1 JB ENGINEERING AND CODE CONSULTING, P.C Cardinal Drive Munster, IN Phone: Fax: JULIUS A. BALLANCO, P.E. President July 9, Engineering Report - Analysis of Sure-Seal Trap Seal Protection Device Client: Scope: Abstract: Sure Seal, LLC P.O. Box Tacoma, WA (253) (253) facsimile Sure Seal LLC manufactures a line of floor drain trap seal protection devices. These devices are designed to prevent loss of the trap seal in a floor drain when the drain is infrequently used. Julius Ballanco, P.E., CPD, FASPE, President, JB Engineering and Code Consulting was asked to evaluate the floor drain trap seal protection devices for compliance with the IAPMO Uniform Plumbing Code, the ICC International Plumbing Code, and the ICC International Residential Code. Many floor drains are installed in a sanitary drainage system for emergency purposes. In the event of a leak, discharge of an emergency valve, or overflowing fixture, the floor drain provides drainage of the water. These floor drains are classified by the Plumbing Codes as emergency floor drains. When a floor drain is not used for an extended period of time, the water trap seal in the floor drain may evaporate. When the trap seal evaporates, sewer gas can leak into the building through this opening in the piping system. The purpose of a trap seal is to prevent the escape of sewer gas into the building. Originally, the method of addressing the evaporation of trap seals was the addition of water periodically to the floor drains. The plumbing industry developed a trap seal primer valve to automatically refill the trap seal. These valves are connected to the potable water supply and periodically discharge a small quantity of water to the trap. Page 1 of 7
2 A second style of trap primer connects to the waste pipe for a fixture. When the fixture is utilized, a small quantity of water is diverted to the trap seal for the floor drain. Sure Seal developed a floor drain trap seal protection device that neither relies on the connection to the potable water, nor the discharge of waste water. The Sure Seal has an elastomeric membrane that seals off the opening of the floor drain outlet, preventing the evaporation of the trap seal. The membrane opens to the drainage system when water or waste enters the floor drain. Sure Seal manufactures four different sizes of floor drain trap seal protection devices. The model numbers and size are, as follows: Model SS2009 Model SS3000 Model SS3509 Model SS inch 3 inch 3-1/2 inch 4 inch Standard Requirements: The national consensus standard regulating floor drain trap seal protection devices is ASSE This standard, entitled ASSE Standard Performance Requirements for Barrier Type Floor Drain Trap Seal Protection Devices, has performance requirements to determine the quality and performance of a product. The testing required in ASSE 1072 includes the following: Flow test Evaporation test Trap seal interference test Opening test Dirt and debris test Floor wax test Grease test Life cycle test Membrane material test Third Party Testing and Listing: Sure Seal had their floor drain trap seal protection devices tested to ASSE 1072 by SGS US Testing Company, Tulsa, OK. SGS US Testing Company issued three test reports on the Sure Seal products. Page 2 of 7
3 SGS US Testing Company Test Report No R2, dated March 18, 2008, was for a Model 3000 and The Model 3000 passed all of the test requirements of ASSE Both Models 3000 and 2000 were rated for all floors. SGS US Testing Company Test Report No. 654: R1, dated January 8, 2010, was for a Model The Model 2009 passed all of the test requirements of ASSE 1072 and was rated for all floors. SGS US Testing Company Test Report No. 654:031645, dated April 13, 2010, was for a Model SS4009. The Model SS4009 passed all of the test requirements of ASSE 1072 and was rated for all floors. A copy of the SGS US Testing Company, Inc. Test Reports are available on the Sure Seal website, The Sure Seal models are listed by IAPMO Research and Testing, Inc., File Number C-4165, as complying with ASSE The IAPMO listing can be reviewed on the IAPMO website, Plumbing Code Requirements: International Plumbing Code - Section requires all plumbing fixtures to have a separate liquid seal trap. This would include emergency floor drains. Section requires traps seals subject to loss by evaporation to have a trap seal primer valve installed. Section allows products to be approved as an alternative by the code official. A product must be proven to be equivalent to the requirements in the code to be accepted as an alternative material. Section allows an alternative engineered design. An alternative engineered design must conform to the intent of the code. International Residential Code - Section P requires all plumbing fixtures to have a separate water seal trap. Section P requires traps for floor drains to be fitted with a trap seal primer valve, or be of a deep seal design. Page 3 of 7
4 Section R allows products to be approved as an alternative by the code official. A product must be at least equivalent to the requirements in the code to be accepted as an alternative material. Uniform Plumbing Code - Section requires all plumbing fixtures to be separately trapped by an approved type of water seal trap. This would include all emergency floor drains. Section requires traps that are infrequently used to be protected with a trap seal primer, except where not deemed necessary by the authority having jurisdiction. Section allows a product to be approved as an alternate material. A product must demonstrate equivalency to the code to be approved. Section allows an alternative engineered design. An alternative engineered design must meet the intent of the code. Engineering Analysis: A trap seal is one of the most important parts of a sanitary drainage system. The trap seal isolates the sewer gas from the inside atmosphere. If the trap seal is lost, this level of protection of the inside atmosphere is also lost. Floor drains designed for emergency purposes rarely, if ever, have any water entering. Without periodic use, the trap seal can evaporate, allowing sewer gas to enter the inside environment. Some studies have shown that a trap seal evaporates approximately 1/16 of an inch a day. At this rate, a standard 2 inch trap seal will be lost in 32 days, allowing the escape of sewer gas. The Plumbing Codes require a trap seal primer when there is a possibility of a trap seal loss. Trap seal primers protect the trap seal by introducing a quantity of water into the trap. If a trap seal primer fails to discharge water for a period of time, the trap seal can still evaporate. This is why the design and installation of a trap seal primer is crucial to the protection of the trap seal. Some water supplied trap seal primers open based on the pressure loss in the piping system. Depending on the plumbing design, the trap seal primer may never open, or it may open many times in a given day. If the valve does not open, the trap seal is not protected. If the valve opens numerous times, there is a waste of potable water. Page 4 of 7
5 Similarly, drainage type trap seal primers rely on the use of the fixture to which they are connected. If the fixture is rarely used, the trap seal can still evaporate. Trap seal primers may require periodic maintenance to remain operational. Without this maintenance, the trap seal is not replenished, and protection of the trap seal is not provided. It is estimated that a high percentage, approaching 30 percent, of trap seal primers are either improperly installed, providing no protection of the trap seal, or malfunctioning, also providing no protection of the trap seal. The Sure Seal models provide protection from evaporation by closing off the opening to the trap seal. This prevents water in the trap seal from evaporating. If the trap seal is lost, the Sure Seal models prevent the escape of sewer gas into the interior environment. While this is not the purpose of the elastomeric membrane, it will provide this level of protection. The national consensus standard, ASSE 1072, provides a means of evaluating any product for its ability to protect a floor drain trap seal. The Sure Seal products meet all of the requirements in this standard and are so listed by IAPMO Research and Testing, Inc. This listing verifies that the products comply with the standard. Compliance with the ASSE 1072 standard also verifies that the Sure Seal models do not restrict the flow into a floor drain. The Sure Seal models allow the maximum flow permitted by the plumbing code to flow into the drain. The standard also verifies that the Sure Seal models will function properly under adverse conditions, such as the introduction of dirt, floor wax, or particles that could hold the membrane partially open. Under these conditions, the Sure Seal models prevent the evaporation of the trap seal while allowing the proper operation of the floor drain. The Sure Seal models are all equivalent to the Plumbing Code requirements for protection of the floor drain trap seal. The Sure Seal models will prevent evaporation of the trap seal. This is equivalent to providing a supply of water, or waste water, periodically to the trap seal, as provided by a trap primer. Unlike trap primers, when a failure occurs, the Sure Seal models provide a second line of defense against the escape of sewer gas. This level of protection exceeds the requirements in the Plumbing Code. Page 5 of 7
6 Section of the ICC International Plumbing Code requires any alternative product to be at least equivalent to the requirements in the code. The Sure Seal models are equivalent. Additionally, they provide an added level of health protection not currently required by code. The Sure Seal models can be accepted as an alternative product for protection of a floor drain trap seal. Section R of the ICC International Residential Code requires any alternative product to be at least equivalent to the requirements in the code. The Sure Seal models are better than a deep seal trap, hence they are more than equivalent. Additionally, they provide an added level of health protection not currently required by code. The Sure Seal models can be accepted as an alternative product for protection of a floor drain trap seal. Section of the IAPMO Uniform Plumbing Code requires any alternate product to demonstrate equivalency. The Sure Seal models have demonstrated equivalency to the requirements in the code by conformance to ASSE Additionally, they provide an added level of health protection not currently required by code. The Sure Seal models can be accepted as an alternate product for protection of a floor drain trap seal. The Sure Seal models can be used as a part of an engineered plumbing design since they provide a level of protection of the floor drain trap seal. This meets the intent of the Plumbing Codes. Conclusions: In my professional engineering opinion, after reviewing the product and the test reports, with my engineering knowledge in this field, to a reasonable degree of engineering certainty, the following conclusions are listed: 1. The Sure Seal Models SS2009, SS3000, SS3509, SS4009 provide an equivalent level of protection of a floor drain trap seal when properly installed in accordance with the manufacturer s instructions. 2. The Sure Seal Models SS2009, SS3000, SS3509, SS4009 comply with the requirements of the ICC International Plumbing Code and ICC International Residential Code as an alternative material. 3. The Sure Seal Models SS2009, SS3000, SS3509, SS4009 comply with the requirements of the IAPMO Uniform Plumbing Code as an alternate material. 4. The Authority Having Jurisdiction should accept the installation of the Sure Seal Models SS2009, SS3000, SS3509, SS4009 as an alternative material, meeting the intent of the code for protection of the floor drain trap seal. Page 6 of 7
7 Certification: This report was prepared by Julius Ballanco, P.E., President, JB Engineering and Code Consulting, P.C., registered as a Professional Engineer in the State of Indiana, license number PE JB Engineering and Code Consulting, P.C. is a registered Engineering Professional Corporation in the State of Indiana, license number PC Cordially yours, Julius Ballanco, P.E., CPD, FASPE President Page 7 of 7
Report of Impact of Food Waste Disposers on Combination Waste and Vent Systems and Individual Vents Terminating to an Air Admittance Valve
Report of Impact of Food Waste Disposers on Combination Waste and Vent Systems and Individual Vents Terminating to an Air Admittance Valve 1 ASPE Research Foundation Report of Impact of Food Waste Disposers
More informationCITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY
Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary
More informationBasic Principles for Sizing Grease Interceptors
Basic Principles for Sizing Grease Interceptors Grease Interceptor is an overall term. It is a product category much like faucet. I am sure you can think of several types of faucets like, kitchen, bath
More informationWhy Do I Have Sewer Smells In My Home or Business?
Why Do I Have Sewer Smells In My Home or Business? Before we discuss why you may be getting smells through your drain pipes, lets first take a look at how your plumbing is supposed to work. Properly constructed
More informationBrian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division
Brian Coppock, Regional Compliance Officer Office of Statewide Health Planning and Development Facilities Development Division CHAPTER 6 WATER SUPPLY AND DISTRIBUTION 601.0 Hot and Cold Water Required.
More informationREVISED AGENDA UNIFORM BUILDING CODE COMMISSION PLUMBING /HEAL TH ADVISORY COMMITTEE
REVISED AGENDA UNIFORM BUILDING CODE COMMISSION PLUMBING /HEAL TH ADVISORY COMMITTEE February 5, 2015 9:30 AM Heber M Wells Bldg Room475 160 E 300 S Salt Lake City, UT This agenda is subject to change
More informationINTERNATIONAL RESIDENTIAL PLUMBING CODE
INTERNATIONAL RESIDENTIAL PLUMBING CODE RP2-06/07 P2705.1 Proponent: Guy Tomberlin, Fairfax County, Virginia, representing Virginia Plumbing and Mechanical Revise as follows: P2705.1General. The installation
More informationPLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
More informationPlumbing Code in Commercial Kitchens
Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International
More informationElement D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
More informationPlumbing Code in Commercial Kitchens. NH BOA May 9, 2012
Plumbing Code in Commercial Kitchens NH BOA May 9, 2012 Main Topics Grease Interceptors Indirect Waste Receptors Cleaning Chemical Dispensers Thermal Expansion IPC - Chapter 10 Traps Interceptors Separators
More informationEditorial Note: bold and underline denotes added text, strikethrough denotes deleted text
Code Amendment 12/20/12 2011 Oregon Plumbing Specialty Code, Grease Interceptors & Fats, Oils and Greases Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text 204.0
More informationNo-Flush Urinals PRESERVING GLOBAL WATER
No-Flush Urinals PRESERVING GLOBAL WATER Why Waterless No-Flush Urinals? For a quarter century, Waterless Co. Inc. has been the inventor, pioneer and driver in the waterless urinal fixture industry. The
More informationDIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER PIPING REPORT HOLDER: CURAFLO IP LLC 4035 E. OASIS STREET MESA, AZ 85215
0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted PMG 1057 Valid: 02/15 to 02/16 DIVISION: 22 00 00 PLUMBING SECTION: 22 11 16 DOMESTIC WATER PIPING
More informationARLINGTON COUNTY CODE. Chapter 18 PLUMBING AND GAS CODES
Chapter 18 18-1. Title and Scope. 18-2. Definitions. 18-3. Availability of Codes. 18-4. Administration and Enforcement. 18-5. Registration of Contractors and Certification Requirements. 18-6. Permits and
More informationJay R. Smith Mfg. Co.
Jay R. Smith Mfg. Co. Automatic Backwater Valve SMITH CUSTOMER DRIVEN FLOOD-GATE FEATURES Index Page Flood-Gate Features and Applications 2 How Flood-Gate Works 3 Flood-Gate Operation & Approvals 4 Valve
More informationMASTERS PLUMBING & GAS SCHOOL Mastering the Art of Our Trade. Course Catalog
1 MASTERS PLUMBING & GAS SCHOOL Mastering the Art of Our Trade Course Catalog Locations: 5 Mark Lane, Hyannis, MA 02601 75 Research Road, Hingham, MA 02043 Masters Plumbing & Gas School offers the required
More informationCHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS
PlumbingCode06_ch10 5/29/06 8:16 AM Page 1 CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS We have covered most of the regulations you will need to know about drains and vents. This chapter will round out
More informationNational Precast Concrete Association
National Precast Concrete Association NOTES 1. This manual does not claim or imply that it addresses any safety-related issues associated with its use. Operation and maintenance of precast concrete grease
More informationSECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES
SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSANITARY SEWER BACKUP. Causes & Prevention
SANITARY SEWER BACKUP Causes & Prevention A. PURPOSE The purpose of this publication is twofold: 1. It provides homeowners with basic information on the causes of sanitary sewer backups. 2. It provides
More informationCHAPTER 11 STORM DRAINAGE
CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be
More informationAt the end of today s seminar you should be better. Recognize the causes of Sewer Lateral backup. Identify techniques to protect your home from
Preventing Sewer Backups Presented by IAPMO Today s Objectives At the end of today s seminar you should be better able to: Recognize the causes of Sewer Lateral backup Identify techniques to protect tyour
More informationCHAPTER 11 STORM DRAINAGE
CHAPTER 11 STORM DRAINAGE SECTION 11 GENERAL 11.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. 11.2 Where required. All roofs,
More informationFIRING RANGE PHASE 1 DESIGN 224500-1
FIRING RANGE PHASE 1 DESIGN 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationWater Damage A Rising Concern
Water Damage A Rising Concern Consumer Information Guide Changing weather patterns and the increased severity of rainstorms has led to increased water losses, making water damage the number one property
More informationLand Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents
Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions
More informationSECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationGas Fired Water Heater Installation
Michigan Department of Energy, Labor & Economic Growth Bureau of Construction Codes P.O. Box 30254 Lansing, Michigan 48909 (517) 241-9302 Bureau of Construction Codes Technical Bulletin Publication Number
More information112039.00 224500 EMERGENCY PLUMBING FIXTURES
PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following emergency plumbing fixtures: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Hand-held drench hoses. 5. Combination
More informationWhen Should Examination Preparation Begin?
Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing
More informationSUMP PUMP. City of Ann Arbor & C O L L E C T I O N S Y S T E M G L O S S A R Y
Foundation A foundation is the bottom part of a building. It s the element that anchors the building to the ground and transmits the building s gravity load directly to the earth. Water damage weakens
More informationThe Impacts of High Efficiency Toilets on Plumbing Drainlines and Sewers
The Impacts of High Efficiency Toilets on Plumbing Drainlines and Sewers July 1, 2011 This article addresses key questions and concerns as well as misperceptions about the impacts of reduced water use
More informationFats, Oil and Grease. Best Management Practices Manual. Information, Pollution Prevention, and Compliance Information For Food Service Facilities
Fats, Oil and Grease Best Management Practices Manual Information, Pollution Prevention, and Compliance Information For Food Service Facilities Pinellas County Utilities Water Quality Management Division
More informationPlugging Home Drains to Prevent Sewage Backup
AE-1476 Plugging Home Drains to Prevent Sewage Backup Why plug drains For homes in areas of the country prone to flooding or heavy rain, taking a few steps to prepare for water levels that could result
More informationDRAIN, WASTE AND VENT PLUMBING
Flow of waste in a drain system Solid and liquid waste flows in vertical pipes much differently than it does in horizontal systems. In near horizontal pipes we talked about maintaining the slope of the
More informationPlumbing Code Sections For Commercial Food Facilities
Plumbing Code Sections For Commercial Food Facilities SCOPE The following list of requirements summarizes the plumbing issues that are commonly addressed in commercial retail food facilities by health
More informationORDINANCE NO. 15 BE IT ORDAINED BY THE COUNCIL OF KANSAS CITY:
ORDINANCE NO. 15 Amending Chapter 60 of the Code of Ordinances of Kansas City, Missouri, entitled Sewers and Sewage Disposal by adding Sections 60-349 through 60-360; and establishing an effective date.
More informationCity of Hillsboro Inflow and Infiltration Elimination Program
City of Hillsboro Inflow and Infiltration Elimination Program Because of continuing problems with overloaded sanitary sewers, the City of Hillsboro is inspecting the sewer system in your neighborhood.
More information6. Principles of effective plumbing systems
6. Principles of effective plumbing systems This chapter summarizes the aims and objectives of a good local plumbing system that is, the drinking-water supply that serves a building and the system for
More informationAlabama Statewide. Arkansas Statewide
Alabama Statewide Alabama generally follows the guidelines of the or ICC, which in turn recognizes the American Society of Sanitary Engineering (ASSE) 1055 requirements, and consequently Alabama s IPC
More informationwww.garyklinka.com Page 1 of 51 Exterior Plumbing Quiz Part 1
www.garyklinka.com Page 1 of 51 Exterior Plumbing Quiz Part 1 Instructions: $60 1. Print these pages..all reference materials are included. 2. Review and answer the simple questions in each mini section.
More informationSECTION THREE CONSTRUCTION CODES
SECTION THREE CONSTRUCTION CODES CHAPTER 36: Construction Codes in Michigan Purpose and Applicability of Regulations Manufacturing facilities and other businesses must be designed according to code in
More informationPlumbing Code. City of San Diego 2013 Plumbing Regulations - Proposed Code Changes (revised 5/15/15)
"Portions of this publication reproduce excerpts from the 2013 California Mechanical Code, Title 24, Part 4 and 2013 California Plumbing Code, Title 24, Part 5, reprinted with the permission of the International
More informationA. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More information4.3 Cisterns and Rain Barrels
4.3 Cisterns and Rain Barrels Rain barrels, cisterns, and tanks are structures designed to intercept and store runoff from rooftops. Rain barrels are used on a small scale while cisterns and tanks may
More informationWhat to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
More informationSECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES
SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES 5.1.0 GENERAL Section five reviews consolidates the various local amendments technical code information
More informationSEPTIC SYSTEMS. 1. Building sewer connects the building plumbing to the septic tank.
SEPTIC SYSTEMS Who Has A Septic System? Approximately 30 percent of Connecticut s population is served by on-site subsurface sewage disposal systems (a.k.a. septic systems). This means a large percentage
More informationWELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION 1 HOUSEKEEPING 2 CHANGES We will be covering the significant changes to the International Residential Code and the changes common to
More information1. Complete, sign and forward the enclosed Sewer User Abatement Application to the following address:
The Narragansett Bay Commission Vincent J. Mesolella One Service Road Chairman Providence, Rhode Island 02905 Raymond J. Marshall, P.E. 401 461 8848 Executive Director 401 461 6540 FAX http://www.narrabay.com
More informationPonti (HB 1048) Act No. 836. Louisiana State Plumbing Code as Promulgated by the Department of Health and Hospitals: Status and Changes
Ponti (HB 1048) Act No. 836 Louisiana State Plumbing Code as Promulgated by the Department of Health and Hospitals: Status and Changes Prior law required the state health officer through the office of
More informationBest Management Practices
for The City of Paso Robles is required to implement a Phase II Municipal Water Program in order to reduce or eliminate the pollutants that enter our waterways from both storm water and non-storm water
More information(a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems.
12.33 - CROSS-CONNECTION CONTROL. (a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems. (b) Definitions. The following definitions shall apply
More informationHow To Build A Backwater Valve
Photos by: Bobby Thompson, Jeff Napier Illustrations: Rudy Martinez Bobby Thompson July 16, 2009 Presented by Jeff Napier A Backwater Valve is a one way valve that is installed on a building sewer to prevent
More informationSEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER
Village of Shorewood, Wisconsin SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER Prepared By: Thomas A. Zoulek, P.E., LEED A.P. Vice President Mid City Plumbing & Heating
More informationPlumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection
Plumbing Code Statutes and Regulations February 2011 Labor Standards and Safety Division Mechanical Inspection Jobs are Alaska s Future MECHANICAL INSPECTION CUSTOMER COUNTER LOCATIONS Main Office MI Anchorage
More informationGeorgia State Amendments to the International Plumbing Code
Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Local Government Assistance Division 60 Executive Park South, N.E. Atlanta, Georgia 30329-2231
More informationControl filling, grading, dredging, and other development which may increase erosion or flood damage; and
ARTICLE 16. FLOOD DAMAGE PREVENTION Section 16-1: Findings of Fact The flood hazard areas of the Town of Lillington are subject to periodic inundation which results in loss of life and property, health
More informationAmendments to the 2012 International Plumbing Code
Amendments to the 2012 International Plumbing Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby
More informationPERMITS REQUIRED & PERMIT EXEMPTIONS
PERMITS REQUIRED & PERMIT EXEMPTIONS This guideline is intended to assist the applicant in determining what types of construction work require a permit. The 1997 California Uniform Administrative Code,
More informationFOOD SERVICE FACILITIES Best Management Practices Stormwater Management Program City of Bluff City P.O. Box 70, Bluff City, TN 37618 423-538-7144
FOOD SERVICE FACILITIES Best Management Practices Stormwater Management Program City of Bluff City P.O. Box 70, Bluff City, TN 37618 423-538-7144 This document may be printed and used for reference by
More informationDate of Authorization November 30, 2006 BMEC Authorization Number 06-09-329 BMEC Application BMEC A2006-11. AUTHORIZATION REPORT The AcornVac System
777 Bay Street, 2 nd Floor Toronto, Ontario, M5G 2E5 Tel: 416 585 4234 Fax: 416 585 7531 Web: www.obc.mah.gov.on. Date of Authorization BMEC Authorization Number 06-09-329 BMEC Application BMEC A2006-11
More informationHALIFAX REGIONAL MUNICIPALITY BY-LAW P-400 RESPECTING REGULATING THE INSTALLATION OF PLUMBING SYSTEMS
HALIFAX REGIONAL MUNICIPALITY BY-LAW P-400 RESPECTING REGULATING THE INSTALLATION OF PLUMBING SYSTEMS BE IT ENACTED by the Council of the Halifax Regional Municipality under the Authority of Section 7
More informationFood Service Facilities
Food Service Facilities Selecting and installing a grease removal device Regional Water Quality Control Plant Operated by the City of Palo Alto for the East Palo Alto Sanitary District, Los Altos, Los
More informationCITY OF SURREY BY-LAW NO. 6569
CITY OF SURREY BY-LAW NO. 6569 As amended by By-laws No. 7026, 02/01/82; 9960, 03/13/90; 10368, 01/22/90; 10797, 01/28/91; 12268, 04/25/94; 12384, 07/02/94; 12828, 05/13/96; 13171, 07/29/97; 13220, 09/22/97;
More informationA. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 22 45 00 - (ADD#2) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org
Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 domenico.barbato@lacity.org b 2011 Los Angeles Plumbing Code LAPC changes from 2008 2011 Los Angeles Plumbing Code Consists of the following:
More informationPlumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations
More informationThe Town of Lakeshore Basement Flooding Information to Residents
The Town of Lakeshore Basement Flooding Information to Residents The following information is intended for residents that have homes connected to Municipal storm and sanitary sewers. However, rural residents
More informationThe Plumbing Pipeline
The Plumbing Pipeline A Newsletter for licensed Plumbers and Drainlayers May 2016, Issue 29 Please copy this bulletin and distribute to your staff. The Plumbing Pipeline is a semi-annual information newsletter
More informationREGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours
Affix label with Candidate Code Number here. If no label, enter candidate Number if known No. 99 REGISTRATION EXAMINATION, JUNE 009 PLUMBING INSTRUCTIONS QUESTION AND ANSWER BOOKLET Time allowed THREE
More informationPlumbing for retail food businesses
Plumbing for retail food businesses Every day, thousands of food outlets in Sydney produce waste, such as cooking oil, grease and food solids. If that waste is discharged directly into our sewers, it can
More information8 plumbing. plumbing. 2010 PulteGroup, Inc. All Rights Reserved.
8 90 2010 PulteGroup, Inc. All Rights Reserved. drains All the water you use leaves the home through a drain. Maintaining drains prevents clogging, overflows, water damage, and other problems. care and
More informationCompliance Document for New Zealand Building Code Clause G13 Foul Water Second Edition
Compliance Document for New Zealand Building Code Clause G13 Foul Water Second Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building
More informationCASS COUNTY COMMISSION POLICY MANUAL 38.07 ADOPTED DATE: FEBRUARY 2, 1998 PAGE 1 OF 9
CASS COUNTY COMMISSION POLICY MANUAL 38.07 SUBJECT: ORDINANCE #1998-2 (FLOOD DAMAGE PREVENTION) ADOPTED DATE: FEBRUARY 2, 1998 PAGE 1 OF 9 NORTH DAKOTA COUNTY OF CASS ORDINANCE #1998-2 Be it ordained and
More informationOVER-HEAD SEWER ASSISTANCE GRANT
OVER-HEAD SEWER ASSISTANCE GRANT The Village of North Aurora has a vested interest in the proper operation of the North Aurora sanitary system. Understanding that some residential users of the sanitary
More informationB. Shop Drawings: Diagram power, signal, and control wiring.
SECTION 224500 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Combination units. 5. Water-tempering equipment. 1.2 SUBMITTALS
More informationBasement Valve Program
Basement Valve Program The following is intended to inform homeowners connected to combined sewers of the options available to prevent basement backups from occurring following a rainstorm. A combined
More informationPMA ONLINE TRAINING Venting for Plumbing Systems
PMA ONLINE TRAINING Venting for Plumbing Systems One Hour Continuing Education Venting PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended
More informationDISTRICT OF COLUMBIA WATER AND SEWER AUTHORITY. a guide to PREVENTING SEWER BACKUPS AND FLOODING
DISTRICT OF COLUMBIA WATER AND SEWER AUTHORITY a guide to PREVENTING SEWER BACKUPS AND FLOODING Sewer backups and flooding can damage District homes and businesses. Sewer blockages are most commonly found
More informationGuidance on applying for approval of installation of a commercial onsite wastewater system
Guidance on applying for approval of installation of a commercial onsite wastewater system This factsheet is designed to assist you to complete an Application to construct or install an apparatus for the
More informationWHEN IS A PERMIT REQUIRED?
WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,
More informationResearch of Grey Water for Use in Residential Applications Original date of publication: 12-14-2007 Updated: 8-06-2008
What is Grey Water? Research of Grey Water for Use in Residential Applications Original date of publication: 12-14-2007 Updated: 8-06-2008 Grey water comes from many sources. Grey water, gray water, greywater,
More informationCITY OF PINOLE SEWER LATERAL ADMINISTRATIVE GUIDELINES
CITY OF PINOLE SEWER LATERAL ADMINISTRATIVE GUIDELINES Adopted by Resolution No. 2012-132 Dated December 18, 2012 1 TABLE OF CONTENTS PURPOSE... 3 I. WHEN INSPECTION IS REQUIRED (PMC 13.20.050, 13.20.060,
More informationDRAFT Guidelines for Manually Diverting Outdoor Wastewater to the Sanitary Sewer
Only RAIN down the Storm Drain... DRAFT Guidelines for Manually Diverting Outdoor Wastewater to the Sanitary Sewer This publication applies to you if: You generate wastewater outdoors, and The wastewater
More informationPREVENTING WET OR FLO ODED BASEMENTS
PREVENTING WET OR FLO ODED BASEMENTS TABLE OF CONTENTS Prevention Tips...Page 1 Why is there Water in my Basement?...Page 2 City of Saskatoon Sewer Systems...Page 3 Why Does Saskatoon Have Two Separate
More informationRHODE ISLAND. Downloaded 01.15.11
Housekeeping/Laundry/Maintenance Section 35.0 Housekeeping RHODE ISLAND Downloaded 01.15.11 35.1 A full time employee of the facility shall be designated responsible for housekeeping services, supervision
More informationCHAPTER 9 VENTS TRANSPORTATION OF SEWER GAS
PlumbingCode06_ch09 5/29/06 8:16 AM Page 1 CHAPTER 9 VENTS Most people don t think much about vents when they consider the plumbing in their home or office, but vents play a vital role in the scheme of
More informationPLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES
PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES Health Systems Protection Rev. 07/2006 35-05-20/06/07/18 OFFICE OF FOOD PROTECTION 417 FEDERAL ST
More informationARLINGTON HEIGHTS MUNICIPAL CODE CHAPTER 22 SEWERS
ARLINGTON HEIGHTS MUNICIPAL CODE CHAPTER 22 SEWERS Article I General Provisions Section 22-101 Definitions Section 22-102 Supervision of Sewer System Section 22-103 Inspections Section 22-104 Use of Public
More informationRainwater is directed away from walls at surface. Any water infiltrating is captured in drains below foundation
Ground Surface Rainwater is directed away from walls at surface. Any water infiltrating is captured in drains below foundation Ground Surface Soil Ground Water Level Basement Wall Groundwater drains to
More informationProposed plumbing system within units at the Bluewater Hotel, 10 West Quay, Ahuriri, Napier
Determination 2010/125 Proposed plumbing system within units at the Bluewater Hotel, 10 West Quay, Ahuriri, Napier 1. The matters to be determined 1.1 This is a Determination under Part 3 Subpart 1 of
More informationBest Management Practices Fats, Oils, & Grease
Best Management Practices Fats, Oils, & Grease for Food Service Facilities Public Works Department Environmental Division Table of Contents A. Introduction B. Purpose of the Manual 1 C. Frequently Asked
More informationHow To Maintain A City Sewer System
54.01 Definitions 54.02 Ownership Chapter 54: Sewers General Provisions 54.03 Operation and funding 54.04 Installation procedure 54.05 Inspections 54.25 Connections 54.26 Mandatory hook-up Regulations;
More informationHERNDON/MUNCEY, INC. Office: (281) 579-0515 INVESTIGATIVE PLUMBING
HERNDON/MUNCEY, INC. Office: (281) 579-0515 INVESTIGATIVE PLUMBING Fax: (281) 579-1960 February 21, 2014 INVOICE NO.: HR18831 TIN: 76-0462307 1 STATIC TEST $350.00 1 HYDROSTATIC $125.00 PAID MASTER CARD
More informationGUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS
GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS Fort Worth Water Department, Pretreatment Services Division, (817)871-8305 A. Introduction: Part I: Guidance for Grease Trap
More informationResidential Plumbing BCN 1058
Residential Plumbing BCN 1058 CHAPTER 7 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System MICHAEL KNOTEK 74 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System PLUMBING FIXTURES
More information15. Design of plumbing systems for industrial and temporary applications
15. Design of plumbing systems for industrial and temporary applications 15.1 Backflow prevention in industrial, commercial and institutional water systems Any water piping installation where there is
More informationfoundation designed to keep water out of the basement.
Preventing Sewer Backups To safeguard your home against flooding from sewer backups, you should understand your home's basic plumbing and the preventative techniques discussed in this brochure. Basement
More information