Optical-Sensor Data Handling



Similar documents
Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

2-Port RS232/422/485 Combo Serial to USB2.0 Adapter (w/ Metal Case and Screw Lock Mechanism) Installation Guide

Why you need to monitor serial communication?

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.

Modbus Communications for PanelView Terminals

WP WinPAC-8x49 Series (WP-8149/8449/8849) is the new generation WinCE based InduSoft PAC (Programmable Automation Controller).

1.1 Connection Direct COM port connection. 1. Half duplex RS232 spy cable without handshaking

Introduction: Implementation of the MVI56-MCM module for modbus communications:

FOXBORO. I/A Series SOFTWARE Product Specifications. I/A Series Intelligent SCADA SCADA Platform PSS 21S-2M1 B3 OVERVIEW

How To Connect A Directsofl To A Powerpoint With An Acd With An Ctel With An Dm-Tel Modem On A Pc Or Ipad Or Ipa (Powerpoint) With A Powerline 2 (Powerline

Alcalde # 1822 Col. Miraflores C.P Guadalajara, Jal. Mexico MX 01 (33) y USA 001 (619) (San Diego, CA.

Semaphore T BOX Applications in Data Center Facilities

Application/Connection Examples

SCADA and Monitoring for Solar Energy Plant

Master-Touch and ValuMass. Modbus Communications. INSTRUCTION MANUAL (Rev. 2.1)

How To Use Safety System Software (S3)

How To Run An Nport I5000A Device Server

SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2

User s Manual TCP/IP TO RS-232/422/485 CONVERTER. 1.1 Introduction. 1.2 Main features. Dynamic DNS

RS-232 COMMUNICATIONS

Quick Installation. A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding. Quick Installation

WEB log. Device connection plans

LAN / WAN Connection Of Instruments with Serial Interface By Using a Terminal Server

Using HyperTerminal with Agilent General Purpose Instruments

To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:

Cable Specifications and Information

Electrical Monitoring and Control System Solution. Guideform Specification

Modbus and ION Technology

scalable data centre energy management solution

MODBUS TCP to RTU/ASCII Gateway. User s Manual

APNT#1168 Modbus - Establishing Communications Hints

Application Note 2. Using the TCPDIAL & TCPPERM Commands to Connect Two TransPort router Serial Interfaces Over TCP/IP.

SCADA Systems. Make the most of your energy. March 2012 / White paper. by Schneider Electric Telemetry & Remote SCADA Solutions

User Manual Revision English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD HD M HD HD M)

Process Control and Automation using Modbus Protocol

Cable Guide. Click on the subject to view the information. Digi Cables Building Cables General Cable Information

White Paper ClearSCADA Architecture

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

IP SERIAL DEVICE SERVER

NETWORK ENABLED EQUIPMENT MONITOR

Application Note. Terminal Server G6

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

Vibration analysis and monitoring Compact. Powerful. Modern technology.

LTM-1338B. Plus Communications Manual

/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards.

Toshiba Serial Driver Help Kepware Technologies

SECTION WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM

User manual Compact Web PLC WP240 series IEC-line

Complete SCADA solution for Remote Monitoring and Control

RS232 Programming and Troubleshooting Guide for Turbo Controls

The Analyst RS422/RS232 Tester. With. VTR, Monitor, and Data Logging Option (LOG2) User Manual

16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide

Single channel data transceiver module WIZ2-434

Radiological Assessment Display and Control System

One Port Serial Server Users Manual Model ESP901, ESP901E

PLCs and SCADA Systems

VM600 CMS Software. VM600 Series Software for Condition Monitoring System (CMS) FEATURES DESCRIPTION

MCB3101 (Class I) WiRobot Serial Bluetooth Wireless Module User Manual

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference :

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

Software Operations Manual

How To Set Up A Modem (Marc) Model (Marc) Model 2 (Marr) Model 1 (Marm) Model 4 (Mariar) Model 8 (Marp) Model 6 (Mar

Dial-Up / Leased-Line Modem. User Manual. AGM Electronics, Inc Dial-Up / Leased-Line Modem, Series ( ) Manual Rev A + - DLM CTS RTS DTR DSR

GV-Data Capture V3 Series User's Manual

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

Connectors and Cables

The Answer to the 14 Most Frequently Asked Modbus Questions

Virtual Integrated Design Getting started with RS232 Hex Com Tool v6.0

Lucien Antonissen Key Account Manager LIOS Technology Germany

Bluetooth to Serial Adapter

ENET-710. ENET Ethernet Module ENET-710 JAN / 06 FOUNDATION

RJ45 Shielded (standard) port pinout. CS9000, Jetstream , Lanstream 2000, RTA8/RJX, RRC16, MTA8/RJX & SXDC8/RJX

Wifi Web Server Module w TF Socket User s Guide

AutoLog ControlMan. Remote Monitoring & Controlling Service

4511 MODBUS RTU. Configuration Manual. HART transparent driver. No. 9107MCM100(1328)

Kurz MODBUS Client User s Guide

RS-232/422/485, Power over Ethernet

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

Cable Pinouts. SRP I/O Module

The Enterprise Operations Platform

SCADA Questions and Answers

WaveReady CFM. Optical Link Monitoring System: Continuous Fiber Monitor

3.1 RS-232/422/485 Pinout:PORT1-4(RJ-45) RJ-45 RS-232 RS-422 RS-485 PIN1 TXD PIN2 RXD PIN3 GND PIN4 PIN5 T PIN6 T PIN7 R+ PIN8 R-

Professional USB to Serial Adapter Hub with COM Retention

Modbus Server SAMSUNG Air Conditioners

Ethernet. Customer Provided Equipment Configuring the Ethernet port.

IntesisBox Modbus Server Fidelio IP

TK C -25 C 95% RH EMC TK701G TK701U TK704G TK704U TK704W. TK-Series Cellular Router

Technical Information POWER PLANT CONTROLLER

LBNP RS-232/485/422 serial device server. User manual

IntesisBox Modbus Server - Mitsubishi Electric G50

Using IDENT M System T with Modbus/TCP

Monitoring solar PV output

ALL-USB-RS422/485. User Manual. USB to Serial Converter RS422/485. ALLNET GmbH Computersysteme Alle Rechte vorbehalten

2-Port RS232/422/485 Combo Serial PCI Card

Wireless Communications for SCADA Systems Utilizing Mobile Nodes

Modbus and ION Technology

Line sheets system host software Measurement and automation systems. Connect and control with ABB. Introduction. Making sense of software

USB TO SERIAL ADAPTER

DSA-1000 / PRT-1000 Device Server / Thermal Printer

Transcription:

Weatherford Reservoir Monitoring System Data Logger Platform Platform Operations Staff Shore Primary Data Flow Path, by SCADA Production Optimization Those who rely on data produced by in-well optical sensors are typically well site production engineers, reservoir engineers, and other operations-related staff within an oil company. The needs of each differ slightly and can vary at different phases of a reservoir s lifetime. Therefore, the following information is compiled for the use of those concerned with the integration of data supplied by Weatherford optical sensing systems into oil company data access and management systems. The diagram below shows a typical offshore platform arrangement: Local Display Real-Time Control Computer Serial MODBUS Oil Co. SCADA System Data Historian Reservoir/Operations Engineer LAN Switch NAS Electro-Optics UPS MODBUS TCP/IP OPC Ethernet Oil Co. LAN/WAN LAN/WAN Can access Data files on NAS Web page data viewer Web page historical graphing ODBC- -compliant database WCS Support Engineer In-Well Sensors As-needed log-on using secure oil company computer Diagnostics Troubleshooting Reconfiguration Historically, MODBUS protocols connected to supervisory control and data-acquisition (SCADA) systems or remote-terminal units (RTUs) have enabled platform production staff to correlate and combine production monitoring data. To maximize the benefit of the optical sensors, the reservoir engineer requires access to data stored at the highest data density possible. All of the Weatherford surface data systems compile data onto local storage media at high rates, ensuring easy access through local or wide-area networks (LAN/WAN). The data-acquisition system software continually undergoes updates and improvement, based on input from the field. Maintenance and upgrade installation can be conveniently performed onshore if the systems are connected through a network, minimizing downtime and reducing the costs associated with transporting technicians to remote, offshore locations. In addition, connecting the systems to a network allows experts to support the software from locations around the world. MODBUS is a registered trademark of Schneider Automation Inc.

Weatherford encourages operators to connect optical data-acquisition systems to both the platform SCADA as well as the business wide-area network. The benefits of connecting the optical surface systems to a LAN/WAN are as follows: Insurance that backup data on the logger can be readily accessed over network if the SCADA/data historian link fails Easy access of higher-density data on the data logger after unplanned events, such as well shut-ins One shared network for MODBUS TCP/IP and OPC Remote troubleshooting, reconfiguring, and upgrading through the network from onshore locations Access to the structured-query-language (SQL) database through standard open database connectivity (ODBC) Connection to Platform Automation System Several kinds of optical surface data-acquisition systems are available. Nearly all of the deployed systems are designed to complement a particular wellsite arrangement; however, the software guiding these systems is identical and is called the Reservoir Monitoring System (RMS). Weatherford s surface systems have a variety of connectivity options, all of which are easily configured at the time of installation. No programming or advanced, custom engineering is necessary. The chart below summarizes the options available: Surface System Environment Air conditioned control room Desert outdoor Subsea support No. of PT gauges supported Sensor Options No. of DTS channels supported No. of flow meters supported MODBUS RS232 MODBUS RS422 Connectivity Options Power Options Local Media RMS-WH N 6 a 0 0 N N N N N N RMS Lite N 3 a 0 0 N N RMS Lite with DTS N 3 a 3 c 0 N N N RMS N 24+ b 0 0 N RMS with DTS N 24+ b 9+ c 0 N RMS with flow and DTS N 24+ b 9+ c 8+ c N a Gauge-type dependent b Modular system allows expansion c Optical switch allows expansion ü = Included feature N = Not available MODBUS RS485 MODBUS TCP/IP OPC Simple serial ASCII string PROFIBUS ODBC SQL database Web viewer 24 V DC 110 V AC 220 V AC CD burner Floppy disk USB (2)

Weatherford surface systems can be connected to wellsite automation systems in the following ways: MODBUS OPC Database CSV ASCIl string PROFIBUS Flat files Following are descriptions of each of these means of connectivity. MODBUS Physical-Layer Interface Options Serial: RS232, RS485, RS422 Connection Speed Signals Isolation DB9 300, 600, 1200, 2400, 4800, 9600, 14400, 19200, 38400, 57.6K, 115.2K baud RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND RS-422: TxD±, RxD±, RTS±, CTS±, GND-485: Data±, GND RS-232: N/A RS-422: 2 KV RS-485: 2 KV Ethernet TCP/IP (MODBUS Only) Connection RJ45 Ethernet 10/100 MODBUS Interface Options Control Master or slave Device Address 1 to 247 Function Code Data Format Options Read holding registers MODBUS function code 03) Allowable assignments 40001 to 49999 Floating point (2 registers) Swapped floating point (2 registers) Double float (4 registers) Swapped doungle float (4 registers) Unsigned integer 16 bit Three MODBUS message types are supported: ASCII framing, RTU framing, or TCP/IP. CSV ASCII String The CSV (comma-separated variable) string output format is not only useful for diagnostic and test purposes, but also for data transfer to third parties who do not support any of the SCADA-type formats. The protocol is simple enough for receiving programs to be expediently written. (3)

Data format Coding ASCII Number of bits per character Data 8 Parity None Stop Bits 1 Message framing Well Name<comma>Date<comma>Time<comma>Value 1<comma>Value 2<comma>... Value N<CR><LF> Example NewWell,6/13/2005, 14:43:26, 196.41786194, 75.53485870 NewWell,6/13/2005, 14:43:29, 196.26698303, 75.57905579 OPC The RMS OLE for process control server (OPC) and client are fully compatible with the OPC Data Access 2.0 standard. Data transfer options include individual items or variable arrays. Flow rate can be expressed in downhole conditions, separator conditions, or standard pressure and temperature conditions. The second pressure/temperature (PT) gauge is used to measure differential, from which density is derived. Pressure Gauge 2-Phase Flow 3-Phase Flow Pressure Gauge kpa Quality Pressure kpa Quality Sound Speed, m/s, Quality m/s Quality Temperature Deg C Quality Temperature Deg C Quality Bulk Velocity, m/s, Quality m/s Quality Bulk Velocity m/s Quality Pressure kpa Quality Oil Flow Rate cu.m/s Quality Temperature Deg C Quality Water Flow Rate cu.m/s Quality Pressure Sensor 2 kpa Quality Total Flow Rate cu.m/s Quality Temperature Sensor 2 Deg C Quality Oil Volume Fraction % Quality Oil Flow Rate cu.m/s Quality Water Volume Fraction % Quality Gas Flow Rate cu.m/s Quality Water Flow Rate cu.m/s Quality Pressure DH kpa Quality Temperature DH Deg C Quality Oil Flow Rate SEP cu.m/s Quality Gas Flow Rate SEP cu.m/s Quality Water Flow Rate SEP cu.m/s Quality Pressure SEP kpa Quality Temperature SEP Deg C Quality Oil Flow Rate STD cu.m/s Quality Gas Flow Rate STD cu.m/s Quality Water Flow Rate STD cu.m/s Quality Pressure STD kpa Quality Temperature STD Deg C Quality (4)

PROFIBUS PROFIBUS is offered as an optional add-on for control room RMS systems only. The RMS system uses PROFIBUS interface cards and software drivers supplied by Softing, Inc. The PROFIBUS option offers several benefits: Provides an intelligent PC interface card for integrating a PC in a PROFIBUS network (1-channel) Provides master/slave functionality with a separate micro-controller for the protocol software Delivers a transfer rate of up to 12 mbit/s Supports all PROFIBUS protocols (multi-protocol support) PROFIBUS DP Options Master Slave Slave address configurable Slave type DP_Slave_Softing_b205 FMS Options Client Server Database Weatherford s RMS software contains an SQL database. In addition, an ODBC driver is available for direct interconnection to other databases. Well Sensor History Table Table name: WellSensor_History Description: This table has information about all sensor tables. Stamp Well Name Sensor Name Sensor Type Depth Date Table Name Age Well Sensor Current Table Table name: WellSensor_Current Description: This table has information about the sensor tables for the current configuration. Stamp Well Name Sensor Name Sensor Type Depth Date Table Name (5)

Pressure Sensor Data Table Table name: WellName_SensorName_Date_Time Description: This table stores the data for this pressure sensor. Stamp PRS PRS TMP TMP Flow Sensor Data Table Table name: WellName_SensorName_Date_Time Description: This table stores the data for this flow sensor. Stamp PRS PRS TMP TMP BV BV SS SS Oil FR Oil FR Water FR Water FR Oil PF Oil PF Water PF Water PF Three-Phase Flow Sensor Data Table Table name: WellName_SensorName_Date_Time Description: This table stores the data for this three-phase flow sensor. Stamp PRS 1 PRS 1 TMP 1 TMP 1 PRS 2 PRS 2 TMP 2 TMP 2 PRS_DH PRS_DH TMP_DH TMP_DH PRS_STD PRS_STD TMP_STD TMP_STD PRS_STD PRS_STD TMP_SEP TMP_SEP BV BV SS SS Oil FR_STD Oil FR_STD Water FR_DH Water FR_DH Gas FR_DH Gas FR_DH (6)

Oil FR_STD Oil FR_STD Water FR_STD Water FR_STD Gas FR_STD Gas FR_STD Oil FR_SEP Oil FR_SEP Water FR_SEP Water FR_SEP Gas FR_SEP Gas FR_SEP VelSOS (Velocity and Speed of Sound) Sensor Table Table name: WellName_SensorName_Date_Time Description: This table stores the data for this VelSOS sensor Stamp BV BV SS SS Total FR Total FR DTS Sensor Table Tablename: WellName_SensorName_Date_Time Description: This table stores the data for this DTS sensor Stamp DTS Data Zone Alarms Flat Files If the RMS system is not configured to use a database and is directly connected to a network through the control computer or through a network-attached storage (NAS) server, the data can be accessed through flat files. For each PT gauge and each flowmeter, an ASCII data file is created every 24 hours, at midnight. The file is tab delimited, and the units of measure are in SI units. Example of a PT gauge file: 12/7/2001 10:16:39 PRS 33832.94 TMP 110.082 12/7/2001 10:16:42 PRS 33832.29 TMP 110.077 12/7/2001 10:16:45 PRS 33833.82 TMP 110.089 12/7/2001 10:16:48 PRS 33834.44 TMP 110.090 12/7/2001 10:16:51 PRS 33833.17 TMP 110.085 (7)

Example of a two-phase flowmeter file: 12/27/2001 14:41:05 PRS 120.240347 TMP 127.330997 SS 4597.636138 BV 3.423553 OilPF 0.001764 WaterPF 0.998236 OilFR 0.000026 WaterFR 0.014785 12/27/2001 14:42:35 PRS 143.142929 TMP 126.334707 SS 4603.990606 BV 3.414589 OilPF 0.001849 WaterPF 0.998151 OilFR 0.000027 WaterFR 0.014745 12/27/2001 14:44:05 PRS 139.685703 TMP 126.244007 SS 4596.178620 BV 3.412020 OilPF 0.002147 WaterPF 0.997853 OilFR 0.000032 WaterFR 0.014730 12/27/2001 14:45:35 PRS 117.066904 TMP 129.337863 SS 4605.759725 BV 3.441207 OilPF 0.000946 WaterPF 0.999054 OilFR 0.000014 WaterFR 0.014874 12/27/2001 14:47:05 PRS 128.955536 TMP 127.445628 SS 4589.666501 BV 3.489948 OilPF 0.001996 WaterPF 0.998004 OilFR 0.000030 WaterFR 0.015068 Each file name is appended with the date, for example: Psensor 1-22Oct2001.dat DTS data are depth based rather than time based. Therefore, they are formatted differently. DTS files adhere to the Canadian Well Logging ASCII Standard (LAS). Both LAS 2.0 and 3.0 standards are supported. The depth data are referenced to the wellhead, negative depths indicate surface cable, and positive depth numbers indicate in-well data. A typical file name is DTS Sensor-08Apr2003-1104.las. A sample LAS file is shown at right. (8)

Network-Attached Storage NAS servers are self-contained, intelligent devices that attach directly to an existing LAN. A file system is located and managed on the NAS device, and data is transferred to users over standard network protocols such as TCP/IP. Weatherford uses Quantum s Snap NAS devices. NAS drives offer larger data storage capacity than local hard drives and protect the investment made in acquiring the data. The SNAP servers are RAID 5 striping with parity (factory default), and RAID 1 monitoring. Another advantage of storing data files on a NAS device is no executable files are running on these servers. Therefore, network corruption is minimized, while control and communication to the computer is restricted from casual users on the network. (9) Weatherford products and services are subject to the Company s standard terms and conditions, available on request or at. For more information contact an authorized Weatherford representative. Unless noted otherwise, trademarks and service marks herein are the property of Weatherford. Specifications are subject to change without notice. Weatherford sells its products and services in accordance with the terms and conditions set forth in the applicable contract between Weatherford and the client.