1 Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA Telephone: (508) / Fax: (508) ADC Part No

2 Exhaust duct work should be designed and installed by a qualified professional. Properly sized duct work is imperative for the dryer(s) to operate efficiently and safely. Improperly sized duct work will create conditions which result in slow drying, increased use of energy, shutdown of the burner by the air flow (sail) switch, burner hi-limit, or basket (tumbler) hi-heat thermostats. A potential fire hazard may be created if the duct work is improperly sized or installed. The dryer must be exhausted to the outdoors. The exhaust duct work should be designed and installed in such a way that it travels as directly as possible to the outdoors with as few elbows as possible. Wherever the duct passes through a wall, ceiling, or roof made of combustible materials, the opening must be two (2) inches larger, all the way around, than the duct. The duct must be centered within this opening. The use of sheet metal screws should be avoided as the projections within the duct work trap lint and cause an increase in friction loss. All duct work connections should be taped to prevent lint and moisture from escaping into the building. Doors should be installed throughout strategic points in the duct work for periodic inspection and cleaning. Where possible, it is suggested to provide a separate (independent) exhaust duct for each dryer. When a dryer is exhausted separately, it is recommended that a back draft damper be installed, if not provided with the dryer. If it is not feasible or possible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be channeled into a "common main duct". The individual ducts should enter the bottom or side of the main duct at an angle of not more than 45 degrees, in the direction of the air flow and should be spaced apart the width of the dryer. When exhausting individual dryers into a main common duct, each dryer must have a back draft damper. To protect the outside end of horizontal duct work from the weather, a 90 degree elbow bent downward should be installed where the exhaust exits the building. If the exhaust duct work travels vertically up through the roof, it should be protected from the weather by using a 180 degree turn to point the opening downward. In both instances, a distance equal to twice the diameter of the exhaust duct must be allowed between the duct opening and the nearest obstruction. Do not use screens, louvers, or caps on the outside opening of the exhaust duct. The following are examples of single and multiple dryer exhaust ducting. 2 American Dryer Corp

3 The pressure of the air in sheet metal ducts is of great importance for safe and efficient operation of the dryer. The air pressures, as small as they are, have a large influence upon the performance of the dryer. There are three pressures present within a duct. The velocity pressure which is the pressure due to the moving stream of air, the static pressure which is the outward push of the air against the walls of the duct, and the total pressure which is the sum of the static and velocity pressures. Only the total and static pressures can be measured. The velocity pressure is then calculated from the difference between the two. The static pressure is the most influential and determining factor in the design of a dryer duct system. American Dryer Corp. recommends that the dryer exhaust duct static pressure not exceed the maximum listed in the dryer installation manual

4 Gages used to measure such small air pressures utilize the elevation of a column of water. This form of gage is called a manometer. One form of this gage is known as a U-tube and is shown in Illustration #1. When one end of the tube is connected to the duct, the static (outward) pressure within the duct forces the water column to be depressed in one leg of the U-tube and up in the other. The elevation of the water column in Illustration #1 is 3.2 inches. Illus. # 1 When measuring such small air pressures the U-tube is often not accurate enough. Such small differences in pressure are most often measured by an inclined tube manometer or a Magnehelic pressure gage as shown in Illustration # 2. Illus. # 2 For convenience and accuracy an instrument known as a Pitot tube is used with the gage. The Pitot tube, as shown in Illustration #3, consists of two tubes - one within the other. The inner tube measures the total pressure alone while the outer tube measures the static pressure alone. Illus. # 3 4 American Dryer Corp

5 To obtain the most accurate static pressure readings of a dryer, the following guidelines should be conformed to. The reading should be taken in a straight section of duct, a minimum of ten (10) times the diameter of the duct (i.e. 10" diameter duct, a straight section 100" in length). The reading should be taken a minimum of 8-1/2 times the diameter upstream of the dryer or nearest elbow, and 1-1/2 times the diameter downstream of the Pitot tube. The following is an example showing the proper location to take a static pressure reading. In designing a dryer exhaust duct system it is not necessary to compute the friction loss of the duct work. American Dryer Corp. recommends that the dryer exhaust duct static pressure not exceed the maximum listed in the dryer installation manual. This maximum allowable static pressure is calculated to provide maximum dryer efficiency. It is necessary to determine the total equivalent length of the duct system. The total equivalent length of the duct system is the actual length of the duct added to the equivalent length of all of the fittings. The equivalent length of a fitting is the length of straight duct of the same size as the fitting in which the friction losses are equal. Equivalent lengths must be determined for all elbows, as well as, any entries which may be incorporated into a common duct system for multiple dryers. The total equivalent length is then used with the total cfm (cubic feet per minute) exhaust rating of the dryer(s) to calculate the minimum round duct diameter. Values of the equivalent length of specific diameter elbows can be determined from Table #1. When designing a single common duct system for multiple dryers, each individual dryer exhaust duct enters the main common duct. The equivalent length of the entry losses for each dryer can be determined from the values listed in Table #

6 Table # 1 Equivalent Resistance of Round Elbows Expressed in Feet of Straight Pipe 90 Elbow For 45 Elbow use 1/2 value shown. For 60 elbow use 2/3 value shown. D R D = 1.5 4" 6' 6" 12' 8" 15' 10" 20' 12" 25' 14" 30' 16" 36' 18" 41' 20" 46' 24" 57' 28" 68' 30" 74' 32" 80' 36" 93' 40" 105' 42" 111' 44" 118' 48" 130' 6 American Dryer Corp

7 Table # 2 Equivalent Entry Losses Expressed in Feet of Straight Pipe Dia of Pipe " 3' 5' 6" 5' 7' 8" 7' 11' 10" 9' 14' 12" 11' 17' 14" 13' 21' 16" 16' 25' 18" 18' 28' 20" 20' 32' 24" 24' 37' 28" 28' 46' 30" 31' 49' 32" 33' 53'

8 TABLE # TOTAL EQUIVALENT OF STRAIGHT DUCT IN FT. 32 Dia 30 Dia 28 Dia 26 Dia 24 Dia 22 Dia 20 Dia 18 Dia 16 Dia 14 Dia 12 Dia 10 Dia 8 Dia 6 Dia CU. FT. OF AIR PER MINUTE 8 American Dryer Corp

9 TABLE # 4 24 Dia 22 Dia 20 Dia 18 Dia 28 Dia 26 Dia 16 Dia 36 Dia 34 Dia 14 Dia 32 Dia 12 Dia 30 Dia TOTAL EQUIVALENT OF STRAIGHT DUCT IN FT. CU. FT. OF AIR PER MINUTE

10 Once the total equivalent length of duct is determined, Tables #3 and #4 are used to determine the minimum diameter round duct to be used. The dryer(s) cfm is read on the left hand side of the chart. The total equivalent length of duct is read across the bottom. The minimum diameter round duct to be used is read at the intersection of the two. Each round duct diameter line on the graph represents the maximum limit for each size shown. When making calculations, if the intersection is in the middle of two diameters, the larger size is chosen (I.E. 600 cfm at 30' use 8" diameter). The following are examples of the procedures to calculate the duct size for a single dryer. Example 1: A dryer has an air flow of 600 cfm (cubic feet per minute) and an 8-inch diameter dryer exhaust connection. The duct run will travel 20 feet and has two (2) - 90 degree elbows. What is the total equivalent length of the duct system? What will be the minimum diameter round duct to be used? Solution: From Table #1 Equivalent length of each 90 degree elbow: Total equivalent length of the duct system: 20 Feet 15 Feet x 2 = 30 Feet 50 Feet From Table #3 The minimum diameter round duct to be used is 8-inches. Example 2: A dryer has an air flow of 1,700 cfm with a 12-inch dryer exhaust connection. The exhaust duct will travel 50 feet with six (6) 90 degree elbows. What is the total equivalent length of the duct system? What will be the minimum diameter round duct to be used? Solution: The initial total equivalent length of the duct system must first be calculated using the dryer exhaust connection size. Equivalent length of each 12" 90 degree elbow: Total equivalent length of the duct system: 50 Feet 25 Feet x 6 = 150 Feet 200 Feet The minimum diameter round duct to be used is 16-inches. 10 American Dryer Corp

11 Because the minimum diameter round duct to be used calculates to a size which is larger than the dryer exhaust connection, the total equivalent length of the duct system must be recalculated using the 16" diameter equivalent lengths. This new total length is then used with the dryer(s) cfm to verify that it still falls within the 16" diameter minimum round duct area. Equivalent length of each 16" 90 degree elbow: Total equivalent length of the duct system: 50 Feet 36 Feet x 6 = 216 Feet 266 Feet The minimum diameter round duct to be used is 16-inches. When calculating and sizing a common exhaust duct for two (2) or more dryers, several steps are required. First, the main common duct size is calculated using the total cfm of all of the dryers and the total equivalent length of the duct system. Second, the individual dryer exhaust ducts, which travel to the common duct, are calculated. Tables 5 and 6 are used to determine the initial common duct size to use in the calculation of the total equivalent length of the duct system. The total cfm of all of the dryers are added and found on the left side of the chart. The friction loss (static pressure) is listed at the bottom of the chart. The value of.3" water column is used at the bottom of the chart. This is the maximum recommended static pressure for the dryer exhaust. The initial minimum diameter round duct is then read at the intersection of the total cfm and the.3" water column value. This initial duct size is then used to calculate the total equivalent length of the duct system

12 TABLE # 5 AIRFLOW Duct CFM 24 Duct 20 Duct 18 Duct 10 Duct 16 Duct 14 Duct Duct 8 Duct 6 Duct Friction Loss in Inches of Water per 100 FT 12 American Dryer Corp

13 TABLE # AIRFLOW 34 Duct 30 Duct CFM Duct 32 Duct 28 Duct 26 Duct 24 Duct Friction Loss in Inches of Water per 100 FT

14 The following examples show how a single common duct for multiple dryers is calculated. Example 1: There are three (3) dryers with 600 cfm each which will be connected to one (1) common exhaust duct. The dryers have an 8" diameter exhaust connection. The main duct will have a total run of 70 feet and include three (3) 90 degree elbows and two (2) 45 degree elbows. Each individual dryer duct will travel ten (10) feet and have one (1) 90 degree elbow, one (1) 45 degree elbow, and enter the common duct at a 45 degree angle. What is the total equivalent length of the common duct system? What is the minimum diameter of the main common duct? What is the total equivalent length of the individual dryer ducts? What is the minimum diameter of the individual dryer ducts? Solution: To determine the total equivalent length and minimum diameter round duct of the main common duct. From Table 5 The intersection of 1,800 cfm (total of 3 dryers at 600 cfm each) and the static pressure of.3" water column is 14" diameter duct. This is the initial size used in calculations. Equivalent length of each 14" 90 degree elbow: Equivalent length of each 14" 45 degree elbow: Total equivalent length of the common duct: 70 Feet 30 Feet x 3 = 90 Feet 15 Feet x 2 = 30 Feet 190 Feet The minimum diameter round duct for the common duct is 16-inches. The total equivalent length must be recalculated using 16" diameter equivalent lengths to determine the total equivalent length. This is necessary because the minimum size shown on Table 3 exceeded the initial size obtained in Table 5. This recalculation is required because the initial size obtained in Table 5 is calculated on a total equivalent length of duct of 100 feet. When the calculated total equivalent length exceeds 100 feet, the minimum diameter, in most cases, increases. Equivalent length of each 16" 90 degree elbow: Equivalent length of each 16" 45 degree elbow: Total equivalent length of the common duct: 70 Feet 36 Feet x 3 = 108 Feet 18 Feet x 2 = 36 Feet 214 Feet The minimum diameter round duct for the common duct is 16-inches. To determine the total equivalent length and minimum diameter round ducts for the individual dryer exhausts. 14 American Dryer Corp

15 When calculating and sizing the individual dryer exhaust ducts, the dryer's exhaust connection size is initially used to determine the total equivalent length. Equivalent length of each 8" 90 degree elbow: Equivalent length of each 8" 45 degree elbow: From Table 2 Equivalent length of entry loss at 45 degree angle for 8": Total equivalent length of each individual dryer duct: 10 Feet 15 Feet x 1 = 15 Feet 7-1/2 Feet x 1= 7-1/2 Feet 11 Feet 43-1/2 Feet The minimum diameter round duct for each individual dryer duct is 8-inches. NOTE: The dryer exhaust duct must never be decreased from the dryer's exhaust connection size. Example 2: There are four (4) dryers which will be connected into a main common duct. The common duct will travel 45 feet and include four (4) 90 degree elbows. There are two (2) dryers with 2,000 cfm each which have a 12" exhaust connection, one (1) dryer with 1,500 cfm which has a 10" exhaust connection, and one (1) dryer with 800 cfm which has an 8" exhaust connection. Each individual dryer exhaust duct will travel 15 feet and include one (1) 90 degree elbow, one (1) 45 degree elbow, and will enter the common duct at a 45 degree angle. What is the total equivalent length of the common duct? What is the minimum diameter round duct to be used for the common duct? What is the total equivalent length and minimum diameter round duct for each of the individual dryer ducts? Solution: To determine the total equivalent length of the main common duct. From Table 5 The intersection of 6,300 cfm (total cfm of 4 dryers) and the static pressure of.3" water column is 22" diameter duct. This is the initial size used in calculations. Equivalent length of each 22" 90 degree elbow: Total equivalent length of the common duct: 45 Feet 1 Feet x 4 = 204 Feet 249 Feet The minimum diameter round duct for the common duct is 28-inches

16 The total equivalent length must be recalculated using 28" diameter equivalent lengths to determine the total equivalent length. This is necessary because the minimum size shown in Table 3 exceeded the initial size obtained from Table 5. Equivalent length of each 28" 90 degree elbow: Total equivalent length of the common duct: 45 Feet 68 Feet x 4 = 272 Feet 317 Feet The minimum diameter round duct for the common duct is 28-inches. To determine the total equivalent length and minimum diameter round duct for the individual dryer ducts. For the dryers with 2,000 cfm each with a 12" diameter exhaust connection. Equivalent length of each 12" 90 degree elbow: Equivalent length of each 12" 45 degree elbow: From Table 2 Equivalent length of entry loss at 45 degree angle for 12": Total equivalent length of each individual dryer duct: 15 Feet 25 Feet x 1 = 25 Feet 12-1/2 Feet 17 Feet 69-1/2 Feet The minimum diameter round duct for each individual dryer duct is 14-inches. The total equivalent length must be recalculated using 14" diameter equivalent lengths to determine the total equivalent length. This is necessary because the minimum size shown in Table 3 exceeds the dryer exhaust connection size used initially. Equivalent length of each 14" 90 degree elbow: Equivalent length of each 14" 45 degree elbow: From Table 2 Equivalent length of entry loss at 45 degree angle for 14": Total equivalent length of the individual dryer duct: 15 Feet 30 Feet 15 Feet 21 Feet 81 Feet The minimum diameter round duct for the individual dryer duct is 14-inches. 16 American Dryer Corp

17 For the dryer with 1,500 cfm with a 10" diameter exhaust connection. Equivalent length of each 10" 90 degree elbow: Equivalent length of each 10" 45 degree elbow: From Table 2 Equivalent length of entry loss at 45 degree angle for 10": Total equivalent length of the individual dryer duct: 15 Feet 20 Feet 10 Feet 14 Feet 59 Feet The minimum diameter round duct for the individual dryer duct is 12-inches. The total equivalent length must be recalculated using 12" diameter equivalent lengths to determine the total equivalent length. This is necessary because the minimum size shown in Table 3 exceeds the dryer exhaust connection size used initially. Equivalent length of each 12" 90 degree elbow: Equivalent length of each 12" 45 degree elbow: From Table 2 Equivalent length of entry loss at 45 degree angle for 12": Total equivalent length of each individual dryer duct: 15 Feet 25 Feet x 1 = 25 Feet 12-1/2 Feet 17 Feet 69-1/2 Feet The minimum diameter round duct for each individual dryer duct is 12-inches. For the dryer with 800 cfm with an 8" diameter exhaust connection. Equivalent length of each 8" 90 degree elbow: Equivalent length of each 8" 45 degree elbow: From Table 2 Equivalent length of entry loss at 45 degree angle for 8": Total equivalent length of the individual dryer duct: 15 Feet 15 Feet 7-1/2 Feet 11 Feet 48-1/2 Feet The minimum diameter round duct for the individual dryer duct is 10-inches

18 The total equivalent length must be recalculated using 10" diameter equivalent lengths to determine the total equivalent length. This is necessary because the minimum size shown in Table 3 exceeds the dryer exhaust connection size used initially. Equivalent length of each 10" 90 degree elbow: Equivalent length of each 10" 45 degree elbow: From Table 2 Equivalent length of entry loss at 45 degree angle for 10": Total equivalent length of the individual dryer duct: 15 Feet 20 Feet 10 Feet 14 Feet 59 Feet The minimum diameter round duct for the individual dryer duct is 10-inches. Notice that, at times, it is necessary to connect a larger duct than what the dryer has for an exhaust connection. This is required in order to keep the static pressure within the maximum allowable of.3" water column. It is often necessary to use either square or rectangular duct instead of round. This may be required due to constricted passageways. In these instances, it is necessary to use a size which has the same friction loss as the round duct. Table 7 lists the minimum cross sectional area equivalents of the round ducts. When using rectangular ducts, the length to width ratio must not exceed 3-1/2 to 1. In some cases it is impossible to meet the minimum size requirements. This may be due to exhaust duct size limitations. In these cases, a booster fan is required in order to meet the recommended static pressure requirements. In an exhaust duct system with individual dryer vents, a booster fan is added to each individual duct. It is more difficult when installing a booster fan into a common duct for multiple dryers. In this case, each dryer should be fitted with a barometric damper to compensate for the increased airflow created by the fan. In either case, a HVAC (heating, ventilating, air-conditioning) engineering firm should be consulted. Should any value exceed the limitations in the tables provided, please consult a HVAC engineering firm. The information given is to assist in the calculation of an exhaust duct system. It may also be used to check the sizing of an existing exhaust duct system to verify whether it is within the recommended guidelines. 18 American Dryer Corp

19 TABLE # 7 Round Duct Diameter (Inches) Minimum Equivalent Cross Sectional Area (Square Inches) ,

20 Problem 1: Three dryers are to be installed into a laundromat. Each dryer has an air flow of 400 cfm and a six (6) inch exhaust connection. Each dryer will be vented separately. Each dryer exhaust will travel 35 feet and have three (3) 90 degree elbows and one (1) 45 degree elbow. What is the total equivalent length and minimum diameter round duct to be used for each dryer duct? Problem 2: A nursing home is installing a new dryer which has an air flow of 2,500 cfm and a 14" diameter exhaust connection. The exhaust duct will travel 60 feet and have two (2) 90 degree elbows and three (3) 45 degree elbows in the run. What is the total equivalent length and minimum diameter round duct to be used? Problem 3: A laundromat owner plans to expand his business. He wants to install eight (8) new dryers which have an air flow of 600 cfm each and an eight (8) inch dryer exhaust connection. He plans to separate the dryers so that there will be two (2) common exhaust ducts with four (4) dryers into each one. Each of the two ducts will travel 43 feet and have three (3) 90 degree elbows. Each individual dryer duct will travel 10 feet and have one (1) 90 degree elbow, one (1) 45 degree elbow, and enter the main common duct at a 45 degree angle. What is the total equivalent length and minimum diameter round duct for each common duct? What is the total equivalent length and minimum round duct diameter for each individual dryer exhaust duct? Problem 4: An institutional laundry is planning on opening in several months. They are currently installing three (3) dryers. One dryer has an air flow of 2,100 cfm with a 12" diameter exhaust connection. One dryer has an air flow of 1,700 cfm with a 12" diameter exhaust connection. One dryer has an air flow of 900 cfm with a 8" diameter exhaust connection. The three (3) dryers are to be vented into one (1) common duct. The common duct will travel 55 feet and have two (2) 90 degree elbows. Each of the individual dryer ducts will travel 10 feet and have one (1) 90 degree elbow, one (1) 45 degree elbow, and enter the common duct at a 45 degree angle. What is the total equivalent length and minimum diameter round duct for the common duct? What are the total equivalent lengths and minimum round duct diameters for each individual dryer duct? ANSWERS FOUND ON PAGE American Dryer Corp

21 Answers: #1 - The total equivalent length is 87-1/2 feet and the minimum round diameter duct is 8-inches. #2 - The total equivalent length is 203-1/2 feet and the minimum round diameter duct is 18-inches. #3 - The total equivalent length of the common duct is 166 feet and has a minimum diameter of 18-inches. Each of the individual dryer ducts has a total equivalent length of 43-1/2 feet and a the minimum round diameter duct is 8-inches. #4 - The total equivalent length of the common duct is 157 feet and has a minimum diameter of 22-inches. The dryer with 2,100 cfm has a total equivalent length of 76 feet and a minimum round diameter duct of 14-inches. The dryer with 1,700 cfm has a total equivalent length of 64-1/2 feet and a minimum round diameter duct of 14-inches. The dryer with 900 cfm has a total equivalent length of 54 feet and a minimum round diameter duct of 10-inches

22 ADC /01/05-0

DRYER VENTING SPECIFICATIONS DRYER SAFETY

DRYER VENTING SPECIFICATIONS DRYER SAFETY DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting

More information

Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums

Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums Dryer Exhaust Systems Types of Clothes Dryers Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums Type Sub 2 Title dryers:

More information

EVALUATION OF EXHAUST VENTILATION SYSTEMS

EVALUATION OF EXHAUST VENTILATION SYSTEMS HSCI 348 Industrical Hygiene Instrumentation Techniques Laboratory No. 5 EVALUATION OF EXHAUST VENTILATION SYSTEMS INTRODUCTION: Of major concern to the Industrial Hygienist is the evaluation and control

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

HVAC Code Requirements

HVAC Code Requirements one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of

More information

Fan Applications & System Guide

Fan Applications & System Guide Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation

More information

INDUSTRIAL PROCESS AIR HANDLING & MEASUREMENT. Air Velocity/Volume Measurement

INDUSTRIAL PROCESS AIR HANDLING & MEASUREMENT. Air Velocity/Volume Measurement 3-06 INTRODUCTION INDUSTRIAL PROCESS AIR HANDLING & MEASUREMENT Air Velocity/Volume Measurement The movement of air is a factor in almost all modern industrial facilities. Industrial air movement is usually

More information

Basic Selection & Proper Application of Overhead Air Distribution Devices

Basic Selection & Proper Application of Overhead Air Distribution Devices Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return

More information

PART 8 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL

PART 8 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL 32 PART 8 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL The heater must be vented as detailed in this Venting Section. Ensure exhaust and intake piping complies with these instructions regarding vent

More information

Ventilation Solutions Laundries. fantech

Ventilation Solutions Laundries. fantech Ventilation Solutions Laundries 2 Laundries A New Day - and a New Name for Dryer Exhaust Fans Remember the good old days when laundry spaces were designed so that clothes dryers could be vented directly

More information

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause

More information

Design Information. Designing Your Dust Collection System. Typical dust or fume collection system

Design Information. Designing Your Dust Collection System. Typical dust or fume collection system Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to

More information

If you live in a mobile home, be sure your stove is of a type specifically approved for use in such a dwelling.

If you live in a mobile home, be sure your stove is of a type specifically approved for use in such a dwelling. Wood Stove Safety If you're among the thousands who have succumbed to the lure of the wood burning stove, keep in mind that the return to the "good old days" of wood stove heating can have some old-fashioned

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

PART 5 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL

PART 5 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL 28 2. Connect DHW (domestic hot water) piping to indirect storage water heater. L. ZONING WITH CIRCULATORS 1. Connect the boiler to the system when using circulator zoning as shown in Boiler Piping Details.

More information

ASX7-4-IOM-7 J30-08579

ASX7-4-IOM-7 J30-08579 INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT

More information

COMMERCIAL GAS DRYER FUELLED BY TOWN GAS CODE OF PRACTICE GU13 (MODULE ONE)

COMMERCIAL GAS DRYER FUELLED BY TOWN GAS CODE OF PRACTICE GU13 (MODULE ONE) COMMERCIAL GAS DRYER FUELLED BY TOWN GAS CODE OF PRACTICE GU13 (MODULE ONE) August 2007 Issue 2 Table of Contents 1. Foreword and Scope...1 2. Terminology...3 3. General...5 4. Gas Meter...6 5. Pipe Connection

More information

Air Leakage and Blower Door Basics

Air Leakage and Blower Door Basics Air Leakage and Blower Door Basics New River Center for Energy Research and Training A Division of Community Housing Partners Air Leakage Requires All of the Following: Air Hole Pressure Difference (Driving

More information

FIRE DAMPER APPLICATION GUIDE

FIRE DAMPER APPLICATION GUIDE FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire

More information

VENTING AND COMBUSTION AIR Roberts Mechanical Equipment Co.

VENTING AND COMBUSTION AIR Roberts Mechanical Equipment Co. VENTING AND COMBUSTION AIR Roberts Mechanical Equipment Co. I II III IV ANSI Categories will tell you a great deal about the boiler and the application. ANSI CATEGORIES I II III IV Left side indicates

More information

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional

More information

VENTILATION GUIDELINES FOR GAS/ELECTRIC REFRIGERATORS

VENTILATION GUIDELINES FOR GAS/ELECTRIC REFRIGERATORS VENTILATION GUIDELINES FOR GAS/ELECTRIC REFRIGERATORS Norcold, Inc. P.O. Box 4248 Sidney, OH 45365-4248 Norcold Technical Support Telephone: 800-444-7210 Fax: 937-497-3183 Web Site: www.norcold.com Part

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL

PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL 41 PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL The heater must be vented as detailed in this Venting Section. Ensure exhaust and intake piping complies with these instructions regarding vent

More information

DBF 4XL Dryer Booster Fans

DBF 4XL Dryer Booster Fans Installation and Operation Manual Item #: 401315 Rev Date: 121514 DBF 4XL Dryer Booster Fans DBF4XL Kit Includes: Dryer Booster Fan, 1 pc Fan Mounting Bracket and Hardware, 1 pc Wall Label (Mount on wasll

More information

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible

More information

Gas Dryer. IMPORTANT: Read and save these instructions. 3-73

Gas Dryer. IMPORTANT: Read and save these instructions. 3-73 Gas Dryer Installation Instructions IMPORTANT: Read and save these instructions. IMPORTANT: Installer: Leave Installation Instructions with the homeowner. Homeowner: Keep Installation Instructions for

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

How to Measure HVAC System Airflow

How to Measure HVAC System Airflow How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and

More information

Figure 22: Typical Individual Venting. Figure 21: Single Water Heater Venting

Figure 22: Typical Individual Venting. Figure 21: Single Water Heater Venting ING THE WATER HEATER The purpose of venting a gas or oil-fired water heater is to completely remove all products of combustion and to vent gasses to the outside air without condensation in the vent or

More information

Ontario Fire Code SECTION 5.18 INDUSTRIAL OVENS FOR BAKING. Illustrated Commentary AND DRYING PROCESSES. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.18 INDUSTRIAL OVENS FOR BAKING. Illustrated Commentary AND DRYING PROCESSES. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.18 INDUSTRIAL OVENS FOR BAKING AND DRYING PROCESSES Illustrated Commentary Office of the Ontario Fire Marshal Industrial Ovens Illustrated Commentary 1 5.18.1. Application

More information

HV AC CODE CHECKLISTS

HV AC CODE CHECKLISTS The following text is informational only and shall serve as an informational guide for HV AC contractors, journeymen, and apprentices working in the Heating, Ventilation, and Air Conditioning industry.

More information

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010

CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory

More information

Chapter 12 Industrial Ventilation

Chapter 12 Industrial Ventilation Chapter 1 Industrial Ventilation Introduction Industrial Ventilation is an important method for reducing employee exposures to airborne contaminants. Ventilation is used to reduce or remove contaminates

More information

*Note: This document is an electronic (scanned) version of the original paper report and formatting may vary somewhat from the original.

*Note: This document is an electronic (scanned) version of the original paper report and formatting may vary somewhat from the original. Guideline No. 97-05 January 19, 1998 Version 1.0 Guideline for Stack Sampling Facilities* Prepared By: Kevin Reeve, B. Sc. Air Emission Specialist Environmental Operations Division Art Schultz, C.E.T.

More information

Grain Drying Tools: Equilibrium Moisture Content Tables and Psychrometric Charts

Grain Drying Tools: Equilibrium Moisture Content Tables and Psychrometric Charts DIVISION OF AGRICULTURE R E S E A R C H & E X T E N S I O N University of Arkansas System Agriculture and Natural Resources FSA1074 Grain Drying Tools: Equilibrium Moisture Content Tables and Psychrometric

More information

Pressure Balancing. Chris Clay The Building Performance Center Brad Turner Southface

Pressure Balancing. Chris Clay The Building Performance Center Brad Turner Southface Pressure Balancing Chris Clay The Building Performance Center Brad Turner Southface Objectives Understand the problems pressure imbalances can cause in a home Review basic pressure principles Demonstrate

More information

City of Bellevue Submittal Requirements 70 TYPE I AND TYPE II KITCHEN HOOD SUBMITTAL CHECKLIST 7/1/2016. A. Project Address:

City of Bellevue Submittal Requirements 70 TYPE I AND TYPE II KITCHEN HOOD SUBMITTAL CHECKLIST 7/1/2016. A. Project Address: City of Bellevue Submittal Requirements 70 TYPE I AND TYPE II KITCHEN HOOD SUBMITTAL CHECKLIST 7/1/2016 This worksheet must accompany plan sets submitted with commercial kitchen hood permit applications.

More information

Industrial Fans. Jonathan F. Hale, MPA Air Systems Corporation

Industrial Fans. Jonathan F. Hale, MPA Air Systems Corporation Industrial Fans Jonathan F. Hale, MPA Air Systems Corporation 1 Air is a Fluid Birds Swim In It! 40,000 CFM =? LBS. AIR/HR. Air =.075 LBS. 1 CU. FT. 40,000 CFM = 90 TONS/HR. = 3,000 LBS/MIN Most Common

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Natural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 )

Natural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 ) Natural Gas Appliance Testing Action Guidelines (n ESA/Low Income 5 ) The purpose of these Action Guidelines is to describe the actions participating contractors and/or inspectors should take in the event

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

MODEL FAI4 FRESH AIR INTAKE KIT

MODEL FAI4 FRESH AIR INTAKE KIT TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com MODEL FAI4 FRESH AIR INTAKE KIT INCLUDES

More information

AABC Specifications for Testing and Balancing HVAC Systems

AABC Specifications for Testing and Balancing HVAC Systems AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL

More information

11/19/2009. Poultry house ventilation system. Poultry house ventilation system design. Example: Exhaust fan capacity rule of thumb

11/19/2009. Poultry house ventilation system. Poultry house ventilation system design. Example: Exhaust fan capacity rule of thumb Poultry house ventilation system Basically consists of exhaust fans and air inlets. Exhaust fan draw in fresh air Poultry House Ventilation System Design Michael Czarick III The University of Georgia Poultry

More information

Flow Measurement Options for Pipeline and Open Channel Flow

Flow Measurement Options for Pipeline and Open Channel Flow Flow Measurement Options for Pipeline and Open Channel Flow October 2013 Presented by Molly Skorpik - 2013 Montana Association of Dam and Canal Systems Conference Irrigation Training and Research Center

More information

CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov

CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

DSRQ - DSRSQ - DSRSQ-THERM

DSRQ - DSRSQ - DSRSQ-THERM DSRQ - DSRSQ - DSRSQ-THERM Specification item: Variable geometry diffuser on 597x597 mm panel developed for rooms with high ceilings where a long throw and a high induction ratio are required. Made up

More information

Fire is the rapid oxidation of a combustible material, releasing heat, light, smoke, and various toxic gases

Fire is the rapid oxidation of a combustible material, releasing heat, light, smoke, and various toxic gases VENTILATION Fire is the rapid oxidation of a combustible material, releasing heat, light, smoke, and various toxic gases If a fire is contained in a building, the heat, smoke, and toxic gases will spread.

More information

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information

More information

Chapter 3.5: Fans and Blowers

Chapter 3.5: Fans and Blowers Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist

More information

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER A steam boiler has been built and installed at a factory for the provision of process steam. The following lists the requirements used in the commissioning

More information

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled

More information

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.

More information

Reducing Heat Stress in the Holding Pens

Reducing Heat Stress in the Holding Pens Reducing Heat Stress in the Holding Pens J.P. Harner III Department of Biological and Agricultural Engineering Kansas State University J.F. Smith Department of Animal Sciences and Industry Kansas State

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT

MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT Date of Inspection: University: Building: Address: Contact Person: Phone number: This inspection

More information

Installation Instructions ERV/PRV Downdraft Vent

Installation Instructions ERV/PRV Downdraft Vent Installation Instructions ERV/PRV Downdraft Vent Tested in accordance with the latest edition of ansi z 21.1 standard for household gas cooking appliances, ANSI/UL 858 household electrical ranges, can/csa-c22.2

More information

Non Domestic Laundry Gas Appliance Installation Code of Practice

Non Domestic Laundry Gas Appliance Installation Code of Practice Non Domestic Laundry Gas Appliance Installation Code of Practice Introduction This code of practice has been produced with the assistance of all Companies within the OPL sector of SLEAT because of the

More information

FORMAL TECHNICAL OPINION

FORMAL TECHNICAL OPINION Jon S. Corzine Governor Issued: March 1985 Revised: June 2001 Code Ref. Update: January 2011 State of New Jersey Department of Community Affairs Division of Codes and Standards PO Box 802 Trenton, New

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

KVL-2 with Plate Shelf

KVL-2 with Plate Shelf Capture Jet Backshelf Hood with Plate Shelf Improved indoor air quality with reduced energy use. Halton Capture Jet with Side-Jet technology reduces the exhaust airflow rates required and improves the

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Some Basics of Duct Design and Installation

Some Basics of Duct Design and Installation September 2003 Retrofitting Existing Ducted Systems GasNetworks HVAC Heating Professionals Fall Conference September 18, 2003 Rick Karg R.J. Karg Associates rjkarg@karg.com Topics Addressed in Session

More information

PERCENT OUTDOOR AIR CALCULATION AND ITS USE

PERCENT OUTDOOR AIR CALCULATION AND ITS USE PERCENT OUTDOOR AIR CALCULATION AND ITS USE APPLICATION NOTE AF-138 (A4 The RH720 calculates Percent Outdoor Air (%OA. In order to take advantage of this feature, it is important to first understand what

More information

HS-901(A) BASIC STEAM HEATING SYSTEMS

HS-901(A) BASIC STEAM HEATING SYSTEMS HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,

More information

LONG LINE SET APPLICATION R-410A

LONG LINE SET APPLICATION R-410A Goodman Manufacturing Company, L.P. 1810 Wilson Parkway / Fayetteville, TN 37334 (888) 593-9988 FAX (931) 438-2273 TECHNICAL PUBLICATION TP-107 INDEX SECTION 1. General Requirements for All Long Line Set

More information

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations

More information

COPPER TUBES IN DOMESTIC HEATING SYSTEMS

COPPER TUBES IN DOMESTIC HEATING SYSTEMS Copper Development Association COPPER TUBES IN DOMESTIC HEATING SYSTEMS Pipe Sizing: Basic Principles Introduction Tube diameters for central heating circuits should be selected so that there is sufficient

More information

Pacific Pump and Power

Pacific Pump and Power Pacific Pump and Power 91-503 Nukuawa Street Kapolei, Hawaii 96707 Phone: (808) 672-8198 or (800) 975-5112 Fax: (866) 424-0953 Email: sales@pacificpumpandpower.com Web: www.pacificpumpandpower.com Pumps

More information

SIZING AND CAPACITIES OF GAS PIPING

SIZING AND CAPACITIES OF GAS PIPING APPENDIX A (IFGS) SIZING AND CAPACITIES OF GAS PIPING (This appendix is informative and is not part of the code.) A.1 General. To determine the size of piping used in a gas piping system, the following

More information

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Page 1 UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Each of the 38 points of requested information is discussed, and references to the supporting manual are given to substantiate the requirement.

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

Canola Drying and Storage Management

Canola Drying and Storage Management Canola Drying and Storage Management Kenneth Hellevang, Extension Engineer Factors affecting canola storage include seed maturity and condition, seed moisture, temperature, length of storage, molds, insects

More information

Duct Design. Presented by Dave Janquart

Duct Design. Presented by Dave Janquart Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length

More information

Installation instructions

Installation instructions Installation instructions Ventilation Fan Model TY-110-A Model TY-110-B Read and save these instructions. Please read these instructions carefully before attempting to install, operate or service the Ventilation

More information

CURTAIN TYPE FIRE DAMPERS

CURTAIN TYPE FIRE DAMPERS URTAIN TYPE FIRE urtain Fire Damper Basics Definition of a Fire Damper: The National Fire Protection Association (NFPA) Standard 9A defines a fire damper as "a device, installed in an air distribution

More information

Steam Injection Humidifiers

Steam Injection Humidifiers SI-1 Steam Injection Humidifiers PURE Humidifier Co. Steam Injection Humidifiers are job-engineered to assure highly efficient steam release into the air stream. Each humidifier is designed for your specific

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

COMMERCIAL GAS DRYER FUELLED BY LIQUEFIED PETROLEUM GAS CODE OF PRACTICE GU13 (MODULE TWO)

COMMERCIAL GAS DRYER FUELLED BY LIQUEFIED PETROLEUM GAS CODE OF PRACTICE GU13 (MODULE TWO) COMMERCIAL GAS DRYER FUELLED BY LIQUEFIED PETROLEUM GAS CODE OF PRACTICE GU13 (MODULE TWO) June 2007 Issue 1 Table of Contents 1. Foreword and Scope... 1 2. Terminology. 3 3. Liquefied Petroleum Gas (LPG)

More information

Natural Air Drying Corn Paul E. Sumner University of Georgia Biological and Agricultural Engineering Department

Natural Air Drying Corn Paul E. Sumner University of Georgia Biological and Agricultural Engineering Department Natural Air Drying Corn Paul E. Sumner University of Georgia Biological and Agricultural Engineering Department Many small farmers prefer to dry crops using unheated or natural air drying in bins in layers

More information

Boiler Plan II Table of Contents

Boiler Plan II Table of Contents Cover Page Table Of Contents Introduction Parts List Additional Materials Assembly instructions Drawings 1-15 Boiler Plan II Table of Contents Introduction This will be a very rewarding project, if you

More information

LLOYD INDUSTRIES INC. DAMPER INSTALLATION INSTRUCTIONS

LLOYD INDUSTRIES INC.  DAMPER INSTALLATION INSTRUCTIONS DAMPER Installation and Maintenance Instructions 1-1/2 Hour Rated, UL Classified model 75 fire dampers For use in fire barriers with ratings of less than 3 hours INSPECTION 1. Inspect for shipping damage.

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used by

More information

Some Basics of Duct Design and Installation

Some Basics of Duct Design and Installation Duct Diagnostics: What s Wrong with this System Smarter Buildings: Smarter Business Residential Conference February 18, 2003 Rick Karg R.J. Karg Associates www.karg.com Topics Addressed in Session Ductwork

More information

INSTALLATION INSTRUCTIONS FOR MINI MAKE-UP AIR MODEL FER

INSTALLATION INSTRUCTIONS FOR MINI MAKE-UP AIR MODEL FER INSTALLATION INSTRUCTIONS FOR MINI MAKE-UP AIR MODEL FER May 2012 VERSION 1.3 Please read instructions carefully before installation. This unit is a complete fresh air make-up package with an integrated

More information

Equipment Options Advantages and Disadvantages ALABAMA NATURAL GAS ASSOCIATION. Darin L. Moore, P.E. Elster American Meter

Equipment Options Advantages and Disadvantages ALABAMA NATURAL GAS ASSOCIATION. Darin L. Moore, P.E. Elster American Meter Equipment Options Advantages and Disadvantages ALABAMA NATURAL GAS ASSOCIATION Darin L. Moore, P.E. Elster American Meter KNOWLEDGE, PLANNING AND IMPLEMENTING REDUCES RISK KNOW THE TYPES OF OVERPRESSURE

More information

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace) UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system

More information

City of Elk River BASEMENT Office Use Only

City of Elk River BASEMENT Office Use Only City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single

More information

Duct Construction and Design. Mark Terzigni SMACNA

Duct Construction and Design. Mark Terzigni SMACNA Duct Construction and Design Mark Terzigni SMACNA Design Methods There are 3 typical methods used for designing non-residential duct systems Equal Friction Static Regain Constant Velocity (exhaust and

More information

A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.

A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment. SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel

More information

Fire, Smoke and Radiation Dampers. Peyton Collie Senior Program Manager Technical Services SMACNA

Fire, Smoke and Radiation Dampers. Peyton Collie Senior Program Manager Technical Services SMACNA Fire, Smoke and Radiation Dampers Peyton Collie Senior Program Manager Technical Services SMACNA Program Code & Regulations Terminology Testing & Rating Damper Installation Codes and Regulations NFPA 90A

More information

Classic Downdraft Vent

Classic Downdraft Vent Classic Downdraft Vent Models: RV30, RV36, RV46 Installation Instructions Includes installation instructions for optional cabinet blower (Dacor model CABP3) Use these downdraft vents only with approved

More information

Room pressure is the difference in pressure between the room itself and the reference it is being compared to.

Room pressure is the difference in pressure between the room itself and the reference it is being compared to. Why Measure Room Static Pressure? What is Room Static Pressure? Room pressure is the difference in pressure between the room itself and the reference it is being compared to. If the room pressure is measured

More information