1 C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS: 1. Q: When does the requirement for the installation of residential fire sprinklers take effect? A: The requirement commences January 1, 2011 with the effective date of the 2010 California Codes. All permits obtained for one and two family approved standard plan homes obtained on or after this date shall include the installation of residential fire sprinklers. The effective date for custom homes will be the date of house plan submission to the Building Department. The standards for this installation are the 2010 edition of NFPA 13D or Section R313.3 of the 2010 edition of the California Residential Code. 2. Q: Will Fire Department be inspecting residential sprinkler system installations? A: Inspections of the installations will be initially conducted by the Fire Department; however, inspections of tract home fire sprinklers may transition in the future to Building Department inspectors subject to further discussion between the two departments. 3. Q: Can a Plumbing Contractor with C-36 license install residential fire sprinklers? A: No. As required by the State of California Business and Professions Code and the Contractors State Licensing Board (CSLB) only a C-16 Fire Protection Contractor may install fire sprinklers. There currently are a limited number of plumbing contractors in California who possess both the C-36 and C-16 license.

2 4. Q: Who may design residential fire sprinkler systems? A: A C-16 Fire Protection Contractor may design, submit plans, and obtain installation permits only for those systems that are installed under their license. Residential fire sprinkler system plans prepared by a California licensed mechanical or fire protection professional engineer (PE) may be used for installation purposes by any C-16 contractor. 5. Q: Which City department will review the plans for residential fire sprinkles? A: For stand-alone systems (fire sprinklers supplied by a separate interior system piping from the domestic cold water system), the Fire Department will review the plans. Stand alone systems will require a deferred submittal directly to the Fire Department. For multi-purpose systems (fire sprinklers and domestic cold water fixtures on the same piping system) a joint plan review will be conducted by the Fire and Building Departments. 6. Q: I have numerous standard plans on file with the Development Department, how should I proceed with updating these plans to reflect the new requirements? A: The Building Department recently issued a bulletin informing developers of the effective date of the 2010 California Building Code Standards. All standard plans must be approved for the 2010 Code revisions prior to January 1, 2011 in order to obtain permits on or after this date. Developers are encouraged to submit fire sprinkler plans as early as possible before the end of the year due to the anticipated volume of plan reviews. 7. Q: How will the permit issuance for residential sprinkler systems be handled? A: The C-16 contractor installing the systems will obtain a permit for each house from the Fire Department for stand-alone systems. Details on the permits for multi-purpose piping systems have yet to be determined. WATER SUPPLY ISSUES 8. Q: Do I need a separate water service to supply residential fire sprinklers? A: No. The design standard allows use of a standard domestic water service to supply both fire sprinklers and domestic water using a common metered service. 9. Q: Is the standard tract home one inch service adequate to provide water for both domestic use and residential fire sprinklers? A: In many cases yes, however: If the one inch domestic service is done in polyethylene (PE) tubing, as has been past practice, it will be more challenging for the fire sprinkler design professional due to the interior diameter of PE tubing.

3 A typical residential sprinkler system design will have a demand of approximately 31 gallons per minute, which includes a required simultaneous 5 gpm domestic demand. Demand may be higher for house designs with sloped ceilings exceeding 4 in 12, beamed or coffered ceiling, or where sprinkler head spacing in excess of 16 X 16 is chosen by the design professional. 10. Q: We have several tracts where the utilities have been installed and we are waiting for the market to turnaround before proceeding with construction of new homes. Will we have to change the water services? A: No. However, as noted in the answer to question #9, the fire sprinkler design professional will need to be creative in their design which may include larger pipe in the house, additional looping of lines, use of reduced spacing sprinklers with lower water demand, and, for some house designs, a booster pump may be needed. 11. Q: Is a UL/FM listed fire pump required for home fire sprinklers as is required for commercial installations? A: No. However, State amendments to the installation requirements include a provision that when a booster pump is needed, it must serve both domestic water and fire sprinkler piping in order to enhance reliability of the pump. The size of pump needed will be determined by the fire sprinkler design professional based on system demand. It is anticipated a pump in the range of 40 gpm at 30 psi will be needed. For multi-purpose systems, the maximum pressure rating for plumbing fixtures must be taken into consideration in choosing a pump. The pump shall be approved for use in potable water systems in California and have brass or stainless steel operating components for reliability. 12. Q: Are there any other special conditions regarding the City water service that the fire sprinkler design professional should be aware of? A: Yes. The design professional needs to consider the following factors: The hydraulic calculation for standard plan homes needs to be based on a far side service connection. The nominal inside diameter of SDR-9 CTS 3408 PE tubing is: 1 inch = /2 inch = inch = For purposes of determining friction losses: the Badger Recordall Model 55 is the current water meter specified by the Water Division for 1 inch services. 1-1/2 inch and 2 inch services use the Neptune T-10 water meter.

4 The following equivalent feet friction loss must be included for the corp stop and angle meter stop devices on the service. 1 inch = 10.6 feet 1-1/2 inch = 13.8 feet 2 inch = 15.1 feet 13. Q: Is there a requirement for a special backflow prevention device for residential fire sprinklers. A: No for one and two story houses. Yes for three story houses. A backflow device is required whenever residential plumbing fixtures or fire sprinklers are located above the second floor. Note that the friction loss from a double check or reduced pressure backflow device will place severe design constraints in supplying adequate water pressure for 3 rd floor residential sprinklers and plumbing fixtures without a booster pump. REQUIREMENTS WITHIN THE HOUSE 14. Q: I have heard that there is a prescriptive design standard that may be used in lieu of hydraulic calculations for home fire sprinklers? A: Yes. Both NFPA 13D and the California Residential Code allow use of a prescriptive pipe sizing method in lieu of hydraulic calculations. However, be advised that these prescriptive methods are conservative and with 40 psi for available water pressure for design purposes may not be feasible. In general, a hydraulic calculation results in smaller pipe sizing than prescriptive methods. 15. Am I required to have a separate piping system for sprinklers and domestic water or can a system be designed with common piping? A: A multi-purpose piping design is allowed using the cold water distribution system. The hydraulic calculation and piping design to assure adequate delivery of water to the sprinkler head at the minimum flow and pressure must be carefully done by the design professional. The pipe or tube and fire sprinkler fittings for multi-purpose systems must be listed for residential fire sprinklers in accordance with UL Q: What type of pipe or tube is required for residential sprinklers? A: The water distribution pipe or tube must be UL listed for fire sprinklers for both multi-purpose and stand-alone systems. The dominate material used until recently for single and duplex homes has been CPVC (Chlorinated Polyvinyl Chloride) in stand-alone piping systems. Three major distributors of PEX tubing (Uponor, REHAU, and Zurn) have received UL 1821 listings for their tubing and fire sprinkler head fittings for use in multi-purpose systems only.

5 17. Q: Are there special requirements for hanging residential sprinkler pipe or tube? A: Yes. In general, pipe or tube must be supported in accordance with the manufacture s listing or NFPA 13D as applicable. Sprinkler pipe or tube must be supported in a manner that prevents movement of the sprinkler head. For PEX tubing, the fire sprinkler head adaptor attaches to the ceiling framing members. For CPVC, there are specific hanger distance requirements for the pipe and from the sprinkler tee fitting per the manufacturer s installation guidelines. Copper pipe hanging is governed by NFPA 13D. 18. Q: Is there an issue with pipe freezing or being subjected to high summer temperatures in the attic? A: Yes. All attic piping needs to be covered with insulation. Pipe or tube diameters may be as small as ¾ and could freeze even in our relatively mild winters. Manufactures also required that PEX and CPVC be protected from the excessively high attic temperature that we experience in the valley. 19. Q: What areas of the house must have fire sprinklers? A: In general, most living space within the house must be provided with fire sprinklers. A state amendment requires that sprinklers be installed in attached garages using residential sprinklers. The following areas do not require fire sprinklers: unfinished attics, open porches and patios, small closets without mechanical equipment, and bathrooms under 55 square feet. Where mechanical equipment is installed in attics, a single fire sprinkler is required to be installed over the unit. 20. Q: Is there a requirement for a pilot sprinkler head in the attic for use in detecting attic fires? A: No. However, many new homes are designed with fuel fired mechanical equipment installed in the attic. A fire sprinkler head must be installed over such units within 12 inches of the roof deck. Because of attic temperatures, a commercial type quick response fire sprinkler with a minimum 200F temperature rating must be used. When using non-metallic CPVC or PEX to supply this sprinkler, the pipe must be protected with a 15 minute thermal barrier. Copper or internally galvanized steel approved for potable water may be used in this application and does not require the thermal barrier. 21. Q: Are there fire sprinkler system design issues that need special attention on these existing standard house plans and on future plan submissions? A: Yes. Your fire sprinkler system design professional needs to address issues such as ceiling fan and light fixture locations, distance of fire sprinklers from heat

6 sources (fire places, HVAC registers, kitchen stoves, etc), and beamed or coffered ceilings. As changing of light fixtures is a common homeowner improvement, fire sprinklers need to be located a minimum of 36 from the centerline of ceiling electrical junction boxes. Under stair storage closets are often missed in fire sprinkler design 22. Q: Are the types of fire sprinklers used in house the same as in commercial systems? A: They are similar. Residential fire sprinklers are somewhat smaller, have a different discharge pattern, require less water to operate effectively, and are tested to a different UL Standard. The minimum flow and pressure for the most commonly used residential sprinkler is 13gpm at 7 psi. As with commercial applications, residential fire sprinkles are available in semi-recessed or concealed configurations. Note that concealed sprinklers cannot be used in garages or areas with temperature in excess of 100F because the concealed plate will eventually fall off. A semi-recessed or pendent, 175F rated residential sprinkler is needed in these areas. 23. Q: Is there a 200 psi pressure test required for residential sprinkler systems as is required for commercial fire sprinkler systems? A: No. Both multi-purpose and stand-alone systems may be hydrostatically tested at normal system operating pressure as required for domestic plumbing. 24. Q: Is a separate shut-off valve permitted for the residential sprinkler system? A: No. The intent of installation the standards is that fire sprinklers cannot be shut-off independent of the domestic water supply to the home. For stand-alone fire sprinkler systems, a shut off valve is installed before the split between sprinklers and domestic, and an additional valve is installed for the domestic lateral. This allows working on plumbing fixtures while still retaining fire sprinkler protection. For multi-purpose piping systems there is no way to shut off fire sprinklers independent of the domestic water plumbing. 25. Q: Is an interior or exterior alarm bell required for residential sprinkler systems? A: No. We are not proposing a local amendment to require an alarm bell. While 93% of California fire jurisdictions that currently have local residential fire sprinkler ordinances require an outside alarm bell, this requirement was not included in the State adoption of residential fire sprinklers. One reason for this is that the future of residential fire sprinkler installation will most likely be multipurpose piping systems where water use from domestic fixtures may activate any water flow switch installed. There are listed water flow switches available now that will only activate upon flow in excess of 11 gpm (most residential fire sprinklers flow a minimum of 13 gpm), but this technology is relatively new and

7 it s long term reliability is unknown. Those developers installing residential sprinklers on separate piping systems within the house should not hesitate to provide a local outside bell and the ability to connect to an alarm company. While the required smoke detectors will sound an interior alarm before fire sprinklers activate, an outside bell can warn a passerby of an interior fire when the home owner is away. 26. Q: Is a residential fire sprinkler system required to be monitored by an alarm company? A: No. There is no requirement for connection to an alarm company. Such connection is a desirable option when a stand-alone residential sprinkler system is installed. As discussed in question #26, use of a special water flow switch would be necessary on a multi-purpose piping system. 27. Q: Is the installation of a water softener affected by the new residential fire sprinkler requirement? A: For a multi-purpose piping system, a water softener device has a significant effect on available water pressure and use of such devices may be precluded. For stand-alone piping systems, the fire sprinkler piping will be connected ahead of the water softener and will have no effect on fire sprinkler operation. 28. Q: Am I required to provide spare fire sprinklers for each house? A: Yes. A spare sprinkler kit that contains one of each type of sprinkler used in the house and associated special wrench(es) is required to be installed in the laundry room or laundry closet. 29. Q: Are there any additional requirements I should be aware of? A: Yes. A homeowner information sheet shall be permanently installed adjacent to the spare sprinkler head kit. The information on the instruction shall be approved by the Fire Department. An example an acceptable information sheet is available from our office. If you have any additional questions please contact either the fire department at or the building department at

DWELLING UNIT FIRE SPRINKLER SYSTEMS

DWELLING UNIT FIRE SPRINKLER SYSTEMS DWELLING UNIT FIRE SPRINKLER SYSTEMS AT2904.1 General. Where installed, residential fire sprinkler systems, or portions thereof, shall be in accordance with NFPA 13D or Section AT2904, which shall be considered

More information

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified. 13D Residential Sprinkler System Plan Review Checklist 2010 OFC and 2007 NFPA 13D Date of Review: Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor:

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

FIRE PROTECTION SYSTEMS INSTALLATION OF RESIDENTIAL SPRINKLERS

FIRE PROTECTION SYSTEMS INSTALLATION OF RESIDENTIAL SPRINKLERS FIRE PREVENTION STANDARD OFFICE OF THE FIRE MARSHAL FIRE PROTECTION SYSTEMS INSTALLATION OF RESIDENTIAL SPRINKLERS SCOPE: This standard applies to the design and installation of automatic fire sprinkler

More information

NFPA 13D

NFPA 13D NFPA 13D 1.1 1.1 This standard shall cover the design and installation of automatic sprinkler systems for protection against the fire hazards in one- and two-family dwellings and manufactured homes. When

More information

INTERNATIONAL RESIDENTIAL CODE PLUMBING

INTERNATIONAL RESIDENTIAL CODE PLUMBING INTERNATIONAL RESIDENTIAL CODE PLUMBING RP1-07/08 P2503.5.1 Proposed Change as Submitted: Proponent: Michael Cudahy, representing Plastic Pipe and Fittings Association Revise as follows: P2503.5.1 Rough

More information

Roland Garcia Pearland Fire Department

Roland Garcia Pearland Fire Department Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

NFPA 13R 1.1 5.1.3 5.2.1

NFPA 13R 1.1 5.1.3 5.2.1 NFPA 13R 1.1 1.1 Scope This standard covers the design and installation of automatic sprinkler systems for protection against fire hazards in residential occupancies up to and including two four stories

More information

Speaker. Steve Leyton Protection Design & Consulting

Speaker. Steve Leyton Protection Design & Consulting Speaker Steve Leyton Protection Design & Consulting Steve Leyton is President of Protection Design & Consulting in San Diego, CA and a member of the Fire Smarts Faculty. He began his career in 1981 on

More information

Residential Fire Sprinklers Introduction to NFPA 13D Standard

Residential Fire Sprinklers Introduction to NFPA 13D Standard Speaker Russ is the Executive Chairman of Telgian Corporation. He holds a degree from the University of Nevada, Las Vegas and a Level IV certification from NICET in Fire Sprinkler Layout. He is a Certified

More information

a guide to residential fire sprinkler systems

a guide to residential fire sprinkler systems a guide to residential fire sprinkler systems What you need to know about a BlazeMaster fire sprinkler system, the world s most specified non-metallic life safety piping system. Modern installation with

More information

VENTURA CITY FIRE DEPARTMENT Fire Prevention Division

VENTURA CITY FIRE DEPARTMENT Fire Prevention Division VENTURA CITY FIRE DEPARTMENT Fire Prevention Division Automatic Fire Sprinkler Handbook Plan Review Status 805-677-3941 Inspection Scheduling 805-658-4717 October 2011 Kevin Rennie, Fire Chief Ventura

More information

13D Systems What, Why and How. Oregon Fire Sprinkler Coalition

13D Systems What, Why and How. Oregon Fire Sprinkler Coalition 13D Systems What, Why and How Oregon Fire Sprinkler Coalition The Fire Problem Statistics National Each day 7 people die home fires Each year on average over 2,500 people die and more than 13,000 people

More information

Your Instructor. Two Biggest Obstacles to Residential Sprinklers. Two Biggest Obstacles to Residential Sprinklers

Your Instructor. Two Biggest Obstacles to Residential Sprinklers. Two Biggest Obstacles to Residential Sprinklers Residential Sprinklers ----- Issues and Answers Your Instructor Jeffrey M. Shapiro, PE Executive Director IRC Fire Sprinkler Coalition 1 2 The IRC Fire Sprinkler Coalition Not-for-profit association representing

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE

BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE BUILD FOR QUALITY BUILD FOR VALUE BUILD FOR LIFE AUTOMATIC FIRE SPRINKLER PROTECTION Residential fire sprinkler system installations are increasing every day thanks to growing buyer demand, lower costs,

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

We look forward to working with you. Worldwide Headquarters 1400 Pennbrook Parkway Lansdale, PA 19446. www.tyco-rapidresponse.com

We look forward to working with you. Worldwide Headquarters 1400 Pennbrook Parkway Lansdale, PA 19446. www.tyco-rapidresponse.com TYCO IS HERE TO HELP Tyco will work closely with you to make the installation of Rapid Response Residential Fire Sprinkler Systems a quick and easy addition to your new home construction. We can develop

More information

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S

H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S H O M E F I R E S P R I N K L E R S S A V E L I V E S, M O N E Y A N D W A T E R A G U I D E F O R W A T E R P U R V E Y O R S HomeFireSprinkler.org F I R E T H E L A R G E ST S I N G L E C AU S E O F

More information

FIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS

FIRE SPRINKLERS IN TOWNHOMES/CONDOMINIUMS CITY OF BLAINE SAFETY SERVICES Fire Inspections 10801 Town Square Drive Blaine MN 55449 Business Phone 763-785-6187 Fax 763-717-2634 City of Blaine Fire Prevention Inspection Policy FIRE SPRINKLERS IN

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

UNDERSTANDING WATER SUPPLY FOR HOME FIRE SPRINKLER SYSTEMS

UNDERSTANDING WATER SUPPLY FOR HOME FIRE SPRINKLER SYSTEMS UNDERSTANDING WATER SUPPLY FOR HOME FIRE SPRINKLER SYSTEMS Saving Lives, Saving Water COMMUNITY WATER SUPPLY You turn on the tap and the water comes out. Pretty simple. On the surface, water supply seems

More information

SACRAMENTO REGIONAL FIRE PREVENTION OFFICERS ASSOCIATION A HANDY GUIDE TO DWELLING CONSTRUCTION REQUIREMENTS

SACRAMENTO REGIONAL FIRE PREVENTION OFFICERS ASSOCIATION A HANDY GUIDE TO DWELLING CONSTRUCTION REQUIREMENTS FIRE DEPARTMENT 10573 E Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com SACRAMENTO REGIONAL FIRE PREVENTION OFFICERS ASSOCIATION A HANDY GUIDE TO DWELLING CONSTRUCTION

More information

PLAN CHECK CORRECTION SHEET FOR NFPA

PLAN CHECK CORRECTION SHEET FOR NFPA PLAN CHECK CORRECTION SHEET FOR NFPA 13 2016 This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. Section: Mechanical Plan

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX: Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2016 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean

More information

AUTOMATIC FIRE SPRINKLER SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEMS MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system

More information

Building & Safety Fern Avenue Lancaster, California

Building & Safety Fern Avenue Lancaster, California Building & Safety 44933 Fern Avenue Lancaster, California 93534 661 723 6144 AFFIDAVIT: SELF CERTIFICATION OF INSTALLATION OF SMOKE AND CARBON MONOXIDE ALARMS FOR COMPLIANCE WITH SECTIONS R314 AND R315

More information

Project Address (Mandatory) The project address must be printed in the title block of every sheet in the plan set.

Project Address (Mandatory) The project address must be printed in the title block of every sheet in the plan set. Cicero The following information is required for the issuance of a building permit. The mandatory items are required to be submitted as part of the initial submittal, but it is advisable to submit all

More information

Sprinkler System Requirements EK Life Safety Consulting, LLC

Sprinkler System Requirements EK Life Safety Consulting, LLC Sprinkler System Requirements 1 Introduction 2 Licensing Standards for Assisted Living Facilities 92.61 Introduction and Application (f)(2) Sprinkler systems. When installed or required, sprinkler systems

More information

NFPA 13 Sprinkler System General Design Plan Review Worksheet February 2010

NFPA 13 Sprinkler System General Design Plan Review Worksheet February 2010 NFPA 13 Sprinkler System General Design Plan Review Worksheet February 2010 Date of Review: Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor

More information

Chapter 7 Plumbing Connections

Chapter 7 Plumbing Connections Chapter 7 Plumbing Connections 7-1 General All plumbing equipment and installations must be designed, constructed, and installed in accordance with this code and where not specific, to the applicable provisions

More information

PLAN REVIEW GUIDE FIRE SPRINKLER SYSTEMS

PLAN REVIEW GUIDE FIRE SPRINKLER SYSTEMS PLAN REVIEW GUIDE FIRE SPRINKLER SYSTEMS PROJECT NAME: PERMIT PROJECT ADDRESS: CONTACT PERSON: CONTRACTOR PHONE Fire sprinkler system installation information shall be provided on the appropriate plans.

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Are Home fire Sprinklers a Reasonable Option for Your New Home?

Are Home fire Sprinklers a Reasonable Option for Your New Home? Be Informed and Choose Wisely Residential Fire Sprinkler Fact Sheet Are Home fire Sprinklers a Reasonable Option for Your New Home? Residential fire sprinklers are not new technology for preserving property

More information

DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS

DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS UP DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS March 2014 This document is not intended to advocate nor discourage the installation of residential sprinkler systems

More information

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector

Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination

More information

University of Houston Master Construction Specifications Insert Project Name SECTION WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Design & Construction Standards, Revised January 2013 5.21.10-1

Design & Construction Standards, Revised January 2013 5.21.10-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

NFPA 14 3.3.5 4.2.3.2

NFPA 14 3.3.5 4.2.3.2 NFPA 14 3.3.5 3.3.5 High-Rise Building. A building where the floor of an occupiable story is greater than 55 ft (17 m) 75 ft (23 m) above the lowest level of fire department vehicle access. 4.2.3.2 4.2.3.2

More information

Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org

Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org b 2011 Los Angeles Plumbing Code LAPC changes from 2008 2011 Los Angeles Plumbing Code Consists of the following:

More information

Lee Fire & Rescue Department. PLAN REQUIREMENTS Fire Suppression/ Automatic Sprinkler System

Lee Fire & Rescue Department. PLAN REQUIREMENTS Fire Suppression/ Automatic Sprinkler System PLAN REQUIREMENTS Fire Suppression/ Automatic Sprinkler System Project Name: Project Address: Code Edition: Tax Map #: Date: All supporting documentation, showing items listed below are required for review.

More information

Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE

Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE Concord Department of Fire and Life Safety FIRE MARSHAL S OFFICE September 1, 2005 Fire Suppression Operations in Residential Occupancies equipped with Residential Fire Sprinkler Systems. Since human beings

More information

Crepps Home Inspection

Crepps Home Inspection Crepps Home Inspection 651 Lincoln Drive Elizabethown, KY 42701 (270) 734-3845 www.crepps-hi.com jcrepps@yahoo.com Inspected By: Josh Crepps HI - 3058 Repair Report Prepared For: John & Jane Doe Property

More information

C. Is the applicable code (NFPA 13, 13R, 13D, 14, 20) and edition correct and shown on the drawing?

C. Is the applicable code (NFPA 13, 13R, 13D, 14, 20) and edition correct and shown on the drawing? Fire Suppression Plan Review General A. Are the shop drawings on the contractor s title block? B. Do the drawings meet the engineer design documents? C. Is the applicable code (NFPA 13, 13R, 13D, 14, 20)

More information

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs TITLE 22 PART 17 CHAPTER 363 RULE 363.11 EXAMINING BOARDS TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs (a) General requirements for Course Providers

More information

PEX Pipes for NFPA 13D Residential Fire Sprinkler Applications

PEX Pipes for NFPA 13D Residential Fire Sprinkler Applications PEX Pipes for NFPA 13D Residential Fire Sprinkler Applications 1 Acknowledgement This presentation was developed in cooperation with PEX system manufacturing members of the Plastic Pipes Institute (PPI),

More information

Amendments to the 2012 International Plumbing Code

Amendments to the 2012 International Plumbing Code Amendments to the 2012 International Plumbing Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby

More information

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Cost Estimation for Materials and Installation of Hot Water Piping Insulation Cost Estimation for Materials and Installation of Hot Water Piping Insulation Prepared for Pacific Northwest National Laboratory Under Contract Number: 18O9O2 By Gary Klein, Managing Partner Affiliated

More information

Engineering Specifications

Engineering Specifications PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID

More information

TECHNICAL DATA. * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0.

TECHNICAL DATA. * Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Sprinkler 111a 1. DESCRIPTION The Viking Quick Response Recessed Flush Dry Sprinkler VK482 is a small high-sensitivity fusible element sprinkler designed for installation on concealed pipe systems where

More information

2006 Codes. Please verify the following before calling for inspection

2006 Codes. Please verify the following before calling for inspection INSPECTION CHECKLIST RESIDENTIAL PLUMBING ROUGH IN 2006 Codes This checklist is intended for use to prepare for an inspection. This is only a general list and is not intended to address all possible conditions.

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

UNIVERSITY OF MISSOURI. 2. Fire Safety systems such as smoke detectors and fire alarms are intended to increase the level of life safety.

UNIVERSITY OF MISSOURI. 2. Fire Safety systems such as smoke detectors and fire alarms are intended to increase the level of life safety. GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

BUILDING PERMIT APPLICATION CHECKLIST

BUILDING PERMIT APPLICATION CHECKLIST BUILDING PERMIT APPLICATION CHECKLIST Evidence of Onsite land use review/approval required on all permit applications proposing new or expanded commercial, multi-family residential, community services,

More information

SECTION FIRE SUPPRESSION SPRINKLER SYSTEM

SECTION FIRE SUPPRESSION SPRINKLER SYSTEM SECTION 21 1300 21 1300-1 PART 1 - GENERAL 1.1 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division.

More information

Orange County Residential Code Compliance Significant Changes to the 5th Edition 2014 Florida Building Code

Orange County Residential Code Compliance Significant Changes to the 5th Edition 2014 Florida Building Code 1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design

More information

Inspecton Report. Property Address:

Inspecton Report. Property Address: Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 bob@nationalhomeinspections.com www.nationalhomeservices.com Property Address: 873

More information

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Bureau Veritas Contact Information

Bureau Veritas Contact Information Bureau Veritas Contact Information Permit Submittal The permit documents and fees will be submitted to the city. Submittal documents should be complete to expedite plan review and permit issuance. Please

More information

A completed Fire Protection Application Form 1. Name of owner or occupant/address

A completed Fire Protection Application Form 1. Name of owner or occupant/address North Las Vegas Fire Prevention Plan Review Checklist City of North Las Vegas Development Services Center Fire Plan Review 2250 N. Las Vegas Blvd., Ste.14 North Las Vegas, Nevada 89030 (702) 633-2615 phone

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 DESCRIPTION A. Hot water circulating pumps, hot water recirculation pumps, and domestic cold water recirculation pumps. 1.2 RELATED WORK A. Section

More information

SECTION 22000. Hot Water Heaters (Hot Water Recirculation Systems and Point-of-Use Water Heaters)

SECTION 22000. Hot Water Heaters (Hot Water Recirculation Systems and Point-of-Use Water Heaters) SECTION 22000 Hot Water Heaters (Hot Water Recirculation Systems and Point-of-Use Water Heaters) PART I - GENERAL A. Description This section includes requirements for materials for installation of Hot

More information

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations

More information

BUILDING SAFETY UNIT

BUILDING SAFETY UNIT POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential

More information

Saving Water and Energy in Residential Hot Water Distribution Systems. Gary Klein California Energy Commission

Saving Water and Energy in Residential Hot Water Distribution Systems. Gary Klein California Energy Commission Saving Water and Energy in Residential Hot Water Distribution Systems Gary Klein California Energy Commission What Do You Want from your Hot Water System? Safety Not too hot Not too cold No harmful bacteria

More information

One of the fundamental design elements that every

One of the fundamental design elements that every Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things

More information

Applications for building permits will not be reviewed until all of the required information has been submitted.

Applications for building permits will not be reviewed until all of the required information has been submitted. NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to

More information

The Viking Corporation s Web site at PTFE Tape. Compression Screw: Brass UNS-C36000

The Viking Corporation s Web site at PTFE Tape.  Compression Screw: Brass UNS-C36000 Sprinkler 101a 1. DESCRIPTION Viking Standard Response Dry Pendent Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. The sprinklers are designed for dry systems

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

40.68 V33, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Standard Spray Dry Type Concealed Pendent V3301 STANDARD RESPONSE V3302 QUICK RESPONSE

40.68 V33, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Standard Spray Dry Type Concealed Pendent V3301 STANDARD RESPONSE V3302 QUICK RESPONSE SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS The Model V33 Series Dry Type Concealed Pendent Sprinkler with threaded cover assembly and ½" adjustment utilizes stainless steel internal components. The V33

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 332a 1. Description Viking Supervised Surefire Preaction Systems Utilize the Viking G-2000P Valve. The small profile, lightweight, pilot operated Viking G-2000P Valve comes complete

More information

APPLICATION DATA SHEET COPPER BRASS BRONZE

APPLICATION DATA SHEET COPPER BRASS BRONZE APPLIATION DATA SHEET OPPER BRASS BRONZE Residential Fire Sprinkler Systems INTRODUTION Automatic fire sprinkler systems are the most effective and economical way to control or extinguish a fire. The same

More information

Vari Inspection Services

Vari Inspection Services Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

Viking Residential Sprinkler Installation Guide

Viking Residential Sprinkler Installation Guide Viking Residential Sprinkler Installation Guide January, 2009 Trusted Above AllT M www.flowbusiness.cl Sprinkler RES1 January 9, 2009 1. DESCRIPTION Viking residential automatic sprinklers are equipped

More information

Building Department Informational Handout

Building Department Informational Handout City of Sonoma Building Department Informational Handout Residential Water Heaters Handout No: 15 Revised: 5/18/15 A water heater is an appliance designed to supply hot water and is equipped with automatic

More information

standard response standard orifice sprinklers 3. technical data Specifications: Sprinkler 104a January 1, 2011

standard response standard orifice sprinklers 3. technical data Specifications: Sprinkler 104a January 1, 2011 January 1, 2011 Sprinkler 104a 1. DESCRIPTION Viking Standard Response Dry Concealed Pendent Standard Orifice Sprinklers are thermosensitive spray suitable for use in areas subject to freezing. The are

More information

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS

A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared

More information

FIRE PROTECTION WET PIPE FIRE SPRINKLER SYSTEM. E. Shop drawing preparation and submittals as hereinafter described.

FIRE PROTECTION WET PIPE FIRE SPRINKLER SYSTEM. E. Shop drawing preparation and submittals as hereinafter described. SECTION 15300 FIRE PROTECTION WET PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division

More information

quick response dry horizontal sidewall sprinklers

quick response dry horizontal sidewall sprinklers February 26, 2014 Sprinkler 106a 1. DESCRIPTION Viking Quick Response Dry Horizontal Sidewall Sprinklers are thermosensitive spray sprinklers suitable for use in areas subject to freezing. The sprinklers

More information

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

City of St. Charles Basement Finish or Remodel

City of St. Charles Basement Finish or Remodel City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct

More information

Inspection Report. Property Address:

Inspection Report. Property Address: Inspection Report provided by: Zimmel Home Inspections Inspector: Tyson Zimmel Tyson Zimmel (Lic.#862) (360) 775-0708 www.zimmelhomeinspections.com Property Address: 123 Fake Street Port Angeles WA 98362

More information

Home Fire Sprinkler Cost Assessment - 2013

Home Fire Sprinkler Cost Assessment - 2013 Home Fire Sprinkler Cost Assessment - 2013 Final Report Prepared by: Newport Partners The Fire Protection Research Foundation One Batterymarch Park Quincy, MA, USA 02169-7471 Email: foundation@nfpa.org

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

Development Services City of Lawrence, KS

Development Services City of Lawrence, KS Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.

More information

Fire Sprinklers: Coming to a Home Near You

Fire Sprinklers: Coming to a Home Near You Fire Sprinklers: Coming to a Home Near You With a smoking record for saving lives and protecting houses, it s no surprise sprinklers were adopted into the International Residential Code BY CHRIS ERMIDES

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT

MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT MISSISSIPPI INSTITUTIONS OF HIGHER LEARNING OFFICE OF RISK MANAGEMENT ANNUAL BUILDING FIRE INSPECTION REPORT Date of Inspection: University: Building: Address: Contact Person: Phone number: This inspection

More information

City of Elk River BASEMENT Office Use Only

City of Elk River BASEMENT Office Use Only City of Elk River BASEMENT Office Use Only Fire and Building Safety Division (FABS) Building Permit Application Notes Scan Permit Total Date Permit # PID # $ Site Address Suite/Unit Structure Type Single

More information

40.52 V27, K4.9. Residential Concealed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date

40.52 V27, K4.9. Residential Concealed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS This Model V27 residential sprinkler is designed to meet the requirements of NFPA 13, 13D and 13R for residential use in a variety of room sizes, depending upon

More information

FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY

FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY FIRE SAFETY MANUAL INSPECTION FORMS...48 FORM F-1 AUTOMATIC SPRINKLER SYSTEMS WEEKLY INSPECTION...48 FORM F-2 AUTOMATIC SPRINKLER SYSTEMS MONTHLY INSPECTION...49 FORM F-3 AUTOMATIC SPRINKLER SYSTEMS QUARTERLY

More information

Home Inspection Report

Home Inspection Report 4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:

More information

BUILDING REGULATIONS. Newbury, New Hampshire

BUILDING REGULATIONS. Newbury, New Hampshire BUILDING REGULATIONS Newbury, New Hampshire Building Regulations last revised: March 11, 2008 Important Notice last revised: January 28, 2015 IMPORTANT NOTICE Please be advised that the following are suggestions

More information