Sizing Circuit Breakers for Self-Regulating Heat Tracers

Similar documents
BSX TM. Self-Regulating Heating Cable. Product Specifications

PRODUCT / APPLICATION INFORMATION

Electric Heat Tracing INSTALLATION PROCEDURES

Complex Piping Design Guide for Self-Regulating Heating Cables

Nelson MI Cable is a high performance, industrial grade heat tracing cable used for applications requiring:

Self-Regulating Low Temperature Heating Cable

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation

EPL225 Series. 225 Watts. AC-DC Power Supplies. Models & Ratings. Summary

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

Three-phase monitoring relay CM-PFE

BASIC NEC CODE RULES AND DESIGN PRACTICE

AC Transport constant current vs. low impedance modes

Application Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship

The FET Constant-Current Source/Limiter. I D = ( V DS )(g oss ) (3) R L. g oss. where g oss = g oss (5) when V GS = 0 (6)

BB800 Off-Grid Solar System

MIQ TM Mineral Insulated Heating Cable INSTALLATION PROCEDURES. (North America)

TC 1818a. Operating Guide. Control Module SWM-015.5

Heating Cable. Construction

Electric Heat Tracing INSTALLATION PROCEDURES

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

POWER AND VOLTAGE RATING

Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Technical data. Danfoss DHP-A

TC 202a Control Module

ACS-30-EU-EMDR-10-MOD

InGaN / Sapphire White Water clear. Parameter Rating Unit

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Unit 7: Electrical devices LO2: Understand electrical sensors and actuators Sensors temperature the thermistor

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

TubeTrace, ThermoTube

"Reliability and MTBF Overview"

3W RGB High Power LED

Advanced Monolithic Systems

High kw Electric Tankless Water Heater Troubleshooting Guide

Constant Voltage Charger Selection for VRLA Batteries

EARTHING SYSTEM CALCULATION

SMD High Power Precision Resistors

Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation.

8146/5 Series Breaker Panelboards

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Transformer Thermal Overload Protection - What s It All About?

Type RP73 Series. SMD High Power Precision Resistors. Key Features. Applications. Characteristics - Electrical - RP73 Series - Standard

E2 Series Electric Furnaces

Pipe Freeze Protection Design/Install Guide

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors

Characterizing Digital Cameras with the Photon Transfer Curve

SURGE PROTECTIVE DEVICES

Using NTC Temperature Sensors Integrated into Power Modules

Installation Instructions. Industrial Heating Cable Products

ME Heat Transfer Laboratory. Experiment No. 7 ANALYSIS OF ENHANCED CONCENTRIC TUBE AND SHELL AND TUBE HEAT EXCHANGERS

KIA7805AF/API~KIA7824AF/API SEMICONDUCTOR TECHNICAL DATA THREE TERMINAL POSITIVE VOLTAGE REGULATORS 5V, 6V, 7V, 8V, 9V, 10V, 12V, 15V, 18V, 20V, 24V.

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Understanding the Terms and Definitions of LDO Voltage Regulators

SELF-REGULATING PIPE TRACING HEATER CABLE

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

AAV003-10E Current Sensor

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

How To Read A Pipe From A Sensor

S101D01/S101D02 S201D01/S201D02

PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, W Compact and T5c fluorescent lamps

Application Note TMA Series

DATA SHEET. TDA1510AQ 24 W BTL or 2 x 12 W stereo car radio power amplifier INTEGRATED CIRCUITS

Installation, Operation and MAINTENANCE INSTRUCTIONS. Industrial Heating Cable Products IMPORTANT GENERAL INSTRUCTIONS

CHAPTER 2 EXAMPLES AND TABLES

The complete range of consumer switchboards and switchgear

NELSON HEAT TRACING SYSTEMS

Steady Heat Conduction

DATA SHEET. TDA1518BQ 24 W BTL or 2 x 12 watt stereo car radio power amplifier INTEGRATED CIRCUITS

1.5A L.D.O. VOLTAGE REGULATOR (Adjustable & Fixed) LM1086

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Solar Power Analysis Based On Light Intensity

Cree XLamp Long-Term Lumen Maintenance

7-41 POWER FACTOR CORRECTION

Experiment #4, Ohmic Heat

KADUNA CLINICS SOLAR SYSTEMS PERFORMANCE TESTING

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, W Compact and T5c fluorescent lamps

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

AXIS PS12 Outdoor Power Supply. Installation Guide

Installation & Maintenance

PWM-90 series IP67 TRC ELECTRONICS, INC Mean Well PWM-90 Series

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

Features. Applications. Truth Table. Close

A Simple Current-Sense Technique Eliminating a Sense Resistor

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Multi-Range Programmable DC Power Supplies 9115 Series

Mineral Insulated Heating

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

UPS Applications and VRLA Battery Sizing

How To Select A Solid State Relay For A Three Phase Resistive Load

British BS 88 Fuses. Introduction

Trip circuit supervision relay. Type RXTCS

Fan Basics and Selection Criteria (How to Use)

Transcription:

Sizing Circuit Breakers for Self-Regulating Heat s Effective Resistance (ohm/m) Introduction Circuit breaker sizing for S/R tracers is quite easily accomplished by using the specification sheet data or CompuTrace heat tracing design software. However, sometimes an engineer or designer asks What is the technical basis for sizing data and the resulting design values? This ThermoTip is intended to show the technical basis on how circuit breaker sizing is accomplished. Key factors in proper sizing are: () the specified start-up temperature, (2) the circuit breaker type and ampacity rating, (3) the specific S/R tracer start-up characteristic, and (4) the total length of heat tracer connected to the circuit breaker. Resistance Characteristic Since a self-regulating heat tracer has a PTC (positive temperature coefficient) resistance characteristic, resistance increases with temperature. An example of heat tracer effective resistance as a function of tracer (not pipe) temperature is shown in Figure. This example is for a freeze protection heat trac- 5 45 4 35 3 25 2 5 5-3 -2-2 3 4 5 6 7 8 Temperature C Fig.: Effective Resistance vs. Temperature Normalized Current. 5.. Peak Electrical/Thermal Equilibrium of Heating Cable Thermal Equilibrium of Pipe,, Log Time (seconds) Fig. 2: Self-Regulating Start-Up Current Response er. Note that the resistance of this freeze protection heat tracer gradually increases from -2º C to 3º C. The typical tracer operating temperature range is between 4º C to 6º C. After 6º C the heat tracer starts to exhibit significant increase in resistance as it approaches its shut-off temperature near 8º C. Start-up Current Characteristic This resistance change with tracer temperature produces the start-up current characteristic of an S/R tracer. An illustrative example of an S/R tracer start-up current characteristic is shown in Figure 2. The start-up current response can be described by three current values: Peak the current that occurs just after energization when the tracer temperature is the same as the pipe temperature (during system start-up) Maximum Current the current level after the heat tracer has attained its equilibrium temperature above the pipe temperature (usually 3 seconds after energization) Operating Current the current level when the pipe has attained its operating temperature or design maintain temperature (several hours after energization depending on the pipe size and fluid contained) T heater = -2 C R = 24 Ω/m At Time = + (energization) Fig. 3a Maximum T heater = +44 C R = 66 Ω/m At Time = 3 seconds Fig. 3b Operation T heater = +59 C R = 5 Ω/m T fluid = -2 C T fluid = -2 C T fluid = +5 C At Time = 4hr Fig. 3c Pipe and Temperature During Start-up and pipe temperature for these three current levels are shown in Figure 3. Form TT22-79

Sizing Circuit Breakers for Self-Regulating Heat s Fig. 3(a) shows the pipe and tracer at energization. The pipe and tracer are at the same temperature of -2º C. In this example the tracer resistance is 24 W/m. The current for this resistance is PEAK current. Fig. 3(b) shows the pipe and tracer after 3 seconds. At this time the pipe has not changed temperature, but the heat tracer has come to its equilibrium temperature of 44º C above the -2º C pipe temperature. The tracer resistance at 44º C is 66 W/m. This results in MAXIMUM current. Fig 3(c) shows the pipe at an operating temperature of 5º C. To attain this pipe temperature may have taken several hours depending on the pipe size. The tracer temperature is now 59º C and has a resistance of 5 W/m. The current from this resistance level is OPERATING current. For this example tracer effective resistance is shown as both a function of start-up time and tracer temperature in Figure 4. Effective Resistance (ohm/m) 5 45 4 35 3 25 2 5 5 Time = Time = 3 s Time = 4hr -3-2 - 2 3 4 5 6 7 8 Temperature C Fig.4: Effective Resistance vs. Temperature & Time This is the basis for the typical start up current response shown in Figure 2. When sizing the circuit breaker, the start-up current response of the tracer must not intersect the (minimum) circuit breaker trip curve. Circuit Breaker Characteristics Circuit breaker trip curves are typically shown on log-log graphs with multiples of the rated current as a function of time. At seconds the multiple of rated current is at or near unity. An example of a typical North American circuit breaker response curve is shown in Figure 5. Note that for this typical North American circuit breaker, the minimum trip curve allows a peak current of times the CB rating. That means for a 2 A breaker a peak current of 2 A would be allowed and not cause a breaker trip. However, after seconds the load current must be under.2 times the CB rating or in the case of a 2 A breaker, 24 A. Circuit breaker trip characteristics are not all the same. Two other common international circuit breaker trip characteristics are Type C and Type B. The trip curves for these two types of circuit breakers are shown in Figure 6(a) and 6(b). Fig. 5: Typical North American Breaker Trip Curve Fig 5: Typical QO GFI Breaker Trip Curve Maximum Amps - at % Loading Fig 6a: Typical European Type C Breaker Trip Curve Maximum Amps - at % Loading Fig. 6a: Typical IEC Type C Breaker Trip Curve Fig 6b: Typical European Type B Breaker Trip Curve Maximum Amps - at % Loading Fig. 6b: Typical IEC Type B Breaker Trip Curve Form TT22-79 2

Sizing Circuit Breakers for Self-Regulating Heat s Other than a lower allowable peak current, the international Type C response curve in Figure 6(a) is quite similar to that of the typical North American circuit breaker. The allowable peak current for the Type B circuit breaker is much lower with a 2. multiplier. Thus, when sizing S/R heat load for a circuit breaker, it is important to specify the breaker class or type in addition to its ampacity rating. There are cases when the tracer maximum current and breaker rating are the same and the tracer start-up current intersects the breaker trip curve. Examples are shown in Figure 8(a) and 8(b). For the QO breaker example the intersection occurred in the first seconds. For the Type B breaker the intersection occurred at time + with peak current. The Circuit Breaker Sizing Process As stated previously the circuit breaker ampacity must be sized so that the tracer start-up current response is under the minimum trip current curve. Or alternatively for a specified circuit breaker, the length of the cable must be sized such that the resulting tracer current response is under the trip curve. For many S/R tracer options, if the maximum current value (current at 3 seconds) is equal or lower than the circuit breaker rating, the tracer start-up current response is under the breaker trip curve (there is no intersection). Figure 7 shows an example. Note that the tracer start-up curve is under the breaker trip curve at all points. This could be a case where the S/R tracer maximum current at 3 sec is just under 2 A and the breaker rating is 2 A. Fig 8a: Typical QO GFI Breaker Trip Curve Fig. 8a: Typical North American Breaker Trip Curve Fig 7: Typical QO GFI Breaker Trip Curve Fig. 7: Typical Maximum North Amps American - % Loading Breaker Trip Curve Maximum Amps - at % Loading Fig 8b: Typical European Type B Breaker Trip Curve Fig. 8b: Typical IEC Type B Breaker Trip Curve Form TT22-79 3

Sizing Circuit Breakers for Self-Regulating Heat s To prevent the breaker tripping, both start-up current curves must be shifted to the left so there is no intersection. This shift can be quantified as percentage of the breaker rating. The resulting percentage value is used to de-rate the effective breaker ampacity or circuit length on % loading. This is shown in Figure 9(a) and 9(b). To avoid an intersection the tracer start-up curve had to be shifted left to 8% of the breaker rating in Figure 9(a) and to 7% of the breaker rating in Figure 9(b). For the North American breaker example, the intersection occurred in the first seconds. For the IEC Type B breaker, the intersection occurred at time + with peak current. If both breakers in these examples had a 2 A rating, the allowable maximum current would be 6 A and 4 A, respectively, not 2 A. So now the question is, How is maximum current established?. Previously, maximum current was defined as: Maximum Current the current level after the heat tracer has attained its equilibrium temperature above the pipe temperature (usually 3 seconds after energization). This is the steady-state current for the S/R cable at the specified start-up temperature at the top or maximum end of the manufacturing power output tolerance. Refer to the top line indicated as Max in Figure for an example. 8 7 Value for -2 C Start-up Fig 9a: Typical QO GFI Breaker Trip Curve Fig. 9a: Typical Maximum North Amps American - 8% Loading Breaker Trip Curve Maximum Amps - at 8% Loading Power Output (W/m) 6 5 Max Min 4 3 2-6 -5-4 -3-2 - 2 3 4 5 6 7 Pipe Temperature C Fig 9b: Typical European Type B Breaker Trip Curve Maximum Amps - 7% Loading Fig. 9b: Typical IEC Type B Breaker Trip Curve Maximum Amps - at 7% Loading Fig. : Max/Min Power Output as a Function of Pipe Temperature The minimum power output curve, bottom line indicated as Min, is used for design to make up the pipe heat loss. With the self-regulating slope characteristic, the lower the pipe temperature the higher the power and resulting current. This is why circuit breaker sizing data is shown for various start-up temperatures. To be conservative the maximum power output curve or tolerance is used for the maximum current value in circuit breaker sizing. Form TT22-79 4

Sizing Circuit Breakers for Self-Regulating Heat s Here is an example of circuit breaker sizing using the basic steps outlined in the preceding discussion. Given: A 24 Vac operating voltage A specified North American circuit breaker with an rating of 2 A Start-up temperature of -2º C A S/R freeze protection tracer with 33 W/m at º C (a -2 type cable) What is the maximum length of tracer that can be applied to the specified North American circuit breaker for the above conditions? Step - When the S/R -2 normalized current response is applied to the North American circuit breaker minimum trip curve the offset or loading factor is found to be 8%. (Refer to Fig. 9a) Step 2 - The specified ampacity for the North American circuit breaker is 2 A. The effective ampacity to avoid tripping with the 8% loading factor is 6 A. Step 3 - For a start-up at -2º C the maximum power output of the S/R -2 heating cable is 57 W/m. At 24 Vac the corresponding maximum current is.24 A/m. Refer to Fig.. Step 4 - By dividing the maximum current of.24 A/m into the effective ampacity of the 2 A North American circuit breaker of 6 A, the resulting length is 67 m. This is the maximum length of the S/R -2 cable that can be applied to the 2 A North American circuit breaker for a -2º C start-up. Summary The sizing of a circuit breaker with an S/R tracer depends on a number of factors: () start-up temperature, (2) tracer start-up current characteristic, (3) circuit breaker type, and (4) circuit breaker ampacity. This ThermoTip has shown how circuit breaker sizing or establishing a maximum circuit length for a given circuit breaker is accomplished. While this process may seem somewhat complex, Thermon s CompuTrace design program quickly and easily performs these basic steps according to the user input values for circuit breaker type and ampacity rating found under the SETTINGS tab of the program. Note that Maximum Current in CompuTrace output should not be used for sizing circuit breakers. The circuit breaker sizing tables found on Thermon specification sheets for self-regulating tracers are also based on these basic steps. In conclusion, use Thermon s CompuTrace design program or the tracer specification sheets for determining maximum tracer circuit lengths. Form TT22-79 5