DESIGN GUIDELINES ROOFING/ROOF PLUMBING

Size: px
Start display at page:

Download "DESIGN GUIDELINES ROOFING/ROOF PLUMBING"

Transcription

1 DESIGN GUIDELINES ROOFING/ROOF PLUMBING VERSION DATE AUTHOR APRIL 2010

2 1.0 Design Principles 1.1 ROOF TYPES STATUS NEW TYPE Pitched Roofs: Pitched metal deck or tile roofs shall generally be provided to all buildings. Flat Roofs: will not be accepted by the University. REFURBISHMENT Flat Roofs shall be: 1. Pitch to be a minimum of one degree greater than that recommended by Manufacturer. 2. Design and installation of metal deck roofs shall comply with AS Design and Installation of Sheet Roof and Wall Cladding 3. Roof design shall incorporate maintenance traffic loads of 1.8kN as per Manufacturer s foot traffic design guidelines. Membrane Roofs Torch on membrane installed as per manufacturers installation instructions. 1.2 MATERIAL SELECTION It is a requirement of the University that the following materials and jointing methods must be specified and installed: COPPER Roof Sheeting Rolled and Seamed (Roofs) Gutters (Eaves, Box and Valleys) Flashings and Cappings JOINTING Sheeting Gutters, Sumps, Rainheads and Outlets. Ridges and Valleys MATERIAL 0.7mm Half Hard Soft Tempered and not less than 0.6mm thick 0.7mm Half Hard 0.7mm Half Hard JOINTING METHODS Concealed fixed with purpose made hooks and clips to allow for thermal movement. Copper sheeting should not be fixed with nails, screws or the like through its oute Seamed or welded Maximum 1.5m centres. Joints to have 75mm lap LEAD Roof Sheeting Gutters (Box and Valleys) Flashings, soakers, parapets and cappings. Lead tacks/clips MATERIAL minimum 40kg per square metre minimum 40kg per square metre minimum 25kg, 30kg preferred per square metre Same weight as the flashing or capping they fix Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 2 of 12

3 JOINTING Flashing Gutters Ridges Valleys Lead tacks/clips JOINTING METHOD 25mm lap and lead burnt 25mm lap and lead burnt maximum 1.5m centres with a 75mm lap maximum 1.2m centres with a 75mm lap To be fixed with clouts compatible with the adjacent roofing material STAINLESS STEEL Roof Sheeting Gutters (Box), sumps, rainheads and outlets MATERIAL 316 with minimum thickness of 0.9mm 316 grade of minimum gauge 1.2mm JOINTING Gutters JOINTING METHOD soldered or welded STEEL AND ALUMINIUM Profiled Steel Roof Sheeting Flat Steel sheeting for Cappings, flashings, trims and the like MATERIAL 0.48 BMT 0.55 BMT ROOF SUPPORT Battens SEALANT (Silicone) SPACING Not greater than 800mm for any roof This degree of support is required to provide adequate long term support of the sheets where they are subjected to maintenance traffic as per manufacturer s foot traffic design guidelines. JOINTING METHOD To be used only to seal lap joints and should not to be used in filling gaps as per manufacturer s instructions. Membrane Roofs Three layer torch on polyester reinforced bitumen based sheet is the preferred system, with a mineral chip upper surface where directly exposed to traffic and weather. The bottom layer should be a vented sheet where there is a likelihood of residual moisture in the substructure. The membrane should be provided with a means to vent the substrate moisture either at its perimeter or with vent cowls spaced across the roof area. Slate roofs Slates should be pre-drilled, not punched, and should be fixed with copper clouts which fit snugly into the hole. Copper hooks or straps should be used to secure the last few slates where finishing off an area of roof. 2. Specific Design Requirements 2.1 SARKING, SUB DECKING AND INSULATION Slate and Tiles Where slates or tiles are fixed over a timber, plywood or compressed sheet sub-deck the roof should have sarking and the space between the sub-decking and the roof covering allowed to ventilate and to drain condensation water to a gutter. Copper roof sheeting should be separated from its supporting deck with a layer of polyester reinforced bitumen sheet Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 3 of 12

4 Insulation and Condensation Control All new and refurbished roofs shall achieve a system thermal resistance level (R-value) of not less than 2.5 for both upward and downward heat flow. 2.2 PENETRATIONS, FLASHINGS, PLANT AND COMMUNICATIONS EQUIPMENT General Consultants refer to Appendix C: Detailed Drawings at the end of this document, for selection of most appropriate detail or specify alternative to the sub topics below. Penetrations Penetration of the roof covering should be avoided wherever possible by attention to the location of equipment and the routing of services lines. When penetrations cannot be avoided they should be grouped and arranged in an orderly fashion to minimise the number of penetrations of the roof, and detailed in accordance with the standard detail methods. Penetration Flashing Sheet flashings on slate or tile roofs should extend up the roof from the penetration to beneath the next tile/slate joint. Where this distance is less than 200mm the flashing shall be extended a further full tile/slate. In each case the flashing is to be folded over at its top end and dressed under the tile/slate. Wall penetrations shall be set out so as to finish clear above the line of any perimeter roof flashing. Individual pipe flashings (Dektite) 'Dektite' or 'Rooftite' are used on a profiled metal deck roof, they shall be used in conjunction with a flat sheet metal cover flashing as indicated on Detail 34 & 35 of Appendix C of this document. Only one Dektite (or equivalent) shall be used for one pipe / conduit that penetrates the roof. The university will not accept fluted flexible electrical conduit with this type of flashing as water travels down the spirals of the conduit and by-passes the flashing. Therefore only smooth surfaced, preferably round, elements should be flashed in this way. 2.3 FASCIAS, SOFFITS, CAPPINGS To be painted as per USYD Finishes for rendered walls. If coverage is needed in lieu of painting then the minimum gauge of materials should 0.60BMT for cappings, flashings, trims and the like. 2.4 SEPARATION STRIPS, EXPANSION JOINTS Movement Roofs are almost invariably constructed of a number of different materials which may adjoin or overly one another. Each material will have its own physical properties, including the degree to which it will move over time with changes in temperature and moisture. Wherever two different materials meet or overlap they should allow each to move independently of the other. This needs to be achieved without compromising the primary function of the roof which is to exclude rainwater. Galvanic Separation Dissimilar metals shall not be fixed in contact with one another, or where rainwater may run off from a nobler to a less noble metal. Mechanical fixings shall be made of the same metal, or a metal of equivalent nobility, as the material through which they are driven wherever practicable; Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 4 of 12

5 Where contact between dissimilar metals cannot be avoided, suitable galvanic separation materials shall be placed between those metals to eliminate direct contact. Separation materials should be weather resistant, UV stable, durable and chemically inert, and might include rubber, neoprene, some sealant materials or commercial grade adhesive tapes; Dissimilar metals should be physically separated from one another to prevent the more noble metal from promoting corrosion of the less noble metal. This separation should also eliminate situations where rainwater will run off a more noble metal onto a less noble metal. Examples: Lead and copper flashings should not be used above or in contact with steel or Zincalume roofing; Brass or steel screws should not be used for aluminium roofing. 2.5 ROOF SAFETY SYSTEMS Introduction Where possible, roof safety should be achieved through the provision of suitable barriers at the edges of roofs, to prevent a fall. Edge barriers might take the form of guard-rails, parapets, adjacent walls, other roofs or the like, or a combination of the above Where the particular roof design does not provide edge barriers, the safety of persons having access to the roof shall be achieved through the use of suitable harness based systems; Static line safety systems are generally preferred to individual anchor point systems as they provide greater flexibility of movement for maintenance personnel. Combinations of static line and individual point systems may be acceptable to achieve full coverage of roofs. Provide Safety Mesh to comply with AS 4389 for flat roofs. The University will not accept surface mounted roof anchors. 3.0 Documents and Certification Requirements Design and documentation utilising these design guidelines are to incorporate the requirements of the following: SAA HB Installation code for metal roofing and wall cladding; AS Fixed Platforms, walkways, stairways and ladders Design, construction and Installation; AS Inspection of Buildings; BCA 2008 Volume 2; AS National Plumbing and Drainage - Stormwater Drainage AS4200 Pliable Building membranes and underlays 1994 AS/NZS Safety Mesh Lead Sheet in Building A guide to Good Practice. Copper Roofing A practical Handbook. AS Design and Installation of Sheet Roof and Wall Cladding AS 3959 Construction of buildings in bush fire-prone areas. Manufacturers Instructions and Recommendations Hydraulic Services see Appendix B: Referenced Documents of this document. Certain fundamental principles such as atmospheric environment, location of campuses, heritage buildings, reducing scheduled maintenance programs and roofing/roof plumbing life be greater than 50 years underpin the more detailed requirements set out in the sections which follow. The resolution of construction details, choices and uses of materials, should have recourse to these fundamental principles and override the above mentioned Australian standards. This document and its accompanying details are intended to provide a basis for the design and documentation of services penetrations through the roofs and walls of the University's Buildings. The size and nature of services vary considerably, as do the methods and materials of construction of the roofs and walls. Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 5 of 12

6 Roof design must meet the following university requirements: Appropriate to the function of the building, safe and effective; Appropriate to the architectural context of the campus locality, noting that various parts of the University's campus contain buildings and precincts of heritage significance; New gutters, sumps, rainheads, shall be oversized by atleast 40%; New or replacements box gutters must have in-built overflow capacity not less than the capacity of the primary outlet(s). Also Minimum clear width 0f 300mm is required for excluding overhangs and obstructions for cleaning/maintenance purposes; Overflows to be a minimum of 25mm from the bottom of the box gutter New or replacements box gutters must be provided with expansions joints appropriate to their length and material of construction; Supports checked for condition by contractor and upgraded to correct fall of 1:100. Stainless Steel and Copper joints must be soldered or welded; New or replacements box gutters shall be configured and positioned so that they may be easily accessed and cleaned; Downpipes to be a minimum of 100mm in diameter; Rainwater collection and disposal systems including gutters, sumps, downpipes shall be designed by a suitably qualified engineer; All new roof designs or major roof refurbishments are to be approved by the Quality Assurance Plumbing and Roofing representative listed in Appendix A of this document prior to construction commences; Supporting of all new roofs and major roof refurbishments, including associated flashings and penetrations, shall have a minimum 10 year warranty on workmanship of the installation and a minimum 20 year warranty on the roofing materials. 3.1 INSPECTIONS AND CERTIFICATION REQUIREMENTS Roof Sheeting and Roof Drainage has been installed and tested in accordance with this document. 3.2 DESIGN DRAWINGS REQUIREMENTS AND RESPONSIBILITIES It is a requirement of the university that each legend page must nominate that: Roof design and penetrations have been designed and documented in accordance with the university Design Guidelines 2009 Version 1.0 All works to comply with the university Design Guidelines 2009 Version 1.0; All works to be installed by a licensed roofer. All new roofs and major roof refurbishments design and documentation must submit the following for review to representatives listed in Appendix A: Relevant CIS Contacts at the end of this document: Gutter, overflow and downpipe sizing calculations (including Australian Rainfall Index used, roof area, etc). Roof design, material selection, flashings, penetrations, fixings, fasteners, waterproofing and vermin proofing measures. Relevant section drawings from Appendix C: Detailed Drawings at the end of this document incorporated into the design provided via the university Project Manager; Detail drawings of the following: Gutters, Valleys, Sumps and Overflows; Penetrations and Flashings Separation Strips and Expansion joints. Jointing details of the above Where detail drawings cannot be resourced from Appendix C: Detailed Drawings of this document then the designer is responsible in documenting detail design drawings. Approval must be granted before construction commences. Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 6 of 12

7 Wind For an individual building or group of buildings, the designers must analyse the risk of wind turbulence. Bushfires Designers to be aware if area of new works or refurbishment is within bushfire zoning. To comply with AS 3959 Construction of buildings in bush fire-prone areas. Painting and Finishes All new and existing plumbing and associated pipe-work, mechanical, fans, cowls etc. on or projecting above roofs must be finished to match the roof colour in proper trades like workmanship, however, all metal framing shall be hot dipped galvanised after fabrication and may be left unpainted. Plant Platforms A minimum clearance of 600mm should be maintained for access beneath any such platform or any equipment or ductwork suspended below it. Steel plant and equipment support platforms installed on roofs shall be manufactured from all hot dip galvanised components. Platforms shall be designed and constructed to be readily assembled or disassembled on site and. so as to minimise site cutting and welding. Floor gratings to platforms should have readily removable panels for access and accommodation of future services. Plant and Equipment Plant and equipment should be located in a plant room designed for the purpose or fixed to adjacent walls/buildings; Where the foregoing cannot be achieved, and plant has to be placed on a roof, or where existing plant is located on a roof, such plant and equipment should be located in such a way that the roof surface and materials are fully accessible for maintenance or replacement; Plant and equipment should be located in such way as to be fully accessible for maintenance and replacement; Where plant and equipment is required to be located on a roof, it shall be placed on steel or aluminium platform structures elevated above the roof surface. A clear space of minimum 600mm shall be provided between the roof surface and the lowest part of the platform structure, or any item of equipment or reticulation suspended below the platform; Platforms shall be designed by a suitably qualified structural engineer to take into account the proposed and likely future equipment loads. Platforms shall be designed in accordance with applicable parts of AS1657, and provided with perimeter guardrails where necessary. Steel platforms shall be constructed using hot dip galvanised members. Walkovers be placed on concrete blocks, with a membrane below. New Plant and equipment to have tundishes for collection of condensate. No condensate is to be emitted onto roof surface. Condensate drain lines and tundishes will not penetrate the roof and must be piped back to a central or nominated penetration zones as coordinated between mechanical and hydraulic services engineers and contractors. 3.3 Communications Equipment Approvals must be obtained from the representatives listed in Appendix A of this document at the following Stages: 1. Preliminary: Designs for installation of communications equipment (transmission towers, relays, satellite dishes, panel and parabolic antennae and the like) including their associated equipment shelters, cable trunking and access requirements. 2. Design (Early Stage) Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 7 of 12

8 Installation of communication equipment with details being provided in relation to any radiation or other hazards might be created. In the case of installations proposed for existing roofs, an assessment of the condition of the roof shall be made prior to commencement of design work. The assessment to take into consideration such matters as structural integrity, weathering condition, existing defects or failures, other equipment or facilities already on the roof, pre-existing hazards on the roof (materials or equipment) and access requirements; New communications equipment shall be kept clear of cappings and flashings (minimum 150mm) and be set back not less than 1000mm from the roof edge or a bounding wall; Where possible, such installations should be designed to be self supporting by virtue of its own weight and configuration, with the minimum number of direct fixings to the building structure. The equipment should be readily removable without damage to the building fabric or creation of a need for major rectification works; The design of such installations shall not impair access for maintenance of the roofing materials or other equipment on the roof; Signage Installations shall include suitable advisory signage placed at the door giving access to the subject roof, warning persons accessing the area of any hazards the installation may generate. Lines shall be painted onto the roof identifying areas and distances that may be unsafe; Testing Design documentation for projects must include a requirement that all box gutters are flood tested prior to issue of certificate of practical completion; Design documentation for projects must include a requirement that all flat membrane roofs are flood tested prior to issue of certificate of practical completion. Where the membrane is exposed, this test is to be carried out when the works are complete. Where the membrane is concealed below a wearing slab, insulation or other overlay material, flood testing is to be carried out after the membrane is complete but before any overlay is placed, and again after the overlay has been completed. 3.4 INSPECTION AND CERTIFICATION REQUIREMENTS 1. Where the structure to which any anchor point is proposed to be attached is timber, an inspection shall be made and report prepared by a suitably qualified person on the condition of the timber member(s). The inspection should be carried out in accordance with AS and extend to cover the whole of the roof of which the member is part. The report should identify the species of the timber as well as its condition; 2. Prior to the installation of any anchor point, a suitably qualified practising structural engineer shall inspect the roof or other structure to which the anchor is intended to be attached, and shall provide a certificate, in a form acceptable to the University, that particular roof or other structure is capable of sustaining the loads that could be applied to it in the event of a fall; 3. Certificate of Safety System. Designed, installed and tested in accordance with AS and this document 4. All anchor points including static line supports shall be provided with a manufacturer's compliance certificate Roof Safety System must meet the following university requirements: No installation of anchor points shall be carried without the prior approval of representatives listed in Appendix A: Relevant CIS Contacts of this document; Any single or double anchor point or static line shall be designed to suit the particular roof and roof structure upon which it is proposed to be mounted; Anchor points shall be installed in locations that are accessible for inspection at any time; Fixing of anchor points to timber and steel structures shall be bolted. Bolted connections shall be designed so as not to inherently weaken the member for which they are made. Screw fixings will not be acceptable under any circumstances; Fixing of anchor points to concrete structures shall be carried out with a complete through bolt assembly with inner and outer plates. Where through bolting is not possible due to particular site constraints, anchor points in concrete shall be effected using an approved chemical insertion method. Any such products and product systems shall be Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 8 of 12

9 used and applied in strict accordance with the manufacturer's written instructions, and a written statement shall be provided from the manufacturer stating that the product and system are suitable for the particular application; All fixings shall be stainless steel 316; Galvanised ladders to be provided at changes in roof levels; Ladders to have landings on flat horizontal surfaces. Barriers to be placed around perimeter of roof safe walkways according to AS Fixed Platforms, walkways, stairways and ladders Design, construction and Installation; After submission of the above approval must be granted from the representatives listed in Appendix A of this document before construction commences. Signage Each complete installation shall include suitable advisory signage and a plan of the installed system, to be placed adjacent to each specified point of access to the system as per AS/NZS Clause Labels and Signs; Testing After installation, each single person anchor point shall be pull tested to 15 kn and each two person anchor point shall be pull tested to 21 kn; Documentation/Drawings Design documentation for roof safety systems should require that at completion of the initial installation of the system, the installing Contractor shall provide to the University the following:- 1. An accurate plan of the installed system, drawn to a suitable scale, locating and describing the nature of each anchor point and other component (eg: static lines) and identifying the structural item to which they are attached; 2. the engineering and manufacturer's certificates called for above; 3. all harnesses, lanyards, carabiners, transfasteners, and other loose or mobile components as necessary; 4. Roof Access detailed drawings to be drawn at Scale 1:5. 5. Training for University nominated personnel in the use of the system. It is also a requirement of the university that each legend page must nominate that: 1. Roof Safety System has been designed and documented in accordance with the university Design Guidelines 2009 Version All works to comply with the university Design Guidelines 2009 Version All works to be installed by a licensed roofer Roof Access Permits and Maintenance Requirements All parts of all roofs must be accessible for maintenance; Where the roof design results in the creation of a roof void, the void should also be accessible for inspection; Access provided to and within roofs should be in accordance with AS and any other applicable safety standards; Access to roof areas should be provided through a service area (eg. plant-room, stairwell, roof space) and preferably not through public areas. Where the foregoing cannot be achieved, that access should be provided in such a way as to preclude unauthorised access; Accessible roof voids should be adequately lit and provided with suitable walkways for maintenance access. Access to Roof Area must not be through windows or mobile equipment for example ladders, step ladders, chairs, etc. Dedicated access walkways must be provided by the installer. Safety Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 9 of 12

10 All persons working on roofs shall have a current WorkCover OH&S GENERAL INDUCTION for construction work in NSW OHS Construction Induction Training Certificate and shall wear shoes suitable for work on the particular roof type. Harnesses shall be worn where required. Where maintenance access is or is likely to be required to a particular roof or plant equipment located on it, consideration shall be given to the installation of plant platforms, ladder brackets, roof anchor and/or static line systems to provide for ongoing safety on the roof. The extent of these requirements to be confirmed prior to the project going to tender with the representatives listed in Appendix A of this document. Definitions Anchor point Fall - Fall Arrest System Work Positioning System Description Any single or multiple fixed anchor point, or static line support point, whether part of a work positioning or fall arrest system, and whether attached to a roof, wall or other structure Either a free fall, impeded fall or uncontrolled slide down a roof or similar structure. Any arrangement of anchor points and other equipment or fixtures which are designed to arrest the fall a User who could reach a position where a fall is possible. Any arrangement of anchor points and other equipment or fixtures which are designed to prevent a User from reaching any point from which they could fall. Appendices: Appendix A: Relevant CIS Contacts Group Acronym Contact Quality Control & Safety - Plumbing & Roofing ( QC&S P&R) Quality Assurance Plumbing & Roofing (CIS QA P&R) Appendix B: Referenced Documents Documents referenced throughout this document can be found at the following page on University of Sydney s Campus Infrastructure & Services (CIS) Internet Hydraulic Services document resides under Design Guidelines CAD Drawing Standard document resides under Design Guidelines Master planning Survey, Grounds conservation Plan and Conservation management Plan reside under Heritage Documents Environmental Policy For Further help on obtaining referenced documents go to the following link: for a full list of contacts. Appendix C: Detailed Drawings (Available on request) Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 10 of 12

11 Drawing Register # Detail Title Version Roof Material 1. Wall flashing folded sheet metal over membrane roof cut in type. B Walls and Membrane Roofs 2. Wall flashing extruded aluminium over membrane roof - pressure seal type B Walls and Membrane Roofs 3. Wall flashing copper over copper box gutter - cut in type (Section) B Walls 4. Wall flashing copper over copper box gutter - cut in type (Section) B Walls 5. Large service box penetration, brass & copper, for membrane on concrete Membrane roof (Plan) 6. Large service box penetration, brass & copper, for membrane on concrete B Membrane and Topping roof (Section) Slab 7. Large service box penetration, brass & copper, for membrane on concrete B mbrane and Topping Slab roof (Section) 8. Large service box penetration colorbond, for colorbond/ zincalume roof on A Colorbond/ zincalume timber frame (Plan) 9. Large service box penetration colorbond, for colorbond/ zincalume roof on B Colorbond/ zincalume timber frame (Section) 10 Large service box penetration colorbond, for colorbond/ zincalume roof on B Colorbond/ zincalume timber frame (Section) 11 Small service box penetration copper, for membrane on concrete roof (Plan) Membrane and Topping Slab 12 Small service box penetration copper, for membrane on concrete roof A Membrane and Topping (Elevation) Slab 13 Small service box penetration copper, for membrane on concrete roof A Membrane and Topping (Section) Slab 14 Small service box penetration copper, for membrane on concrete roof A Membrane and Topping (Section) Slab 15 Small service box penetration slate,/tile roof (Plan) Slate/Tile 16 Small service box penetration slate,/tile roof (Elevation) A Slate/Tile 17. Small service box penetration slate,/tile roof (section) B Slate/Tile 18 Small service box penetration slate,/tile roof (section) H Slate/Tile 19 Small service box penetration colorbond roof (Plan) Colorbond 20 Small service box penetration colorbond roof (Elevation) A Colorbond 21 Small service box penetration colorbond roof B Colorbond 22 Small service box penetration colorbond roof (section) B Colorbond 23 Upstream cover flashing, sheet metal, for profiled metal roofs A Colorbond and Copper 24 Small diameter penetration spigots, lead, for slate/ tile roofs (section) A Slate / Tile 25 Small diameter penetration spigots, lead, for slate/ tile roofs (Isometric A Slate/Tile views) 26 Small diameter penetration spigots, lead, for slate/ tile roofs (section) A Slate/Tile 27 Concrete machinery pad mount. (Plan and Section) and uni-strut bracket A Membrane mounting for hydraulic, electrical and refrigeration lines transversing membrane on concrete roof. 28 Concrete pad and uni-strut bracket mounting for hydraulic, electrical and A Membrane refrigeration lines transversing membrane on concrete roof. 29 upvc fume cupboard exhaust through membrane on concrete roof (section) C Membrane 30 Wall flashing, lead, over membrane/ concrete roof - no cavity B Walls and Membrane Roofs 31 Wall flashing, lead, over membrane/ concrete roof - with cavity B Walls and Membrane Roofs 32 Vent pipe penetration through membrane./ concrete roof (plan) Membrane 33 Vent pipe penetration through membrane./ concrete roof (section) A Membrane 34 Vent pipe penetration through metal roof (plan) (Dektite) Colorbond 35 Vent pipe penetration through metal roof (section) (Dektite) B Colorbond Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 11 of 12

12 36 Structural steel pipe penetration and plant platform through membrane/ Membrane concrete roof (plan) 37 Structural steel pipe penetration and plant platform through membrane/ A Membrane concrete roof (section) 38. Structural steel pipe penetration and plant platform through metal deck roof Colorbond (plan) 39. Structural steel pipe penetration and plant platform through metal deck roof B Colorbond (section) 40. Membrane perimeter detail where bounding wall is metal clad A Colorbond Walls 41 upvc fume exhaust through slat/ tile roof C Slate / Tile 42 upvc fume exhaust through metal roof C Colorbond 43 Weatherhood (removable) for wall penetrations A Wall 44 Vent pipe penetrations through slate/ tile roof. A Slate / Tile Roofing_and_Penetrations_2009_version_1_with_amendmentsJL.doc Page 12 of 12

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035 Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí

More information

When considering Roof drainage design the following should be taken into account:

When considering Roof drainage design the following should be taken into account: Roof Drainage Design The primary objective of a gutter or spouting system is to remove water from the roof catchment area and channel that water to the ground drainage. Water ingress can have detrimental

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1 Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.

More information

AUTHORITIES AND RESPONSIBILITES...

AUTHORITIES AND RESPONSIBILITES... Table of Contents 1 PURPOSE... 1 2 SCOPE... 1 3 GLOSSARY OF TERMS... 2 4 AUTHORITIES AND RESPONSIBILITES... 2 5 TECHNICAL REQUIREMENTS... 2 5.1 Introduction... 2 5.2 Design and Documentation... 3 5.2.1

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single

More information

0845 0098 980 www.nicholsonsts.com

0845 0098 980 www.nicholsonsts.com 0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Including. Rubershield-Pro. Breather Membrane

Including. Rubershield-Pro. Breather Membrane Including RubershieldPro Breather Membrane 2 Ruberoid produces a wide range of underslating membranes, primarily to be installed below tiles, slates or metal roofing providing a secondary barrier against

More information

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

NRG 75 CRF NRG GREENBOARD WALL SYSTEM NRG GREENBOARD WALL SYSTEM NRG Energy Efficient Building Systems is pleased to announce a revolution in lightweight cladding systems. NRG Building Systems is the first and only company to achieve CodeMark

More information

SECTION 07 61 13 STANDING SEAM METAL ROOFING

SECTION 07 61 13 STANDING SEAM METAL ROOFING SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced

More information

GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY

GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY July 2008 1.0 SCOPE These guidelines describe the way in which air conditioning units shall be installed or replaced

More information

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers.. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3

More information

Epdm Flat Roofing Systems

Epdm Flat Roofing Systems Epdm Flat Roofing Systems EDPM can be fully bonded, loose laid and ballasted or mechanically attached depending on the existing roof and its proposed usage. This applies to roofs to be refurbished and

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

Technical Solution Sheet 7.08 7: Mechanical Services (Including duct heating)

Technical Solution Sheet 7.08 7: Mechanical Services (Including duct heating) 7: Mechanical Services (Including duct heating) Split System Air Conditioning AIM The aim of this technical solution is to inform practitioners on the requirements for the safe discharge of condensate

More information

The formation of roof waterproofing details calls for

The formation of roof waterproofing details calls for 3.5 BUILT-UP ROOFING DETAIL DESIGN INTRODUCTION The formation of roof details calls for a combination of the skills of the designer and the roofer. There are many different approaches to detail design

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

FLASHMAN WINDOW AND DOOR FLASHING SYSTEM. Product. Scope. Appraisal No. 573 [2013]

FLASHMAN WINDOW AND DOOR FLASHING SYSTEM. Product. Scope. Appraisal No. 573 [2013] FLASHMAN WINDOW AND DOOR FLASHING SYSTEM This Appraisal replaces BRANZ Appraisal No. 573 (2007). Amended 05 February 2016. BRANZ Appraisals Technical Assessments of products for building and construction.

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)

More information

SECTION 07400 STANDING SEAM METAL ROOF

SECTION 07400 STANDING SEAM METAL ROOF SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and

More information

State of Connecticut Department of Public Health RADON PROGRAM

State of Connecticut Department of Public Health RADON PROGRAM State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES

EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING

More information

Issue of the Guidelines on Prevention of Water Seepage in New Buildings

Issue of the Guidelines on Prevention of Water Seepage in New Buildings graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose

Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5 1. Purpose The purpose of this practice note is to address the incidence of deck and roof membrane

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

Detached accessory structures that contain no conditioned floor area are exempt.

Detached accessory structures that contain no conditioned floor area are exempt. RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of

More information

How To Build A Gambrel Roof And A Gable End Roof

How To Build A Gambrel Roof And A Gable End Roof Dutch Gable or Gambrel Roof and The Scotch Valley The folowing pages are an extract from Carp 12 text TAFE NSW Construction and Transport Division 71 HIP and VALLEY ROOFING GAMBREL / DUTCH GABLE The effect

More information

Fixed Access Ladders. Table of Contents. 1. Legislative Requirements

Fixed Access Ladders. Table of Contents. 1. Legislative Requirements Fixed Access Ladders Engineering Data Sheet 2-04 Revised: January 1997 Table of Contents 1. Legislative Requirements 2. General 3. Rungs 4. Side Rails 5. Safety Cages 6. Attachment & Anchoring 7. Platforms

More information

Multi-layer Insulation Blanket for Roofs

Multi-layer Insulation Blanket for Roofs Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof

More information

KAHU RESIDENTIAL ROOFING RRKA DETAIL LIST

KAHU RESIDENTIAL ROOFING RRKA DETAIL LIST KAHU DETAIL LIST 00 / 24 COVER SHEET 01 / 24 ROOF RIDGE 02 / 24 SAWTOOTH RIDGE 03 / 24 SAWTOOTH EAVE 04 / 24 ROOF VALLEY 05 / 24 ROOF - CHANGE PITCH 06 / 24 EAVE WITH METALLINE FASCIA 07 / 24 EAVE WITH

More information

Ubiflex. Non-lead flashing system

Ubiflex. Non-lead flashing system Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes

More information

Preformed Metal Roofing and Siding

Preformed Metal Roofing and Siding Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision

More information

WorkSafe Guidance Document FALL PROTECTION IN RESIDENTIAL CONSTRUCTION

WorkSafe Guidance Document FALL PROTECTION IN RESIDENTIAL CONSTRUCTION WorkSafe Guidance Document FALL PROTECTION IN RESIDENTIAL CONSTRUCTION WorkSafe Guidance Document Fall Protection in Residential Construction Table of Contents Executive Summary... 1 Introduction... 1

More information

7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME

7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME 7. Installation Window involves the fixing of window frame at an earlier construction stage and subsequent of the window sashes. This is a highly workmanship dependent process. Only trained and approved

More information

Residential Inspection Guidelines

Residential Inspection Guidelines Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against

More information

WATERPROOFING FOR CONCRETE STRUCTURES

WATERPROOFING FOR CONCRETE STRUCTURES MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck

More information

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,

More information

Sun Windows General Information Sun New Construction Window Installation Instructions

Sun Windows General Information Sun New Construction Window Installation Instructions Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

Roof Curbs, Extensions and Equipment Supports

Roof Curbs, Extensions and Equipment Supports Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....

More information

Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated.

Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standing-seam metal roofing, custom fabricated. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: Show installation

More information

STANDING SEAM SHEET METAL ROOFING

STANDING SEAM SHEET METAL ROOFING STANDING SEAM SHEET METAL ROOFING GENERAL INFORMATION 1.1 For all standing seam metal roofing work consult Columbia University Facilities Exteriors and Historic Preservation group. 1.2 Fabricator is responsible

More information

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.

More information

Services Enclosures and Protected Shafts - Maintaining Compartmentation

Services Enclosures and Protected Shafts - Maintaining Compartmentation Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping

More information

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It

More information

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3

More information

Premium Nixalite All Stainless Steel Bird Barrier Spikes Includes specifications for: Premium Nixalite Models S, H and W and Mounting Hardware.

Premium Nixalite All Stainless Steel Bird Barrier Spikes Includes specifications for: Premium Nixalite Models S, H and W and Mounting Hardware. Three-Part Specifications - Copyright 2014 - Nixalite of America Inc Premium Nixalite All Stainless Steel Bird Barrier Spikes Includes specifications for: Premium Nixalite Models S, H and W and Mounting

More information

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength. INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal

More information

PART E SPECIFICATIONS

PART E SPECIFICATIONS PART E SPECIFICATIONS Page 1 of 5 PART E - SPECIFICATIONS GENERAL E1. APPLICABLE SPECIFICATIONS, STANDARD DETAILS AND DRAWINGS E1.1 The City of Winnipeg Works and Operations Division Standard Construction

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

CI SfB. (4-) Nn2. Onduline. Mini Profile. Onduline Garden Roof Range. Onduline Building Products Ltd

CI SfB. (4-) Nn2. Onduline. Mini Profile. Onduline Garden Roof Range. Onduline Building Products Ltd CI SfB (4-) Nn2 Onduline Mini Profile Onduline Garden Roof Range Onduline Building Products Ltd Onduline Garden Roof Range Onduline Mini Profile The new Onduline Mini Profile sheets have been designed

More information

ROOFS - Guidance for Repair, Maintenance and Replacement

ROOFS - Guidance for Repair, Maintenance and Replacement ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed

More information

I-Line - Snap-On Feature

I-Line - Snap-On Feature Oct 2012 I-Line - Snap-On Feature DATA SHEET Snap-On features - Guaranteed truelines every time Bailey I-Line Snap-On is an architectural cladding feature offering creative possibilities for architects

More information

Roofers Guide to Underslating Membranes

Roofers Guide to Underslating Membranes Roofers Guide to Underslating Membranes IKO is a worldwide enterprise, with more than 3000 employees, and manufacturing plants in Canada, the United States, United Kingdom, Belgium, Holland, France and

More information

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

VM ZINC : standing seam Guidelines for specification and installation

VM ZINC : standing seam Guidelines for specification and installation VM ZINC : standing seam Guidelines for specification and installation Junglim Architecture - QUARTZ-ZINC Roofing and cladding system in VM ZINC Roofs from a 3 pitch and facades Freedom with shape and appearance

More information

FLASHCLAD VERTICAL WEATHERBOARD CAVITY SYSTEM. Product. Scope. Appraisal No. 829 [2013] Appraisal No. 829 (2013) Amended 05 February 2016

FLASHCLAD VERTICAL WEATHERBOARD CAVITY SYSTEM. Product. Scope. Appraisal No. 829 [2013] Appraisal No. 829 (2013) Amended 05 February 2016 WEATHERBOARD CAVITY SYSTEM Amended 05 February 2016 BRANZ Appraisals Technical Assessments of products for building and construction. Flashclad Limited PO Box 346 Kaiapoi 7633 North Canterbury Tel: 0800

More information

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details D Installation Details D1 General D2 Walls D3 Ceilings D4 Reference D Installation Details D Contents D1 General Installation and Fastening Sequence for Steel Studs D1.1 Fastener Selection D1.3 D2 Walls

More information

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Department of Advanced Education and Skills Apprenticeship and Trades Certification Division Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Note to Apprenticeship Applicants

More information

Installation Manual for STANDING SEAM ROOFING

Installation Manual for STANDING SEAM ROOFING Installation Manual for STANDING SEAM ROOFING Absolute Steel Toll Free 877-833-3237 / Phone 480-768-1618 / Fax 480-768-1514 www.metalroofingsource.com Standing Seam features approximately one-inch high

More information

Residential Deck Safety, Construction, and Repair

Residential Deck Safety, Construction, and Repair Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the

More information

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS.

BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)

More information

Window Installation Instructions

Window Installation Instructions Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments Cannon T4 Modular Data Centres For Outside Deployment & Challenging Environments A high performance, full specification Data Centre, up to Tier 4* resilience, instantly deployable A highly secure Data

More information

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

Colonnade Security Pipe

Colonnade Security Pipe Description: Round & Square downpipe formed from extruded 6060 T4 aluminium in various sizes (Ø83mm, Ø108mm, 83x83 mm & 108x108mm*) & supplied with a complete range of accessories i.e. Offsets, bends,

More information

Packaged Terminal Air Conditioner Wall Sleeve Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation

More information

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new

More information

The WANZ Guide to Window Installation

The WANZ Guide to Window Installation The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check

More information

Cupa Natural Slate Roofing design and fixing guide

Cupa Natural Slate Roofing design and fixing guide Cupa Natural Slate Roofing design and fixing guide Cupa Natural Slate synonymous with quality Currently the Spanish slate industry is the undisputed market leader in natural slate production, with 90%

More information

NRCA s steep-slope manual is thoroughly revised for 2013

NRCA s steep-slope manual is thoroughly revised for 2013 Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA

More information

AA Solar and Sun Power Plus

AA Solar and Sun Power Plus AA Solar and Sun Power Plus www.aasolar.co.nz www.sunpowerplus.co.nz -1- Contents Chapter Title Page 1 General information 3 2 Safety and Installer Responsibilities 4 3 Technical Specifications 5 4 Tools

More information

Bituminous Sheet Flat Roofs: Their repair and maintenance

Bituminous Sheet Flat Roofs: Their repair and maintenance Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and

More information

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam

More information

Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions

Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions All questions and concerns please call 904-696-9700 Discount Direct Metal Roofing Plus Rib metal roofing panels are a strong,

More information

BLACK JACK ALL WEATHER ROOF COATING

BLACK JACK ALL WEATHER ROOF COATING PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.

More information

STEP-BY-STEP. construction guide. Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet.

STEP-BY-STEP. construction guide. Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet. STEP-BY-STEP construction guide Delivering better priced Conservatories, Sun Lounges and Garden Rooms via the Internet. Welcome to our CONSERVATORY AND SUNROOM CONSTRUCTION GUIDE What is the specification

More information

Sample Drawing Package for One and Two Family Dwelling Applications

Sample Drawing Package for One and Two Family Dwelling Applications Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx

More information

Solicitation DTFACN-11-R-00079 Attachment #9

Solicitation DTFACN-11-R-00079 Attachment #9 These specs are only a general overview of the typical VOR Roof construction. These are for reference only. Each individual project will have its own specifications. 1 VOR Roof Projects IDIQ Solicitation

More information

Reticulation sewers in basements Technical guidelines

Reticulation sewers in basements Technical guidelines Reticulation sewers in basements Technical guidelines Overview What These guidelines explain our technical requirements for laying sewers in building basements. The scope of the guide is restricted to

More information

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM

STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally

More information