Switchgear Application Issues for Mission Critical Power Systems, Part One

Size: px
Start display at page:

Download "Switchgear Application Issues for Mission Critical Power Systems, Part One"

Transcription

1 Switchgear pplication Issues for Mission Critical Power Systems, Part One BSTRCT With the advent of high reliability data centers and telecommunication facilities, designers of commercial power face new challenges including local power generation and advanced transfer systems. This article is intended to explore the fundamental design issues pertaining to switchgear equipment used in these applications. Part one will discuss system voltage selection and control system design. Part two is dedicated to the subject of fault tolerance and two fundamental design issues with ground fault protection. I. INTRODUCTION Fueled by advances in communication technology and the explosive expansion of the national fiber optic backbone, the 1990 s decade brought about unprecedented growth in data center construction. This growth presented a special problem to data center designers. The sheer number of facilities being built necessitated a high volume design approach, yet there was no industry consensus on the reliability requirements of data centers. Today we see a variety of design approaches from which three common themes have emerged: 1. Utility source is generally considered to be at 99.9% availability level. This necessitates local power generation in the form of standby or prime power generators. 2. Maintainability is engineered into the data center design through redundant power flow paths such that scheduled maintenance can be performed on any piece of equipment without down time (maintenance bypass). 3. Redundant power paths are designed in such a way that an unscheduled loss of any one path will not cause loss of the load. Figure 1 presents a simple power distribution, which accomplishes most of these tasks (ll illustrations are at the end of the document). Circuit breakers within switchgear equipment perform the necessary switching operations. We will use Figure 1 throughout the remainder of this document to illustrate the fundamental design considerations with mission critical power systems. II. MEDIUM VOLTGE VERSUS LOW VOLTGE TRNSFER Utility company plays a major part in the voltage selection process. Large data centers are typically supplied directly from distribution lines at medium voltage (1000V to 38,000V). The three main voltage classes in this category are 5KV, 15KV, 27KV and 38KV. Small facilities are typically supplied at 480V from utility pad mounted transformers. Multiple utility services are provided along with local generators. t some point within the power distribution, these alternate sources must be switched. Designers of large data centers must choose the voltage for switching operations. Figure 2 provides the medium voltage switching alternate to Figure 1. In this scheme, 15KV generators are switched with the two utility sources. Switching operation at medium and low voltage are very different. Vacuum interrupters are commonly used for medium voltage switching operations. SF6 is an alternate technology. In comparison, low

2 voltage power circuit breakers continue to utilize air break technology. Each device is optimized for long life and ease of maintenance. Power system parameters are also significantly different between medium voltage and low voltage systems. Compared to low voltage systems, medium voltages allow us to transfer power over long distances. Long cable lengths introduce additional capacitance, which affects the transient response of the power system. Frequent switching is the common characteristic of automatic transfer systems. s most transient phenomena are statistical, frequent operation naturally increases the exposure of the data center. These transients have been known and documented under various headings - since medium and high voltages were introduced into utility systems. However, such troublesome occurrences were rare within commercial power distribution. This is because, unlike data centers, typical commercial power is not frequently switched. Transient Recovery and Multiple Re-ignitions Transient Recovery Voltage (TRV) is the voltage that appears across circuit breaker contacts during the interruption process (Figure 3). Of special interest is short circuit TRV, which is the transient recovery voltage associated with short circuit current interruption. TRV is a high frequency oscillation and a function of power system capacitance and inductance. Calculation of TRV is not as straight forward as calculations pertaining to fault currents and load flow. Special transient simulations may be required to estimate TRV values. NSI standard C37 series stipulate the TRV requirements for medium voltage circuit breaker application. However, for commercial power design, these requirements are often ignored and circuit breakers are specified solely on the basis of their short circuit and continuous current ratings. This can bring about a non-optimum application of circuit breakers. Multiple re-ignition is a phenomenon associated with the arc extinction process inside the medium voltage circuit breaker interruption chamber. If multiple re-ignitions occur, we encounter the possibility of other high frequency resonance problems within the power system. The exact physics of multiple reignitions is not thoroughly documented. Various researchers have provided explanations of this phenomenon and offered mitigation methodologies. The point of the above discussion is not to discourage medium voltage transfer. The point to be taken is that a more in-depth analysis of the power system is required where medium voltage transfer is employed. This illustrates the value of the engineering specialty for mission critical power. III. SWITCHGER CONTROL SYSTEM DESIGN Design of the automatic transfer system is an art of its own. Even though this art has been around for many years, it has not been adequately documented or standardized. However, there are some fundamental principles, or axioms, which can be applied to this field. These principles can also be incorporated into the project specifications. From each circuit breaker we derive three sets of signals in the form of open/closed contacts: 1. The auxiliary contacts give us the status of the circuit breaker 2. The bell alarm contact or overcurrent trip switch closes only when the low voltage circuit breaker trips due to a fault. For medium voltage circuit breakers the overcurrent relay output is used directly 2

3 3. The cell switch tells us whether the drawout type circuit breaker is in the connected or test position The first intuitive distinction to be made is by looking over the control schematics. re the above three types of contacts used in the control system? Referring to figure 1, let s assume that the bell alarm contact from circuit breaker M is not used in the control system. Now assume that a fault exists on bus. Circuit breaker M will trip in response to this fault. But if the bell alarm contact is not used, the automatic control system will start generator 1 and close circuit breaker G into a dead bus fault a very non-optimum action for a mission critical system. So, in response to a fault, the system must lock itself out. The bell alarm contact must be used in the control system. If the cell switch is not used, circuit breaker maintenance will be hampered. Referring to figure 1, let s assume that circuit breaker M is put into the test position. By putting the circuit breaker in test, maintenance personnel will be able to open and close the circuit breaker several times to assure its proper operation. But each time the circuit breaker is opened, the automatic control system is liable to attempt to perform other switching operations in order to correct what it perceives to be loss of power to the bus. The cell switch can tell the control system to stand down when circuit breaker testing is being performed. Cell switch must be used in the control system. It is not too difficult to distinguish the amateur from the pro in this field. The pro knows how to utilize all the tools available to him. You may be thinking that the above points are so commonplace that they will never be overlooked that is until you come across a system in the field that violates these basic rules. Microprocessor Control Nirvana What about the microprocessor revolution? The old analog devices have a tendency to crowd the doors and covers on switchgear equipment and they have no recording capability. With modern microprocessor control systems, we can create a database of system events, we can automate alarming and monitoring and we can have access to information anywhere such as on the world wide web. There is enormous advantage is utilizing microprocessor and communication technologies especially in a data center. But we should not ignore the fundamentals. Mission critical systems, by definition, must be fault tolerant, including a condition where the microprocessor based system is not operational. This can happen due to control power loss or other factors. In order to create a high level of reliability, we must design the system with maximum redundant automation. But in order to give the system full fault tolerance, we must have a manual back up, which is completely dependent on human interaction. So we must have two independent control systems. The automatic system and the manual system must be completely independent of one another. problem arises when these two systems are combined. For example, it is common to run all input and output signals of circuit breakers into a PLC (Programmable Logic Controller). If the manual controls are in any way connected to the PLC, the purpose of manual control is defeated. Manual controls must have a completely redundant path to the circuit breakers they control. The way this paradox of automatic / manual control is resolved is by observing a set of basic guidelines: 1. Manual / uto switch must be provided to give the operator the choice between the modes of operation 3

4 2. The manual mode must have all anti-paralleling interlocking in place independent of the automatic system. The anti-paralleling interlocks will not allow two sources to be closed together on the same bus. 3. n analog voltmeter is necessary on each source. The old analog indicating voltmeters are indispensable for this application. Digital devices depend on control power availability. So here is the basic science behind this art: 1. Design your manual controls independent of any electronic systems. 2. Place your automatic controls on top of this manual layer. You can get as creative as you want with the automatic controls, using the latest technology with redundant microprocessors and communication systems. Control Power can be the Show Stopper Design of the control power is the most fundamental and the most important consideration for mission critical power transfer systems. If this step is over-looked, the most redundant automatic system will be dysfunctional when it is most needed. reliable source of control power is the conditioned power from UPS (Uninterruptible Power Supply) equipment inside the data center. Use the conditioned data center power as the primary control power source. Use the various switched sources as alternate sources. void conditioning and storage devices that may not receive sufficient maintenance over time. Where UPS equipment or storage batteries are used, these devices must be readily accessible and conspicuous. IV. CONCLUSIONS Design of mission critical power systems is an art and a science. The need for high reliability forces us to re-think our traditional design practices. Switchgear equipment is at the heart of data center power distribution. Switchgear reliability directly impacts data center reliability. In the process of re-thinking traditional design concepts we must not abandon the basic principles. Microprocessor revolution and communication technologies have changed the way we look at the world around us. But they do not change the fundamentals of this art. 4

5 Switchgear pplication Issues for Mission Critical Power Systems, Part Two BSTRCT Within part one we explored selection of system voltage for automatic transfer operation. We also discussed several issues in the design of switchgear automatic control systems. In part two, we explore the issue of fault tolerance and the frailties of ground fault protection. I. INTRODUCTION One of the most basic considerations in the design of data center power is the choice of system grounding. Commercial power systems are typically solidly grounded. In comparison, modern data centers are often high resistance grounded. In a high resistance grounded system, the first ground fault will initiate an alarm instead of tripping circuit breakers. However, many data center designers continue to use the solidly grounded power system for various reasons. This article discusses fault tolerance and two basic pitfalls that data center designers face when utilizing solidly grounded power systems. II. DESIGN FOR FULT TOLERNCE Examining Figure 1, if we have a fault on Bus, the utility source will trip and the generator will not start. Therefore, bus will not be able to supply the loads. Uninterruptible Power Supply (UPS) equipment on side can only carry the load for a limited period of time until their battery runs down. However, static switches inside the PDU (Power Distribution Unit) equipment will continue to supply the load by transferring to bus B power. Therefore, the computer loads will not be dropped. Similarly, examining figure 2, we observe that a fault on the generator bus will remove this bus. But side B can continue supplying power to the data center due to the existence of the medium voltage tie circuit breaker. If the tie circuit breaker were not included, the entire load would be dropped. Further improvement can be envisioned by supplying the UPS static bypass devices from an alternate source - third utility source backed up by a third generator. While this introduces other factors, such as synchronism of various sources, overall power availability is improved by increasing redundancy. Similar analyses can and must be applied at every point within the power system. III. THE FIRST PITFLL IN GROUND FULT PROTECTION When we speak of a fault in any power system, generally we are speaking of ground fault. Ground faults are the most common type of fault. In cable distribution systems, they are usually the result of insulation deterioration due to aging. However, they can be caused by human error during equipment maintenance. Solid grounding provides a return path for ground fault currents. Therefore, tripped overcurrent protective devices easily identify the location of the fault. However, when multiple sources of power are tied together, ground fault protection gets complicated. One major source of complication is the way system neutral conductors are used. In order to supply 277 V fluorescent lighting a small portion of the total load in a data center - system designers often extend neutral conductors throughout the power distribution system. Figure 4 illustrates the neutral conductor connections for a portion of the system in figure 1. 5

6 With this arrangement of neutral conductors, a fault on bus will have multiple return paths to the source. Normally we expect the ground current depicted in figure 4 to return through the neutral to ground bond of the utility transformer. However, as illustrated in figure 4, a portion of this current may return through the neutral to ground bond of the generator, travel over the neutral bus and return to the utility source as neutral current. This can complicate ground fault protection. Circuit breaker M may not sense sufficient ground current to trip, while circuit breaker G senses a ground current even if the generator is off. Therefore, some designers argue that the circuit depicted in figure 4 is a violation of the National Electrical Code (NEC) rticle due to the multiple ground connections employed. Local electrical inspectors may in fact interpret article to disallow the connection shown in figure 4. But such interpretation is not universal. If we had utilized a single neutral to ground connection, (figure 5) we would still have a problem with ground fault protection. If the generator is on and the utility source is off, the fault current will return to the generator as neutral current defeating the ground fault system. dditionally, often circuit breakers M and G are in different switchboards. Considering figure 5, if the neutral conductor is somehow disconnected between bus and the generator, the generator source will be ungrounded an undesirable condition and a violation of NEC. Therefore, single point grounding is not an optimum solution. The problem shown in figure 4 gets much more complicated when we consider the neutral conductors on bus B and the neutrals derived from the UPS sources. The real problem is in tying together the neutral conductors of multiple systems. Even though there is no standardization in this area, switchgear manufacturers can solve these problems by proper design of ground fault protection. This may necessitate employing extra current sensors and dual ground fault sensing units on circuit breakers. But this added complexity must be weighed against the need for extending the neutrals. If 277 V power is needed for fluorescent lights, a stable neutral can be easily derived downstream using an isolation transformer. Eliminating the neutral conductors from the remainder of the system will save significant amount of copper, which will help defer the cost of an isolation transformer for lighting loads. IV. THE SECOND PITFLL IN GROUND FULT PROTECTION This second issue is rather insidious, as it is not very evident. Figure 6 shows the system of figures 4 and 5, but with neutral conductors removed and each source properly grounded. Even though the system in figure 6 will respond correctly to fault currents, it can cause spurious tripping of circuit breakers due to circulating currents. Circulating currents sometimes exist when multiple sources of power are tied together. They appear due to differences in the magnitudes or phase angles of source voltages and they may exist due to harmonics. Third harmonic currents have been known to circulate between generator and utility sources under certain conditions. Figure 6 illustrates the circulating current. Ground fault protection of both circuit breakers M and G will interpret this current as ground fault, causing incorrect circuit breaker tripping. Therefore, the simple radial ground fault protection should not be applied to multiple source mission critical systems. If there were a direct connection between bus and bus B such as by a tie circuit breaker the circulating current problem would get more complicated. The complication grows in proportion to the 6

7 number of inter-tied sources. But all such problems can be solved by proper design of the ground fault system. For example, the circulating current problem depicted in Figure 6 can be corrected by tying the ground fault sensors together as shown in figure 7. Working many scenarios of circulating currents and ground faults will prove that the circuit shown in figure 7 is workable. V. CONCLUSIONS Fault tolerance must be engineered into the power system using an intuitive process. The system must have a method of continuing power supply through a redundant path to computer loads when there is a fault on any bus. Ground fault protection design is significantly simplified if the neutral conductors from multiple systems are not tied together. Stable grounded neutral can be derived close to the 277 V lighting loads where it is needed. Isolation transformers have been successfully employed in this application for many years. Presence of multiple sources necessitates evaluating circulating currents for mission critical power systems. Ground fault protection may malfunction due to circulating currents if the system is not properly designed. 7

8 UTILITY UTILITY B B BUS BUS B PDU FROM LTERNTE PDU COMPUTER Figure 1: Basic Data Center Power Distribution 8

9 UTILITY B UTILITY B BUS BUS B PDU FROM LTERNTE PDU COMPUTER Figure 2: Medium Voltage Version of Data Center Power System 9

10 TRV FULT TRV1>C1 -C2 (Type 4) TRV1>C1 -C2 (Type 4) TRV1>XX0001(Type 4) TRV1>XX0001-XX0011(Type 8) CURRENT Voltage (V) Time (ms) SOURCE VOLTGE Figure 3: Transient Recovery Voltage Due to Short Circuit Current Interruption. Circuit Breaker Contacts Part at Time Zero. rcing Continues Until Current Goes to Zero. TRV ppears cross the Circuit Breaker Contacts s Soon s Current Goes to Zero. TRV 10

11 UTILITY SOURCE M G GROUND FULT SENSOR BUS FULT Figure 4: Multiple Return Paths Cause Ground Fault Mis-operation UTILITY SOURCE M G BUS FULT Figure 5: Single Point Grounding Does Not Solve Ground Fault Mis-operation Problem 11

12 UTILITY SOURCE M G BUS Figure 6: Circulating currents can cause ground fault nuisance tripping UTILITY SOURCE M GROUND FULT TRIP G M G BUS Figure 7: Properly Designed Ground Fault Protection Requires Special Connection of Sensors 12

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)

More information

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

Paralleling Switchgear

Paralleling Switchgear Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more

More information

New standardized approach to arc flash protection

New standardized approach to arc flash protection New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200

More information

Application of Four-Pole Circuit Breakers within Data Centers

Application of Four-Pole Circuit Breakers within Data Centers Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Power Monitoring for Modern Data Centers

Power Monitoring for Modern Data Centers Power Monitoring for Modern Data Centers December 2010/AT304 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision #1 12/10 By their nature, mission critical

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

Critical-Power Automatic Transfer Systems Design and Application

Critical-Power Automatic Transfer Systems Design and Application Critical-Power Automatic Transfer Systems Design and Application Bill Brown, P.E., Jay Guditis, Square D Critical Power Competency Center 1. INTRODUCTION An important requirement of mission-critical electric

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more

More information

Extend the Life of Existing Switchgear

Extend the Life of Existing Switchgear Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

The Application of Circuit Breakers to Reduce Downtime in Datacentres

The Application of Circuit Breakers to Reduce Downtime in Datacentres The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the

More information

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

AC Versus DC Power Distribution

AC Versus DC Power Distribution AC Versus DC Power Distribution Issues to consider when comparing options for improving data center energy efficiency By Robert W. Johnson Chief Engineer, Platform Development and Intellectual Property,

More information

Report in respect of. Service Disruption on 9 April 2012

Report in respect of. Service Disruption on 9 April 2012 Report in respect of Service Disruption on 9 April 2012 1. Introduction On 9 April 2012, a power outage occurred in the Shatin Switching Centre, one of three switching centres deployed by SmarTone Mobile

More information

Grounding of AC generators and switching the neutral in emergency and standby power systems

Grounding of AC generators and switching the neutral in emergency and standby power systems Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.

More information

SWITCHGEAR. EGP Switchgear

SWITCHGEAR. EGP Switchgear SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

SMART SENSOR COLLECTION

SMART SENSOR COLLECTION TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE

More information

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG

More information

Atlanta Chapter IEEE Industry Applications Society

Atlanta Chapter IEEE Industry Applications Society Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.

More information

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

21 st Century Facilities

21 st Century Facilities Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

30 ms High Speed Transfer System (HSTS) Product Description

30 ms High Speed Transfer System (HSTS) Product Description 30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system

More information

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY Scope These program criteria apply to programs having titles involving Electrical Engineering Technology including: electrical engineering, electrical

More information

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran

More information

Robson Forensic Engineers, Architects, Scientists & Fire Investigators

Robson Forensic Engineers, Architects, Scientists & Fire Investigators PROFESSIONAL EXPERIENCE 2015 to Robson Forensic, Inc. present Associate Provide technical investigations, analysis, reports, and testimony for failure analysis toward the resolution of commercial property

More information

Arc Flash Energy Mitigation Techniques

Arc Flash Energy Mitigation Techniques Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International

More information

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com] ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [Dick@indtests.com; 916-660-2837]

More information

HIGH VOLTAGE SHORE CONNECTION

HIGH VOLTAGE SHORE CONNECTION Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS SECTION 16999 ELECTRICAL ACCEPTANCE TESTS PART 1 2. AND 3. COMBINED 1.1 SUMMARY A. Description of Systems 1. Furnish all labor, materials, test equipment, and technical supervision to perform and record

More information

conventional system operation

conventional system operation conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than

More information

Mike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC

Mike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC Mike Holt s Illustrated Guide to NEC Requirements for Generators and Standby Power Systems Rule 220.87, Articles 445, 700, 701, and 702 Based on the 2011 NEC Extracted from Mike Holt s Illustrated Guides

More information

Fault Characteristics in Electrical Equipment

Fault Characteristics in Electrical Equipment 1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through

More information

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace. SAFETY Industrial DESCRIBE hazards and precautions taken to avoid injury in the workplace. Example #1: All of the following are common PPE used to perform maintenance activities EXCEPT: a. Safety Glasses

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Occupational Profile: Electrical & Electronics Engineering Technician

Occupational Profile: Electrical & Electronics Engineering Technician Occupational Profile: Electrical & Electronics Engineering Technician A competent Electrical & Electronics Engineering Technician should be able to demonstrate the following skills and competences: 1.

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

Increased power protection with parallel UPS configurations

Increased power protection with parallel UPS configurations Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton

More information

Isolated-Parallel UPS Configuration

Isolated-Parallel UPS Configuration Isolated-Parallel UPS Configuration 1 Inhalt 1 Introduction... 4 2 IP systems configuration... 6 3 Projects... 17 4 Conclusions... 17 2 Abstract The isolated-parallel UPS configuration has become well

More information

T-016: Paralleling Application Manual

T-016: Paralleling Application Manual Application Engineering T-016: Paralleling Application Manual English Original Instructions 6-2014 A040W370 (Issue 4) Table of Contents 1. INTRODUCTION... 1 1.1 Overview... 1 1.2 About This Manual...

More information

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS Definition: Zone Selective Interlocking (ZSI) - A method which allows two or more ground fault breakers to communicate with each other so that a short circuit or ground fault will be cleared by the breaker

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

Choosing the Best Solution for Reducing Arc Energy

Choosing the Best Solution for Reducing Arc Energy CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors

More information

Minimizing Impact of Electric Utility Outages with Backup Generation

Minimizing Impact of Electric Utility Outages with Backup Generation Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility

More information

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, 18 80 W Compact and T5c fluorescent lamps

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, 18 80 W Compact and T5c fluorescent lamps EXCEL oneall series Product description Noise-free precise control via DSI signal, switchdim, corridorfunction or DALI DALI-MEMORY Extended DALI commands CELMA energy class A1 1) Interfaces DALI DSI switchdim

More information

Paralleling Power Sources Which Share a Common Neutral

Paralleling Power Sources Which Share a Common Neutral Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Integrated Power Systems for Data Centers

Integrated Power Systems for Data Centers Integrated Power Systems for Data Centers A Commitment to Data Centers Caterpillar is committed to providing optimum value to the Data Center industry by leveraging our engineering, manufacturing, distribution,

More information

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

ELECTRICAL SAFETY RISK ASSESSMENT

ELECTRICAL SAFETY RISK ASSESSMENT ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures

More information

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information