- Views:
Transcription
1
2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services may be addressed at the conclusion of this presentation.
3 This presentation is protected by U.S. and International copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is prohibited. American Architectural American Architectural Manufacturers Association 2010
4 Comparison of the AAMA/WDMA/CSA 101/I.S.2/A lab test (referred to as NAFS-08) to the AAMA 502 quality assurance field test and the AAMA 511 forensic evaluation Determination of appropriate water test pressures, test durations and water applications via NAFS-08, AAMA , and How to specify project-specific p quality assurance field testing The proper use of AAMA 511 for forensic The proper use of AAMA 511 for forensic evaluations
5 NAFS-08 Lab Testing Performed on prototype specimen to validate product performance ratings Intro oduc ction 502 Quality Assurance Field Testing Performed on newly installed products to verify installed performance of the product and the installation 511 Forensic Testing Performed on wall assemblies with known water control problems as a means to accurately identify suspect wall construction components and details
6 NAFS Overview
7 iew verv FS Ov NAF Utilizes ASTM E 547 and/or E 331 for test methodology Test is performed under controlled environmental conditions Test sample is installed strictly per the manufacturer s instructions in a precise test buck opening
8 NAF FS Ov verv iew Conversion as per NAFS-08 15% for R, LC, CW 20% for AW Water Resistance Test Pressure is capped at psf for the U.S. and psf for Canada Gateway Requirements Performance Minimum i Minimumi Minimumi Class Design Structural test Water Pressure, Pa pressure, Pa Resistance (psf) (psf) Test Pressure, Pa (psf) R LC CW AW
9 6.00 PSF (~50 mph) Equivalent hydrostatic water head 1.16 NAFS Overview
10 7.50 PSF (~55 mph) Equivalent hydrostatic water head 1.44 NAFS Overview
11 AAMA AAMA 502
12 AAMA Original publication by AAMA AAMA Added reference to AAMA accredited laboratory and first introduced the 1/3 WTP reduction for water resistance testing of installed products AAM MA 502 AAMA Defined newly installed as prior to issuance of the occupancy permit not to exceed 6 months after installation of the fenestration product.
13 ASTM E 783 Field Measurement of Air Leakage through Installed Exterior Windows and Doors AAM MA 502 ASTM E 1105 Field Determination of Water Penetration of Installed Exterior Windows, Curtain Walls and Doors by Uniform or Cyclic Static Air Pressure Difference
14 Requires testing agency to report and make adjustments for ambient conditions. In some cases, temporary enclosures are required to reduce adverse effects of wind and temperature at the project site. 502 MA 5 AAM
15 The default air leakage for quality assurance field testing is 1.5 times the applicable laboratory standard d for the product type and performance class 502 MA 5 AAM
16 TO OUTSIDE BAROMETRIC PRESSURE ALTERNATE TEST CHAMBER PRESSURE MEASURING DEVICE TEST CHAMBER EXHAUST VALVE AAM MA 502 PRESSURE GAUGE VALVE CALIBRATED WATER SPRAY RACK W THE CHAMBER SHALL NOT BE PERMITTED TO MAKE ANY CONTACT WITH THE FENESTRATION PRODUCT AIR SYSTEM INNERMOST PLANE FOR WATER PENETRATION (REFERENCE PARAGRAPH 4.3.4) 4)
17 Requires testing agency to report and make adjustments for ambient conditions Test is performed on the entire fenestration product opening 502 MA 5 AAM
18 The test pressure shall not be less than 91Pa(19psf) ( MA 5 AAM Tests shall be conducted at a static test pressure equal to 2/3 of the tested and rated laboratory performance per AAMA/WDMA/CSA 101/I.S. 2/A440
19 AAM MA Newly installed fenestration product(s) shall be field tested in accordance with AAMA 502, "Voluntary Specification for Field Testing of Newly Installed Fenestration Products." 2. Test three (unless otherwise specified) of the fenestration product specimens after the products have been completely installed for air leakage resistance and water penetration resistance as specified. 3. Air leakage resistance tests shall be conducted at a uniform static test pressure of Pa ( psf). The maximum allowable rate of air leakage shall not exceed L/s m2 ( cfm/ft2) 4. Water penetration resistance tests shall be conducted at a static test pressure of Pa ( psf). No water penetration shall occur as defined in Section of AAMA 502
20 1/3 reduction to the laboratory rating of the WTP is the default Sill Dam test is removed from 502 and moved to the 511 document 502 MA 5 AAM
21 Method A Product only testing has been eliminated from the and moved to AAMA MA 5 AAM If the source of the water cannot be determined, a forensic evaluation using the procedures outlined in AAMA 511 shall be performed
22 AAMA AAMA 503
23 AAM MA 503 AAMA 503 was originally published in 1992 AAMA 503 is a similar document to AAMA 502 for Storefronts, Curtain Walls & Sloped Glazing Systems. Updated in 2003 & 2008 AAMA Defined newly installed as prior to issuance of the occupancy permit not to exceed 6 months after issuance of the occupancy permit.
24 AAMA 503
25 Storefronts Curtain Wall Sloped Glazing AAMA 503
26 503 MA 5 AAM Curtain Wall Chamber Arrangement
27 Storefronts Curtain Wall Sloped Glazing AAMA 503
28 Sloped Glazing Systems Chamber Arrangement 503 MA 5 AAM
29 Storefronts Curtain Wall Sloped Glazing AAMA 503
30 Forensic Investigation
31 ASTM References in AAMA 511 n Fore ensic Inve estig gatio ASTM E 2128, Standard Guide for Evaluating Water Leakage of Building Walls This guide describes methods for determining and evaluating water leakage of exterior walls. A wall is considered a system including its exterior and interior finishes, fenestration, and structural components.
32 n Fore ensic Inve estig gatio Involves more than just testing The purpose of diagnostic testing is to recreate water leaks that t are known to occur AAMA 511 testing either follows up on AAMA 502 and 503 testing or is used in a water intrusion investigation
33 n Fore ensic Inve estig gatio The ultimate goal of 511 diagnostic testing is to recreate existing leakage behavior that occurs under in-service conditions.
34 n Fore ensic Inve estig gatio Four Preliminary Steps prior to testing Review of project documents Evaluation of design concept Determination of service history Inspection Three Steps During and After Testing Investigative Testing Analysis Report
35 n Fore ensic Inve estig gatio Step #1: Review Project Documents Architectural drawings Structural drawings Shop drawings Installation instructions Contracts Purchase orders Specifications Warranties
36 n Fore ensic Inve estig gatio Step # 2: Evaluation of Design Concept Water management concept Critical details Test reports Flashing Sealants Weep Holes
37 n gatio estig c Inve ensic Fore Step # 3: Determination of Service History Review maintenance records Interview knowledgeable personnel Research leak history
38 n Fore ensic Inve estig gatio Step #4: Inspection Interior observations Exterior observations Observe workmanship Observe product deficiency Develop a hypothesis for the source of the water intrusion
39 Forensic Investigation
40 n Fore ensic Inve estig gatio Determination is based on: Field Standards Laboratory Standards Prior Testing Weather Data Experience
41 n Fore ensic Inve estig gatio Simulate the weather events Obtain wind speed If calculated wind speed is greater then 2/3 of the rated WTP for the product it may be that the product was not the most appropriate for the project. At least one pressure difference test must be done at the 2/3 pressure
42 n Fore ensic Inve estig gatio ASCE 7 accounts for: Exposure Height above grade Basic wind speed (or weather data) Location of specimen within façade
43 Forensic Investigation
44 n gatio estig c Inve ensic Fore The objective of testing is to identify the leak paths
45 Exam mple 1 MA 511- AAM Consistent leaks more than one year Heaviest leakage twice during September 2005 Class II Building height is 33 ft., window (z) is 27 ft. above ground Window is 4 high x 4 wide, wind area (A) of 16 ft 2 AAMA rating C35
46 AAMA 511 Example #1
47 Estimating the Test Pressure Exam mple MA 5 AAM ASCE/SEI 7 05 analysis is used with the following information: Location of building (Newark, NJ) Building usage designation (Class II) Exposure level (Exposure B) Building ud gdesign (enclosed structure with a flat roof ) Building height (33 ft.) Window area (16 square ft.) From these features, the water resistance test pressure is, theoretically, 2.4 psf.
48 Exam mple 1 Local weather data is analyzed by daily readings for September of 2005, allowing the investigator to observe the weather condition, amount of precipitation it ti and maximum wind speed for each day MA 511- AAM
49 AAMA 511 Example #1
50 Exam mple MA 5 AAM The maximum 5 second gust wind speeds are recorded for every day in September in which measurable rainfall occurred Date Rain Fall (in) Max Wind Speed (mph) 5-Sec. Gust 4-Sep Sep Sep
51 Exam mple MA 5 AAM Only two leak events are reported during September 2005 Average wind determined to be 34 mph Date Rain Fall (in) Max Wind Speed (mph) 5-Sec. Gust 4-Sep Sep Sep
52 Exam mple 1 MA 511- AAM Result = 2.1 psf which is the differential pressure used to evaluate the window opening in question Weather data analysis is used to determine field water penetration resistance pressure Table 3 of AAMA/WDMA/CSA 101/I.S. 2/A shows tested water penetration resistance pressure The result of the weather data analysis (2.2 psf ) is the differential pressure used to evaluate the window opening in question
53 Exam mple 2 MA 511- AAM Leak Reported during storm on September 21, 2005 Class II, Exposure C Building height is 60 ft., window (z) is 55 ft. above ground Window is 2 high x 2 wide, wind area (A) of 4 ft2 AAMA rating C35
54 Estimating the Test Pressure Exam mple MA 5 AAM ASCE/SEI 7 05 analysis is used with the following information: i Location of building (Chicago, Il) Building usage designation (Class II) Exposure level (Exposure C) Building design (enclosed structure with a flat roof ) Building height (60 ft.) Window area (4 square ft.) From these features, the water resistance test pressure is, theoretically, 3.2 psf.
55 Exam mple MA 5 AAM Referring to tabulated local weather data above, the investigator can determine and record the maximum 5 second gust speeds on the date of the reported leak Date Rain Fall (in) Max Wind Speed (mph) 5-Sec. Gust 21-Sep
56 11- Exam mple 2 AAM MA 5 52 mph can now be used in Eq from SEI/ASCE 7 05 to establish a wind pressure of psf Since specimen height is above 60 feet above grade, this wind pressure is inserted into Eq to calculate maximum test pressure Result = 8.4 psf, which is greater than the laboratory water penetration ti resistance it test tpressure of psf as prescribed for a C 35 product rating. Since calculated differential air test pressure exceeds the rated performance value for the product, investigator shall first perform at least 1 test at 2/3 of the product performance rating prior to testing at calculated pressure.
57 Interior Weep Holes Water shall cover all horizontal surfaces expected to be wet Tape applied over Exterior Weep Test Water Head measured from bottom of exterior wrap AAMA 511 Example #2
58 he Le eak reating t Recr Need to determine: How to apply water How long to run test Whether or not to include differential pressure How much air pressure How to step or phase pressure
59 Recreating the Leak
60 Recreating the Leak
61 eak reating the Le Recr How long would you test these substrates?
62 eak reating the Le Recr Which application best fulfills the objective?
63 Recreating the Leak
64 Recreating the Leak
65 eak reating the Le Recr How does differential pressure affect the test specimen?
66 eak reating the Le Recr Start with zero differential pressure then step up to higher pressures
67 Recreating the Leak
68 Recreating the Leak
69 ng t he Le eak Recr reati Start testing at lower elevations and work higher Introduce one new element at a time into each new water test Use isolation to protect features from water spray Do not turn the water off at the first moment a leak appears Try to trace the leak from the exterior to the interior and use destructive wall probes as required to identify this leak path Do not end non-leaking tests until you are confident the specimen is not contributing to leakage
70 he Le eak ng t reati Recr No or limited leak history Leak reported as window leak when leak is actually from another source Not enough water pressure Not able to achieve differential pressure Owner does not want to remove interior finishes No or limited access to concealed wall areas Inclement weather Isolation failures
71 Identifying the Source
72 Identifying the Source
73 Identifying the Source
74 Identifying the Source
75 Identifying the Source
76 Analysis s and Rep porti ng The forensic investigator has the responsibility to make every attempt to ascertain the exact path of water intrusion Conclusions are formed in this step on the basis of the inspection and testing data collected in the previous steps. If conclusions cannot be fully supported by sound scientific principles then additional investigation is needed
77 Analysis s and Rep porti ng All reports shall be self-contained documents Shall include justification for deviations from the methodology described in the standard The reports shall not include any unsubstantiated opinions or conclusions. If results are not conclusive the forensic investigator shall present options for obtaining conclusive results
78 Please take a moment to complete the evaluation form. Thank You.
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
More informationTEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
More informationFIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
More informationEvaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
More informationTEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
More informationMOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
More informationWATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,
More informationSpecifying Windows. Performance Standards
1 Specifying Windows and ddoors Using Performance Standards 2 This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed
More informationTesting Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures
Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures R. A. Van Straaten 1, G. A. Kopp 2, J. F. Straube 3 1 Research Lab for Better Homes, University of Western
More informationDuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1
Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357
More informationTEST REPORT. Report No.: B3404.01-801-47. Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95
Architectural Testing TEST REPORT Report No.: B3404.01-801-47 Rendered to: CROFT, LLC. Magnolia, Mississippi PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95 SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
More informationPERFORMANCE TEST REPORT
PERFORMANCE TEST REPORT CCLW JOB #08-5152-1 DATES OF FORMAL TESTING SEPTEMBER 19 & 23, 2008 TEST LOCATION CONSTRUCTION CONSULTING LABORATORY WEST 4751 WEST STATE STREET, SUITE B ONTARIO, CA 91762 PH: 909-591-1789
More informationAssessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC pbeers@gciconsultants.com What is a Curtain Wall System? A curtain wall system is an outer covering of a building
More informationArchitectural Testing
FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard
More informationField Water Testing - Lessons Learned
Quicklinks Lots of Questions - How About Answers Let's Start with the Specifications Test Methods VS. Performance Standard Using the Correct Test Method Conclusion About the Author Compilation of Test
More informationresist water infiltration and avoid water damage to buildings.
INTRODUCTION Uncontrolled water penetration through the building façade, exterior walls, and especially fenestrations (windows) results in billions of dollars of damage in the con struction industry every
More informationPERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INCORPORATED SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly Title Summary of Results Air Infiltration
More informationPERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration
More informationT H E A A M A C E R T I F I C A T I O N P R O G R A M
T H E A A M A C E R T I F I C A T I O N P R O G R A M AAMA STANDS FOR QUALITY Since 1962, AAMA Certification, the original third-party window performance program, has provided manufacturers with the means
More informationREPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013
REPORT NUMBER: 100900226COQ-003 ORIGINAL ISSUE DATE: July 19, 2013 TEST REPORT EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 1500 BRIGANTINE DRIVE COQUITLAM, BC V3K 7C1 CANADA RENDERED TO PHOENIX
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
More informationASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
More informationWATER TESTING MISCONCEPTIONS: F ENESTRATION PRODUCT CERTIFICATION AND FORENSIC INVESTIGATION OF BUILDING LEAKAGE
WATER TESTING MISCONCEPTIONS: F ENESTRATION PRODUCT CERTIFICATION FORENSIC INVESTIGATION OF BUILDING LEAKAGE F RANCESCO J. SPAGNA, PE; SIMPSON GUMPERTZ BRON S. BUCHBERG, PE HEGER, INC. 41 Seyon Street,
More informationInstaller Training and Certification Overview
Installer Training and Certification Overview Outline of This Presentation The Need for a Training Program The History of the Program Details of the Training Program The Certification Process The Need
More informationfoot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
More informationTable of Contents PART 1 WINDOW SELECTION GUIDE. Window and Door Selection Guide
VOLUME 1 - WINDOWS AND DOORS Window and Door Selection Guide PART 1 WINDOW SELECTION GUIDE WSG-11 PART 2 - PERFORMANCE SPECIFICATIONS Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows
More informationWilliamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, 2013. (68 pages)
INNOVATIVE BUILDING AND ARCHITECTURE CONSULTANTS Mr. Bud Hall Senior Vice President of construction Turnberry Associates 19501 Biscayne Boulevard, Suite 400 Aventura, FL 33180 Subject: The Nashville Hilton
More informationresearch highlight Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification
research highlight November 2003 Technical Series 03-125 Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification introduction Over the past decade, there has been
More informationPERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall
Architectural Testing PERFORMANCE TEST REPORT Rendered to: UNITED STATES ALUMINUM CORPORATION SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall Title Summary of Results Air Infiltration
More informationAAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY
Architectural Testing AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: EAGLE WINDOW & DOOR COMPANY SERIES/MODEL: Series 01 Axiom Clad One-Piece Casement Fixed 6060 PRODUCT TYPE: Aluminum Clad Fixed
More informationTEST REPORT. Rendered to: INTERNATIONAL WINDOW Hayward, California. PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222
Architectural Testing TEST REPORT Report No.: C2375.01-301-44 Rendered to: INTERNATIONAL WINDOW Hayward, California PRODUCT TYPE: Aluminum Hopper SERIES/MODEL: 7222 SPECIFICATIONS: AAMA/WDMA/CSA 101/I.S.2/A440-05,
More informationCity of San Diego, CWP Guidelines
PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,
More informationPERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE
PERFORMANCE EVALUATION OF THE CERAMITEX RVR SYSTEM IN ACCORDANCE WITH AAMA 508-07 FOR PRESSURE EQUALIZATION BEHAVIOR & WATER PENETRATION RESISTANCE Report to: Ceramitex Inc. 520 Clarke Rd. London, Ontario
More informationSECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: info@alpolic.com www.alpolic-northamerica.com This MANU-SPEC utilizes
More informationExterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
More informationJANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs
JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC 97909-071 085113 ALUMINUM WINDOWS Guide Specs SECTION 085113 ALUMINUM WINDOWS This suggested guide specification has been developed using the current edition
More informationMario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract
Commissioning of Exterior Building Envelopes of Large Buildings for Air Leakage and Resultant Moisture Accumulation using Infrared Thermography and Other Diagnostic Tools Mario D. Gonçalves, Patenaude-Trempe
More informationSECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
More informationPERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
More informationcan be seen in the contrast between solid masonry-wall construction
Introduction tal moisture, higher applied loads, larger pace with increased construction activity. Over the past several decades, there has deflections, and reduced water storage In the end, it seems our
More information10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005
10DBMC International Conference On Durability of Building Materials and Components Wall Cladding System Durability Lessons Learned from the Premature Deterioration of Wood-Framed Construction Clad with
More informationTEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
More informationTotal Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA
Total Building Commissioning: Case Study of the U.S. District Courthouse in Salt Lake City, Utah, USA Boggarm S. Setty, P.E., Fellow ASHRAE Setty & Associates, Ltd. 3040 Williams Drive, Suite 600, Fairfax,
More informationBECx& Building Airtightness. Presented by: Eric Amhaus Principal
BECx& Building Airtightness Presented by: Eric Amhaus Principal The Building Enclosure 2007 study: out of 17,000 construction defect claims, 69% result of moisture related defects in building enclosure
More informationBUILDING ENVELOPE COMMISSIONING FOR THE EVERYDAY COMMISSIONING AGENT
BUILDING ENVELOPE COMMISSIONING FOR THE EVERYDAY COMMISSIONING AGENT Building Envelope for the Everyday CxA Presented by: Mark F. Warren, CCP, LEED AP Senior Vice President - WSP Flack + Kurtz Anand Seth,
More informationNon Invasive Roof Leak Detection Using Infrared Thermography
Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
More informationPreventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
More informationWindow Sill Details for Effective Drainage of Water
Construction Technology Update No. 76 Window Sill Details for Effective Drainage of Water By M.A. Lacasse and M.M. Armstrong Satisfactory window performance demands a good product and proper installation.
More informationUPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS Executive Summary: There is a proposal at the Joint Committee on Administrative
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
More informationAIR-INS inc. 1320, MONTÉE STE-JULIE, VARENNES (Québec) J3X 1P8 TEL: (514) 652-0838 - FAX: (514) 652-7588
1320, MONTÉE STE-JULIE, VARENNES (Québec) J3X 1P8 TEL: (514) 652-0838 - FAX: (514) 652-7588 RESISTANCE TO WATER PENETRATION TESTING "NOVABRIK" BRICK CLADDING Prepared for: Mr. Michel Bouchard, Eng. Les
More informationSun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
More informationHow To Control Water Penetration In A Window
WATER PENETRATION CONTROL FOR WINDOWS A SERVICE LIFE APPROACH David R. Ricketts, P.Eng. 1 and Silvio Plescia, P.Eng. 2 INTRODUCTION Building envelope performance problems and their close link to poor window
More informationINSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
More informationWATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION
WATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION for Florida Concrete & Products Association and NCMA Education and Research Foundation Conducted by: Masonry Information Technologists
More informationSECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
More informationNAFS and The 2012 Building Code
NAFS and The 2012 Building Code Presented to BCBEC on 2013-04-18 Al Jaugelis B.Sc. Arch. ajaugelis@rdhbe.com NAFS changes everything... No more ABC s New concepts New terminology New rating system New
More informationA ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
More informationAppendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria
Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards
More informationAAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure
A M E R I C A N A R C H I T E C T U R A L AAMA 2400-10 Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure M A N U F A C T U
More informationThe Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage Sam Hagerman, Hammer and Hand Sam@HammerandHand.com Florian Speier, Zola Windows Florian@ZolaWindows.com Paul Grahovac,
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
Architectural Testing PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Mahogany Entry Door PRODUCT TYPE: 6' x 8' Double Outswing Hardwood TDL Door with Half Circle TDL Transom
More informationRDH Building Sciences Inc.
MAK LTR 2007 03 26 Proposal for Building Enclosure Consulting Services RDH Building Sciences Inc. 509 FAIRVIEW AVENUE N SEATTLE WA 98109-5507 TEL 206 324 2272 FAX 206 324 6339 SEA@RDHBE.COM WWW.RDHBE.COM
More information2011 Energy Efficiency Expo!
Welcome to the 2011 Energy Efficiency Expo! Thank you to our session sponsors! Comparison Between the 2009 and 2012 International Energy Conservation Code What s coming when the new commercial energy code
More informationTechniques for Finding and Documenting Moisture Intrusion in Buildings with an Infrared Imager by: R.W. Olsen & Greg Stockton
Techniques for Finding and Documenting Moisture Intrusion in Buildings with an Infrared Imager by: R.W. Olsen & Greg Stockton Abstract Moisture intrusion is a serious problem for the building owner and
More informationWindow Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
More informationHow To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
More informationImpact-Resistant Windows and Sliding Glass Doors
Impact-Resistant Windows and Sliding Glass Doors Make Your Home A SafeHarbor. SafeHarbor Impact-Resistant Windows and Sliding Glass Doors are designed to look like traditional windows and doors, but they
More informationThe Florida Building Code
Setting New Standards for Safety The Florida Building Code Florida Building Commission Florida Department of Community Affairs The Florida Building Code System The Florida Building Commission Florida Building
More informationMarch 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
More informationDESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 8 DOORS AND WINDOWS 08 50 00 WINDOWS
SECTION INCLUDES Metal Windows Vinyl/Aluminum Clad Wood Windows Solid Fiberglass and Vinyl Windows Wood Windows (Historic Preservation only) RELATED SECTIONS 02 83 00 Lead Paint Remediation 06 10 00 Rough
More informationHow To Test Water Penetration On Concrete Block And Mortar
WATER PENETRATION TEST ON CONCRETE BLOCK MASONRY Vilató, Rolando Ramirez 1 1 PhD, Prof., Mackenzie Presbyterian University, School of Engineering, São Paulo, rolandovilato@yahoo.com This paper considers
More informationIntroduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
More informationSECTION 08560 SERIES 1500 VINYL PATIO DOORS
SERIES 1500 VINYL PATIO DOORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Patio Doors 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100: Rough Carpentry. C. Section 06200: Finish
More informationCH. 2 LOADS ON BUILDINGS
CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends
More informationSeptember 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationFigure 1A. Typical brick veneer installation over wood frame construction.
Figure 1A. Typical brick veneer installation over wood frame construction. BACKGROUND In general, the description of any building, whether a high-rise or a warehouse, can be simplified into two basic components:
More informationMIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B8049.01-401-18. Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B8049.01-401-18 Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida PRODUCT TYPE: Aluminum Storefront with Double Doors SERIES/MODEL:
More informationWindows, skylights, vents, and glazed portions of doors are critical components of a building s
WINDOWS, DOORS, AND OPENING PROTECTION 10 Windows, Doors, and Opening Protection 10.1 Introduction Windows, skylights, vents, and glazed portions of doors are critical components of a building s envelope.
More informationWaterproofing Problems: A Simple Explanation, A Simple Solution
Waterproofing Problems: A Simple Explanation, A Simple Solution The purpose of this paper is to point out the underlying causes of waterproofing problems and simple means of preventing them. Such problems
More informationSECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
More informationThe replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
More informationStuccoSpec Moisture Testing Inspection
e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012
More informationSimplified Steel Stair Design for Commercial and Institutional Buildings
Simplified Steel Stair Design for Commercial and Institutional Buildings Collaborating with steel stair fabricators during the design of commercial and institutional buildings promotes integrated practice
More informationFacts on Water Intrusion. Water Intrusion Causes Major Problems Before and After Construction. July 1, 2011
Water Intrusion Causes Major Problems Before and After Construction By Scott Spiderman Mulholland CGC CDDC CMR CMA CIEC When buildings leak, the environmental, structural and long term performance can
More informationD. Mark Davis, Craddock Davis and Krause- Dallas, TX Leonard W. Woods, Jackson Walker- Austin, TX Mark H. McGivern, CCA, LLC, New York, NY
ANATOMY OF A CONSTRUCTION DEFECT CASE PRESENTERS- D. Mark Davis, Craddock Davis and Krause- Dallas, TX Leonard W. Woods, Jackson Walker- Austin, TX Mark H. McGivern, CCA, LLC, New York, NY TODAYS OBJECTIVE
More informationWeather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group
Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group Since water intrusion is among the most damaging problems
More informationClad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
More informationTEST REPORT. Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California
Architectural Testing TEST REPORT Report No.: A8865.01-301-41 Rendered to: BRISTOLITE SKYLIGHTS Santa Ana, California TYPE: Dome Assembly Only SERIES/MODEL: Nano Insulgel - ALT-CM-2-CPM/16 mm CNANO Thermally
More informationI S S U E 1/2013 VOLUME 30 NUMBER 1. Water Testing: Richard P. Kadlubowski, AIA and Courtenay Bauer
I S S U E 1/2013 VOLUME 30 NUMBER 1 Journal of architectural technology published by Hoffmann Architects, Inc., specialists in the rehabilitation of building exteriors. Water Testing: A Tool for Owners
More informationAST M F 1642-04/GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M
AST M F 1642-04/GSA TS01 T EST R EPO R T Rendered to: UNI T E D ST A T ES A L U M INU M SE RI ES/M O D E L : B W3250 PR O DU C T T YPE : Aluminum Combination Fixed Window Summary of Results Title Test
More informationAIA PRESENTATION. Standing Seam Metal Roofing Seminar SSRLU2B 1 LU/HSW Hour
AIA PRESENTATION Standing Seam Metal Roofing Seminar SSRLU2B 1 LU/HSW Hour Best Practice MBCI is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned
More informationNFRC 102-2010 THERMAL PERFORMANCE TEST REPORT. Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning)
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT Rendered to: CR LAURENCE CO., INC. SERIES/MODEL: 7500 Concealed Vent TYPE: Projecting (Awning) Summary of Results Standardized Thermal Transmittance (U-Factor)
More informationColorado State University. Durrell Center Roof Repair
Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon
More informationEDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction
Application and Design is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to
More informationA. Work on this project shall consist of, but is not limited to, the following:
PART 1 - GENERAL CLEANING AND RESTORATION OF SECTION 05900-1 1.1 SUMMARY A. Work on this project shall consist of, but is not limited to, the following: 1. Clean and treat all exposed anodized architectural
More informationWater Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
More informationReplacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product
More information