Pressure Reducing Valve Calculation Example

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "Pressure Reducing Valve Calculation Example"

Transcription

1 Pressure Reducing Valve Calculation Example Procedure to Calculate the Pressure Values required to factory set a Pressure Reducing Valve. 1) First calculate the maximum static pressure available on the supply side of the PRV at all levels. Calculate the Maximum Static Pressure at the Pump: Add the City Static Pressure to the Fire Pump Maximum Churn Pressure. The City Test and Fire Pump are at the same elevation so an elevation correction is not required. Maximum Static = 90 PSI + (150 psi x 1.18) = = 267 PSI at the pump elevation. The Maximum Static Pressure at each PRV equals the Maximum Static Pressure at the Pump reduced by the elevation above the pump. The Fire Sprinkler Outlet on the 10th floor is 110 feet above the Fire Pump. Maximum Static = 267 PSI - (110 Ft x.4331 PSI/Ft) = PSI The Hose Outlet on the 10th floor is 105 feet above the Fire Pump. Maximum Static = 267 PSI - (105 Ft x.4331 PSI/Ft) = PSI Subtract the elevation pressure to determine the Maximum Static Pressure at each Outlet. See the chart below. 2) Then calculate the demand flow and pressure required on the system side of each PRV. a) Standpipe Top hose outlet demands a flow of 250 GPM and Minimum Required Pressure of 100 PSI at the PRV outlet plus 250 GPM at the next outlet. b) Calculate the sprinkler system demand. Use a flow of 225 GPM at 110 PSI at the PRV outlet - typical each level plus 100 GPM Inside Hose allowance. 3) Next calculate the maximum residual pressure available at the demand flow on the supply side of each PRV at all levels. It will be easier to calculate the pressures for all Hose Outlets first and then the pressures for the sprinkler system outlets. For this calculation all Safety Margins are taken on the system side of the PRV and the remainder of the Standpipe and Supply Pipe will flow at the maximum pressure that the combined City and Fire Pump can provide. Calculate from the top Sprinkler System or Hose Outlets using the demand flow for each to the city supply leaving NO Safety Margin. (To find the maximum start residual pressure add the Safety Margin Pressure to your Start pressure.)

2 This is the Initial Input Screen used to calculate the maximum residual pressure available at the demand flow on the supply side of each PRV at all levels. Start with the Demand Flow (225 GPM) and Pressure (110 PSI + 10 PSI Safety). (Any start pressure will do to begin with as we will be adding the safety margin back in and recalculating.) Initial calculation is 83.8 PSI below curve. Add this to the start pressure ( ) and recalculate. Adjust the start pressure until the safety margin is equal to or very close to 0.0 PSI. Note: A separate calculation is required to find the maximum pressure for the first floor Node FS1 as this is not an outlet along the hydraulic path we are currently calculating.

3 General Calculation Program Job - Pressure Reducing Valve Calculation Example Date - 03/21/12 File - F:\HES\HydraCALC\Ver50\Data\Jobs\Pressure Reducing Valve Calculation Example.wx1Time - 09:25:02 AREA CALCULATED - HEAD FLOW SUMMARY Actual Req. Delta Actual Req. Delta ID K-Factor Flow Flow Flow. Press. Press. Press PRV n/a Pt H10 n/a Pt Total K Factors Total Fixed Flows... 2 Sum Actual Flow Sum Required Flow Sum Delta Flow Max Delta Flow Max Delta Pressure AREA CALCULATED - COMPLETE SUMMARY Start Finish Diam. Start Normal Pf Elev/Fixed Flow Vel Point Point Pres. Pres. Pres. PRV <- FS FS10 <- H H10 <- FS FS9 <- H H9 <- FS FS8 <- H H8 <- FS FS7 <- H H7 <- FS FS6 <- H H6 <- FS FS5 <- H H5 <- FS FS4 <- H H4 <- FS FS3 <- H H3 <- FS FS2 <- H H2 <- SP SP1 <- TOR TOR <- BOR BOR <- PMPO System Demand Pressure Safety Margin Pump Outlet Press. From Pump Curve ( PMPI - PMPO ) Pump Inlet PMPI <- UG UG1 <- TEST Total Flow Pipe with highest velocity: PRV - FS10 (15.078) Water Supply Point TEST Total Flow From Water Supply Curve Pressure From Water Supply Curve System Pressure Demand At Supply Curve Safety Margin at Supply Curve

4 4) Fill in the Specification Chart with the required hydraulic information for the manufacturer. The maximum residual pressure available at the Fire Sprinkler system demand at the 10 th Floor PRV is shown below. The maximum residual pressure available at the Fire Sprinkler system PRV for all the other floors can be quickly found by subtracting the friction loss of the 2 ½ pipe from the pressure available at each Fire Sprinkler system node along the standpipe. Examples - (At node FS = PSI) (At node FS = PSI) All the maximum residual pressures can now be supplied to the PRV manufacturer. Shown are values for the Fire Sprinkler System for the 10 th and 2 nd floors. Note: The actual required pressure on the system side of the PRV must include the safety margin desired. Therefore, the minimum pressure required is 120 PSI = 110 PSI as calculated + (10 PSI Safety). The Fire Sprinkler System Demand Flow is 225 GPM with a required Pressure of 120 PSI.

5 Repeat the calculation to determine the maximum residual pressure available at the Hose PRV for all the floors. Initial Input Screen used to calculate the maximum residual pressure available at the hose flow on the supply side of each PRV at all levels. The Standpipe Top hose outlet demands a flow of 250 GPM and Minimum Pressure of 100 PSI at the PRV outlet plus 250 GPM at the next outlet. (Any start pressure will do to begin with as we will be adding the safety margin back in and recalculating until there is no safety margin remaining.)

6 General Calculation Program Job - Pressure Reducing Valve Calculation Example Date - 03/21/12 File - F:\HES\HydraCALC\Ver50\Data\Jobs\Pressure Reducing Valve Calculation Example.wx1Time - 10:35:40 AREA CALCULATED - HEAD FLOW SUMMARY Actual Req. Delta Actual Req. Delta ID K-Factor Flow Flow Flow. Press. Press. Press PRV n/a Pt H9 n/a Pt Total K Factors Total Fixed Flows... 2 Sum Actual Flow Sum Required Flow Sum Delta Flow Max Delta Flow Max Delta Pressure AREA CALCULATED - COMPLETE SUMMARY Start Finish Diam. Start Normal Pf Elev/Fixed Flow Vel Point Point Pres. Pres. Pres. PRV <- H H10 <- FS FS9 <- H H9 <- FS FS8 <- H H8 <- FS FS7 <- H H7 <- FS FS6 <- H H6 <- FS FS5 <- H H5 <- FS FS4 <- H H4 <- FS FS3 <- H H3 <- FS FS2 <- H H2 <- SP SP1 <- TOR TOR <- BOR BOR <- PMPO System Demand Pressure Safety Margin Pump Outlet Press. From Pump Curve ( PMPI - PMPO ) Pump Inlet PMPI <- UG UG1 <- TEST Total Flow Pipe with highest velocity: PRV - H10 (16.753) Water Supply Point TEST Total Flow From Water Supply Curve Pressure From Water Supply Curve System Pressure Demand At Supply Curve Safety Margin at Supply Curve

7 The maximum residual pressure available at the Standpipe demand at the 10th Floor Hose PRV is shown below. The maximum residual pressure available at the Hose PRV for all the other floors can be quickly found by subtracting the friction loss of the 2 ½ pipe from the pressure available at each Standpipe Hose node along the standpipe. Examples - (At node FS = PSI) (At node H = PSI) All the maximum residual pressures can now be supplied to the PRV manufacturer.

8 Below is an example of a field adjustable PRV made by Elkhart Brass Fire Fighting Equipment. Follow the manufacturer s guide for proper field adjustment of the pressure reducing valves. Similar hydraulic pressure information is required in order to factory set or to field adjust a PRV.

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

Vemco, Inc. [ CALCULATING SYSTEM CURVE ] Advanced Analysis of Pumping Systems Requires and Understanding of "System Curve"

Vemco, Inc. [ CALCULATING SYSTEM CURVE ] Advanced Analysis of Pumping Systems Requires and Understanding of System Curve 2012 Vemco, Inc. [ CALCULATING SYSTEM CURVE ] Advanced Analysis of Pumping Systems Requires and Understanding of "System Curve" In order to analyze many pumping systems, a thorough understanding of "System

More information

Pressure Limiting Driver (PLD)

Pressure Limiting Driver (PLD) Pressure Limiting Driver (PLD) Discharge Pressure Control Suction Pressure Control June 9 2009 Mark Evans Clarke Fire Protection Products Justin Strousse Clarke Fire Protection Products Overview Discharge

More information

DRILL OF THE MONTH. REFERENCES: Pumping Apparatus Driver Operator Handbook, 3 rd Edition,

DRILL OF THE MONTH. REFERENCES: Pumping Apparatus Driver Operator Handbook, 3 rd Edition, DRILL OF THE MONTH DRILL TOPIC: FIRE GROUND HYDRAULICS REVIEW TIME REQUIRED: 2-3 HOURS MATERIALS: Dry Erase Board, Flip Chart, Handouts REFERENCES: Pumping Apparatus Driver Operator Handbook, 3 rd Edition,

More information

NFPA 14 3.3.5 4.2.3.2

NFPA 14 3.3.5 4.2.3.2 NFPA 14 3.3.5 3.3.5 High-Rise Building. A building where the floor of an occupiable story is greater than 55 ft (17 m) 75 ft (23 m) above the lowest level of fire department vehicle access. 4.2.3.2 4.2.3.2

More information

City of South Salt Lake Fire Marshal Regulations for Water Based Fire Protection and Water Supply Systems

City of South Salt Lake Fire Marshal Regulations for Water Based Fire Protection and Water Supply Systems City of South Salt Lake Fire Marshal Regulations for Water Based Fire Protection and Water Supply Systems Rev. Oct. 2012 1 Fire Flow 508.1 Required water supply. An approved water supply capable of supplying

More information

DPO Hydraulics Refresher

DPO Hydraulics Refresher DPO Hydraulics Refresher References: Pumping Apparatus Driver/Operator Handbook-IFSTA Essentials of Firefighting Handbook-IFSTA Fire Stream Practices-IFSTA INTRODUCTION To produce effective fire streams,

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water

More information

Fire Pump Layout and Sizing. Victoria B. Valentine, P.E.

Fire Pump Layout and Sizing. Victoria B. Valentine, P.E. Fire Pump Layout and Sizing Victoria B. Valentine, P.E. Learning Outcomes Identify the appropriate sections of NFPA 20 that apply to sizing and layout of fire pumps. Identify the components of a fire pump

More information

C. Is the applicable code (NFPA 13, 13R, 13D, 14, 20) and edition correct and shown on the drawing?

C. Is the applicable code (NFPA 13, 13R, 13D, 14, 20) and edition correct and shown on the drawing? Fire Suppression Plan Review General A. Are the shop drawings on the contractor s title block? B. Do the drawings meet the engineer design documents? C. Is the applicable code (NFPA 13, 13R, 13D, 14, 20)

More information

1.02 Scope of Work A. Provide a complete fire pump system as defined by the latest edition of NFPA 20

1.02 Scope of Work A. Provide a complete fire pump system as defined by the latest edition of NFPA 20 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fire pumps. This document is not intended to serve as a guide specification.

More information

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes

More information

SPRINKLER SYSTEM HYDRAULICS

SPRINKLER SYSTEM HYDRAULICS G.1.1.1.1 ublication of Global sset rotection Services LLC SRINKLER SYSTEM HYDRULICS INTRODUCTION The two basic methods for designing sprinkler systems are the pipe schedule method and the hydraulic design

More information

CHAPTER 8 WATER DISTRIBUTION SYSTEMS

CHAPTER 8 WATER DISTRIBUTION SYSTEMS CHAPTER 8 WATER DISTRIBUTION SYSTEMS Distribution system is a network of pipelines that distribute water to the consumers. They are designed to adequately satisfy the water requirement for a combination

More information

SIZING OF WATER PIPING SYSTEM

SIZING OF WATER PIPING SYSTEM SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures

More information

Pacific Pump and Power

Pacific Pump and Power Pacific Pump and Power 91-503 Nukuawa Street Kapolei, Hawaii 96707 Phone: (808) 672-8198 or (800) 975-5112 Fax: (866) 424-0953 Email: sales@pacificpumpandpower.com Web: www.pacificpumpandpower.com Pumps

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Fire Pump Testing Requirements & Practices. Tom Jordan, FPE Facilities Engineering Cornell university

Fire Pump Testing Requirements & Practices. Tom Jordan, FPE Facilities Engineering Cornell university Fire Pump Testing Requirements & Practices Tom Jordan, FPE Facilities Engineering Cornell university Who s in the Audience? Presentation Outline Cornell and its systems Pressure and flow Fire pumps explained

More information

Design & Construction Standards, Revised January 2013 5.21.10-1

Design & Construction Standards, Revised January 2013 5.21.10-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

Friction Loss Charts 2008

Friction Loss Charts 2008 Irrigation Association Friction Loss Charts 2008 Tables are based upon the following Hazen-Williams Equation: H f = 0.2083 100 C 1.852 Q1.852 D 4.866 The result is multiplied by 0.433 to give pounds per

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

ESTIMATING FIRE PROTECTION WATER DEMANDS

ESTIMATING FIRE PROTECTION WATER DEMANDS GAP.14.1.1.0 A Publication of Global Asset Protection Services LLC ESTIMATING FIRE PROTECTION WATER DEMANDS INTRODUCTION What constitutes an adequate water supply has generated much discussion over the

More information

PRESSURE REGULATOR FOR USE IN ALL IRRIGATION SYSTEMS

PRESSURE REGULATOR FOR USE IN ALL IRRIGATION SYSTEMS REGULATOR FOR USE IN ALL IRRIGATION SYSTEMS SPECIFICATIONS Sealed regulating units, field replaceable (2000 Series) Built in indicator pops out when proper pressure is achieved (2000 Series) Accurate regulator

More information

NFPA 14 Standpipes & Hose Valves Presented by American Fire Sprinkler Association DISCLAIMER 1/26/15. To receive credit for this seminar:

NFPA 14 Standpipes & Hose Valves Presented by American Fire Sprinkler Association DISCLAIMER 1/26/15. To receive credit for this seminar: NFPA 14 Standpipes & Hose Valves Presented by American Fire Sprinkler Association 1 www.firesprinkler.org 2 DISCLAIMER This seminar and its content is not a formal interpretation issued pursuant to NFPA

More information

Pressure Drop Basics & Valve Sizing

Pressure Drop Basics & Valve Sizing Pressure Drop Basics & Valve Sizing What is Pressure Drop? The difference in pressure between two points in a system, caused by resistance to flow. What Pressure Drop is Not? Pressure drop is pressure

More information

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority

More information

Hose Operations. Lynbrook Fire Department Training Committee

Hose Operations. Lynbrook Fire Department Training Committee Hose Operations Lynbrook Fire Department Training Committee Introduction Types and sizes of Fire Hose Basic Engine Operation Hose Evolutions Hose Handling Water Flow (Volume) Reach Vocabulary Volume Pressure

More information

Operating, Installation, and Maintenance Instructions

Operating, Installation, and Maintenance Instructions ELKHART BRASS MFG. CO., INC. 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 Operating, Installation, and Maintenance Instructions RAM Personal Portable Monitor

More information

ON-LOT SEWAGE DISPOSAL PROGRAM DESIGN OF PRESSURE-DOSED ELEVATED SAND MOUND BED

ON-LOT SEWAGE DISPOSAL PROGRAM DESIGN OF PRESSURE-DOSED ELEVATED SAND MOUND BED ON-LOT SEWAGE DISPOSAL PROGRAM DESIGN OF PRESSURE-DOSED ELEVATED SAND MOUND BED INSTRUCTIONS In order to design an elevated sand mound bed using pressure dosing which meets Pennsylvania Department of Environmental

More information

Valve Pressure Loss & Flow

Valve Pressure Loss & Flow Valve Pressure Loss & Flow The valve coefficient, Cv, is a number which represents the capability of a valve (or any flow component) to flow a fluid. The larger the Cv, the larger the flow at a given pressure

More information

Hydraulic Modeling: Pipe Network Analysis

Hydraulic Modeling: Pipe Network Analysis Utah State University DigitalCommons@USU All Graduate Plan B and other Reports Graduate Studies 12-2012 Hydraulic Modeling: Pipe Network Analysis Trevor T. Datwyler Utah State University Follow this and

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

LIVESTOCK WATER SYSTEM DESIGN #2. Selecting Small Diameter Pipe

LIVESTOCK WATER SYSTEM DESIGN #2. Selecting Small Diameter Pipe Livestock Watering Order No. 590.304-2 January 2006 LIVESTOCK WATER SYSTEM DESIGN #2 Selecting Small Diameter Pipe This Factsheet describes types of pipe, pressure rating systems used, and how to select

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Hydrant flow testing data provides important

Hydrant flow testing data provides important feat40606.qxd 5/30/06 5:24 PM Page 44 The use of hydrant flow testing data to design automatic sprinkler systems has gotten easier thanks to new computer modeling software. By Dr. Sang H. Wong Hydrant

More information

Firefighter Review. Instructor Guide

Firefighter Review. Instructor Guide Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing

More information

Saving Water with Pressure Regulation and Check Valves Introduction to Hydraulics

Saving Water with Pressure Regulation and Check Valves Introduction to Hydraulics Saving Water with Pressure Regulation and Check Valves Introduction to Hydraulics Greg Palumbo Product Manager Commercial Sprays gpalumbo@rainbird.com David Perl Product Manager Commercial Rotors dperl@rainbird.com

More information

FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY

FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY INSPECTION...49 FORM F-3 AUTOMATIC SPRINKLER SYSTEMS QUARTERLY

More information

GCO 2431 Irrigation 1

GCO 2431 Irrigation 1 GCO 2431 Irrigation 1 BASIC HYDRAULICS & SYSTEM DESIGN IRRIGATION INSTRUCTOR Doug Callison Area Specifications Manager 1/4/98 DESIGN TERMINOLOGY Scale = mechanical or engineering measurements. Plan view

More information

Principles of Relay Pump Operations

Principles of Relay Pump Operations Principles of Relay Pump Operations September 2003 Slide 5-5-1 Relay Pumping Principles Relay 2+ pumpers move water from distances that would require excessive pressures if only one pumper is employed

More information

Automatic Sprinkler System Calculations

Automatic Sprinkler System Calculations SECTION FOUR CHAPTER 3 Automatic Sprinkler System Calculations Russell P. Fleming Introduction Applications Where Water Is Appropriate Water is the most commonly used fire extinguishing agent, mainly due

More information

Choosing a Pump for Rainwater Harvesting

Choosing a Pump for Rainwater Harvesting Choosing a Pump for Rainwater Harvesting Introduction Water harvesting is the practice of capturing rainwater runoff, normally from a rooftop, and storing it in a tank or cistern for use around a home

More information

Fire Protection Water Supply Information Packet. Commercial and Residential. Exeter Township Fire Department Office of the Fire Marshal

Fire Protection Water Supply Information Packet. Commercial and Residential. Exeter Township Fire Department Office of the Fire Marshal Fire Protection Water Supply Information Packet Commercial and Residential Exeter Township Fire Department Office of the Fire Marshal 2007 1 PURPOSE The regulations governing water supplies for fire protection

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified. 13D Residential Sprinkler System Plan Review Checklist 2010 OFC and 2007 NFPA 13D Date of Review: Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor:

More information

2011 NFPA 25 Standpipe Testing Excerpts

2011 NFPA 25 Standpipe Testing Excerpts 2011 NFPA 25 Standpipe Testing Excerpts 6.3 Testing Where water damage is a possibility, an air test shall be conducted on the system at 25 psi (1.7 bar) prior to introducing water to the system. Extreme

More information

FOUNTAIN PUMP SYSTEM DESIGN. by Jacques Chaurette p. eng.

FOUNTAIN PUMP SYSTEM DESIGN. by Jacques Chaurette p. eng. FOUNTAIN PUMP SYSTEM DESIGN by Jacques Chaurette p. eng. page.2 NEW FOUNTAIN PUMP SYSTEM CALCULATIONS AND PUMP SELECTION To select a centrifugal pump that is appropriate for a fountain design we need to

More information

FOAM PROPORTIONING & LOOSE EQUIPMENT SECTION INDEX

FOAM PROPORTIONING & LOOSE EQUIPMENT SECTION INDEX FOAM PROPORTIONING & LOOSE EQUIPMENT SECTION INDEX Williams High Head Through-the-Pump 1500 Portable Foam System... J2 Williams Pressure Reducing Valve (WPRV/3, 3P, 4 & 4P)...J3 Tank Farm Fire Fighting

More information

UNDERSTANDING GRAVITY-FLOW PIPELINES. Water Flow, Air Locks and Siphons

UNDERSTANDING GRAVITY-FLOW PIPELINES. Water Flow, Air Locks and Siphons Livestock Watering Order No. 590.304-5 January 2006 UNDERSTANDING GRAVITY-FLOW PIPELINES Water Flow, Air Locks and Siphons This Factsheet discusses the problems and solutions of gravity flow pipe system

More information

DOMESTIC WATER PIPE SIZING

DOMESTIC WATER PIPE SIZING INFORMATION BULLETIN / PUBLIC - PLUMBING CODE REFERENCE NO.: LAPC 610.5 & 610.11 Effective: 01-01-2014 DOCUMENT NO.: P/PC 2014-009 Revised: Previously Issued As: P/PC 2011-009 DOMESTIC WATER PIPE SIZING

More information

Developed by Lieutenant Bryan Clark December 2010

Developed by Lieutenant Bryan Clark December 2010 S TANDPIPE O PERATIONS(1.1) NFPA 14 NFPA 13E Developed by Lieutenant Bryan Clark December 2010 T ASK S KILL DESCRIPTION AND DETAIL Firefighting in buildings equipped with standpipes is challenging, and

More information

NOTE: The Hydrant in the circle is the test Hydrant. Residual and Static flows are measured here. Loop

NOTE: The Hydrant in the circle is the test Hydrant. Residual and Static flows are measured here. Loop NOTE: The Hydrant in the circle is the test Hydrant. Residual and Static flows are measured here. Figure 1 Loop Test Hydrant (Choose Either) Measure Residual & Static Pressures Dead End Main - Water One

More information

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style

More information

Booster Pump and Ejector Nozzle Selection

Booster Pump and Ejector Nozzle Selection Introduction: Booster Pump and Ejector Nozzle Selection Hydro Instruments offers a standard nozzle for each of our ejectors. However, we also offer alternate nozzle choices for each ejector. Each nozzle

More information

DETERMINING TOTAL DYNAMIC HEAD

DETERMINING TOTAL DYNAMIC HEAD DETERMINING TOTAL DYNAMIC HEAD The total dynamic head of a water system must be considered when determining the size of pumping equipment to be installed. It determines the various head losses that the

More information

NFPA 13R 1.1 5.1.3 5.2.1

NFPA 13R 1.1 5.1.3 5.2.1 NFPA 13R 1.1 1.1 Scope This standard covers the design and installation of automatic sprinkler systems for protection against fire hazards in residential occupancies up to and including two four stories

More information

NFPA 13D

NFPA 13D NFPA 13D 1.1 1.1 This standard shall cover the design and installation of automatic sprinkler systems for protection against the fire hazards in one- and two-family dwellings and manufactured homes. When

More information

Water Supply. Simulation of Water Distribution Networks. Mohammad N. Almasri. Optimal Design of Water Distribution Networks Mohammad N.

Water Supply. Simulation of Water Distribution Networks. Mohammad N. Almasri. Optimal Design of Water Distribution Networks Mohammad N. Water Supply Simulation of Water Distribution Networks The Use of EPANET Mohammad N. Almasri 1 Introduction This presentation focuses on two issues: The simulation of water distribution networks (WDNs)

More information

FIRE DEPARTMENT HYDRAULICS

FIRE DEPARTMENT HYDRAULICS FIRE DEPARTMENT HYDRAULICS BASIC CONCEPTS & FORMULAS WATER MEASUREMENTS 1 Cubic foot of water weighs 62.5 pounds 1 Cubic foot of water contains 1,728 cubic inches 1 Cubic foot of water contains 7.5 gallons

More information

Fire Protection Equipment

Fire Protection Equipment 123456 Fire Protection Equipment #SVL100 Model 353 Alarm Valves "Automatic" Sprinkler 150 Gordon Drive Exton, PA 19341 USA Tel: (610) 3631400 8006262682 Fax: (610) 5249073 8008586857 www.kiddefire.com

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

Toms River Fire Academy

Toms River Fire Academy Pump School Manual Toms River Fire Academy Table of contents Chapter 1 Characteristics of Water Page 3 Pressures, Atmospheric, Static, Residual, Head.Page 7 Chapter 2 Pump Construction and Gauges Page

More information

Module 9: Flow Rate 4/29/2015. Introduction. Introduction. When you complete this lesson, you should be able to: AWWA Hydraulics

Module 9: Flow Rate 4/29/2015. Introduction. Introduction. When you complete this lesson, you should be able to: AWWA Hydraulics Module 9: AWWA Hydraulics Introduction When you complete this lesson, you should be able to: Calculate flow rate in open channel and fullflowing pipes. Introduction Recall the discussion of average and

More information

15401 GENERAL REQUIREMENTS FIRE PROTECTION DESIGN CRITERIA SPRINKLER EQUIPMENT STANDPIPE AND FIRE HOSE EQUIPMENT

15401 GENERAL REQUIREMENTS FIRE PROTECTION DESIGN CRITERIA SPRINKLER EQUIPMENT STANDPIPE AND FIRE HOSE EQUIPMENT SECTION 15400 - FIRE PROTECTION SYSTEMS SECTION DESCRIPTION 15401 GENERAL REQUIREMENTS 15402 FIRE PROTECTION DESIGN CRITERIA 15403 SPRINKLER EQUIPMENT 15404 FIRE PUMPS 15405 STANDPIPE AND FIRE HOSE EQUIPMENT

More information

One of the fundamental design elements that every

One of the fundamental design elements that every Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things

More information

Chapter 11 Pump Ops 1

Chapter 11 Pump Ops 1 1. The process for making the fire pump operational begins: a. En route to the emergency scene b. Immediately after receiving dispatch c. After connecting to the water source and determining proper operating

More information

The Jockey Pump, an Important Part of a Fire Pump System.

The Jockey Pump, an Important Part of a Fire Pump System. The Jockey Pump, an Important Part of a Fire Pump System. May 18, 2008 A Jockey Pump is an important component of a fire pump system. The Jockey Pump is not as mundane, as many engineers, contractors and

More information

CHAPTER 2: The Plumbing System

CHAPTER 2: The Plumbing System CHAPTER 2: The Plumbing System SECTION I: SIZING REQUIREMENTS Establish building dimensions Building height can be determined either by architectural drawings or # of floors times height/floor. (ex: 1

More information

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE. SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION

More information

The In-Line Gauge in Standpipe Operations

The In-Line Gauge in Standpipe Operations The In-Line Gauge in Standpipe Operations BY RUSS CHAPMAN Your engine company receives a report of fire in a mid-rise elderly housing complex during morning coffee at the beginning of a shift. You know

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29 _02 A centrifugal with a 12 in. diameter impeller requires a power input of 60 hp when the flowrate is 3200 gpm against a 60 ft head. The impeller is changed to one with a 10 in. diameter. Determine the

More information

Open Channel Diffusers

Open Channel Diffusers Open Channel Diffusers Application Information: Open channel diffusers are used to increase mixing and absorbance efficiency of a chemical solution into the process water. Specifically designed penetrations

More information

Delta Power Company 4484 Boeing Drive - Rockford, IL 61109

Delta Power Company 4484 Boeing Drive - Rockford, IL 61109 INDEX Description Page Delta Power Rotary Flow Divider, Positive Displacement (Application Data) 36 P Series, Equal Flow Two Sections 39 P Series, Equal Flow Multi-Sections 40 PM Series, Equal Flow Multi-Sections

More information

Minor losses include head losses through/past hydrants, couplers, valves,

Minor losses include head losses through/past hydrants, couplers, valves, Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within

More information

Hayward Hydraulics and Pump Sizing For Existing Pools

Hayward Hydraulics and Pump Sizing For Existing Pools Hayward Hydraulics and Pump Sizing For Existing Pools Copyright 2011 Hayward Industries Table of Contents Introduction Page 1 Hydraulic Terms & Definitions Pages 2-4 Hydraulic Example Page 5 How To Determine

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

Water hammering in fire fighting installation

Water hammering in fire fighting installation Water hammering in fire fighting installation Forward One of major problems raised in the fire fighting network installed at Pioneer company for pharmaceutical industry /Sulaymania was the high water hammering

More information

HIGH VISCOSITY FILTER SYSTEMS

HIGH VISCOSITY FILTER SYSTEMS HIGH VISCOSITY FILTER SYSTEMS High Viscosity Filter Cart P/N 36970 High Viscosity Hand Held P/N 36971 Owner's Manual Table of Contents Customer Satisfaction...2 Introduction...3 Typical Applications...3

More information

DEPARTMENT OF PUBLIC WORKS STANDARD SPECIFICATION FOR DOMESTIC AND FIRE WATER STORAGE AND FIRE WATER SUPPLY FOR PUBLIC BUILDINGS

DEPARTMENT OF PUBLIC WORKS STANDARD SPECIFICATION FOR DOMESTIC AND FIRE WATER STORAGE AND FIRE WATER SUPPLY FOR PUBLIC BUILDINGS PW 345 DEPARTMENT OF PUBLIC WORKS STANDARD SPECIFICATION FOR DOMESTIC AND FIRE WATER STORAGE AND FIRE WATER SUPPLY FOR PUBLIC BUILDINGS MAY 2004 DEPARTMENT OF PUBLIC WORKS STANDARD SPECIFICATION FOR DOMESTIC

More information

Module 9: Basics of Pumps and Hydraulics Instructor Guide

Module 9: Basics of Pumps and Hydraulics Instructor Guide Module 9: Basics of Pumps and Hydraulics Instructor Guide Activities for Unit 1 Basic Hydraulics Activity 1.1: Convert 45 psi to feet of head. 45 psis x 1 ft. = 103.8 ft 0.433 psi Activity 1.2: Determine

More information

Energy Efficiency Considerations in Pumps and Pump Stations

Energy Efficiency Considerations in Pumps and Pump Stations Energy Efficiency Considerations in Pumps and Pump Stations Jeff Foray, P.E. (JeffForay@KennedyJenks.com) WSU Extension Energy Program 14 March 2014 How Do You Save Energy? Don t design it wrong Operate

More information

Big Water 101. Blackwood Fire Company Engine Company Training

Big Water 101. Blackwood Fire Company Engine Company Training Big Water 101 Blackwood Fire Company Engine Company Training Engine Work The job of the engine is to get water on the fire. Plain and simple. Accomplishing that can be a problem depending on the circumstances.

More information

AURORA PACKAGED FIRE PUMP SYSTEMS

AURORA PACKAGED FIRE PUMP SYSTEMS AURORA PACKAGED FIRE PUMP SYSTEMS AURORA Packaged Fire Pump Systems At the heart of our systems you ll find the Aurora pumps you ve relied on for over 90 years. Aurora offers custom and pre-engineered

More information

Index 11.1. Page. Pumping Systems...11.2-11.4 Intensifiers...11.5 Gas Boosters...11.6-11.7 High Pressure Generators...11.8-11.9

Index 11.1. Page. Pumping Systems...11.2-11.4 Intensifiers...11.5 Gas Boosters...11.6-11.7 High Pressure Generators...11.8-11.9 Pumping Systems, Intensifiers, Gas Boosters and High Pressure Generators High Pressure Equipment Company produces a number of components and systems for general industrial, elevated pressure applications.

More information

Pipe Sizes For Water Distribution System Design

Pipe Sizes For Water Distribution System Design Appendix D Pipe Sizes For Water Distribution System Design D-. This appendix contains information to help determine pipe sizes when designing a water distribution system. Use Table D- and Tables D- through

More information

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2. May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use

More information

Introduction to Water Pipe Sizing

Introduction to Water Pipe Sizing ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920 Introduction to Understanding the Many Methods to Size Water Pipe Presented by: Rainier Bratsch-Blundel, CPSI Plumbing Professor

More information

Tracking Number 50i47r3 Revision to NSF/ANSI NSF International Issue 47, Revision 3 (September 2013)

Tracking Number 50i47r3 Revision to NSF/ANSI NSF International Issue 47, Revision 3 (September 2013) NSF/ANSI Standard Equipment for Swimming Pools, Spas, Hot Tubs and other Recreational Water Facilities Evaluation criteria for materials, components, products, equipment and systems for use at recreational

More information

Theory, Application, and Sizing of Air Valves

Theory, Application, and Sizing of Air Valves Theory, Application, and Sizing of Air Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com 1 THEORY, APPLICATION,

More information

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps

More information

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS FAIRBANKS NIJHUIS Packaged Fire Pump Systems At the heart of our systems you ll find the Fairbanks Nijhuis pumps you ve relied on for over 90 years. Fairbanks

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID

More information

Springdale Fire Department Backup Driver Certification Program. Behavioral Objectives

Springdale Fire Department Backup Driver Certification Program. Behavioral Objectives Springdale Fire Department Backup Driver Certification Program Backup Driver Task Book I. Obtain required prerequisites 1. Performance a. Complete Probationary Program b. Complete CEVO Fire Course c. Complete

More information

BASIC PUMPING STANDARD OPERATING GUIDELINE

BASIC PUMPING STANDARD OPERATING GUIDELINE BASIC PUMPING STANDARD OPERATING GUIDELINE DATE APPROVED: March 2008 DATE REVISED: June 2014 I. Scope This standard establishes a guideline for pumping a fire apparatus. II. Definitions 1. Appliance A

More information

Selecting a Vertical Turbine Pump (Information required from client)

Selecting a Vertical Turbine Pump (Information required from client) Selecting a Vertical Turbine Pump (Information required from client) 1. Liquid to be pumped: (Note: If liquid is not clear water, the following must also be ascertained). a. Foreign material present in

More information

Project Address (Mandatory) The project address must be printed in the title block of every sheet in the plan set.

Project Address (Mandatory) The project address must be printed in the title block of every sheet in the plan set. Cicero The following information is required for the issuance of a building permit. The mandatory items are required to be submitted as part of the initial submittal, but it is advisable to submit all

More information