 (65mm) Schedule 40 Cross-Main - 6 (150mm) Schedule 10 Feed Main - 6 (150mm) Schedule 10 6" (150mm) Cross-Main and 2 1/2" (65mm) Riser Nipples Discharging K5.6 (K80) Sprinkler 2" (50mm) Branch Lines 20 sprinklers (10 on each side of cross main) 6" (150mm) Dry pipe riser Figure gallon dry pipe system a. Size of the test orifice: The size of the inspectors test orifice will not only affect the trip time as previously discussed, but will affect the water transit time. In order for water to fill the piping between the dry pipe valve and the test connection, it must displace air. The size of the test orifice determines the rate at which air leaves the system through the orifice. Figure 5 shows three examples where the only variable changed from the system shown in Figure 4 is the size of the inspectors test orifice. [11]
12 WATER TRANSITION TIME Transit Times for Various Orifice Sizes Water Transit Time K5.6 (K80) K8.0 (K115) K11.2 (K160) Orifice Size K Factor Figure 5 Comparison of a single K5.6, K8.0 and K11.2 (K80, K115 and K160) water transition times. b. Water supply: While all water supplies are unique, they share one common trait for any given flow; there is a corresponding pressure. As flow increases, the pressure available decreases. For any given flow, the higher the pressure and the greater the flow, the faster the water will displace air and reach the inspectors test in a dry pipe system. A weak water supply is resisted by air pressure in the system as well as lower flow rates that delay the transition time. Prior to dry pipe valve actuation, the system air pressure setting is dependent upon the static water supply pressure to the system and will vary by location. The valve trip pressures for the water supplies shown in Figure 6 are 10.9 (0,75), 14.6 (1,00) and 18.2-psi (1,25 bar) respective to the 60 (4,1), 80 (5,5), and 100-psi (6,9 bar) water supplies. Air pressures will be further detailed in Section C. Figure 6 shows the water transit times for the system shown in Figure 4 with varying water supplies. [12]
13 WATER TRANSITION TIME Transit Times for Various Water Supplies Water Transit Time Time (sec) Static-Residual-Flow Metric = (4,1 2,8 5678) (5,5 4,1 5678) and (6,9 5,5 5678) respectively. Figure 6 Comparison of residual water supply. c. Air pressure in system when valve trips: Air pressure in the system resists the fill rate of the water supply. Figure 7 clearly shows the effect of air pressure in the system shown in Figure 4 when the dry pipe valve trips, specifically when the test orifice is as small as K5.6 (K80). Figure 7 shows the effect of the air pressure in a given system. Transit Times for Various Air Pressures Water Transit Time (2,1) 25 (1,7) 20 (1,4) 15 (1,0) Air Pressure PSI (bar) Figure 7 Comparison water transition times with different air pressures in the system. [13]
14 WATER TRANSITION TIME d. System piping volume and arrangement: This is based on how much of the system volume will fill with water during the transition period (the remainder of the volume is trapped air) and the physical distance the water has to travel to the inspectors test valve. Figure 10 shows a comparison of a 30-branch line by 30-sprinkler gallon (8426 liter) system, 20-branch line by 20-sprinkler gallon (4272 liter) system (shown in Figure 8), and a 10-branch line by 10-sprinkler gallon (1555 liter) system (shown in Figure 9). The pipe sizes remained the same. The volume of a system is very difficult to change without changing another variable such as trapped air (pipe size) or distance. Keeping the same size pipe and shortening the system to change the volume will add a distance factor. In this comparison, the cross main is 200 ft (61m) shorter with 20 fewer branch lines, and the branch lines are 200 ft (61m) shorter with 20 fewer sprinklers. Keep in mind the reduction of trapped air in the branch lines, as this will be referenced in the piping configuration section below. Some of the results shown in Figure 10 are also affected by the distance reduction factor. Reference Figure 10 as a guide for the effect of a volume change and realize that there are other factors involved with the results. 6" (150mm) Cross-Main and 2 1/2" (65mm) Riser Nipples Discharging K5.6 (K80) Sprinkler 2" (50mm) Branch Lines 20 sprinklers (10 on each side of cross main) 6" (150mm) Dry pipe riser Figure 8 - Isometric of center feed tree gallon (4272 liter) capacity (20 lines by 20 lines sprinklers) [14]
15 WATER TRANSITION TIME 6" (150mm) Cross-Main and 2 1/2" (65mm) Riser Nipples Discharging K5.6 (K80) Sprinkler 2" (50mm) Branch Lines 10 sprinklers (5 on each side of cross main) 6" (150mm) Dry pipe riser Figure 9 - Isometric of a center feed tree gallon (1555 liter) capacity (10 lines by 10 lines sprinklers) Transit Times for Various System Volumes Water Transit Time Time (sec) (1550) (4272) (8426) System Volume Gallons (Liters) Figure 10 Comparison of water transition by volume. Piping arrangement plays an important role in the performance of water transition time. Through several examples, an understanding can be derived of the variables that are to follow. For example, the gallon (4272 liter) system in Figure 4 is a center feed, 20-branch line by 20- sprinkler per line system. If we cap 19 of the branch lines and half of the end line as shown in Figure 11, the results may be a surprise. This 421-gallon (1594 liter) system (Figure 11) will take [15]
16 WATER TRANSITION TIME 8 (36.5 versus 28.5) seconds longer to deliver water (transition time) than the original gallon (4272 liter) system shown in Figure 4. Why? All of the trapped air in the system has to be vented from the sprinkler prior to water arrival. In the smaller system, there are no pockets of air to compress, or non-flowing volumes for the water front to push the air except out of the open sprinkler. The single open sprinkler cannot exhaust air as fast as the 6"(150mm) riser can fill the system causing back pressure of air and slowing the fill rate of water. 6" (150mm) Cross-Main and 2 1/2" (65mm) Riser Nipples Discharging K5.6 (K80) Sprinkler 2" (50mm) Branch Lines 10 sprinklers (5 on each side of cross main) 6" (150mm) Dry pipe riser Figure 11 - Isometric of a single branch line tree - (same systems as Figure 4 with exceptions noted) If the above example begins to bring an understanding of the effects of the piping configuration with respect to trapped air, reference Figure 12. This system represents the identical system shown in Figure 11, except that cross main and four branch lines beyond the open test sprinkler line have been added. The additional main and lines bring the system volume from 421- gallon (1594 liter) capacity to 633 gallons (2396 liters). With the added pipe in Figure 12, the trapped air located in the cross main with the plugged branch lines has an additional volume beyond the flowing line that allows air compression as the water enters the system. Even though the test sprinkler is the same distance from the source with the same pipe size as Figure 11, the water transition time is reduced from 36.5 seconds to 18.7 seconds. The water front filling the system pushes air in the cross main into the trapped volume beyond the test sprinkler faster than it could push the air out of the open sprinkler in the single path shown in Figure 11. This brings the water to the open sprinkler in less time as shown, despite the fact that the volume has been increased! [16]
17 WATER TRANSITION TIME 1/2 Last Branch Line plugged Cross-Main 19 lines plugged Branch Line Volume = 633 gallon (2396 liter) system 14.6-psi (1.01 bar) air in System at Trip 80/60/1500 (5,4/4,1/5768) Water Supply Water Transit Time = 18.7 seconds Discharging K5.6 (K80) Sprinkler Dry pipe riser Figure 12 - Isometric of a single brahcn line tee (Figure 11) with 4 additional branch lines beyond the Inspectors test valve. Now refer to the original system with 20 branch lines shown in Figure 4. This piping network contains a large amount of non-flowing volume that allows the water front to displace air by compressing it into the trapped branch lines. The original 20-branch gallon (4272 liter) volume system had a water transition time of 28.5 seconds. This is a much faster water transition time than the 36.5 seconds of the system shown in Figure 11 and slower than the 18.7-second water transition of the system shown in Figure 12. When a dry pipe valve is equipped with an accelerator, the valve will trip faster, as we have previously discussed. When the valve actuation time is decreased through the use of an accelerator, the residual air pressure in the system is much higher than would have been experienced had the air pressure been allowed to reach the normal trip ratio. The result is that when using a quick opening device on a dry valve, the incoming water front is subjected to more air pressure in the system at the instant the valve trips. As previously shown, additional air pressure at the time of the valve trip will delay the water transition time. Piping arrangement plays a significant role in water transition as demonstrated in the examples above. Volume is not always the key indicator for transition times. Volume and piping configuration must to be considered. These are variables that have never been previously addressed by any codes or design standards. [17]
18 COMPRESSION 3. Compression: This is the time water first reaches the test outlet to the time when the water pressure is maintained above the minimum required. This is often referred to as "full flow" or "when the outlet stops spurting air". This value is easier to establish by computer calculations than the judgment of three people standing at the test outlet debating the definition. The most definite description of full compression is the point or time at which the water volume entering the riser equals the water volume discharging from the sprinkler. This truly means that all of the trapped air is compressed and stable (no longer fluctuating). This value is not known in the field and can be identified by computer validation. The more critical measure for adequate fire protection is the point at which the discharging sprinkler meets or exceeds its minimum flow or density requirement. A field test or delivery time calculation should end when the sprinkler is functioning at the minimum designed flow. Additional air escaping from the sprinkler is not significant as long as the discharge density is not disrupted. [18]
19 SprinkFDT SprinkFDT Computer calculations will soon be available for dry pipe system performance. NFPA # edition allows calculations to be submitted in lieu of a field validation test. Tyco Fire Products (Central, Gem and Star) has invested a considerable amount of time and money to develop this technology in a form that is available to the fire sprinkler industry. This program is called the SprinkFDT. This dry pipe model is characterized by a system of straight pipes connected by nodes. Nodes can represent either a point of transition from one pipe size to another, elbows or bends, tees and laterals for dividing or mixing streams and valves, and exit nozzles such as a open sprinkler. The water supply can be modeled as either a static water supply or variable water supply like a pump driven water supply. Currently, the model accepts only one water supply source but can be easily adapted to accept water from more than one source, if desired. The dry pipe system modeled is the conventional tree-type system (i.e., single cross-main supplies water to branch lines that are fitted with automatic sprinklers). Each pipe/node in the model is categorized as members of a Feed Main, Cross Main, Riser Nipple, Branch Line and drop/sprig portion of the dry pipe system. The SprinkFDT equations for flow properties of the gas and liquid are based on equations for unsteady fluid flow. These equations are used to solve for flow properties in the regions of fluid flow and gas flow in the system at any point in time, with the appropriate boundary and continuity conditions coupling the equations for water and gas. Additionally, the program models such phenomena as bubble flow and mixing between gas and liquid. [19]
20 SprinkfDT The input screens are as simple as tree generators as in most computer hydraulic programs or node-by-node input for more complicated systems. The output information will be similar to hydraulic calculations, only the summary data is based on trip and transition times verses water flow and friction loss. The detailed design criteria are specified in NFPA #13 2 as shown in Figure 13. A system can be calculated to meet these criteria in lieu of the field validation test. See NFPA edition 2 for more information. The SprinkFDT model will allow more than one sprinkler to activate as required by Figure 13. Hazard Number of Most Remote Sprinklers Maximum Time of Initially Open Water Delivery Residential 1 15 Seconds Light 1 60 Seconds Ordinary I 2 50 Seconds Ordinary II 2 50 Seconds Extra I 4 45 Seconds Extra II 4 45 Seconds High Piled Storage 4 40 Seconds Figure 13 NFPA # Water delivery criteria for calculated systems. Single head water supply testing may be necessary for maintenance and inspection per NFPA #25 2 to measure and record changes over time. These tests from a test outlet are for reference only and are not required to meet the 60-second rule if the system was designed by the calculation method described above. [20]
21 CONCLUSION Conclusion Individual variables affect system performance as has been demonstrated. It is difficult to show the true effect of certain variables when they cause other factors to change as well, such as water supply, volume and air pressure. The SprinkFDT model made the exploration all of these variables in dry pipe systems possible. Too many other factors change between systems and project sites to have a true comparison of variables on installed systems. Dry system performance will be greatly improved with the knowledge of actual water delivery times. Future performance based designs can take advantage of actual water delivery in modeling versus the prescriptive volume time rules in older editions of NFPA. The following items were found to deviate from traditional beliefs about dry systems and may lead to new considerations when designing dry pipe sprinkler systems: The K factor of the test orifice can influence trip, water transition and compression times. The system volume will not always be a good indicator of system performance. Changes in the critical path of water to the test outlet and the volume of trapped air between the two can greatly affect the water transition and compression time. Strong water supplies such as 80-psi residual and above tend to dampen the effect of variables and provide more consistent water transition times. Air pressure in the critical path can delay the water transition time. Reference 1 The Fire Protection Engineering Handbook, Published by the National Fire Protection Association Quincy MA and Society of Fire Protection Engineers Reference 2 NFPA Standards, Published by the National Fire Protection Association Quincy MA.
22 DRY SPRINKLERS ABOUT THE AUTHOR JAMES E GOLINVEAUX Senior Vice President, Research & Development Mr. Golinveaux s areas of interest include the research, design and applications of automatic fire sprinklers as well as their history. His interest in the fire sprinkler industry was sparked by his father s 27 years in the fire service. Beginning as a designer in the early 1980 s and later as a design manager for a fire protection firm in California, he applied local and national standards to develop working drawings for automatic fire sprinkler systems. Mr. Golinveaux became active and continues his involvement today through his membership on numerous committees such as the National Fire Protection Association (Member of NFPA 13 Discharge & Installation), International Conference of Building Officials, Society of Fire Protection Engineers and Southern Building Code Congress International. By 1991, Mr. Golinveaux s strong application knowledge of the automatic fire sprinkler industry afforded him the opportunity to work on the East Coast as the Director of Technical Services for Central Sprinkler Company. Mr. Golinveaux was responsible for the technical responses to worldwide production of automatic fire sprinkler system components. He continued his involvement in the industry and represented Central on many national committees including the National Fire Protection Research Foundation, Research and Advisory Council on Fire Suppression Futures and Underwriters Laboratories Industry Advisory Committee for automatic sprinklers. Mr. Golinveaux s many talents and wealth of knowledge were recognized by Central where he was Senior Vice President of Engineering and was directly responsible for the Production Plant with over 600 employees, the Engineering/R & D, Quality Control and Technical Services operations. Currently, Mr. Golinveaux is Senior Vice President of Research and Development for Tyco Fire & Building Products, which represents Central, Gem and Star branded products. In addition to the support of the industry through his numerous committee memberships, Mr. Golinveaux also contributes his time as a speaker for national education seminars sponsored by organizations such as the Society of Fire Protection Engineers, Universities, Highly Protected Risk (HPR) Insurance Companies, National Apprenticeship and Training, and Trade Associations as well as state and local fire authorities. He has educated many on the latest sprinkler technology and its associated codes and standards. Mr. Golinveaux s co-authored the published article Fire Test Performance of Extra Large Orifice Sprinklers in Rack Storage of Group A Plastics in Warehouse-Type Retail Occupancies. He is also named on numerous U.S. Patents relating to automatic sprinklers. [22]
23 [23]
24 WORLDWIDE HEADQUARTERS Tyco Fire & Building Products 451 N. Cannon Avenue Lansdale, PA , Fax UNITED STATES Central Sprinkler Company 451 N. Cannon Avenue Lansdale, PA , Fax Brea, CA: , Fax Decatur, GA: , Fax King of Prussia, PA: , Fax Jessup, MD: , Fax Carol Stream, IL: , Fax Irving, TX: , Fax Kent, WA: , Fax Avon, MA: , Fax Pompano Beach, FL: , Fax Hayward, CA: , Fax Murray UT: , Fax Greensboro, NC: , Fax Tigard, OR: , Fax Parma, OH: , Fax Kansas City, MO: , Fax Gem Sprinkler & Star Sprinkler 7071 S. 13th Street, Ste. 103 Oak Creek, WI , Fax National Distribution Facility PO Box 2806 Lubbock, TX CANADA Regional Headquarters Stone Road West, Suite 404 Guelph, ON N1G 4W , Fax LATIN AMERICA Regional Headquarters South America, Central America & Caribbean 1500 S.W. 5th Court, Suite A Pompano Beach, FL , Fax Regional Headquarters - Mexico Hamburgo 231A Piso 2 Colonia Juarez Mexico, D.F Mexico , Fax: EUROPE & MIDDLE EAST Regional Headquarters Kopersteden 1, NL-7547 TJ Enschede P.O. Box 198, 7500 AD Enschede, The Netherlands , Fax Stockport, UK: , Fax Paris Nord II, France: , Fax Rodgau Germany: , Fax Coslada Madrid, Spain: , Fax Lørenskog, Norway: , Fax Lammhult, Sweden: , Fax Dublin, Ireland: , Fax Bolzano,Italy: , Fax Milano, Italy: , Fax Dubai, United Arab Emirates: , Fax Budapest, Hungary: , Fax Wels/Thalheim, Austria: , Fax ASIA Regional Headquarters No.45 Tuas Avenue 9, Singapore Central Sprinkler Company Singapore: , Fax Shanghai, China: , Fax Beijing, China: , Fax Chengdu, China: , Fax Gem Sprinkler Company & Star Sprinkler Inc. Singapore: , Fax Kuala Lumpur, Malaysia: , Fax Hong Kong: , Fax Printed in USA / RPI / 9.02 / 3M / 2002
Quick Opening Devices (Dry Pipe Valve Accelerators)
Quick Opening Devices () A Technical Analysis: Mechanical vs. Electronic James Golinveaux, Sr. Vice President, Research & Development Tyco Fire Products INTRODUCTION.............................[4] DEFINITIONS...............................[5]
RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001
Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can
Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator
Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator Andy L. Kaempfer Business Development Manager Potter Electric Signal Company, LLC 1609 Park 370 Place St. Louis,
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS
GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style
Minor losses include head losses through/past hydrants, couplers, valves,
Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
Select the Right Relief Valve - Part 1 Saeid Rahimi
Select the Right Relief Valve - Part 1 Saeid Rahimi 8-Apr-01 Introduction Selecting a proper type of relief valve is an essential part of an overpressure protection system design. The selection process
Automatic Fire Sprinkler System Checklist
Fire Prevention rd Location: 701 E. 3 Avenue Mail to: P.O. Box 1579 Moses Lake, WA 98837 (509) 765-2204 www.ci.moses-lake.wa.us Automatic Fire Sprinkler System Checklist Please print in Black or Blue ink
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
LCT 1025 (08/08) Copyright 2008 Harleysville Mutual Insurance Company Page 1 of 5 All rights reserved
Bonding and Grounding of Flammable Liquid Containers Provided by Harleysville s Risk Control Department 800-523-6344 ext 8100 www.harleysvillegroup.com/riskcontrol Summary The movement of volatile liquids,
Chapter 10. Control Design: Intuition or Analysis?
Chapter 10 Control Design: Intuition or Analysis? Dan P. Dumdie 10.1 Introduction In previous chapters, we discussed some of the many different types of control methods available and typically used in
Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.
ASGMT / Averaging Pitot Tube Flow Measurement Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. Averaging Pitot Tube Meters Introduction
Get the benefits of Norgren s unique range of Online services
Get the benefits of Norgren s unique range of Online services Make your job easier and save time - everything you need to select, design and purchase Norgren pneumatics is in one convenient location, available
Heating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
Water hammering in fire fighting installation
Water hammering in fire fighting installation Forward One of major problems raised in the fire fighting network installed at Pioneer company for pharmaceutical industry /Sulaymania was the high water hammering
Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)
Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0.6 bar -to- 1.9 bar) Max 3. Reset externally. Cover removal is not
RESPONSE TIME INDEX OF SPRINKLERS
, Number l, p.1-6, 29 RESPONSE TIME INDEX OF SPRINKLERS C.K. Sze Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT The Plunge test would be carried
Application of the Orifice Meter for Accurate Gas Flow Measurement page 1. Application of the Orifice Meter for Accurate Gas Flow Measurement.
Application of the Orifice Meter for Accurate Gas Flow Measurement page 1 DANIEL MEASUREMENT AND CONTROL WHITE PAPER Application of the Orifice Meter for Accurate Gas Flow Measurement www.daniel.com Summary
Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description The TYCO Type D3 PROTECTO- SPRAY Nozzles are open (non-automatic) directional
2015 Growth in data center employment continues but the workforce is changing
Published in Conjunction with MARKET BRIEFING GLOBAL DATA CENTER EMPLOYMENT 2015 2015 Growth in data center employment continues but the workforce is changing Globally, the number of people working in
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust
Safer.Smarter.Tyco. Watermist fire protection Technology you can trust / 2 / / 3 / Trust in Tyco Tyco s AquaMist Systems Tyco Fire Protection Products helps to keep people, property and the environment
Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and
COUNTERBALANCE VALVES
COUNTERBALANCE VALVES Introduction They are modulating valves which allow free flow into the actuator and then block the reverse flow until they feel a pilot pressure inversely proportional to the load
Frequently Asked Questions
Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.
Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description
Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are
Pressure Relief and Regulating Valves
Pressure Relief and Regulating Valves With blocked center directional valves and variable displacement pumps, or open center directional valves and fixed displacement pumps where fast response, low leakage
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES by Kazuhiro Takeda Research Manager, Research and Development Center and Kengo Hirano Instrument and Control Engineer,
Clark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008
HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2
Transformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 [email protected] www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS
Ambit Asset/ Ambit BancWare Focus ALM
Ambit Asset/ Liability Management Ambit BancWare Focus ALM Better information and analysis means better decisions. Managing the risk on the balance sheet today requires diligence and flexible, scalable
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
The Jockey Pump, an Important Part of a Fire Pump System.
The Jockey Pump, an Important Part of a Fire Pump System. May 18, 2008 A Jockey Pump is an important component of a fire pump system. The Jockey Pump is not as mundane, as many engineers, contractors and
Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps
Pump ED 101 Positive Displacement Pumps Part I Reciprocating Pumps Joe Evans, Ph.D http://www.pumped101.com There are many pump designs that fall into the positive displacement category but, for the most
Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009
Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort
Pressure drop in pipes...
Pressure drop in pipes... PRESSURE DROP CALCULATIONS Pressure drop or head loss, occurs in all piping systems because of elevation changes, turbulence caused by abrupt changes in direction, and friction
1805 Series Relief Valves
October 2011 1805 Series Relief Valves P1026 1805G Type 1805-2 Type 1805-4 Figure 1. Typical 1805 Relief Valves Introduction The 1805 Series relief valves are designed for use in farm tap applications
Agilent Automotive Power Window Regulator Testing. Application Note
Agilent Automotive Power Window Regulator Testing Application Note Abstract Automotive power window regulator tests require the use of accurate data acquisition devices, as they cover a wide range of parameters
The Secret of Hydraulic Schematics. BTPHydraulics www.iranfluidpower.com
The Secret of Hydraulic Schematics BTPHydraulics www.iranfluidpower.com www.iranfluidpower.com Table of Contents The Secret to Reading and Interpreting Hydraulic Schematics... 1 Hydraulic System Schematics...
Theory, Application, and Sizing of Air Valves
Theory, Application, and Sizing of Air Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com 1 THEORY, APPLICATION,
AMBIT ISLAMIC BANKING. Ambit Risk Management & Compliance
AMBIT ISLAMIC BANKING Ambit Risk Management & Compliance AMBIT RISK MANAGEMENT & COMPLIANCE FOR ISLAMIC BANKING With Islamic banking growing at rapid rates, a new and highly competitive playing field has
Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.
DAN-LIQ-TG-44-rev0208 February 2008 Daniel Liquid Control Valves Technical Guide www.daniel.com Daniel Measurement and Control Theory, Principle of Operation and Applications This brochure has been prepared
RESIDENTIAL SPRINKLER INSTALLATION GUIDE
RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,
Example. Fluid Power. Circuits
Example Fluid Power Circuits To Enhance Symbol Reading Skills To Work On Circuit Reading Skills With Answers HI LO Pump Circuit 18 A1 B1 17 16 15 13 Set 14 2,000 PSI PG2 Set 500 PSI 12 11 7 8 10 PG1 9
Pressure Limiting Driver (PLD)
Pressure Limiting Driver (PLD) Discharge Pressure Control Suction Pressure Control June 9 2009 Mark Evans Clarke Fire Protection Products Justin Strousse Clarke Fire Protection Products Overview Discharge
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
Fluid Automation: The Unsung Contributor to Plant Economic Performance. A Management Brief From ASCO Numatics
Fluid Automation: The Unsung Contributor to Plant Economic Performance A Management Brief From ASCO Numatics Controlling the flow of profit A fluid automation product such as a valve operates to shut on
TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
Mission-critical fire protection HI-FOG for data centres
Mission-critical fire protection HI-FOG for data centres Modern fire protection for a data-driven world We make a strong case that HI-FOG is the best available fire protection for mission-critical data
Automatic Sprinkler System Calculations
SECTION FOUR CHAPTER 3 Automatic Sprinkler System Calculations Russell P. Fleming Introduction Applications Where Water Is Appropriate Water is the most commonly used fire extinguishing agent, mainly due
Extended Coverage Sprinklers
Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Air Eliminators and Combination Air Eliminators Strainers
Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.
1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 thru inch (DN40 thru DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical
The face of consistent global performance
Building safety & security global simplified accounts The face of consistent global performance Delivering enterprise-wide safety and security solutions. With more than 500 offices worldwide Johnson Controls
Global Data Center Location Insights March 2013
Global Data Center Location March 2013 This report is solely for the use of Talent Neuron clients and Talent Neuron Subscribers. No part of it may be circulated, quoted, or reproduced for distribution
Series MJC Multiple Jet Controls DN20, DN25, DN40, and DN50, 12 bar BSPT Inlet & Outlets Threads General Description.
Worldwide Contacts www.tyco-fire.com Series Multiple Jet Controls DN20, DN25, DN40, and DN50, 2 bar BSPT Inlet & Outlets Threads General Description The TYCO Series Multiple Jet Controls are control valves
IFS ApplIcAtIonS For Document management
IFS Applications for Document management OUR SOLUTION S DNA When we first set out to create IFS Applications over 25 years ago, our goal was to make the most usable business software on the market. And
Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com
Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
The big pay turnaround: Eurozone recovering, emerging markets falter in 2015
The big pay turnaround: Eurozone recovering, emerging markets falter in 2015 Global salary rises up compared to last year But workers in key emerging markets will experience real wage cuts Increase in
Make the invisible visible! SENSORS WITH EXCELLENT BACKGROUND SUPPRESSION
Make the invisible visible! SENSORS WITH EXCELLENT BACKGROUND SUPPRESSION photoelectric sensors Thanks to its vision for innovation and technological enhancement, Contrinex keeps on setting new standards
Basic Hydraulics and Pneumatics
Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:
Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation /2 thru 8 Inch (DN thru DN200) General Description The DV5 Supervised Single
Unit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 2 HYDRAULIC AND PNEUMATIC CYLINDERS The material needed for outcome 2 is very extensive
Cost Estimation for Materials and Installation of Hot Water Piping Insulation
Cost Estimation for Materials and Installation of Hot Water Piping Insulation Prepared for Pacific Northwest National Laboratory Under Contract Number: 18O9O2 By Gary Klein, Managing Partner Affiliated
Technical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS
GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS 1.0 PURPOSE 1.1 To provide an overview of fire extinguisher use
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
Ethanol-Water Phase Separation White Paper
Ethanol-Water Phase Separation White Paper Samir Jain Background The use of ethanol as a fuel in the United States has significantly increased over the past decade. Today, greater than 80% of all retail
Unit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 3 HYDRAULIC AND PNEUMATIC MOTORS The material needed for outcome 2 is very extensive
Fire Sprinkler Monitoring PRODUCTS. Accessories Alarm Bells Waterflow Detectors Pressure Switches Supervisory Switches Explosion-Proof
Fire Sprinkler Monitoring PRODUCTS Accessories Alarm Bells Waterflow Detectors Pressure Switches Supervisory Switches Explosion-Proof 2 Fire Sprinkler Monitoring Products During a fire condition, sprinkler
III. CHANGING BALANCE BETWEEN AGE GROUPS
Population Ageing 195-25 III. CHANGING BALANCE BETWEEN AGE GROUPS A. BROAD AGE GROUPS The young-old balance is shifting throughout the world The increasing proportions of aged persons have been accompanied,
Welcome to UL Protecting People, Products and Places
Welcome to UL Protecting People, Products and Places A symbol 22 billion ul marks appear on 69,795 manufacturers produced ul certified * 23,612 certified for energy star* of trust Facts & Figures 2014
Pacific Pump and Power
Pacific Pump and Power 91-503 Nukuawa Street Kapolei, Hawaii 96707 Phone: (808) 672-8198 or (800) 975-5112 Fax: (866) 424-0953 Email: [email protected] Web: www.pacificpumpandpower.com Pumps
Installers and specifiers seeking information and advice on radiator thermostats and their application will find no better source than Danfoss.
DOMESTIC HEATING CONTROLS ARE EASY PART 5 - RADIATOR THERMOSTATS Fig.1. RAS-C 2 and RAS-D 2 radiator thermostats with RLV-D lockshield valve Radiator Thermostats (TRVs), the original and straight forward
Users Guide. By Dr. Don J. Wood Dr. Srinivasa Lingireddy. Featuring the Surge Wizard
Users Guide By Dr. Don J. Wood Dr. Srinivasa Lingireddy Featuring the Surge Wizard Copyrighted KYPIPE LLC 2010 1 EPASurge Users Guide Overview EPASurge is a powerful transient analysis program designed
MANURE COLLECTION AND TRANSFER SYSTEMS IN LIVESTOCK OPERATIONS WITH DIGESTERS. A. C. Lenkaitis GEA Farm Technologies Inc. (Houle USA), Naperville, IL
MANURE COLLECTION AND TRANSFER SYSTEMS IN LIVESTOCK OPERATIONS WITH DIGESTERS A. C. Lenkaitis GEA Farm Technologies Inc. (Houle USA), Naperville, IL INTRODUCTION Manure collection systems are influenced
Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description The TYCO Type EA-1 PROTECTO- SPRAY Directional Spray Nozzles are automatic
Fisher 377 Trip Valve
377 Trip Valve Product Bulletin Fisher 377 Trip Valve Fisher 377 pressure sensing trip valves are for control applications where a specific valve/actuator action is required when supply pressure falls
Pressure Reducing Valve Calculation Example
Pressure Reducing Valve Calculation Example Procedure to Calculate the Pressure Values required to factory set a Pressure Reducing Valve. 1) First calculate the maximum static pressure available on the
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS
LECTURE 28 to 29 ACCUMULATORS FREQUENTLY ASKED QUESTIONS 1. Define an accumulator and explain its function A hydraulic accumulator is a device that stores the potential energy of an incompressible fluid
WORLD. Geographic Trend Report for GMAT Examinees
2011 WORLD Geographic Trend Report for GMAT Examinees WORLD Geographic Trend Report for GMAT Examinees The World Geographic Trend Report for GMAT Examinees identifies mobility trends among GMAT examinees
Flygt Ball Check Valves
4/13 Supersedes: 6/96 The basic purpose of a check valve is to permit flow in one direction, prevent flow in the opposite direction and perform this function automatically and with minimum maintenance.
Experiment # 3: Pipe Flow
ME 05 Mechanical Engineering Lab Page ME 05 Mechanical Engineering Laboratory Spring Quarter 00 Experiment # 3: Pipe Flow Objectives: a) Calibrate a pressure transducer and two different flowmeters (paddlewheel
CASE STUDY. Automotive Components. Bosch Drancy, France Brake NVH Testing. Braking Systems. France. Automotive. PULSE, Transducers
CASE STUDY Bosch Drancy, France Brake NVH Testing France Automotive PULSE, Transducers The world-renowned Bosch group is a major producer of a vast range of automotive components. The company is an OEM
TECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description
Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,
Testing Theories of Policy-Making: Educational Funding MICAH MCFADDEN
MICAH MCFADDEN This paper was written for Dr.Tures Politics of Developed Systems course. Policy-making is an essential part of every government. Each government must enact policies based on their own philosophies,