1 INNOVATIVE BUILDING AND ARCHITECTURE CONSULTANTS Mr. Bud Hall Senior Vice President of construction Turnberry Associates Biscayne Boulevard, Suite 400 Aventura, FL Subject: The Nashville Hilton Downtown Dear Mr. Hall: In accordance with our agreement, IBA Consultants, Inc. has reviewed the observations and recommendations included in Williamson and Associates Report of Building Exterior Condition Evaluation, dated January 2 nd 2013 for the exterior walls, glass and glazing and roof areas of the aforementioned project and we offer the following recommendations for remediation. Referenced Documents: Williamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, (68 pages) On pages 13 thru 15 of Williamson and Associate s report, conclusions and recommendations are provided for exterior wall, glass and glazing and roofing systems and summarized in line items 1 thru 9 on page 15 as follows: SUMMARY OF RECOMMENDATIONS (by Williamson and Associates): 1.) Repair EIFS (cracks, sealant, missing sealant, cleaning and apply elastomeric coating). 2.) Masonry (Repair cracks, deteriorated mortar, seal penetrations, and apply elastomeric coating). 3.) Barrier Precast (route and seal cracks, inspect and replaced failed joints). 4.) Granite (Inspect to verify sealant behind panel at precast to concrete knee wall, provide silicone sealed joints, provide weeps). 5.) Stucco (check for leakage, seal reveals, and apply elastomeric coating 6.) Windows (repair wet glazing and perimeter sealant, verify weeps are present and working. 7.) Skylights (Coordinate with Structural Engineer and Skylight Engineer).
2 Page 2 of 6 8.) Roofs (replace roofing, provide new coping, check overflow heights, install overflows, maintain roof, and consider replacement of remaining roofs years ) Retaining Wall (repair spalled and deteriorated concrete, obtain recommendations from Structural Engineer) IBA s Repair Recommendations based on Observations and Recommendations specified in Williamson and Associates Report referenced above: 1. Exterior Insulation Finish System (EIFS) Repair A. IBA concurs that any/all cracks, holes or other breaches in the exterior base and finish coats of the EIFS could permit uncontrolled water leakage to building interior if not repaired. Further, we agree all perimeter sealant work should be repaired at all locations where discontinuities (i.e.: voids, gaps, etc.) exist, or where cohesion /adhesion failure of the sealant has occurred during the in service life of the building. B. Repair all cracks, small holes, impact damage or other imperfections that exist in the base and exterior finish coats of the EIFS in strict accordance with dryvit CARE EIFS Repair Procedures (DS498) provided in Appendix D of this report. C. Repair and /or replace all sealant deficiencies with Dow 790 silicone sealant in strict compliance with Dow Corning Installation Recommendations and Dow Corning EIFS Restoration Guide provided in Appendix F and A of this report. D. After completion of EIFS and Sealant repairs, we recommend coating the EIFS with Dow Corning AllGuard Silicone Elastomeric coating for added protection against uncontrolled air and water leakage. E. During the EIFS remediation the Curtainwall window sill flashings will need to be addressed. Per the Williamson report, they will need to be removed and reworked to promote weeping of the curtainwall system. Based on Williams observations, the curtainwall and window assemblies have been wet sealed on the exterior eliminating the requirement for the systems to weep. IBA recommends further investigation of this condition to determine a proper course of action.
3 Page 3 of 6 2. Masonry/CMU Repair A. IBA concurs that a single wythe CMU wall system could permit uncontrolled water leakage to building interior thru any unsealed cracks, deteriorated mortar joints, or penetrations that exist in the exterior surface of the wall assembly. B. We recommend all existing deteriorated mortar joints be repaired or replaced in accordance with American Concrete Institute (ACI) guidelines. C. We recommend all penetrations in the exterior surface of the CMU wall be sealed with Dow 790 silicone sealant. After completion of required joint and sealant repairs, we recommend application of Dow Corning Elastomeric coating over the exterior surface of the CMU wall to provide a watertight assembly. Clean, prepare the CMU wall substrate and apply the elastomeric coating in strict compliance with manufacturers recommendations. 3. Barrier Precast and Granite Repair A. IBA concurs that the precast concrete panel system should be inspected for cracks and evidence of sealant failure at perimeter joinery. B. Route and seal cracks, and replace all defective sealant joints with Dow 790 silicone sealant. Clean, prepare concrete substrates and install sealant in strict compliance with manufacturers recommendations. Good crack repair techniques depend on understanding the cause of the cracking experienced and selecting the appropriate repair procedure that takes the cause into account. Otherwise, the repair may be temporary. We suggest further investigation be performed to verify that the cause of the cracking is not attributed to a structural issue that could require a more in depth repair procedure. Refer to the American Concrete institute publication ACI 224.R-07 Cause, Evaluation, and Repair of Cracks in Concrete Structures provided in Appendix E of this report. C. Repair and replace broken granite panels at the base of the precast wall. Inspect and verify joint formed between the base of the precast concrete panel and the concrete knee wall is properly sealed with silicone sealant to ensure water tightness. Install or repair existing sealant joint as required with Dow 790 silicone sealant per sealant manufacturer s recommendations. Seal joint formed between granite and concrete knee wall and provide weeps to drain water penetration experienced thru the granite veneer to the building exterior.
4 Page 4 of 6 4. Stucco A. IBA believes that further investigation is required to determine the source of the suspected water intrusion at this location in order to determine an appropriate plan for remediation. The detailed assessment should include forensic water testing in an attempt to determine the source of water intrusion, if any. B. If determined water leakage is occurring the stucco veneer, than we agree converting the stucco system to a barrier type system would be appropriate. Seal all reveals with Dow 790 silicone sealant and apply Dow Allguard elastomeric coating to prevent water infiltration. Install in strict compliance with manufacturers recommendations. 5. Windows/ Curtain wall Repair A. IBA recommends all glass to metal to metal to metal wet seals be inspected for proper joint design, adhesion loss, cohesive failure or discontinuities/voids in the existing sealant work. Any breaches/penetrations that exist in the surface applied wet seals could cause uncontrolled water leakage to the building interior. B. Repair or replace all glass to glass and glass to metal sealant deemed to be deficient with Dow 795 silicone applied in strict accordance with sealant manufacturers recommendations. Note: In the summary of recommendations included in the Williamson report, it states verify weeps are present and working. Further, Williamson adds weeps must be provided to prevent premature glazing unit failure. IBA disagrees with this statement, being that the system is wet sealed preventing air and wind driven water from infiltrating the system, thus eliminating the need for weeps. We recommend all exterior glass to metal, metal to metal joinery and all weep holes be sealed to prevent air and water intrusion into the glass and glazing system. C. Inspect and repair all perimeter sealant applications. IBA recommends Dow Corning 790 Silicone be used for these applications. Install in strict compliance with manufacturers recommendations.
5 Page 5 of 6 6. Roofing A. IBA has been informed that the roofs are slated for replacement. The following items should be addressed during the replacement: 1. Wind load calculations will be required to determine an appropriate roof assembly. Wind uplift pressures need to be confirmed before a roof system can be determined. 2. Secondary overflow provisions are required by use of secondary drains or scuppers. These are currently noted as missing by Williamson in some locations and possibly installed in the wrong elevation at other locations. 7. Site Retaining Wall Repairs A. Further evaluation is required to determine the extent of the spalled concrete. Structural Engineer to review and provide appropriate repair procedure. Per Williamson, the sidewalk should also be replaced. Follow the industry standards set forth by the American Concrete Institute when implementing these repairs. Reference Documents included separate from this report Appendix A: Dryvit EIFS repair Procedures Appendix B: Dow Corning Allguard Product data Appendix C: Dow Corning Allguard Application and Maintenance Guide Appendix D: Dow Corning EIFS Restoration Guide Appendix E: Dow Corning 790 Silicone Sealant Product data Appendix F: ACI 224.R-07 Cause, Evaluation, and Repair of Cracks in Concrete Structures Appendix G: Dow Corning 795 Silicone Sealant Product data
6 Page 6 of 6 Please call me should you have any questions or concerns regarding the above information. Respectfully Submitted, Reviewed by, Michael Presciti Director of Forensic Services IBA Consultants, Inc. Dave Becher Sr. Consultant IBA Consultants, Inc. The information contained herein has been prepared subject to the terms and conditions of an Agreement and is not intended for use by any recipient other than the party to the aforesaid Agreement. IBA Consultants, Inc. is not the Engineer or Architect of Record. Accordingly, IBA Consultants, Inc., its affiliates, agents, representatives and assigns do not make any representations or warranties of any kind, express or implied, about the completeness, accuracy, reliability, or suitability of the statements, conclusions, information, products, services, or related graphics, charts, tabulations or photographs contained herein for any purpose whatsoever other than that which is contained within the aforesaid Agreement. Any reliance that the recipient places on such information is therefore strictly at the recipients own risk. In no event will IBA Consultants, Inc., its affiliates, agents, representatives and assigns be liable for any loss or damage including without limitation, indirect or consequential loss or damage, or any loss or damage whatsoever arising from, out of, or in connection with, the use of the materials contained herein by any recipient of this information who is not a party to the aforesaid Agreement.
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
More informationFIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
More informationWater Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
More informationWATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,
More informationQuality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
More informationAssessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC pbeers@gciconsultants.com What is a Curtain Wall System? A curtain wall system is an outer covering of a building
More informationStucco Moisture Inspection Report
Stucco Moisture Inspection Report For the Property Located At: Sample Inspection St. Report Prepared Ecusively For: Potential Buyer Pace FL. 32571 >< 850.393.6106 >< ofc- 850-941-8600 > Email: pat@moistureconsultantsinc.com
More informationStructural Assessment Report
Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive
More information7 INNOVATIONS IN SECONDARY DRAINAGE SYSTEMS
7 INNOVATIONS IN SECONDARY DRAINAGE SYSTEMS K. F. YAROSH Dow Corning S.A., Parc Industriel-Zone C, B-7180 Seneffe, Belgium SUMMARY: This paper will review innovative internal backup secondary drainage
More informationBlock Lofts Condominiums
Block Lofts Condominiums Building Envelope Condition Assessment 747 Ralph McGill Boulevard Atlanta, Georgia Presented to: Block Lofts Condominium Home Owners Association C/o Heritage Property Management
More informationRDH Building Sciences Inc.
MAK LTR 2007 03 26 Proposal for Building Enclosure Consulting Services RDH Building Sciences Inc. 509 FAIRVIEW AVENUE N SEATTLE WA 98109-5507 TEL 206 324 2272 FAX 206 324 6339 SEA@RDHBE.COM WWW.RDHBE.COM
More informationThe Ultimate in Weathersealing Versatility. Dow Corning 123 Silicone Seal
The Ultimate in Weathersealing Versatility Dow Corning 123 Silicone Seal Effective and attractive EIFS restoration When urethane sealants fail on EIFS-clad buildings, leaks and interior damage typically
More informationEAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
More informationRoof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
More informationSECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
More informationWhen dealing with a potential moisture problem, time is of the essence. Taking a proactive approach will save you money and headaches down the road.
If you own a house clad in something known as exterior insulated finish systems (EIFS), also known as synthetic stucco, you are probably trying to cope with a small but growing feeling of anxiety. You
More informationTITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
More informationWaterproofing Problems: A Simple Explanation, A Simple Solution
Waterproofing Problems: A Simple Explanation, A Simple Solution The purpose of this paper is to point out the underlying causes of waterproofing problems and simple means of preventing them. Such problems
More informationTEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
More informationPELLA 350 SERIES VINYL WINDOW & PATIO DOOR LIMITED WARRANTY
PELLA 350 SERIES VINYL WINDOW & PATIO DOOR LIMITED WARRANTY IMPORTANT NOTICE: Read this entire Pella Limited Warranty and Limitation of Liability ( Limited Warranty ) before purchasing or installing this
More informationJOSEPH P. SOLINSKI. Membership affiliations and committee board standings are maintained with the following industry organizations:
JOSEPH P. SOLINSKI Page 1 of 5 SUMMARY Diversified experience within the Curtain Wall Industry has provided a complete spectrum of background and training. Mr. Solinski s more than 29 years of experience
More informationWarranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
More informationFinegan Inspection Services, Inc.
Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY
More informationSeptember 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
More informationInstaller Training and Certification Overview
Installer Training and Certification Overview Outline of This Presentation The Need for a Training Program The History of the Program Details of the Training Program The Certification Process The Need
More informationNew Construction Stud Frame Vinyl Window Installation Guide
New Construction Stud Frame Vinyl Window Installation Guide This manual contains procedures based on ASTM E2112 and Installation Masters Installer Training & Certification Program Manual RLC-1 The procedures
More informationClaim No.: DOCUMENT TYPE: INVEST ENGINEERING REPORT Date of Loss: October 29, 2012. 384 Ocean Avenue Long Branch, NJ
January 9, 2013 Mr. Richard Swink National General Adjuster York SLA 5501 LBJ Freeway, Suite 375 Dallas, Texas 75240 Email: rswink@swinkinsurance.com Tel: 214/673-4148 (M) RE: Claim No.: TBD DOCUMENT TYPE:
More informationTEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
More informationSun Vinyl New Construction Windows Homeowner's Warranty
Sun Windows Sun Vinyl New Construction Windows Homeowner's Warranty Vinyl Sun Windows, Inc. warrants for a period of 2 years that the quality of workmanship and materials of vinyl items shall be free from
More informationAAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure
A M E R I C A N A R C H I T E C T U R A L AAMA 2400-10 Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure M A N U F A C T U
More informationADDENDUM NO. 2. DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015
ADDENDUM NO. 2 DATE: September 14, 2015 INVITATION FOR BID: IFB J160004535 Fire Station #22 Roof Replacement Project DATED: August 25, 2015 RECEIPT DATE: September 30, 2015 (CHANGED) OPENING DATE: October
More informationWe urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
More informationDecember 24, 2008. twalker@sedaconstruction.com. SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216
December 24, 2008 twalker@sedaconstruction.com SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216 RE: Georgetown Community 2C - Revised Assessment Date: October
More informationNRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
More informationcontinuing professional education. As such, it construed to be an approval or endorsement by
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any
More informationJANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition
More informationStandard Method for Sampling and Analysis of. of Chlorine Containing Bleaches. Soap Products
GUIDE SPECIFICATION FOR GENERAL CLEANING AND REMOVAL OF MOLD AND MILDEW ON EXTERIOR INSULATED AND FINISH SYSTEMS AND STUCCO DIVISION 07240 and DIVISION 09240 8/05 PART I: GENERAL 1.01 DESCRIPTION AND SCOPE
More informationROOF INSPECTION & MAINTENANCE
Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long
More informationCommercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
More informationAvoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
More information2008-2009 Cost Comparisons for Common Commercial Wall Systems
An Independent Study LA MS KY TN AL GA SC NC FL 2008-2009 Cost Comparisons for Common Commercial Systems CAPITAL BUILDING CONSULTANTS PROFESSIONAL CONSTRUCTION ESTIMATORS 2008 2009 INDEPENDENT COST COMPARISONS
More information10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005
10DBMC International Conference On Durability of Building Materials and Components Wall Cladding System Durability Lessons Learned from the Premature Deterioration of Wood-Framed Construction Clad with
More informationCase Studies of the Cause and Origin of Fungal Growth in Residential and Commercial Structures
Case Studies of the Cause and Origin of Fungal Growth in Residential and Commercial Structures Stewart M. Verhulst, M.S., P.E. 1 Erik L. Nelson, Ph.D., P.E., M.ASCE 2 Deepak Ahuja, M.S., P.E.,M.ASCE 3
More informationIssue of the Guidelines on Prevention of Water Seepage in New Buildings
graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural
More informationWATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION
WATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION for Florida Concrete & Products Association and NCMA Education and Research Foundation Conducted by: Masonry Information Technologists
More informationSELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide
SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER
More informationCommercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
More informationSECTION 3 ONM & J STRUCTURAL ANALYSIS
Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION
More informationPELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007
PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT November 2007 PURPOSE OF INVESTIGATION Determine possible locations of moisture intrusion into and through facade. Determine cause of horizontal and vertical
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationMortar Glass Block Installation System
Mortar Glass Block Installation System Pittsburgh Corning Mortar Glass Block Installation System Assembly Instructions Introduction: The Mortar I System utilizes Pittsburgh Corning perimeter channels on
More informationMario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract
Commissioning of Exterior Building Envelopes of Large Buildings for Air Leakage and Resultant Moisture Accumulation using Infrared Thermography and Other Diagnostic Tools Mario D. Gonçalves, Patenaude-Trempe
More informationTHERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS
THERMOTEK SELF ADHESIVE MEMBRANE +G OVER DESCRIPTION SELF ADHESIVE OVER (8YR) BS-SA/CS 1 0 No 0. SUBSTRATE 1. BASE SHEET G FIBER GLASS BASE. THERMOTEK SELF ADHESIVE 3.0 FP GRANULE COMPONENTS AND WEIGHTS
More informationRoof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
More informationINSTALLATION INSTRUCTION - INSTRUCCIONES DE INSTALACION FOR DOUBLE-HUNG VENT REPLACEMENT WINDOW
Vinyl Windows and Doors Manufactured by Pella Corporation INSTALLATION INSTRUCTION - INSTRUCCIONES DE INSTALACION FOR DOUBLE-HUNG VENT REPLACEMENT WINDOW Lea las instrucciones en español en el reverso.
More information3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations
3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations Any penetration through the stucco that is left unsealed will allow entry of moisture. Even an average size home can have an extreme
More informationThe Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage Sam Hagerman, Hammer and Hand Sam@HammerandHand.com Florian Speier, Zola Windows Florian@ZolaWindows.com Paul Grahovac,
More informationSpringlok Flashing System
Springlok Flashing System Why Fry Reglet? Fry Reglet s comprehensive selection of moisture prevention products offer the ultimate in protection from the elements. Available nationwide in a variety of materials
More information201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE
STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,
More informationSchool Construction Authority Architecture & Engineering
SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following
More informationArchitectural Testing
FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard
More informationStuccoSpec Moisture Testing Inspection
e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012
More informationReplacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product
More information2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award George Washington University Ross Hall Façade Restoration
2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award George Washington University Ross Hall Façade Restoration 2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award
More informationNatatorium Building Enclosure Deterioration Due to Moisture Migration
Buildings 2012, 2, 534-541; doi:10.3390/buildings2040534 OPEN ACCESS buildings ISSN 2075-5309 www.mdpi.com/journal/buildings/ Case Study Natatorium Building Enclosure Deterioration Due to Moisture Migration
More informationPART E SPECIFICATIONS
PART E SPECIFICATIONS Page 1 of 5 PART E - SPECIFICATIONS GENERAL E1. APPLICABLE SPECIFICATIONS, STANDARD DETAILS AND DRAWINGS E1.1 The City of Winnipeg Works and Operations Division Standard Construction
More informationBuilding Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More information1 RCNY 101-14 CHAPTER 100. (b) References. See Administrative Code sections 28-105.1, 28-105.4, item 6 and 28-105.4.2.1.
1 RCNY 101-14 CHAPTER 100 Subchapter A Administration 101-14 Categories of work that may or may not require a permit. (a) Scope. This rule establishes categories of work that may be classified as a minor
More informationExterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
More informationImportant Information for Installer & Homeowner
Important Information for Installer & Homeowner Homeowner: Please keep this information for your records, do not discard! Installation Instructions for Wood Frame Construction Replacement (See other side
More informationSTRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA
STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael
More informationSpandrel Glass Types and Recommendations
Spandrel Glass Types and Recommendations Introduction PPG has long offered recommendations regarding alternatives for glass spandrel applications. Over the years these recommendations were included in
More informationThe existing roof angle change terminations and flashings when sound and intact can be reused.
January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing
More informationINNOVATIVE. ADAPTABLE. ENERGY EFFICIENT.
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT. awipanels.com From freezing, sub-zero temperatures to Contents dry heat or high humidity, Mother Nature continually tests the limits of building envelopes. That's
More informationCity of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
More informationStucco Failures and Remediation
BEST2 Case Studies Session WB4-1 Stucco Failures and Remediation Roger G. Morse AIA, and Paul E. Haas CSP, CIH ABSTRACT Stucco over a single wythe of concrete block is widely used as wall construction
More information7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME
7. Installation Window involves the fixing of window frame at an earlier construction stage and subsequent of the window sashes. This is a highly workmanship dependent process. Only trained and approved
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design
Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)
More informationFIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
More informationExterior Repair Project. By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek. Building Technology Consultants, PC BTC
Exterior Repair Project Glen Ellyn Public Library By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek Outline 2010 and 2011 Roof Replacement and Facade Repair Project Review Primary Reasons for
More informationInstallation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read
More informationPERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
More informationHEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationINSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
More informationMeasure Guideline: Water Management at Tub and Shower Assemblies
Measure Guideline: Water Management at Tub and Shower Assemblies Bruce Dickson IBACOS, Inc. December 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the United States
More informationAir-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
More informationPERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
More informationThe Harold J. Becker Company, Inc.
The Harold J. Becker Company, Inc. It is the mission of The Harold J. Becker Company, Inc. to deliver the absolute best possible quality product at the most efficient cost to our clients, while providing
More informationVer. 2. Guide to. Inspecting Residential Brick Veneer
Ver. 2 Guide to Inspecting Residential Brick Veneer 1. A guide created by industry professionals. The knowledgeable staff at MASONPRO together with technical support from the Masonry Institute of Michigan
More informationEvaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
More informationDow Corning AllGuard Silicone Elastomeric Coating. Application and Maintenance Guide
Dow Corning AllGuard Silicone Elastomeric Coating Application and Maintenance Guide Contents This document is intended to provide installation and field testing instructions for Dow Corning AllGuard Silicone
More informationPRE INSTALLATION MANUAL
REINFORCED CONCRETE PIPE PRE INSTALLATION INSPECTION & REPAIR MANUAL Kentucky Transportation Cabinet Kentucky Department of Highways Division of Materials 1227 Wilkinson Boulevard Frankfort, KY 40601 (502)
More informationReference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls
Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto
More informationMetropolitan Builders Association Masonry & Concrete Standard
Metropolitan Builders Association Masonry & Concrete Standard Background Masonry and concrete work in residential construction often provides the base structure upon which the house is built or as a veneer.
More informationTHERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS
OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV
More informationBetter Budgeting: Roof Management Plans Help Estimate Costs
Better Budgeting: Roof Management Plans Help Estimate Costs Inside ASHE Summer 2015 Depending upon the complexity of a hospital roof, the average cost for a replacement roof can range from $15 to $40 per
More informationAnalysis II Façade Redesign: Architectural Precast Panels
Analysis II Façade Redesign: Architectural Precast Panels Analysis II Façade Redesign: Architectural Precast Panels Overview: This analysis covers the comparison of the current EIFS façade and my proposed
More informationfoot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
More informationCZAR Engineering, L.L.C.
CZAR Engineering, L.L.C. Lamont H. Czar, P.E. Phone: (609) 653-9445 5014 Fernwood Avenue Fax:(609)653-2015 Egg Harbor Township, New Jersey 08234 www.czarengineering.com May 3, 2013 Craig Dothe, Architect
More informationGeorgia State University. Urban Life Building Roof Replacement
ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT
More information