Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009



Similar documents
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

Introduction. Harmonics and IEEE 519 Page 1 of 19

Practical Overview of Mine Power System Harmonics

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage

Product Data Bulletin

Power Quality Standards for Electric Service

Typical Data Requirements Data Required for Power System Evaluation

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Power System Harmonics

APPLICATION OF IEEE STD HARMONIC LIMITS

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Current transformer selection guide

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin

Short Circuit Current Calculations

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks

Rule Fast Track Analysis for National Life Insurance Co.

Harmonic Distortion and Variable Frequency Drives

APPLICATION OF IEEE STD HARMONIC LIMITS

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Design of Electrical Power Supply System in an Oil and Gas refinery. Master of Science Thesis in Electric Power Engineering

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

LM1036 Dual DC Operated Tone/Volume/Balance Circuit

Module Title: Electrotechnology for Mech L7

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Radial Distribution Test Feeders

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

Nuclear Power Plant Electrical Power Supply System Requirements

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Neutral Currents in Three Phase Wye Systems

Variable Frequency Drives and Energy Savings

CONSULTANT REPORT. Behavior of Two Capstone 30kW Microturbines Operating in Parallel with Impedance Between Them CALIFORNIA ENERGY COMMISSION

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

The design and performance of Static Var Compensators for particle accelerators

21 st Century Facilities

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

ETAP Validation Cases and Comparison Results

3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS

Checking Capacitor Banks for Failed Capacitors

PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

Three phase circuits

Power Factor The Basics

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

ECONOMIC AND ELECTRICAL BENEFITS OF HARMONIC REDUCTION METHODS IN COMMERCIAL FACILITIES

EEL303: Power Engineering I - Tutorial 4

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

How To Improve Power Quality

Line Reactors and AC Drives

Joslyn Clark Controls, Inc.

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

Part 1 System Modeling & Studies for Existing Systems

Loading Considerations When Paralleling Transformers

Simulation of Cable Overloading Problem on a University Distribution System

SECTION VARIABLE FREQUENCY DRIVES

Running a Load Flow Analysis

Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants

Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

POWER FACTOR CORRECTION

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Specifying a Variable Frequency Drive s

7. Reactive energy compensation

HVAC Applications. VFD considerations for HVAC systems...

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer

EARTHING SYSTEM CALCULATION

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

Kinetic energy recovery on railway systems with feedback to the grid

Creating a One-line Diagram

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Hyperlinks are Inactive

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

CS4525 Power Calculator

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters

Electrical Fault Level Calculations Using the MVA Method

CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland

HVDC Light, a tool for electric power transmission to distant loads

Medium voltage circuit breaker

DRIVING LOOOONG CABLES

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

HARMONICS AND HOW THEY RELATE TO POWER FACTOR. W. Mack Grady The University of Texas at Austin Austin, Texas 78712

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

FREQUENCY RESPONSE ANALYZERS

LM 358 Op Amp. If you have small signals and need a more useful reading we could amplify it using the op amp, this is commonly used in sensors.

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Step Voltage Regulators

Switch board datasheet EB

Transcription:

PotashCorp New Brunswick Division Picadilly Potash Project ETAP SIMULATION Prepared by: Carlos Reinel Senior Engineer R&D Department Power Survey International Approved by: Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009 Page 1 of 15

TABLE OF CONTENTS 1. GENERAL 1.1 Purpose of this Study 1.2 Data Available 1.3 Assumptions 1.4 Summary 2. RESULTS 2.1 ETAP Single Line Diagram 2.2 Current and Voltage Harmonics at PCC 2.3 Filter Currents 2.4 Capacitor Voltages 2.5 Conclusions 3. APPENDIX 3.1 IEEE Guidelines Page 2 of 15

1. GENERAL 1.1 Purpose of this Study The purpose of this study is to check the harmonic distortion at the Point of Common Coupling in compliance with IEEE 519 guidelines. This study is based on available data as indicated in the next section. The system simulation has been performed using ETAP Software Version 5.5.6 1.2 Data Available Following files and documents were available: Penobsquis VFD MCCs.pdf Motor List Picadilly VFD MCCs.pdf Motor List Load Distribution for Cap Banks Pic and Pen.xls Excel Spreadsheet PSMV1003-1.dwg Drawing # 130-20-10000 PSMV1003-1.dwg Drawing # 130-20-10001 PSMV1003-2.dwg Drawing # 130-20-10002 320-20-41201%20R1_6142-1.pdf System Layout Page 3 of 15

Filter Data BANKS 1,2 Step1 Nominal 2000 KVAR Effective 2011 KVAR @ 13.8 KV C 26.74 µf / ph C 6x500.06 KVAR @ 9.96 KV XL 4.490 Ohms N 4.70 h Step2 Nominal 2000 KVAR Effective 1968 KVAR @ 13.8 KV C 27.86 µf C 6x500.73 KVAR @ 9.96 KV XL 2.199 Ohms N 6.58 h BANKS 3, 4, 5 Step1 Nominal 2500 KVAR Effective 2632 KVAR @ 13.8 KV C 35.00 µf C 6x600.45 KVAR @ 9.54 KV XL 3.431 Ohms N 4.70 h Step2 Nominal 2500 KVAR Effective 2572 KVAR @ 13.8 KV C 35.00 µf C 6x600.39 KVAR @ 9.54 KV XL 1.751 Ohms N 6.58 h Step3 Nominal 2500 KVAR Effective 2535 KVAR @ 13.8 KV C 34.98 µf C 6x600.07 KVAR @ 9.54 KV XL 0.706 Ohms N 10.34 h Serving you since 1948 Page 4 of 15

1.3 Assumptions Following the data specified above and having installed the one line diagram on ETAP, the following assumptions were made: Utility: Isc = 4.18 ka sym. @ 138 kv 1,000 MVA Tie-breakers Open at all voltage levels Feeder 1007A Open Harmonic Injections As per Amec Specifications #156930-E-SP-16331, Section 2.2 Sources of Harmonic Currents, pages 14-16 Page 5 of 15

1.4 Summary Harmonic Currents - IEEE519 Compliance As per Section 2.2 of this report, a compliance with IEEE 519 guidelines was found for the simulated system at the PCC point. The only remark due is that the mine hoist drives do not show any low end harmonic injection for n < 35, but adding limited harmonics (less than 5%) below that frequency does not change the results. Page 6 of 15

2. RESULTS 2.1 ETAP Single Line Diagram Page 7 of 15

Page 8 of 15

2.2 Current and Voltage Harmonics at PCC Serving you since 1948 The following table shows the harmonic currents at the primary side of the main 40 MVA 138/13.8 kv transformers T303 and T304: T303 T304 T303 T304 [%] [%] Amp Amp 1 IEEE 100 100 115.06 96.20 5 4 0.2750 0.3243 0.32 0.31 7 4 0.0347 0.0532 0.04 0.05 11 2 0.0105 0.0211 0.01 0.02 13 2 0.0122 0.0271 0.01 0.03 17 1.5 0.0088 0.0188 0.01 0.02 19 1.5 0.0083 0.0169 0.01 0.02 23 0.6 0.0055 0.0100 0.01 0.01 25 0.6 0.0039 0.0073 0.00 0.01 29 0.6 0.0040 0.0071 0.00 0.01 31 0.6 0.0035 0.0066 0.00 0.01 35 0.3 0.0731 0.1439 0.08 0.14 37 0.3 0.0469 0.0906 0.05 0.09 41 0.3 0.0017 0.0024 0.00 0.00 43 0.3 0.0018 0.0024 0.00 0.00 47 0.3 0.0588 0.1042 0.07 0.10 49 0.3 0.0467 0.0811 0.05 0.08 59 0.3 0.0172 0.0282 0.02 0.03 61 0.3 0.0105 0.0169 0.01 0.02 71 0.3 0.0037 0.0056 0.00 0.01 73 0.3 0.0075 0.0113 0.01 0.01 THD 5 0.3016 0.3970 The above table show comfortable compliance with IEEE limits for Isc/IL < 20 (most demanding condition, worst case possible). Page 9 of 15

The following table shows the voltage harmonics at the main 13.8 kv busses SGR303 and SGR304 (40 MVA main transformers, secondary side): SGR303 SGR304 SGR303 SGR304 [%] [%] Volts Volts 1 100 100 13800 13800 5 0.1511 0.1501 20.85 20.71 7 0.0291 0.0336 4.02 4.64 11 0.0142 0.0196 1.96 2.71 13 0.0209 0.0300 2.89 4.14 17 0.0193 0.0274 2.67 3.78 19 0.0199 0.0277 2.74 3.82 23 0.0151 0.0201 2.08 2.77 25 0.0116 0.0158 1.61 2.17 29 0.0134 0.0179 1.84 2.47 31 0.0126 0.0177 1.74 2.44 35 0.3161 0.4416 43.63 60.94 37 0.2114 0.2945 29.17 40.64 41 0.0073 0.0088 1.01 1.22 43 0.0076 0.0091 1.05 1.26 47 0.3169 0.4364 43.73 60.22 49 0.2590 0.3553 35.74 49.03 59 0.1091 0.1503 15.05 20.74 61 0.0678 0.0934 9.36 12.89 71 0.0267 0.0367 3.68 5.06 73 0.0551 0.0757 7.60 10.44 THD 0.60 0.82 Voltage THD values are well below IEEE limit of 3% for Special Applications (worst case). Page 10 of 15

2.3 Filter Currents The following tables show the filter currents for the different filter steps: F1.STP1 F1.STP2 F1.STP1 F1.STP2 F3.STP1 F3.STP2 F3.STP3 F3.STP1 F3.STP2 F3.STP3 [%] [%] Amps Amps [%] [%] [%] Amps Amps Amps 1 100 100 83.13 81.37 100 100 100 109.81 107.32 105.75 5 5.4861 1.7564 4.56 1.43 4.9544 1.7440 0.9789 5.44 1.87 1.04 7 0.1866 1.7576 0.16 1.43 0.1590 1.2774 0.3724 0.17 1.37 0.39 11 0.0466 0.1189 0.04 0.10 0.0332 0.0841 0.8508 0.04 0.09 0.90 13 0.0567 0.1328 0.05 0.11 0.0388 0.0904 0.4394 0.04 0.10 0.46 17 0.0372 0.0811 0.03 0.07 0.0256 0.0556 0.1852 0.03 0.06 0.20 19 0.0331 0.0708 0.03 0.06 0.0231 0.0493 0.1527 0.03 0.05 0.16 23 0.0194 0.0407 0.02 0.03 0.0141 0.0294 0.0841 0.02 0.03 0.09 25 0.0139 0.0290 0.01 0.02 0.0099 0.0205 0.0572 0.01 0.02 0.06 29 0.0135 0.0278 0.01 0.02 0.0096 0.0197 0.0533 0.01 0.02 0.06 31 0.0124 0.0255 0.01 0.02 0.0084 0.0172 0.0460 0.01 0.02 0.05 35 0.2743 0.5597 0.23 0.46 0.1834 0.3735 0.9829 0.20 0.40 1.04 37 0.1727 0.3517 0.14 0.29 0.1150 0.2338 0.6117 0.13 0.25 0.65 41 0.0046 0.0094 0.00 0.01 0.0035 0.0072 0.0186 0.00 0.01 0.02 43 0.0046 0.0093 0.00 0.01 0.0035 0.0071 0.0182 0.00 0.01 0.02 47 0.2002 0.4053 0.17 0.33 0.1302 0.2632 0.6757 0.14 0.28 0.71 49 0.1562 0.3160 0.13 0.26 0.1012 0.2044 0.5235 0.11 0.22 0.55 59 0.0547 0.1104 0.05 0.09 0.0339 0.0682 0.1733 0.04 0.07 0.18 61 0.0329 0.0663 0.03 0.05 0.0202 0.0406 0.1031 0.02 0.04 0.11 71 0.0111 0.0223 0.01 0.02 0.0065 0.0131 0.0331 0.01 0.01 0.03 73 0.0222 0.0447 0.02 0.04 0.0129 0.0260 0.0657 0.01 0.03 0.07 THD % 5.51 2.63 4.97 2.24 2.05 IRMS A 83.26 81.40 109.95 107.35 105.77 Where: F1.STP1 is Filter 1 Step1, etc. Note: Only Filters 1 and 3 are listed above. The fundamental and harmonic currents of Filter 2 are almost identical as for Filter 1. The fundamental and harmonic currents of Filters 4 and 5 are almost identical as for Filter 3. This is because the currents depend mainly on the filter components (Filter 1 and 2 are identical and Filters 3 to 5 are identical). The bus impedances are also basically identical on each of both filter types, as no cabling has been considered in this simulation and the transformers for feeding each filter type are identical. Loads are all different though, but they do not affect the Z bus /Z filter ratio calculation by any considerable value. This fact was double-checked on the ETAP model. The table above shows there will be no major harmonic over-loading of the filter reactors due to the extremely limited harmonic currents. Page 11 of 15

2.4 Capacitor Voltages The following tables show the filter voltages for the different filter steps: F1.STP1 F1.STP2 F3.STP1 F3.STP2 F3.STP3 Volts Volts Volts Volts Volts 1 13,800 13,800 13,800 13,800 13,800 5 94.42 32.44 101.23 34.83 19.28 7 2.33 18.32 2.36 18.54 5.33 11 0.27 0.67 0.32 0.79 7.90 13 0.31 0.71 0.32 0.72 3.45 17 0.16 0.35 0.16 0.35 1.15 19 0.13 0.28 0.13 0.28 0.84 23 0.07 0.13 0.07 0.13 0.38 25 0.04 0.09 0.04 0.09 0.24 29 0.04 0.07 0.04 0.07 0.19 31 0.03 0.06 0.03 0.06 0.17 35 0.75 1.49 0.75 1.49 3.87 37 0.44 0.88 0.44 0.88 2.28 41 0.01 0.02 0.01 0.02 0.04 43 0.01 0.02 0.01 0.02 0.04 47 0.39 0.78 0.40 0.79 1.99 49 0.29 0.58 0.30 0.58 1.47 59 0.08 0.16 0.08 0.16 0.41 61 0.05 0.09 0.05 0.09 0.24 71 0.01 0.03 0.01 0.03 0.07 73 0.03 0.05 0.03 0.05 0.13 SUM 13,900 13,857 13,907 13,860 13,849 Where: F1.STP1 is Filter 1 Step1, etc. Note: Only Filters 1 and 3 are listed above. Same is valid as for the harmonic currents. Page 12 of 15

2.5 Conclusions As per Section 2.2 of this report, a compliance with IEEE 519 guidelines was found for the simulated system at the PCC point and there will be no major harmonic over-loading of the filter reactors due to the extremely limited harmonic currents of the hoist drives. Voltage harmonics will also not represent any major problem for the capacitors. Some harmonics at the low frequency end could result higher than the predicted values from this model, as some 5 th, 7 th and 11 th harmonics will most likely spill over from the large hoist drives anyhow. A hoist duty cycle would help to improve the accuracy of the predicted harmonic levels considering that peak torque requirements of mine hoist drives for about 10 to 20 seconds every 2 minutes are normally about 200% or even higher. Page 13 of 15

3. APPENDIX 3.1 IEEE Guidelines IEEE 519 Guidelines for Current Distortion Page 14 of 15

IEEE 519 Guidelines for Voltage Distortion Serving you since 1948 Page 15 of 15