Plumbing Code in Commercial Kitchens. NH BOA May 9, 2012
|
|
|
- Benedict Brown
- 10 years ago
- Views:
Transcription
1 Plumbing Code in Commercial Kitchens NH BOA May 9, 2012
2 Main Topics Grease Interceptors Indirect Waste Receptors Cleaning Chemical Dispensers Thermal Expansion
3 IPC - Chapter 10 Traps Interceptors Separators
4 Section 1002 Trap Requirements Fixture Traps. Each fixture shall be separately trapped by a liquid-seal trap, except as otherwise permitted by this code. The vertical distance from the fixture outlet to the trap weir shall not exceed 24 inches, and the horizontal distance shall not exceed 30 inches measured from the centerline of the fixture outlet to the centerline of the inlet of the trap. The height of a clothes washer standpipe above trap shall conform to Section A fixture shall not be double trapped.
5 Section Exception #3 A grease interceptor intended to serve as a fixture trap in accordance with the manufacturer s installation instructions shall be permitted to serve as the trap for a single fixture or a combination sink of not more than three compartments where the vertical distance from the fixture outlet to the inlet of the interceptor does not exceed 30 inches and the developed length of the waste pipe from the most upstream fixture outlet to the inlet of the interceptor does not exceed 60 inches.
6 GT2700 Grease Interceptor Installation & Cleaning Instructions Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at ( ) gpm and a properly sized flow control fitting. INSTALLATION 1. Zurn Light Commercial Grease Interceptors should be installed as close as possible to the fixture being served. Always install where there is easy access for cover removal and cleaning. 4. The cleanout plug should be installed over the outlet of the interceptor. 5. The interceptor is to be installed using no-hub couplings.
7 Design of traps. Fixture traps shall be self-scouring. Fixture traps shall not have interior partitions, except where such traps are integral wih the fixture or where such traps are constructed of an approved material that is resistant to corrosion and degradation Prohibited Traps 6. Drum traps Exception: Drum traps used as solids interceptors and drum traps serving chemical waste systems shall not be prohibited Trap seals. Each fixture trap shall have a liquid seal of not less than 2 inches and not more than 4 inches or deeper for for special designs relating to accessible fixtures.
8
9 Where required. Interceptors and separators shall be provided to prevent the discharge of oil, grease, sand and other substances harmful or hazardous to the building drainage system, the public sewer, the private sewage disposal system or the sewage treatment plant or processes.
10 Approval. The size, type and location of each interceptor and of each separator shall be designed and installed in accordance with the manufacturer s instructions and the requirements of this section based on the anticipated conditions of use. Wastes that do not require treatment or separation shall not be discharged into any interceptor or separator.
11 Approval. The size, type and location of each interceptor and of each separator shall be designed and installed in accordance with the manufacturer s instructions and the requirements of this section based on the anticipated conditions of use. Wastes that do not require treatment or separation shall not be discharged into any interceptor or separator.
12 Grease Interceptors and Automatic Grease Removal Device required. (cont.) Fixtures and equipment shall include: pot sinks pre-rinse sinks soup kettles or similar devices wok stations floor drains or sinks into which kettles are drained automatic hood wash units dishwashers without pre-rinse sinks.
13 Food Waste Grinders Where food waste grinders connect to grease interceptors, a solids interceptor shall separate the discharge before connecting to the grease interceptor. Solids interceptors and grease interceptors shall be sized and rated for the discharge of the food waste grinder. Emulsifiers, chemicals, enzymes and bacteria shall not discharge into the food waste grinder.
14 GT2700 Grease Interceptor Installation & Cleaning Instructions Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at ( ) gpm and a properly sized flow control fitting. INSTALLATION 1. Zurn Light Commercial Grease Interceptors should be installed as close as possible to the fixture being served. Always install where there is easy access for cover removal and cleaning. 2. A flow control must be installed as close as possible to the underside of the fixture. The flow control must be installed with the vent or (air intake) on the downstream side of the orifice plate. The vent connection is positioned to the top of the flow control fitting and piped upward higher than source of water, or to building vent system 3. It is recommended that a cleanout tee be installed before the flow control to access the flow control orifice and clear debris. 4. The cleanout plug should be installed over the outlet of the interceptor. 5. The interceptor is to be installed using no-hub couplings. 6. Outlet piping should be connected to the sanitary drain, and pipe size should be equal to or larger than the inlet piping. Outlet pipe should also be vented so the interceptor is not siphoned. 7. Solid waste should not go into an interceptor. Food grinder waste and other solids should be captured in the sink or by a solids interceptor before reaching the grease interceptor. Form # JS2 Date: 3/13/09 C.N. No Rev. F Page 1 of 2 ZURN LIGHT COMMERCIAL PLUMBING PRODUCTS 2640 South Work Street Falconer, NY Phone: 1-800/ Fax: 716/ World Wide Web:
15
16
17
18
19
20 In compliance?
21 Rate of flow controls Grease interceptors shall be equipped with devices to control the rate of water flow so that the water flow does not exceed the rated flow. The flow- control device shall be vented and terminate not less than 6 inches (152 mm) above the flood rim level or be installed in accordance with the manufactures instructions.
22
23 GT2700 Grease Interceptor Installation & Cleaning Instructions Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at ( ) gpm and a properly sized flow control fitting. INSTALLATION 1. Zurn Light Commercial Grease Interceptors should be installed as close as possible to the fixture being served. Always install where there is easy access for cover removal and cleaning. 2. A flow control must be installed as close as possible to the underside of the fixture. The flow control must be installed with the vent or (air intake) on the downstream side of the orifice plate. The vent connection is positioned to the top of the flow control fitting and piped upward higher than source of water, or to building vent system 3. It is recommended that a cleanout tee be installed before the flow control to access the flow control orifice and clear debris. 4. The cleanout plug should be installed over the outlet of the interceptor. 5. The interceptor is to be installed using no-hub couplings. 6. Outlet piping should be connected to the sanitary drain, and pipe size should be equal to or larger than the inlet piping. Outlet pipe should also be vented so the interceptor is not siphoned. 7. Solid waste should not go into an interceptor. Food grinder waste and other solids should be captured in the sink or by a solids interceptor before reaching the grease interceptor. Form # JS2 Date: 3/13/09 C.N. No Rev. F Page 1 of 2 ZURN LIGHT COMMERCIAL PLUMBING PRODUCTS 2640 South Work Street Falconer, NY Phone: 1-800/ Fax: 716/ World Wide Web:
24 Grease interceptors and automatic grease removal devices not required. A Grease interceptor or an automatic grease removal device shall not be required for individual dwelling units or any private living quarters.
25 Chapter 8 Indirect/Special Waste
26 802.1 Where Required. Food-handling equipment and clear-water waste shall discharge through an indirect waste pipe as specified in Sections through
27 Section Food Handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
28 Air gap. The air gap between the indirect waste pipe and the flood level rim of the waste receptor shall be a minimum of twice the effective opening of the indirect waste pipe. Chapter 2 Definitions: Air Gap (Drainage System): The unobstructed vertical distance through the free atmosphere between the outlet of the waster pipe and the flood level rim of the receptacle into which the waste pipe is discharging. Floor Level Rim: The edge of the receptacle from which water overflows.
29
30 Waste Receptor 2 x D
31 802.3 Waste Receptors. Every waste receptor shall be of an approved type. A removable strainer or basket shall cover the waste outlet of waste receptors. Waste receptors shall be installed in ventilated spaces. Waste receptors shall not be installed in bathrooms or toilet rooms or in any inaccessible or unventilated space such as a closet or storeroom. Ready access shall be provided to waste receptors.
32 Size of Receptors. A waste receptor shall be sized for the maximum discharge of all indirect waste pipes served by the receptor. Receptors shall be installed to prevent splashing or flooding.
33 Open hub waste receptors. Waste receptors shall be permitted in the form of a hub or pipe extending not less than 1 inch (25.4 mm) above a water-impervious floor and are not required to have a strainer.
34 The 3 Bay Sink
35
36
37
38
39
40
41 Food Utensils, Dishes, Pots and Pan Sinks Sinks used for the washing, rinsing or sanitizing of utensils, dishes, pots, pans, or service ware used in the preparation, servicing or eating of food shall discharge indirectly through an air gap or an air break or directly connect to the drainage system.
42
43
44 WASH RINSE SANITIZE WITH GREASE INTERCEPTION, DIRECTLY CONNECTED
45 Wash, rinse and sanitize with grease interception, indirectly connected using an approved waste receptor
46 CHEMICAL DISPENSERS AT THE MOP SINK
47
48
49
50
51
52
53
54 Expansion Tanks Required? Section 607 Hot Water Supply System Thermal expansion control. A means of controlling increased pressure caused by thermal expansion shall be provided where required in accordance with Sections and Pressure-reducing valve. For water service system sizes up to and including 2 inches, a device for controlling pressure shall be installed where, because of thermal expansion, the pressure on the downstream side of a pressure-reducing valve exceeds the pressure reducing valve setting Backflow prevention device or check valve. Where a backflow prevention device, check valve or other device is installed on a water supply system utilizing storage water heating equipment such that thermal expansion causes an increase in pressure, a device for controlling pressure shall be installed. IRC P2903.4
55 Plumbing Safety & Licensing Inspectors Ron Lemere Ext Sam Zannini Jr Ext Earl Middlemiss Ext Contact Jeff Cyr Ext
Plumbing Code in Commercial Kitchens
Plumbing Code in Commercial Kitchens City of Concord Code Administration 225-8580 Dan Clark Plumbing Inspector Tedd Evans, Chief Building Inspector Code References from the 2009 edition of the International
CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS
PlumbingCode06_ch10 5/29/06 8:16 AM Page 1 CHAPTER 10 TRAPS, CLEAN-OUTS, AND INTERCEPTORS We have covered most of the regulations you will need to know about drains and vents. This chapter will round out
Top 10+ Mistakes of DWV plumbing design
Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of
Plumbing Code Sections For Commercial Food Facilities
Plumbing Code Sections For Commercial Food Facilities SCOPE The following list of requirements summarizes the plumbing issues that are commonly addressed in commercial retail food facilities by health
Fats, Oil and Grease. Best Management Practices Manual. Information, Pollution Prevention, and Compliance Information For Food Service Facilities
Fats, Oil and Grease Best Management Practices Manual Information, Pollution Prevention, and Compliance Information For Food Service Facilities Pinellas County Utilities Water Quality Management Division
PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES
PLAN REVIEW AND APPROVAL FOR FOOD ESTABLISHMENTS PLUMBING REQUIREMENTS FOR FOOD ESTABLISHMENT PREMISES Health Systems Protection Rev. 07/2006 35-05-20/06/07/18 OFFICE OF FOOD PROTECTION 417 FEDERAL ST
Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text
Code Amendment 12/20/12 2011 Oregon Plumbing Specialty Code, Grease Interceptors & Fats, Oils and Greases Editorial Note: bold and underline denotes added text, strikethrough denotes deleted text 204.0
PLUMBING & CROSS-CONNECTION CONTROL
PLUMBING & CROSS-CONNECTION CONTROL. MODULE 4 VII. Typical Retail Food Service Cross-Connections VIII. Air Gaps and Air Breaks for Drains and Waste IX. Grease Interceptors VII. TYPICAL RETAIL FOOD SERVICE
PLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
CITY OF GOLDEN DEPARTMENT OF PUBLIC WORKS, ENVIRONMENTAL SERVICES DIVISION
CITY OF GOLDEN DEPARTMENT OF PUBLIC WORKS, ENVIRONMENTAL SERVICES DIVISION Grease, So What's the Problem? Does your facility produce grease? All commercial cooking facilities generate Fats, Oil, and Grease
Brian Coppock, Regional Compliance Officer. Office of Statewide Health Planning and Development Facilities Development Division
Brian Coppock, Regional Compliance Officer Office of Statewide Health Planning and Development Facilities Development Division CHAPTER 6 WATER SUPPLY AND DISTRIBUTION 601.0 Hot and Cold Water Required.
Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling February 2001 contents General Information 3 Inspection 4 New Drain and Vent Installations
PMA ONLINE TRAINING Venting for Plumbing Systems
PMA ONLINE TRAINING Venting for Plumbing Systems One Hour Continuing Education Venting PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended
Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling October 2014 contents General Information
New or Remodeled Food Service Establishment Checklist**
ToTo Protect and Promote the Health and the Environment of the People of Kittitas County New or Remodeled Food Service Establishment Checklist** **Some items may not be required for limited food service
GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS
GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS AND INTERCEPTORS Fort Worth Water Department, Pretreatment Services Division, (817)871-8305 A. Introduction: Part I: Guidance for Grease Trap
Goal The goal of this seminar is for participants to reinforce their knowledge on specific topics in the IPC and IRC as it relates to plumbing.
Introduction Description This seminar is intended to provide participants with specific topics from the 2009 International Plumbing Code (IPC ) and the 2009 International Residential Code (IRC ) as it
FOG PRETREATMENT INFORMATION. New London Public Utilities F.O.G. Program 120 Broad Street New London, CT 06320
FOG PRETREATMENT INFORMATION 1 New London Public Utilities F.O.G. Program 120 Broad Street New London, CT 06320 Kathryn Willis Program Coordinator Phone: 860-447-5222 Introduction This information package
SAN JACINTO RIVER AUTHORITY GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS, INTERCEPTORS AND SEPERATORS
SAN JACINTO RIVER AUTHORITY GUIDANCE DOCUMENT FOR SIZING AND INSTALLATION OF GREASE TRAPS, INTERCEPTORS AND SEPERATORS Part I: Guidance for Grease Trap/Grease Interceptor Sizing and Design Criteria A.
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION
WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION 1 HOUSEKEEPING 2 CHANGES We will be covering the significant changes to the International Residential Code and the changes common to
Residential Plumbing BCN 1058
Residential Plumbing BCN 1058 CHAPTER 7 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System MICHAEL KNOTEK 74 Plumbing Fixtures and Sizing the Drain, Waste, and Vent System PLUMBING FIXTURES
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 8 - INDIRECT WASTES
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 8 - INDIRECT WASTES Adopting Agency BSC SFM HCD DSA OSHPD CSA DPH AGR DWR CA 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt Entire Chapter X X X X X X X X X Adopt
SINKS / DISHMACHINES. Food Preparation Sink
ENVIRONMENTAL HEALTH DIVISION 2120 Diamond Blvd., Suite 200 Concord, CA 94520 Phone: (925) 692-2500 Fax: (925) 692-2505 www.cchealth.org/eh/ SINKS / DISHMACHINES Food Preparation Sink A separate stainless
National Precast Concrete Association
National Precast Concrete Association NOTES 1. This manual does not claim or imply that it addresses any safety-related issues associated with its use. Operation and maintenance of precast concrete grease
What to Expect From the Examination. How to Study the Plumbing Codes
Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.
CHAPTER 9 VENTS. copper drainage tube Type DWV, Schedule 40 plastic piping, or borosilicate glass.
CHAPTER 9 VENTS 901 GENERAL 901.1 Scope The provisions of this chapter shall govern the materials, design, construction, and installation of vents. 901.2 Protection of Trap Seals The protection of trap
2006 Codes. Please verify the following before calling for inspection
INSPECTION CHECKLIST RESIDENTIAL PLUMBING ROUGH IN 2006 Codes This checklist is intended for use to prepare for an inspection. This is only a general list and is not intended to address all possible conditions.
Chapter 8 Water and Sewage Systems
Chapter 8 Water and Sewage Systems Proper sanitary controls pertaining to the water supply system and sewage and liquid waste disposal systems are necessary in all types of food establishments to prevent
Manual contents includes:
Fats, Oil, and Grease (FOG) Best Management Practices (BMP) For Food Service Facilities Information, Pollution Prevention, and Compliance Information (2/07/06) Fats, oil and grease (FOG) can have negative
6. Principles of effective plumbing systems
6. Principles of effective plumbing systems This chapter summarizes the aims and objectives of a good local plumbing system that is, the drinking-water supply that serves a building and the system for
Best Management Practices Fats, Oils, & Grease
Best Management Practices Fats, Oils, & Grease for Food Service Facilities Public Works Department Environmental Division Table of Contents A. Introduction B. Purpose of the Manual 1 C. Frequently Asked
Grease Trap Maintenance, Procedures and Cleaning Logs
SAWS Grease Reduction Program Grease Trap Maintenance, Procedures and Cleaning Logs Don t Feed the Grease Monster Best Management Practices for Commercial Food and Restaurant Facilities Train kitchen staff
ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920. Wet Venting. Incorporating Stack Venting and NPC Harmonization
ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920 Wet Venting Incorporating Stack Venting and NPC Harmonization Presented by: Rainier Bratsch-Blundel, CPSI Plumbing Professor
CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004
Bellevue Bothell Kenmore Kirkland Issaquah Mercer Island Sammamish Snoqualmie Woodinville CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004 This checklist is intended for use to prepare
ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007
ONE AND TWO FAMILY DWELLINGS Plumbing July, 2007 The following are general requirements pertaining to plumbing in one and two family dwellings. This does not represent all the provisions regulating plumbing
Fats, Oil, and Grease (FOG) Best Management Practices (BMP) For Food Service Facilities. Guidance Manual
Fats, Oil, and Grease (FOG) Best Management Practices (BMP) For Food Service Facilities Guidance Manual Boise Public Works Department May 2007 Table of Contents SECTION...PAGE A. INTRODUCTION...1 B. PURPOSE
Element D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
Amendments to the 2012 International Plumbing Code
Amendments to the 2012 International Plumbing Code North Central Texas Council of Governments region The following sections, paragraphs, and sentences of the 2012 International Plumbing Code are hereby
Grease Traps and Interceptors
Grease Traps and Interceptors Dorchester County Water and Sewer Introduction Fats, oils, and greases (FOG) can build up in sewer pipes, resulting in costly and messy overflows. It is bad for business,
SOUTHERN NEVADA PLUMBING CODE AMENDMENTS
SOUTHERN NEVADA 2000 PLUMBING CODE AMENDMENTS Clark County Published March, 2003 By JURISDICTIONS City of Las Vegas 500 S. Grand Central Pkwy 731 S. 4 th Street Las Vegas, Nevada 89155 Las Vegas, Nevada
Chapter 5 Water, Plumbing, and Waste
Chapter 5 Water, Plumbing, and Waste Parts 5-1 WATER 5-2 PLUMBING SYSTEM 5-3 MOBILE WATER TANK AND MOBILE FOOD ESTABLISHMENT WATER TANK 5-4 SEWAGE, OTHER LIQUID WASTE, AND RAINWATER 5-5 REFUSE, RECYCLABLES,
2006 IPC INTERNATIONAL PLUMBING CODE AMENDMENTS PLANNING & DEVELOPMENT SERVICES DEPARTMENT
2006 IPC INTERNATIONAL PLUMBING CODE AMENDMENTS Ordinance No. 3771 Adopted April 1, 2008 Effective June 30, 2008 PLANNING & DEVELOPMENT SERVICES DEPARTMENT ORDINANCE NO. 3771 AN ORDINANCE OF THE COUNCIL
CHAPTER 10 TRAPS AND INTERCEPTORS
CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS
WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS a. New Plumbing and Gas Piping Systems. This code in conjunction with the Plumbing and Fuel Gas Codes of the State of New York shall apply to plumbing
Hydro Mechanical v. Gravity Grease Interceptors TS 400 2 1 Saturday 9:00am 12:00pm Rand Ackroyd
Hydro Mechanical v. Gravity Grease Interceptors TS 400 2 1 Saturday 9:00am 12:00pm Rand Ackroyd CAPTURING the GREASE MODEL CODE EDITION Copyright 2011 .Hydro Mechanical vs Gravity Grease Interceptors UPC,
How do I clean my grease trap? Refer to Grease Trap and Interceptor Maintenance.
Fats, Oil, and Grease Best Management Practices Manual Information, Pollution Prevention, and Compliance Information for Publicly-Owned Treatment Plants Fats, oil and grease - - also called FOG in the
CHAPTER 26 PLUMBING CODE
CHAPTER 26 PLUMBING CODE 26.01 PLUMBING CODE The Illinois Plumbing Code as promulgated by the Illinois Department of Public Health at 77 Illinois Administrative Code, Part 890, is hereby adopted as the
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
REVISED AGENDA UNIFORM BUILDING CODE COMMISSION PLUMBING /HEAL TH ADVISORY COMMITTEE
REVISED AGENDA UNIFORM BUILDING CODE COMMISSION PLUMBING /HEAL TH ADVISORY COMMITTEE February 5, 2015 9:30 AM Heber M Wells Bldg Room475 160 E 300 S Salt Lake City, UT This agenda is subject to change
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
Georgia State Amendments to the International Plumbing Code
Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Planning and Environmental Management Division 60 Executive Park South, N.E. Atlanta,
Backflow Bulletin #1
Backflow Bulletin #1 FIRE PROTECTION SYSTEMS Chemicals in the System Anti-Freeze, Foam, Corrosion Inhibitors, etc. Chemicals in the System Glycerin Glycerin or similar food-grade non-toxic additive Siamese
Fats, Oil and Grease Program Kit
Fats, Oil and Grease Program Kit Rochester, MN Water Reclamation Plant 2015 COMPLIANCE, REQUIREMENTS AND BEST MANAGEMENT PRACTICES FOR FOG CONTROL AT FOOD SERVICE ESTABLISHMENTS P a g e 0 Table of Contents
Compliance Department
Compliance Department Compliance Checklist Inspection Checklist Installation Checklist Inspector:... Establishment:... Signature:... Address:... Date:... Contact Name:... Time Inspection Started:... Phone:...
Best Management Practices and Grease Control Device Maintenance for Food Service Establishment Employees
Best Management Practices and Grease Control Device Maintenance for Food Service Establishment Employees OBJECTIVE Fully understand how using kitchen Best Management Practices (BMPs) to control Fats, Oils,
INTERCEPTORS TABLE OF CONTENTS S-WD-INTER-1 0812
TABLE OF CONTENTS Pictorial Index Product Recommendations Grease Interceptors Commonly Specified Options Typical Installations Oil Interceptors Commonly Specified Options Typical Installations Sediment
NPCA WHITE PAPER DESIGN CONSIDERATIONS AND DISCUSSION OF PRECAST CONCRETE GRAVITY GREASE INTERCEPTORS
NPCA WHITE PAPER DESIGN CONSIDERATIONS AND DISCUSSION OF PRECAST CONCRETE GRAVITY GREASE INTERCEPTORS TABLE OF CONTENTS Introduction...2 Guidance & Discussion on Specifying Grease Interceptors...2 Necessity
Prevent Blockages in the Sanitary Sewer System
FATS, OILS & GREASE - BMPs The following Best Management Practices (BMPs) tables are listed below: Prevent blockages in the Sanitary Sewer System Properly Maintain Grease Traps and Interceptors to Prevent
31. ECO-INFO -- SEPTIC SAFE PROTECT YOUR HEALTH AND ENVIRONMENT YOUR SEPTIC PUMP-OUT SYSTEM with SELF ASSESSMENT TROUBLE SHOOTING GUIDE
31. ECO-INFO -- SEPTIC SAFE PROTECT YOUR HEALTH AND ENVIRONMENT YOUR SEPTIC PUMP-OUT SYSTEM with SELF ASSESSMENT TROUBLE SHOOTING GUIDE Edited 21/12/01 Wyong Shire Council has many non sewered areas that
BEST ENVIRONMENTAL MANGEMENT PRACTICES
Learn how to prevent pollution, maintain a grease interceptor, minimize waste, and protect your sewer lateral by following these. BEST ENVIRONMENTAL MANGEMENT PRACTICES For FOOD SERVICE FACILITIES This
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 10 - TRAPS AND INTERCEPTORS 1 2 1/AC AC SS SS/CC 1 2 3 4
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 10 - TRAPS AND INTERCEPTORS Adopting Agency BSC SFM HCD DSA OSHPD CSA DPH AGR DWR CA 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt Entire Chapter X X X Adopt
Fats, Oil, and Grease Best Management Practices Manual. Pollution Prevention and Compliance Information for Publicly-Owned Treatment Plants
Fats, Oil, and Grease Best Management Practices Manual Pollution Prevention and Compliance Information for Publicly-Owned Treatment Plants Acknowledgements The manual was produced by Brown and Caldwell
MIFAB INTERCEPTOR SELECTION GUIDE
MIFB INTERCEPTOR SELECTION GUIDE There are three main types of interceptors: grease, oil and solids. Each of them requires different considerations for sizing, operation and maintenance. The information
Plumbing. Helpful Hints Residential Construction. Lincoln County. Bert Polk Plumbing Inspector
Plumbing Helpful Hints Residential Construction Bert Polk Plumbing Inspector Lincoln County 2015 Waste and vent fittings Vent 90 medium 90 long 90 1/16 bend,1/8 bend,1/6 bend, medium 90 san tee combination
CHAPTER 11 STORM DRAINAGE
CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be
Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code. Table of Contents
Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage Policy Statements Table of Contents Chapter 2 Definitions
Grease 101. Why is Grease a Problem?
Grease 101 Grease is hydrophobic, meaning it floats on top of water, and adheres to other material such a sewer pipes. All too often, grease is washed into the plumbing system, usually through the kitchen
DRAIN, WASTE AND VENT PLUMBING
Flow of waste in a drain system Solid and liquid waste flows in vertical pipes much differently than it does in horizontal systems. In near horizontal pipes we talked about maintaining the slope of the
City of Clare Grease and Sand Interceptor Policy
City of Clare Grease and Sand Interceptor Policy A. Purpose It is the duty of the City of Clare to prevent the excessive introduction of grease, oil and sand into the sewer system and wastewater treatment
CHAPTER 9 VENTS TRANSPORTATION OF SEWER GAS
PlumbingCode06_ch09 5/29/06 8:16 AM Page 1 CHAPTER 9 VENTS Most people don t think much about vents when they consider the plumbing in their home or office, but vents play a vital role in the scheme of
General Information on Starting a Restaurant Business in Alabama
General Information on Starting a Restaurant Business in Alabama This information is intended to give a general idea and overview of Health Department construction requirements for starting a retail food
PLUMBING. For HOME OWNERS
PLUMBIG For HOM OR If your property is located in the ational cenic rea, the Columbia River Gorge IRODUCIO Commission requires you to comply with all ational cenic rea regulations. hey can be contacted
Does Part of My Basement Floor Have to Be Removed to Install. Where Does the Water from the Sump Pump Go?...Page 5
PROTECTIVE PLUMBING - WHAT IS IT? TABLE OF CONTENTS Protective Plumbing What is it?...page 1 What is Foundation Drainage?...Page 2 What is a Sump Pumping System?...Page 4 Does Part of My Basement Floor
INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville
Bellevue Bothell Burien Issaquah Kenmore Kirkland INSPECTION CHECKLIST Residential Plumbing Rough In April 2011 Mercer Island Mill Creek Sammamish Snohomish County Snoqualmie Woodinville 2009 Codes This
1.2 How Does FOG Affect You?. 2 1.3 The City of Huntington Beach FOG Control Program.. 2
Contents SECTION 1.0 What is FOG?.... 2 1.2 How Does FOG Affect You?. 2 1.3 The City of Huntington Beach FOG Control Program.. 2 SECTION 2.0 HOW TO ACHIEVE COMPLIANCE WITH THE FOOD SERVICE ESTABLISMENT
CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY
Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary
Georgia State Amendments to the International Plumbing Code
Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Local Government Assistance Division 60 Executive Park South, N.E. Atlanta, Georgia 30329-2231
SOUTH CAROLINA. Downloaded January 2011
SOUTH CAROLINA Downloaded January 2011 1401. General (II) B. When meals are catered to a facility, such meals shall be obtained from a meal service establishment graded by the Department, pursuant to R.61
Disposal of Fats, Oils, Grease and Food Waste Best Management Practice for Catering Outlets
Disposal of Fats, Oils, Grease and Food Waste Best Management Practice for Catering Outlets Working in partnership with: Blank inside front cover page Best Management Practice for Catering Outlets Fat,
NOTABLE CHANGES TO THE PLUMBING SECTION OF THE BUILDING CODE* EFFECTIVE DECEMBER 31, 2014
NOTABLE CHANGES TO THE PLUMBING SECTION OF THE BUILDING CODE* EFFECTIVE DECEMBER 31, 2014 Purpose and Legislative intent: This local law implements section 28-601.1 of the administrative code, which requires
INTERNATIONAL RESIDENTIAL PLUMBING CODE
INTERNATIONAL RESIDENTIAL PLUMBING CODE RP2-06/07 P2705.1 Proponent: Guy Tomberlin, Fairfax County, Virginia, representing Virginia Plumbing and Mechanical Revise as follows: P2705.1General. The installation
2014 Oregon Plumbing Specialty Code New Oregon Amendments
2014 OPSC Oregon Amendments Effective October 1, 2014 2014 Oregon Plumbing Specialty Code New Oregon Amendments This document outlines all the new Oregon Amendments adopted during the code promulgation
Fats, Oils, and Grease Best Management Practices Manual
Fats, Oils, and Grease Best Management Practices Manual Information, Pollution Prevention and Compliance Information For Food and Beverage Establishments 1 Contact Information: Mendocino City Community
City of Green Bay Department of Public Works Engineering Department
City of Green Bay Department of Public Works Engineering Department The Difference Between Sanitary & Storm Sewers Contact Information: Department of Public Works City Hall 100 North Jefferson Street,
Montgomery County Health Department Mobile Food Guidelines. Definitions
Montgomery County Health Department Mobile Food Guidelines Definitions Commissary A permitted food establishment to which a mobile unit returns on a daily basis for such tasks as discarding liquid and/or
Basic Principles for Sizing Grease Interceptors
Basic Principles for Sizing Grease Interceptors Grease Interceptor is an overall term. It is a product category much like faucet. I am sure you can think of several types of faucets like, kitchen, bath
Division A. Compliance, Objectives and Functional Statements
Division A Compliance, Objectives and Functional Statements British Columbia Plumbing Code 2012 Division A Part 1 Part 1 Compliance Section 1.1 General 1.1.1. Application of this Code... 5 1.1.2. Internal
FOOD SERVICE FACILITIES Best Management Practices Stormwater Management Program City of Bluff City P.O. Box 70, Bluff City, TN 37618 423-538-7144
FOOD SERVICE FACILITIES Best Management Practices Stormwater Management Program City of Bluff City P.O. Box 70, Bluff City, TN 37618 423-538-7144 This document may be printed and used for reference by
This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink.
1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. The unit will start automatically. Please pay particular
Bio-Clean. for Septic Systems. Tips for Using Bio-Clean. Page Index METRIC CONVERSIONS
Bio-Clean for Septic Systems METRIC CONVERSIONS 1 tablespoon = 15ml 1/4 cup = 57 ml 1/3 cup = 76 ml 1/2 cup = 114 ml 1 pint = 1/2 litre 1 quart = 1 litre 1/2 gallon = 2 litres 1 gallon = 4 litres 1 pound
Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 [email protected]
Dominic i Barbato Dpt. Of Building and Safety (818) 374 4361 [email protected] b 2011 Los Angeles Plumbing Code LAPC changes from 2008 2011 Los Angeles Plumbing Code Consists of the following:
When Should Examination Preparation Begin?
Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing
Why Do I Have Sewer Smells In My Home or Business?
Why Do I Have Sewer Smells In My Home or Business? Before we discuss why you may be getting smells through your drain pipes, lets first take a look at how your plumbing is supposed to work. Properly constructed
STEPS NECESSARY FOR APPROVAL TO OPERATE A FOOD SERVICE ESTABLISHMENT
STEPS NECESSARY FOR APPROVAL TO OPERATE A FOOD SERVICE ESTABLISHMENT 1. Submit completed application to this office at least 21 days prior to commencing operation. The application will NOT be considered
Sanitary Waste & Vent TS 100 1 1 Friday 9:00am 12:00pm Peter Kraut PE
Sanitary Waste & Vent TS 100 1 1 Friday 9:00am 12:00pm Peter Kraut PE Waste & Vent Part 1 October 28, 2011 9:00 10:30 AM Peter A. Kraut, P.E. B.S. Architectural Engineering Technology Wentworth Institute
Department of Public Utilities. Information for Property Owners & Residents about Sewer Backup Incidents. September 2014.
Department of Public Utilities Information for Property Owners & Residents about Sewer Backup Incidents September 2014 Page 1 of 6 General Information The City of New Bern Utilities Department makes a
15. Design of plumbing systems for industrial and temporary applications
15. Design of plumbing systems for industrial and temporary applications 15.1 Backflow prevention in industrial, commercial and institutional water systems Any water piping installation where there is