Pressure Reducing Valve Calculation Example

Size: px
Start display at page:

Download "Pressure Reducing Valve Calculation Example"

Transcription

1 Pressure Reducing Valve Calculation Example Procedure to Calculate the Pressure Values required to factory set a Pressure Reducing Valve. 1) First calculate the maximum static pressure available on the supply side of the PRV at all levels. Calculate the Maximum Static Pressure at the Pump: Add the City Static Pressure to the Fire Pump Maximum Churn Pressure. The City Test and Fire Pump are at the same elevation so an elevation correction is not required. Maximum Static = 90 PSI + (150 psi x 1.18) = = 267 PSI at the pump elevation. The Maximum Static Pressure at each PRV equals the Maximum Static Pressure at the Pump reduced by the elevation above the pump. The Fire Sprinkler Outlet on the 10th floor is 110 feet above the Fire Pump. Maximum Static = 267 PSI - (110 Ft x.4331 PSI/Ft) = PSI The Hose Outlet on the 10th floor is 105 feet above the Fire Pump. Maximum Static = 267 PSI - (105 Ft x.4331 PSI/Ft) = PSI Subtract the elevation pressure to determine the Maximum Static Pressure at each Outlet. See the chart below. 2) Then calculate the demand flow and pressure required on the system side of each PRV. a) Standpipe Top hose outlet demands a flow of 250 GPM and Minimum Required Pressure of 100 PSI at the PRV outlet plus 250 GPM at the next outlet. b) Calculate the sprinkler system demand. Use a flow of 225 GPM at 110 PSI at the PRV outlet - typical each level plus 100 GPM Inside Hose allowance. 3) Next calculate the maximum residual pressure available at the demand flow on the supply side of each PRV at all levels. It will be easier to calculate the pressures for all Hose Outlets first and then the pressures for the sprinkler system outlets. For this calculation all Safety Margins are taken on the system side of the PRV and the remainder of the Standpipe and Supply Pipe will flow at the maximum pressure that the combined City and Fire Pump can provide. Calculate from the top Sprinkler System or Hose Outlets using the demand flow for each to the city supply leaving NO Safety Margin. (To find the maximum start residual pressure add the Safety Margin Pressure to your Start pressure.)

2 This is the Initial Input Screen used to calculate the maximum residual pressure available at the demand flow on the supply side of each PRV at all levels. Start with the Demand Flow (225 GPM) and Pressure (110 PSI + 10 PSI Safety). (Any start pressure will do to begin with as we will be adding the safety margin back in and recalculating.) Initial calculation is 83.8 PSI below curve. Add this to the start pressure ( ) and recalculate. Adjust the start pressure until the safety margin is equal to or very close to 0.0 PSI. Note: A separate calculation is required to find the maximum pressure for the first floor Node FS1 as this is not an outlet along the hydraulic path we are currently calculating.

3 General Calculation Program Job - Pressure Reducing Valve Calculation Example Date - 03/21/12 File - F:\HES\HydraCALC\Ver50\Data\Jobs\Pressure Reducing Valve Calculation Example.wx1Time - 09:25:02 AREA CALCULATED - HEAD FLOW SUMMARY Actual Req. Delta Actual Req. Delta ID K-Factor Flow Flow Flow. Press. Press. Press PRV n/a Pt H10 n/a Pt Total K Factors Total Fixed Flows... 2 Sum Actual Flow Sum Required Flow Sum Delta Flow Max Delta Flow Max Delta Pressure AREA CALCULATED - COMPLETE SUMMARY Start Finish Diam. Start Normal Pf Elev/Fixed Flow Vel Point Point Pres. Pres. Pres. PRV <- FS FS10 <- H H10 <- FS FS9 <- H H9 <- FS FS8 <- H H8 <- FS FS7 <- H H7 <- FS FS6 <- H H6 <- FS FS5 <- H H5 <- FS FS4 <- H H4 <- FS FS3 <- H H3 <- FS FS2 <- H H2 <- SP SP1 <- TOR TOR <- BOR BOR <- PMPO System Demand Pressure Safety Margin Pump Outlet Press. From Pump Curve ( PMPI - PMPO ) Pump Inlet PMPI <- UG UG1 <- TEST Total Flow Pipe with highest velocity: PRV - FS10 (15.078) Water Supply Point TEST Total Flow From Water Supply Curve Pressure From Water Supply Curve System Pressure Demand At Supply Curve Safety Margin at Supply Curve

4 4) Fill in the Specification Chart with the required hydraulic information for the manufacturer. The maximum residual pressure available at the Fire Sprinkler system demand at the 10 th Floor PRV is shown below. The maximum residual pressure available at the Fire Sprinkler system PRV for all the other floors can be quickly found by subtracting the friction loss of the 2 ½ pipe from the pressure available at each Fire Sprinkler system node along the standpipe. Examples - (At node FS = PSI) (At node FS = PSI) All the maximum residual pressures can now be supplied to the PRV manufacturer. Shown are values for the Fire Sprinkler System for the 10 th and 2 nd floors. Note: The actual required pressure on the system side of the PRV must include the safety margin desired. Therefore, the minimum pressure required is 120 PSI = 110 PSI as calculated + (10 PSI Safety). The Fire Sprinkler System Demand Flow is 225 GPM with a required Pressure of 120 PSI.

5 Repeat the calculation to determine the maximum residual pressure available at the Hose PRV for all the floors. Initial Input Screen used to calculate the maximum residual pressure available at the hose flow on the supply side of each PRV at all levels. The Standpipe Top hose outlet demands a flow of 250 GPM and Minimum Pressure of 100 PSI at the PRV outlet plus 250 GPM at the next outlet. (Any start pressure will do to begin with as we will be adding the safety margin back in and recalculating until there is no safety margin remaining.)

6 General Calculation Program Job - Pressure Reducing Valve Calculation Example Date - 03/21/12 File - F:\HES\HydraCALC\Ver50\Data\Jobs\Pressure Reducing Valve Calculation Example.wx1Time - 10:35:40 AREA CALCULATED - HEAD FLOW SUMMARY Actual Req. Delta Actual Req. Delta ID K-Factor Flow Flow Flow. Press. Press. Press PRV n/a Pt H9 n/a Pt Total K Factors Total Fixed Flows... 2 Sum Actual Flow Sum Required Flow Sum Delta Flow Max Delta Flow Max Delta Pressure AREA CALCULATED - COMPLETE SUMMARY Start Finish Diam. Start Normal Pf Elev/Fixed Flow Vel Point Point Pres. Pres. Pres. PRV <- H H10 <- FS FS9 <- H H9 <- FS FS8 <- H H8 <- FS FS7 <- H H7 <- FS FS6 <- H H6 <- FS FS5 <- H H5 <- FS FS4 <- H H4 <- FS FS3 <- H H3 <- FS FS2 <- H H2 <- SP SP1 <- TOR TOR <- BOR BOR <- PMPO System Demand Pressure Safety Margin Pump Outlet Press. From Pump Curve ( PMPI - PMPO ) Pump Inlet PMPI <- UG UG1 <- TEST Total Flow Pipe with highest velocity: PRV - H10 (16.753) Water Supply Point TEST Total Flow From Water Supply Curve Pressure From Water Supply Curve System Pressure Demand At Supply Curve Safety Margin at Supply Curve

7 The maximum residual pressure available at the Standpipe demand at the 10th Floor Hose PRV is shown below. The maximum residual pressure available at the Hose PRV for all the other floors can be quickly found by subtracting the friction loss of the 2 ½ pipe from the pressure available at each Standpipe Hose node along the standpipe. Examples - (At node FS = PSI) (At node H = PSI) All the maximum residual pressures can now be supplied to the PRV manufacturer.

8 Below is an example of a field adjustable PRV made by Elkhart Brass Fire Fighting Equipment. Follow the manufacturer s guide for proper field adjustment of the pressure reducing valves. Similar hydraulic pressure information is required in order to factory set or to field adjust a PRV.

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

Pressure Limiting Driver (PLD)

Pressure Limiting Driver (PLD) Pressure Limiting Driver (PLD) Discharge Pressure Control Suction Pressure Control June 9 2009 Mark Evans Clarke Fire Protection Products Justin Strousse Clarke Fire Protection Products Overview Discharge

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water

More information

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes

More information

SIZING OF WATER PIPING SYSTEM

SIZING OF WATER PIPING SYSTEM SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures

More information

Pacific Pump and Power

Pacific Pump and Power Pacific Pump and Power 91-503 Nukuawa Street Kapolei, Hawaii 96707 Phone: (808) 672-8198 or (800) 975-5112 Fax: (866) 424-0953 Email: sales@pacificpumpandpower.com Web: www.pacificpumpandpower.com Pumps

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

Pressure Drop Basics & Valve Sizing

Pressure Drop Basics & Valve Sizing Pressure Drop Basics & Valve Sizing What is Pressure Drop? The difference in pressure between two points in a system, caused by resistance to flow. What Pressure Drop is Not? Pressure drop is pressure

More information

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority

More information

Operating, Installation, and Maintenance Instructions

Operating, Installation, and Maintenance Instructions ELKHART BRASS MFG. CO., INC. 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 Operating, Installation, and Maintenance Instructions RAM Personal Portable Monitor

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

Hydrant flow testing data provides important

Hydrant flow testing data provides important feat40606.qxd 5/30/06 5:24 PM Page 44 The use of hydrant flow testing data to design automatic sprinkler systems has gotten easier thanks to new computer modeling software. By Dr. Sang H. Wong Hydrant

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Firefighter Review. Instructor Guide

Firefighter Review. Instructor Guide Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing

More information

Automatic Sprinkler System Calculations

Automatic Sprinkler System Calculations SECTION FOUR CHAPTER 3 Automatic Sprinkler System Calculations Russell P. Fleming Introduction Applications Where Water Is Appropriate Water is the most commonly used fire extinguishing agent, mainly due

More information

FIRE DEPARTMENT HYDRAULICS

FIRE DEPARTMENT HYDRAULICS FIRE DEPARTMENT HYDRAULICS BASIC CONCEPTS & FORMULAS WATER MEASUREMENTS 1 Cubic foot of water weighs 62.5 pounds 1 Cubic foot of water contains 1,728 cubic inches 1 Cubic foot of water contains 7.5 gallons

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

Water Supply. Simulation of Water Distribution Networks. Mohammad N. Almasri. Optimal Design of Water Distribution Networks Mohammad N.

Water Supply. Simulation of Water Distribution Networks. Mohammad N. Almasri. Optimal Design of Water Distribution Networks Mohammad N. Water Supply Simulation of Water Distribution Networks The Use of EPANET Mohammad N. Almasri 1 Introduction This presentation focuses on two issues: The simulation of water distribution networks (WDNs)

More information

Toms River Fire Academy

Toms River Fire Academy Pump School Manual Toms River Fire Academy Table of contents Chapter 1 Characteristics of Water Page 3 Pressures, Atmospheric, Static, Residual, Head.Page 7 Chapter 2 Pump Construction and Gauges Page

More information

One of the fundamental design elements that every

One of the fundamental design elements that every Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things

More information

CHAPTER 2: The Plumbing System

CHAPTER 2: The Plumbing System CHAPTER 2: The Plumbing System SECTION I: SIZING REQUIREMENTS Establish building dimensions Building height can be determined either by architectural drawings or # of floors times height/floor. (ex: 1

More information

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29 _02 A centrifugal with a 12 in. diameter impeller requires a power input of 60 hp when the flowrate is 3200 gpm against a 60 ft head. The impeller is changed to one with a 10 in. diameter. Determine the

More information

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE. SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

The In-Line Gauge in Standpipe Operations

The In-Line Gauge in Standpipe Operations The In-Line Gauge in Standpipe Operations BY RUSS CHAPMAN Your engine company receives a report of fire in a mid-rise elderly housing complex during morning coffee at the beginning of a shift. You know

More information

The Jockey Pump, an Important Part of a Fire Pump System.

The Jockey Pump, an Important Part of a Fire Pump System. The Jockey Pump, an Important Part of a Fire Pump System. May 18, 2008 A Jockey Pump is an important component of a fire pump system. The Jockey Pump is not as mundane, as many engineers, contractors and

More information

Delta Power Company 4484 Boeing Drive - Rockford, IL 61109

Delta Power Company 4484 Boeing Drive - Rockford, IL 61109 INDEX Description Page Delta Power Rotary Flow Divider, Positive Displacement (Application Data) 36 P Series, Equal Flow Two Sections 39 P Series, Equal Flow Multi-Sections 40 PM Series, Equal Flow Multi-Sections

More information

Open Channel Diffusers

Open Channel Diffusers Open Channel Diffusers Application Information: Open channel diffusers are used to increase mixing and absorbance efficiency of a chemical solution into the process water. Specifically designed penetrations

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

Module 9: Basics of Pumps and Hydraulics Instructor Guide

Module 9: Basics of Pumps and Hydraulics Instructor Guide Module 9: Basics of Pumps and Hydraulics Instructor Guide Activities for Unit 1 Basic Hydraulics Activity 1.1: Convert 45 psi to feet of head. 45 psis x 1 ft. = 103.8 ft 0.433 psi Activity 1.2: Determine

More information

Introduction to Water Pipe Sizing

Introduction to Water Pipe Sizing ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920 Introduction to Understanding the Many Methods to Size Water Pipe Presented by: Rainier Bratsch-Blundel, CPSI Plumbing Professor

More information

Water hammering in fire fighting installation

Water hammering in fire fighting installation Water hammering in fire fighting installation Forward One of major problems raised in the fire fighting network installed at Pioneer company for pharmaceutical industry /Sulaymania was the high water hammering

More information

Minor losses include head losses through/past hydrants, couplers, valves,

Minor losses include head losses through/past hydrants, couplers, valves, Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within

More information

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2. May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use

More information

Index 11.1. Page. Pumping Systems...11.2-11.4 Intensifiers...11.5 Gas Boosters...11.6-11.7 High Pressure Generators...11.8-11.9

Index 11.1. Page. Pumping Systems...11.2-11.4 Intensifiers...11.5 Gas Boosters...11.6-11.7 High Pressure Generators...11.8-11.9 Pumping Systems, Intensifiers, Gas Boosters and High Pressure Generators High Pressure Equipment Company produces a number of components and systems for general industrial, elevated pressure applications.

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID

More information

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps

More information

Pipe Sizes For Water Distribution System Design

Pipe Sizes For Water Distribution System Design Appendix D Pipe Sizes For Water Distribution System Design D-. This appendix contains information to help determine pipe sizes when designing a water distribution system. Use Table D- and Tables D- through

More information

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS FAIRBANKS NIJHUIS Packaged Fire Pump Systems At the heart of our systems you ll find the Fairbanks Nijhuis pumps you ve relied on for over 90 years. Fairbanks

More information

Springdale Fire Department Backup Driver Certification Program. Behavioral Objectives

Springdale Fire Department Backup Driver Certification Program. Behavioral Objectives Springdale Fire Department Backup Driver Certification Program Backup Driver Task Book I. Obtain required prerequisites 1. Performance a. Complete Probationary Program b. Complete CEVO Fire Course c. Complete

More information

Appendix B Forms for Inspection, Testing, and Maintenance

Appendix B Forms for Inspection, Testing, and Maintenance Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete

More information

Pressure drop in pipes...

Pressure drop in pipes... Pressure drop in pipes... PRESSURE DROP CALCULATIONS Pressure drop or head loss, occurs in all piping systems because of elevation changes, turbulence caused by abrupt changes in direction, and friction

More information

Design Criteria & Service Goals

Design Criteria & Service Goals 4.1 Design Life of Improvements The design life of a water system component is sometimes referred to as its useful life or service life. The selection of a design life is a matter of judgment based on

More information

10/9/2012. Poultry Farm Water Supply. Alabama Burglar & Alarm System. Industry Upgrades. Drinkers Fans Water Supply

10/9/2012. Poultry Farm Water Supply. Alabama Burglar & Alarm System. Industry Upgrades. Drinkers Fans Water Supply Poultry Farm Water Supply Jess Campbell & Jim Donald - Auburn University National Poultry Technology Center 1 Alabama Burglar & Alarm System 2 Industry Upgrades Ceilings, Sidewalls & Insulation Ventilation

More information

REGULATORS 175/153 Series

REGULATORS 175/153 Series 175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed

More information

Theory, Application, and Sizing of Air Valves

Theory, Application, and Sizing of Air Valves Theory, Application, and Sizing of Air Valves VAL-MATIC VALVE AND MANUFACTURING CORP. 905 RIVERSIDE DRIVE, ELMHURST, IL 60126 TEL. (630) 941-7600 FAX. (630) 941-8042 www.valmatic.com 1 THEORY, APPLICATION,

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

FILLING AND PURGING THE SYSTEM

FILLING AND PURGING THE SYSTEM FILLING INSTRUCTIONS FOR WATER HEATER OR CONDENSING BOILER (City Water) Safety tip: Before beginning, turn off power to boiler and circulator. FILLING AND PURGING Step 1: Close Return Manifold Isolation

More information

Gypsum Fire Protection District. Fire Sprinkler System Submissions

Gypsum Fire Protection District. Fire Sprinkler System Submissions Gypsum Fire Protection District Fire Sprinkler System Submissions Fire Sprinkler System Submissions for permit will fall under one of two categories: new installations or remodels. New installations or

More information

FIRE INSPECTION CHECKLIST

FIRE INSPECTION CHECKLIST Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 2010 Edition NFPA 1, Uniform Fire Code, Florida 2010 Edition NFPA 101, Life Safety Code, Florida 2010 Edition NFPA 13, 2007

More information

HYDROSTATIC TEST PUMPS

HYDROSTATIC TEST PUMPS HYDROSTATIC TEST PUMPS MANUAL HYDROSTATIC TEST PUMPS Ideal for testing residential water lines. Also for pressure testing small pressure tanks, sprinkler, boiler and solar systems. Lightweight and easy

More information

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS Second Edition Prepared by NAHB Research Center, Inc. 400 Prince Georges Boulevard Upper Marlboro, MD 20774-8731 DISCLAIMER This

More information

Chapter 8: Flow in Pipes

Chapter 8: Flow in Pipes Objectives 1. Have a deeper understanding of laminar and turbulent flow in pipes and the analysis of fully developed flow 2. Calculate the major and minor losses associated with pipe flow in piping networks

More information

I. Introduction. 10 minutes

I. Introduction. 10 minutes I. Introduction 10 minutes Introduction (1 of 2) An uninterrupted water supply is: The primary weapon for extinguishment Essential for fire fighter safety Ensuring a dependable water supply is a critical

More information

pvc well casing & drop pipe

pvc well casing & drop pipe CertainTeed pvc well casing & drop pipe PVC Well Products Sure Fit PVC well casing and drop pipe have gained broad acceptance since their introduction almost 40 years ago. Today, due to its outstanding

More information

In-Line Air Separators

In-Line Air Separators Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI

More information

Commercial & Municipal Retrofit 2015 VFD Rebate

Commercial & Municipal Retrofit 2015 VFD Rebate 2015 VFD Rebate Section A: MEMBER INFORMATION Member Name Electric Account Number Rate Number Facility Address City State Zip Code Service Location Identification Email Mailing Address (if different from

More information

Hydraulic Pump/Motor Division Hydraulic Pump/Motor Division

Hydraulic Pump/Motor Division Hydraulic Pump/Motor Division Parker Piston Pumps Otsego Core Competency... Piston Pumps PAVC Series : 4 displacements from 33-100 cc/r, 207 Bar, 3000 RPM PVP Series : 9 displacements from 16-140 cc/r, 250 Bar, 3000 RPM PV Plus : 12

More information

This document was scanned from hard copy to portable document format (PDF) and edited to 99.5% accuracy. Some formatting errors not detected during

This document was scanned from hard copy to portable document format (PDF) and edited to 99.5% accuracy. Some formatting errors not detected during FA-155 / May 1995 This document was scanned from hard copy to portable document format (PDF) and edited to 99.5% accuracy. Some formatting errors not detected during the optical character recognition process

More information

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC.

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC. 81471067 Electric Monitor Motor Control Panel For use with Model 8394059 SPIT-FIRE Monitor Installation, Operation, and Maintenance Instructions FOR ATEX APPLICATIONS 1302 WEST BEARDSLEY AVENUE P.O. BOX

More information

Flygt Ball Check Valves

Flygt Ball Check Valves 4/13 Supersedes: 6/96 The basic purpose of a check valve is to permit flow in one direction, prevent flow in the opposite direction and perform this function automatically and with minimum maintenance.

More information

SECTION 15300 - FIRE PROTECTION PIPING SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL

SECTION 15300 - FIRE PROTECTION PIPING SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of The University of Texas at Austin for automatic fire sprinkler and standpipe systems.

More information

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth

More information

Sta-Rite Industries Basic Training Manual

Sta-Rite Industries Basic Training Manual LOW SPEED BOOSTER PUMP HIGH SPEED FILTER PUMP AUX 1 AUX 2 1915 0895 Sta-Rite Industries Basic Training Manual THIRD EDITION Hydraulics Pumps Motors Filtration Heaters 2668 0397NF 2003 Sta-Rite Industries,

More information

Slide 1. Slide 2. Slide 3 288,817,200,000. Thank you for attending the session on Hot Water Re-Circulation.

Slide 1. Slide 2. Slide 3 288,817,200,000. Thank you for attending the session on Hot Water Re-Circulation. Slide 1 Thank you for attending the session on Hot Water Re-Circulation. Hot Water Re-Circulation National Conference Center Lansdowne, VA March 25 th & 26 th, 2010 Slide 2 AGENDA Water Waste Statistics

More information

Roland Garcia Pearland Fire Department

Roland Garcia Pearland Fire Department Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and

More information

Second Revision No. 106-NFPA 72-2014 [ Global Comment ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 106-NFPA 72-2014 [ Global Comment ] Supplemental Information. Submitter Information Verification. Committee Statement of 1 9/22/2014 2:03 PM Second Revision No. 106-NFPA 72-2014 [ Global Comment ] Revise Figures A.17.6.3.1.1(c) and A.17.7.5.4.2.2(a) to replace the smoke detector symbol (a hexagon with a whisp of smoke)

More information

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,

More information

Automatic Fire Sprinkler System Checklist

Automatic Fire Sprinkler System Checklist Fire Prevention rd Location: 701 E. 3 Avenue Mail to: P.O. Box 1579 Moses Lake, WA 98837 (509) 765-2204 www.ci.moses-lake.wa.us Automatic Fire Sprinkler System Checklist Please print in Black or Blue ink

More information

The conditions below apply to the curves shown on the following pages.

The conditions below apply to the curves shown on the following pages. GENERAL INFORMATION STAINLESS STEEL, SILVERLINE, EVERGREEN & GOLDLINE SERIES PERFORMANCE CURVE CONDITIONS The conditions below apply to the curves shown on the following pages. a. The Performance curves

More information

Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County

Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology Public Utility District No. 1 of Chelan County This paper describes how to calculate energy saved by installing a variable

More information

SPP Pumps Inc. Atlanta

SPP Pumps Inc. Atlanta SPP Pumps Inc. Atlanta UL Listed, FM Approved Fire Pump Sets Horizontal Split Case Pumps Flows from 200-5000 US GPM Vertical Turbine Flows to 5000 US GPM In-Line Pumps Flows to 750 US GPM End Suction Flows

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes

More information

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are

More information

CHAPTER. Fire Pumps FIRE PUMP OVERVIEW. Fire Pump Unit Defined. Fire Pump Unit Responsibility

CHAPTER. Fire Pumps FIRE PUMP OVERVIEW. Fire Pump Unit Defined. Fire Pump Unit Responsibility Fire Pumps CHAPTER 4 Commissioning of fire pumps is much more involved than commissioning of most other systems and must be completed correctly to verify operation of this critical equipment. This chapter

More information

Spouts and Flow Regulators

Spouts and Flow Regulators Spouts and Flow Regulators Durable, chrome plated brass spouts A wide selection of flow regulators Chicago Faucets Spouts and Flow Regulators Chicago Faucets offers one of the widest selection of spouts

More information

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007 TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.

More information

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS 2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS Water system improvements proposed for inclusion into Western s service area shall be designed in accordance with all appropriate AWWA standards, include

More information

HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS

HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS Shiwei William Guan, Ph.D. Vice President, R&D and International Business Madison Chemical Industries Inc. 490

More information

Fiberstars Mini Lighted Laminar Flow Fountains

Fiberstars Mini Lighted Laminar Flow Fountains Fiberstars Mini Lighted Laminar Flow Fountains SAVE THESE DIRECTIONS! These directions are provided to ensure the proper installation and operation of Fiberstars Mini Lighted Laminar Flow Fountain. The

More information

Selection Of Centrifugal Pumping Equipment 1

Selection Of Centrifugal Pumping Equipment 1 Circular 1048 Selection Of Centrifugal Pumping Equipment 1 Dorota Z. Haman, Fedro S. Zazueta, Forrest T. Izuno 2 INTRODUCTION The pump is an essential component of an irrigation system. Proper selection

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

Delta Fire manufacture and supply a comprehensive range of Marine Fire Fighting Equipment.

Delta Fire manufacture and supply a comprehensive range of Marine Fire Fighting Equipment. Marine FIRE FIGHTING Equipment Delta Fire manufacture and supply a comprehensive range of Marine Fire Fighting Equipment. The recent aquisition of the Foundrite range of international couplings, fittings

More information

Division 21. Fire Suppression

Division 21. Fire Suppression 21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven

More information

HOUSTON FIRE DEPARTMENT HIGH-RISE SURVEY CHECKLIST

HOUSTON FIRE DEPARTMENT HIGH-RISE SURVEY CHECKLIST This is a Fill Out On Computer & Print Form Only! No hand written forms accepted! TOTAL PAPER FORMS NEEDED: 3 - - - Original & 2 Copies HOUSTON FIRE DEPARTMENT HIGH-RISE SURVEY CHECKLIST High-rise Id #

More information

TECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200)

TECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200) September 18, 2009 30a 1. DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial systems. They are available with an

More information

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 thru inch (DN40 thru DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

KODAK VERSAMARK, INC.

KODAK VERSAMARK, INC. KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF

More information

SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT

SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT [Sub-Art. or Sec.]* SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT TABLE OF CONTENTS Art. or Sec.** [1700.0] Art. 1 General [1700.1] 923 Scope [1700.2] 924 Standards [1700.3] 925 Definitions

More information

DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS

DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS UP DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS March 2014 This document is not intended to advocate nor discourage the installation of residential sprinkler systems

More information

PERFORMANCE EVALUATION OF A DRINKING WATER DISTRIBUTION SYSTEM USING HYDRAULIC SIMULATION SOFTWARE FOR THE CITY OF OILTON, OKLAHOMA

PERFORMANCE EVALUATION OF A DRINKING WATER DISTRIBUTION SYSTEM USING HYDRAULIC SIMULATION SOFTWARE FOR THE CITY OF OILTON, OKLAHOMA PERFORMANCE EVALUATION OF A DRINKING WATER DISTRIBUTION SYSTEM USING HYDRAULIC SIMULATION SOFTWARE FOR THE CITY OF OILTON, OKLAHOMA By NEHA MANGESH BHADBHADE Bachelor of Science in Instrumentation and

More information

C I T Y O F S E L M A F I R E D E P A R T M E N T

C I T Y O F S E L M A F I R E D E P A R T M E N T C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:

More information