1 Report of Impact of Food Waste Disposers on Combination Waste and Vent Systems and Individual Vents Terminating to an Air Admittance Valve 1 ASPE Research Foundation

2 Report of Impact of Food Waste Disposers on Combination Waste and Vent Systems and Individual Vents Terminating to an Air Admittance Valve by Curtis A. Ray, Jr., CPD and Max Weiss 2 ASPE Research Foundation

3 This research project was conducted under the direction, and with funding from, the American Society of Plumbing Engineers Research Foundation, Inc. The Board of Directors of the American Society of Plumbing Engineers Research Foundation is as follows: President: Vice Presidents: Treasurer: Secretary: Julius Ballanco, PE, CPD, FASPE Mitch Clemente, CPD William Erickson William Hughes, CPD, FASPE, LEED AP Curtis Ray Jr., CPD Max Weiss Stanley Wolfson Carol Johnson, CPD, LEED AP Jim Kendzel, MPH, CAE Copyright 2013 by American Society of Plumbing Engineers Research Foundation, Inc. All rights reserved, including rights of reproduction and use in any form or by any means, including the making of copies by any photographic process, or by any electronic or mechanical device, printed or written or oral, or recording for sound or visual reproduction, or for use in any knowledge or retrieval system or device, unless permission in writing is obtained from the publisher. 3 ASPE Research Foundation

4 Purpose The purpose of this research project was to investigate the impact that food waste disposers have on the venting of the drainage system when vented by a combination waste and vent system or an individual vent that terminates to an air-admittance valve (AAV). The 2012 International Plumbing Code (IPC), published by the International Code Council (ICC), restricts the installation of food waste disposers on combination waste and vent systems, reportedly based on the presumption that such installations will compromise waste and vent system performance. This research establishes that there is no measurable effect on venting or adjacent trap seal integrity by operation of food waste disposers either in the case of a combination waste and vent system or in the case of an individual vent incorporating an air-admittance valve. Method Two test apparatuses representing plumbing installations were constructed: one utilizing a commercial food waste grinder in accordance with Diagram 3.1b and one utilizing a residential food waste grinder in accordance with Diagram 3.1c of the Test Protocol in Appendix A. Residential Apparatus The plumbing diagrams provided for 40 feet of drain, sloped at 1/4 inch per foot, and 45 feet of vent. Each apparatus was measured and verified to be in accordance with the prescribed dimensions of the test protocol relative to the test being conducted. The residential food waste grinder was InSinkErator 1 HP Evolution Excel, and the commercial food waste grinder was InSinkErator Model SS200. Ambient barometric pressure, temperature, and humidity within the laboratory were measured and recorded at mbar, 23.5 C, 18.2 percent respectively. 4 ASPE Research Foundation

5 Clear traps at the disposer and downstream fixture with adjacent lined charts calibrated at.200-inch lined intervals were utilized to maximize visualization of hydraulic performance. All test increments were filmed, and that film constitutes the demonstrative portion of this report. (Go to aspe.org/fooddisposertestvideos to view the recordings.) Residential Disposer TrAP Residential DownstreAM Fixture TrAP 5 ASPE Research Foundation

6 CoMMercial Disposer TrAP The food component introduced was 2 cups of La Choy Chicken Chow Mein for the residential test and 3 cups of La Choy Chicken Chow Mein for the commercial test. Water and food components were introduced in each increment in accordance with the provisions of the Test Protocol. Residential Food Quantity COMMerCIAL Food Quantity 6 ASPE Research Foundation

7 Observation No perceptible movement or diminishment of trap water-seal integrity was observed in any of the Test Protocol increments in either the residential or commercial versions. The only water movement observed in the object trap was a minimal reaction to disposer starting torque and vibration transmitted through test apparatus piping. Following the culmination of Test Protocol testing, a slug load consisting of 5 gallons was discharged to the receiving sink in approximately 10 seconds, thereby creating a flow load of approximately gallons per minute. The object trap showed no measurable change in water-seal integrity during the enlarged loading. Conclusion The installation and operation of food waste disposers in combined waste and vent systems in either a domestic or commercial piping system produce no compromise of adjacent trap seals or venting functions. This is true in open venting and AAV venting systems. 7 ASPE Research Foundation

8 APPendix A Test Protocol 1.0 PurPose 1.1 The purpose of this research project is to investigate the hydraulic impact food waste disposers have on the venting of the drainage system when vented by a combination waste and vent system or an individual vent that terminates to an air-admittance valve. The 2012 International Plumbing Code restricts the installation of food waste disposers on combination waste and vent systems. The research will establish whether such a restriction is justified. 1.2 Some jurisdictions have questioned the use of food waste disposers on sinks that have individual vents that terminate to an air-admittance valve. This research will determine if such concerns are valid. 2.0 DEFinitions & NOMenCLAture 2.1 Definitions Combination Waste and Vent: A specially designed system of waste piping embodying the horizontal wet venting of one or more sinks or floor drains by means of a common waste and vent pipe adequately sized to provide free movement of air above the flow line of the drain. 2.2 Nomenclature AAV = Air-admittance valve DWV = Drainage, waste, and vent PVC = Polyvinyl chloride Inch = Inches 3.0 TEST ASSEMbly 3.1 Three test assemblies will be constructed for testing. (Separate assemblies are not required. A standard test assembly can be modified for each series of tests.) See the three diagrams (3.1a, 3.1b, and 3.1c) below for the layout of the test assembly. DiagrAM 3.1a Legend 1. Sink 2. Residential Food Waste Disposer 3. Vat of water 4. Vent 8 ASPE Research Foundation

9 DiagrAM 3.1b Legend 1. Sink 2. Residential Food Waste Disposer 3. Vat of water 4. Vent DiagrAM 3.1c Legend 1. Sink 2. Residential Food Waste Disposer 3. Vat of water 4. Vent 3.2 Pipe Material All drainage and vent pipe and fittings shall be DWV PVC. The trap and trap arm shall be clear plastic so the trap seal can be observed during testing. 3.3 The drain pipe for the test assemblies (Diagrams 3.1a, 3.1b, and 3.1c) shall be piped per the diagram and at the sizes indicated. This pipe shall lay across the floor with a slope of 1/4 inch per foot terminating at the vat for water reclamation. 3.4 The vent pipe for the test assemblies (Diagrams 3.1a, 3.1b, and 3.1c) shall be piped per the diagram and at the sizes indicated. The vent pipe extension can run in any alternate method as long as no traps are formed. 3.5 Connect the largest food waste disposer to the test assembly for both the residential test and the commercial test. Fill each trap with water to establish a 2-inch trap seal. 4.0 TEST ProtoCOL 4.1 General Set up a video camera to record water motion in the drain pipe Place indexed board behind both traps to record fluctuations as the test is performed. 4.2 Residential Assembly (Diagram 3.1a) Preparation (A1 through A5): None required Test Cycles (A1 through A5) Flow the maximum amount of water (maximum of 1.5 gallons per minute [gpm]), wait five seconds, and then turn on the food waste disposer Run the food waste disposer for 25 seconds, turn off the food waste disposer, and then Record the traps for water movement during the entire test cycle time Wait two minutes, and repeat the test a minimum of four more times. 9 ASPE Research Foundation

10 4.2.3 Preparation (A6 through A10) Place 2 cups of La Choy Chicken Chow Mein in the food waste disposer Test Cycles (A6 through A10) Flow the maximum amount of water (maximum of 1.5 gpm), wait five seconds, and then turn on the food waste disposer Run the food waste disposer for 25 seconds, turn off the food waste disposer, and then Record the traps for water movement during the entire test cycle time Observation After each test cycle (A1 through A10), measure the depth of the trap seal in the adjacent sink trap and document the results. The minimum trap seal required for a successful test is 1-1/2 inches. 4.3 Commercial test assembly (Diagram 3.1b) Preparation (B1 through B5): None required Test Cycles (B1 through B5) Flow the maximum amount of water (maximum of 3 gpm), wait five seconds, and then turn on the food waste disposer Run the food waste disposer for 60 seconds, turn off the food waste disposer, and then Record the traps for water movement during the entire test cycle time Wait 5 minutes and repeat the test a minimum of 4 more times Preparation (B6 through B10) Place 3 cups of La Choy Chicken Chow Mein in the food waste disposer Test Cycles (B6 through B10) Flow the maximum amount of water (maximum of 3 gpm), wait five seconds, and then turn on the food waste disposer Run the food waste disposer for 60 seconds, turn off the food waste disposer, and then Record the traps for water movement during the entire test cycle time Observation After each test cycle (B1 through B10), measure the depth of the trap seal in the adjacent sink trap and document the results. The minimum trap seal required for a successful test is 1-1/2 inches. 10 ASPE Research Foundation

11 4.4 AAV Assembly (Diagram 3.1c) Preparation (C1 through C5): None required Test Cycles (C1 through C5) Flow the maximum amount of water (maximum of 1.5 gpm), wait five seconds, and then turn on the food waste disposer Run the food waste disposer for 25 seconds, turn off the food waste disposer, and then Record the traps for water movement during the entire test cycle time Wait two minutes, and repeat the test a minimum of four more times Preparation (C6 through C10) Place 2 cups of La Choy Chicken Chow Mein in the food waste disposer Test Cycles (C6 through C10) Flow the maximum amount of water (maximum of 1.5 gpm), wait five seconds, and then turn on the food waste disposer Run the food waste disposer for 25 seconds, turn off the food waste disposer, and then Record the traps for water movement during the entire test cycle time Observation After each test cycle (C1 through C10), measure the depth of the trap seal in the adjacent sink trap and document the results. The minimum trap seal required for a successful test is 1-1/2 inches. 5.0 TEST ProtoCOL 5.1 Record and document all results and observations for each test assembly. END ProtoCOL 11 ASPE Research Foundation

JB ENGINEERING AND CODE CONSULTING, P.C. 1661 Cardinal Drive Munster, IN 46321 Phone: 219-922-6171 Fax: 219-922-6172 E-Mail: JBEngineer@aol.

JB ENGINEERING AND CODE CONSULTING, P.C. 1661 Cardinal Drive Munster, IN 46321 Phone: 219-922-6171 Fax: 219-922-6172 E-Mail: JBEngineer@aol. JB ENGINEERING AND CODE CONSULTING, P.C. 1661 Cardinal Drive Munster, IN 46321 Phone: 219-922-6171 Fax: 219-922-6172 E-Mail: JBEngineer@aol.com JULIUS A. BALLANCO, P.E. President July 9, 2010 - Engineering

More information

Storm Drainage System Research Project

Storm Drainage System Research Project Storm Drainage System Research Project Flow Rate through RooF DRains 1 ASPE Research Foundation Storm Drainage System Research Project Flow Rate Through Roof Drains by Julius Ballanco, PE, CPD, FASPE The

More information

PLUMBING ROUGH IN INSPECTION

PLUMBING ROUGH IN INSPECTION This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.

More information

PMA ONLINE TRAINING Venting for Plumbing Systems

PMA ONLINE TRAINING Venting for Plumbing Systems PMA ONLINE TRAINING Venting for Plumbing Systems One Hour Continuing Education Venting PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be

More information

Chapter 7 Plumbing Connections

Chapter 7 Plumbing Connections Chapter 7 Plumbing Connections 7-1 General All plumbing equipment and installations must be designed, constructed, and installed in accordance with this code and where not specific, to the applicable provisions

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER 11 STORM DRAINAGE SECTION 11 GENERAL 11.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. 11.2 Where required. All roofs,

More information

Top 10+ Mistakes of DWV plumbing design

Top 10+ Mistakes of DWV plumbing design Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of

More information

CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass.

CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass. CHAPTER 9 VENTS 901 GENERAL 901.1 Scope The provisions of this chapter shall govern the materials, design, construction, and installation of vents. 901.2 Protection of Trap Seals The protection of trap

More information

ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920. Wet Venting. Incorporating Stack Venting and NPC Harmonization

ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920. Wet Venting. Incorporating Stack Venting and NPC Harmonization ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920 Wet Venting Incorporating Stack Venting and NPC Harmonization Presented by: Rainier Bratsch-Blundel, CPSI Plumbing Professor

More information

Residential Plumbing BCN 1058

Residential Plumbing BCN 1058 Residential Plumbing BCN 1058 CHAPTER 7 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System MICHAEL KNOTEK 74 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System PLUMBING FIXTURES

More information

APPLICATION FOR GRAYWATER IRRIGATION SYSTEM PERMIT SIMPLE RESIDENTIAL GRAVITY SYSTEMS, NO STORAGE

APPLICATION FOR GRAYWATER IRRIGATION SYSTEM PERMIT SIMPLE RESIDENTIAL GRAVITY SYSTEMS, NO STORAGE APPLICATION FOR GRAYWATER IRRIGATION SYSTEM PERMIT SIMPLE RESIDENTIAL GRAVITY SYSTEMS, NO STORAGE Please read the California Plumbing Code Chapter 16A-1 Design Requirements before completing this form.

More information

When Should Examination Preparation Begin?

When Should Examination Preparation Begin? Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing

More information

Basic Principles for Sizing Grease Interceptors

Basic Principles for Sizing Grease Interceptors Basic Principles for Sizing Grease Interceptors Grease Interceptor is an overall term. It is a product category much like faucet. I am sure you can think of several types of faucets like, kitchen, bath

More information

SANITARY SEWER SPECIFICATIONS

SANITARY SEWER SPECIFICATIONS SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,

More information

One of the fundamental design elements that every

One of the fundamental design elements that every Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things

More information

Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org

Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org b 2011 Los Angeles Plumbing Code LAPC changes from 2008 2011 Los Angeles Plumbing Code Consists of the following:

More information

Amendments to the 2012 International Plumbing Code

Amendments to the 2012 International Plumbing Code Amendments to the 2012 International Plumbing Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby

More information

SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER

SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER Village of Shorewood, Wisconsin SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER Prepared By: Thomas A. Zoulek, P.E., LEED A.P. Vice President Mid City Plumbing & Heating

More information

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations

More information

PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES

PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES Health Systems Protection Rev. 07/2006 35-05-20/06/07/18 OFFICE OF FOOD PROTECTION 417 FEDERAL ST

More information

SECTION 221413 FACILITY STORM DRAINAGE PIPING

SECTION 221413 FACILITY STORM DRAINAGE PIPING SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC

PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. Section:

More information

Sanitary Waste & Vent TS 100 1 1 Friday 9:00am 12:00pm Peter Kraut PE

Sanitary Waste & Vent TS 100 1 1 Friday 9:00am 12:00pm Peter Kraut PE Sanitary Waste & Vent TS 100 1 1 Friday 9:00am 12:00pm Peter Kraut PE Waste & Vent Part 1 October 28, 2011 9:00 10:30 AM Peter A. Kraut, P.E. B.S. Architectural Engineering Technology Wentworth Institute

More information

What to Expect From the Examination. How to Study the Plumbing Codes

What to Expect From the Examination. How to Study the Plumbing Codes Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.

More information

Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012

Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012 Plumbing Code in Commercial Kitchens NH BOA May 9, 2012 Main Topics Grease Interceptors Indirect Waste Receptors Cleaning Chemical Dispensers Thermal Expansion IPC - Chapter 10 Traps Interceptors Separators

More information

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information

More information

Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text

Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text Code Amendment 12/20/12 2011 Oregon Plumbing Specialty Code, Grease Interceptors & Fats, Oils and Greases Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text 204.0

More information

CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY

CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary

More information

CHAPTER 9 VENTS TRANSPORTATION OF SEWER GAS

CHAPTER 9 VENTS TRANSPORTATION OF SEWER GAS PlumbingCode06_ch09 5/29/06 8:16 AM Page 1 CHAPTER 9 VENTS Most people don t think much about vents when they consider the plumbing in their home or office, but vents play a vital role in the scheme of

More information

CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004

CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004 Bellevue Bothell Kenmore Kirkland Issaquah Mercer Island Sammamish Snoqualmie Woodinville CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004 This checklist is intended for use to prepare

More information

B. Shop Drawings: Diagram power, signal, and control wiring.

B. Shop Drawings: Diagram power, signal, and control wiring. SECTION 224500 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Combination units. 5. Water-tempering equipment. 1.2 SUBMITTALS

More information

Chapter 16.130 PLUMBING CODE

Chapter 16.130 PLUMBING CODE DISSCUSSION ITEM 3 ATTACHMENT E Chapter 16.130 PLUMBING CODE 16.130.100 Plumbing Code - Incorporation. There is incorporated by reference, for purpose of adopting regulations, provisions, conditions, terms,

More information

Saving Water and Energy in Residential Hot Water Distribution Systems. Gary Klein California Energy Commission

Saving Water and Energy in Residential Hot Water Distribution Systems. Gary Klein California Energy Commission Saving Water and Energy in Residential Hot Water Distribution Systems Gary Klein California Energy Commission What Do You Want from your Hot Water System? Safety Not too hot Not too cold No harmful bacteria

More information

DRAIN, WASTE AND VENT PLUMBING

DRAIN, WASTE AND VENT PLUMBING Flow of waste in a drain system Solid and liquid waste flows in vertical pipes much differently than it does in horizontal systems. In near horizontal pipes we talked about maintaining the slope of the

More information

Plumbing Code Sections For Commercial Food Facilities

Plumbing Code Sections For Commercial Food Facilities Plumbing Code Sections For Commercial Food Facilities SCOPE The following list of requirements summarizes the plumbing issues that are commonly addressed in commercial retail food facilities by health

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes)

SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) SIERRA LAKES COUNTY WATER DISTRICT P.O. Box 1039, Soda Springs, CA 95728-1039 (7300 Short Road, Serene Lakes) Maintenance Office Administrative Office Billing Office 530-426-7802 530-426-7800 916-332-4872

More information

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Cost Estimation for Materials and Installation of Hot Water Piping Insulation Cost Estimation for Materials and Installation of Hot Water Piping Insulation Prepared for Pacific Northwest National Laboratory Under Contract Number: 18O9O2 By Gary Klein, Managing Partner Affiliated

More information

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS

SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS 1001 SOUTH LEECHBURG HILL LEECHBURG, PA 15656 Phone: 724-845-9355 Fax: 724-845-1186 SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS 1. General

More information

C I T Y O F S E L M A F I R E D E P A R T M E N T

C I T Y O F S E L M A F I R E D E P A R T M E N T C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:

More information

Isometric Plumbing Drawings

Isometric Plumbing Drawings Building Inspections Isometric Plumbing Drawings All commercial building permit applications, in which the plumbing system has not been designed by a mechanical engineer, must include two sets of isometric

More information

2006 Codes. Please verify the following before calling for inspection

2006 Codes. Please verify the following before calling for inspection INSPECTION CHECKLIST RESIDENTIAL PLUMBING ROUGH IN 2006 Codes This checklist is intended for use to prepare for an inspection. This is only a general list and is not intended to address all possible conditions.

More information

PERMITS REQUIRED & PERMIT EXEMPTIONS

PERMITS REQUIRED & PERMIT EXEMPTIONS PERMITS REQUIRED & PERMIT EXEMPTIONS This guideline is intended to assist the applicant in determining what types of construction work require a permit. The 1997 California Uniform Administrative Code,

More information

Job Ready Assessment Blueprint. Plumbing. Test Code: 3061 / Version: 01

Job Ready Assessment Blueprint. Plumbing. Test Code: 3061 / Version: 01 Job Ready Assessment Blueprint Plumbing Test Code: 3061 / Version: 01 Measuring What Matters Specific Competencies and Skills Tested in this Assessment: Professionalism Exhibit professional behavior Describe

More information

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination

More information

1. Site plans assist the Fire Department to determine where a potential spill can be contained. The detailed site plan shall include the following:

1. Site plans assist the Fire Department to determine where a potential spill can be contained. The detailed site plan shall include the following: Secondary Containment, Spill Control and Drainage Guidelines for Hazardous Materials per 2010 CFC PURPOSE The intent of this guideline is to provide the requirements for the design and construction of

More information

Assessment Blueprint PHCC Educational Foundation Plumbing Year 2

Assessment Blueprint PHCC Educational Foundation Plumbing Year 2 Assessment Blueprint PHCC Educational Foundation Plumbing Year 2 Post-Test Code: 7662 Copyright 2008. All Rights Reserved. General Assessment Information PHCC Educational Foundation Plumbing Year 2 General

More information

Division A. Compliance, Objectives and Functional Statements

Division A. Compliance, Objectives and Functional Statements Division A Compliance, Objectives and Functional Statements British Columbia Plumbing Code 2012 Division A Part 1 Part 1 Compliance Section 1.1 General 1.1.1. Application of this Code... 5 1.1.2. Internal

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

This page does not print. Placeholder for Cover art IPS CORPORATION

This page does not print. Placeholder for Cover art IPS CORPORATION This page does not print. Placeholder for Cover art IPS CORPORATION INDEX STUDOR ENGINEERED PRODUCTS TECHNICAL MANUAL INDEX Index... 1 Studor Overview... 2 Products Redi-Vent... 3 Ultra-Vent... 4 Mini-Vent...

More information

Plumbing Code in Commercial Kitchens

Plumbing Code in Commercial Kitchens Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International

More information

Brian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division

Brian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division Brian Coppock, Regional Compliance Officer Office of Statewide Health Planning and Development Facilities Development Division CHAPTER 6 WATER SUPPLY AND DISTRIBUTION 601.0 Hot and Cold Water Required.

More information

Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection

Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Jobs are Alaska s Future MECHANICAL INSPECTION CUSTOMER COUNTER LOCATIONS Main Office MI Anchorage

More information

Teacher Assessment Blueprint. Plumbing. Test Code: 5175 / Version: 01. Copyright 2010 NOCTI. All Rights Reserved.

Teacher Assessment Blueprint. Plumbing. Test Code: 5175 / Version: 01. Copyright 2010 NOCTI. All Rights Reserved. Teacher Assessment Blueprint Plumbing Test Code: 5175 / Version: 01 Copyright 2010 NOCTI. All Rights Reserved. General Assessment Information Blueprint Contents General Assessment Information Written Assessment

More information

15430 SAFETY SHOWERS AND EYEWASHES

15430 SAFETY SHOWERS AND EYEWASHES 15430 SAFETY SHOWERS AND EYEWASHES PART 1: GENERAL 1.01 RELATED SECTIONS 01005 - ENVIRONMENTAL HEALTH 11600 LABORATORY EQUIPMENT 15020 - LABORATORIES 15130 - PIPING SPECIALITES 15400 - PLUMBING 15420 -

More information

Compliance Document for New Zealand Building Code Clause G13 Foul Water Second Edition

Compliance Document for New Zealand Building Code Clause G13 Foul Water Second Edition Compliance Document for New Zealand Building Code Clause G13 Foul Water Second Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.

WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION. WET/DAMP BASEMENTS PROBLEM. IS THIS BASEMENT LEAKING OR COULD WE HAVE ANOTHER PROBLEM? Water line arching up on wall in corners of basement. Water collecting on concrete floor starting in corners. ANSWER:

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

Ordering Terms. Installation Terms

Ordering Terms. Installation Terms 20a Plumbing Terms & Conditions September 28-30, 2015 Ordered By August 17, 2015 Ordering Terms 1. To receive discount prices, order and payment must be received by 8/17/15. 2. Credit will not be given

More information

Carriers, Fixtures & Piping

Carriers, Fixtures & Piping Regardless of application and/or installation needs, there are fixture supports available to meet even the harshest design requirements. by William M. Smith Over the years, I m sure that each of you in

More information

BUILDING TRADES II PLUMBING: ROUGH-IN AND FINAL TEACHER S GUIDE

BUILDING TRADES II PLUMBING: ROUGH-IN AND FINAL TEACHER S GUIDE BUILDING TRADES II PLUMBING: ROUGH-IN AND FINAL TEACHER S GUIDE INTRODUCTION This Teacher s Guide provides information to help you get the most out of Plumbing: Rough-In and Final. The contents in this

More information

2. What building projects are exempted? (permit not required)

2. What building projects are exempted? (permit not required) BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID

More information

Guide for Efficient Hot Water Delivery Systems

Guide for Efficient Hot Water Delivery Systems s 1.0 Introduction This guide is designed to help builders better understand and meet the hot water delivery system criteria as specified in the WaterSense New Home Specification (WaterSense new home specification).

More information

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability. Codes and High Performance Hot Water Systems Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.com Annual Energy Use for Heating Water Natural Gas Gallons Per Day

More information

Sewer Service Diagram (SSD) Requirements

Sewer Service Diagram (SSD) Requirements Sewer Service Diagram (SSD) Requirements A Sewer Service Diagram (SSD) shows the location of private wastewater service pipes on a property. In NSW where Fair Trading and delegated authorities are responsible

More information

Understanding and Designing Plumbing Systems

Understanding and Designing Plumbing Systems Lesson A3 15 Understanding and Designing Plumbing Systems Unit A. Mechanical Systems and Technology Problem Area 3. Construction Systems Lesson 15. Understanding and Designing Plumbing Systems New Mexico

More information

CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS

CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS PlumbingCode06_ch10 5/29/06 8:16 AM Page 1 CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS We have covered most of the regulations you will need to know about drains and vents. This chapter will round out

More information

Proposed plumbing system within units at the Bluewater Hotel, 10 West Quay, Ahuriri, Napier

Proposed plumbing system within units at the Bluewater Hotel, 10 West Quay, Ahuriri, Napier Determination 2010/125 Proposed plumbing system within units at the Bluewater Hotel, 10 West Quay, Ahuriri, Napier 1. The matters to be determined 1.1 This is a Determination under Part 3 Subpart 1 of

More information

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal. 2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other

More information

INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville

INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville Bellevue Bothell Burien Issaquah Kenmore Kirkland INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville 2009 Codes This

More information

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours Affix label with Candidate Code Number here. If no label, enter candidate Number if known No. 99 REGISTRATION EXAMINATION, JUNE 009 PLUMBING INSTRUCTIONS QUESTION AND ANSWER BOOKLET Time allowed THREE

More information

APPENDIX M-2 SANITARY SEWER TECHNICAL MEMORANDUM. Stadium Reconstruction EIR

APPENDIX M-2 SANITARY SEWER TECHNICAL MEMORANDUM. Stadium Reconstruction EIR APPENDIX M-2 SANITARY SEWER TECHNICAL MEMORANDUM Stadium Reconstruction EIR Appendices \ AECOM Technical Services, Inc 401 West A Street Suite 1200 San Diego, CA 92101 www.aecom.com 619-610-7600 tel 619-610-7601

More information

The following definitions apply with regard to requirements specified in this document:

The following definitions apply with regard to requirements specified in this document: GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved

More information

112039.00 224500 EMERGENCY PLUMBING FIXTURES

112039.00 224500 EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following emergency plumbing fixtures: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Hand-held drench hoses. 5. Combination

More information

Georgia State Amendments to the International Plumbing Code

Georgia State Amendments to the International Plumbing Code Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Local Government Assistance Division 60 Executive Park South, N.E. Atlanta, Georgia 30329-2231

More information

ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007

ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007 ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007 The following are general requirements pertaining to plumbing in one and two family dwellings. This does not represent all the provisions regulating plumbing

More information

Sewer and Stormwater Back-ups Policy Adopted by Council October 4, 2010

Sewer and Stormwater Back-ups Policy Adopted by Council October 4, 2010 Sewer and Stormwater Back-ups Policy Adopted by Council October 4, 2010 A. Purpose The purpose of this policy is to explain how and why sewer or stormwater backups occur, what to do in the event a homeowner

More information

Sewage Compliance Form Instructions

Sewage Compliance Form Instructions CITY OF JOHNSTOWN DEPARTMENT OF COMMUNITY & ECONOMIC DEVELOPMENT 401 MAIN STREET ROOM 200 JOHNSTOWN, PA 15901 814-533-2017 FAX 814-539-5816 RENEE K. DALY DIRECTOR Sewage Compliance Form Instructions 1)

More information

PVC Pipe Restriction Law and Legislation 1) NYS PVC Pipe Restriction Law (Repealed)

PVC Pipe Restriction Law and Legislation 1) NYS PVC Pipe Restriction Law (Repealed) PVC Pipe Restriction Law and Legislation 1) NYS PVC Pipe Restriction Law (Repealed) * 246. Uses of standard piping materials. 1. Building sewers under public ways. Building sewers under public ways shall

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

WHEN IS A PERMIT REQUIRED?

WHEN IS A PERMIT REQUIRED? WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,

More information

Plumbing Supply Piping Planning Tool Reducing Water Wasted Waiting for Hot

Plumbing Supply Piping Planning Tool Reducing Water Wasted Waiting for Hot Plumbing Supply Piping Planning Tool Reducing Water Wasted Waiting for Hot Craig Selover Selover Consulting craig@dotmc.us H:248 542-3010 C:248 917-1380 Floor Plan Floor Plan All Piping WaterSense,HERS,

More information

SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES

SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions

More information

Fats, Oil and Grease. Best Management Practices Manual. Information, Pollution Prevention, and Compliance Information For Food Service Facilities

Fats, Oil and Grease. Best Management Practices Manual. Information, Pollution Prevention, and Compliance Information For Food Service Facilities Fats, Oil and Grease Best Management Practices Manual Information, Pollution Prevention, and Compliance Information For Food Service Facilities Pinellas County Utilities Water Quality Management Division

More information

SECTION 5: SANITARY SEWER SYSTEM DESIGN

SECTION 5: SANITARY SEWER SYSTEM DESIGN SECTION 5: SANITARY SEWER SYSTEM DESIGN 5.01 GENERAL Sanitary sewer improvements shall be designed to serve the ultimate level of City development as defined in the General Plan and the Wastewater Facilities

More information

WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION

WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION 1 HOUSEKEEPING 2 CHANGES We will be covering the significant changes to the International Residential Code and the changes common to

More information

Drainage of rainwater has

Drainage of rainwater has Drainage of rainwater has long been considered an essential attribute for the proper performance of any roof system. Long-term and excessive accumulation of water will contribute to the deterioration of

More information

2012 B.C. Plumbing Code

2012 B.C. Plumbing Code Agenda Introduction Plumbing only changes Code Format On-line version Effective dates Code Changes Fire Blocks & Fire Stopping Changes in Forms, Checklists and Reduced Fees. Question and Answers Introductions

More information

SECTION 33 31 00.13 ABANDONMENT OF SEWER MAINS

SECTION 33 31 00.13 ABANDONMENT OF SEWER MAINS SECTION 33 31 00.13 ABANDONMENT OF SEWER MAINS PART 1: GENERAL 1.01 SECTION INCLUDES A. Abandonment in place, by cutting and capping, of existing sewers, junction structures, manholes, service lines, and

More information

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS a. New Plumbing and Gas Piping Systems. This code in conjunction with the Plumbing and Fuel Gas Codes of the State of New York shall apply to plumbing

More information

PMI 2014 Spring Conference. Lee Mercer IAPMO - Senior Vice President Industry Relations and Business Development Lee.mercer@iapmo.

PMI 2014 Spring Conference. Lee Mercer IAPMO - Senior Vice President Industry Relations and Business Development Lee.mercer@iapmo. PMI 2014 Spring Conference Lee Mercer IAPMO - Senior Vice President Industry Relations and Business Development Lee.mercer@iapmo.org 1 What is the Green Supplement? Turnkey document IAPMO philosophy Covers

More information

GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS

GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS Fort Worth Water Department, Pretreatment Services Division, (817)871-8305 A. Introduction: Part I: Guidance for Grease Trap

More information

Extreme Water Savings. The Next Frontier in Drainage and Plumbing Systems

Extreme Water Savings. The Next Frontier in Drainage and Plumbing Systems Extreme Water Savings The Next Frontier in Drainage and Plumbing Systems 1 Program Registration McGraw-Hill Construction is a registered provider with The American Institute of Architects Continuing Education

More information

Roland Garcia Pearland Fire Department

Roland Garcia Pearland Fire Department Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information