QNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT)



Similar documents
Quanser NI-ELVIS Trainer (QNET) Series: QNET HVAC. Heating, Ventilation, and Air Conditioning (HVAC) User Manual. User Manual

A Design of a PID Self-Tuning Controller Using LabVIEW

Lab 3: Introduction to Data Acquisition Cards

Data Acquisition Using NI-DAQmx

Laboratory 4: Feedback and Compensation

2.6. In-Laboratory Session QICii Modelling Module. Modelling Module Description

PID Control. Chapter 10

IPB-IB ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESS CONTROL INDUSTRIAL STEAM BOILERS. BECK VIDEO Scan w/ Smartphone

ε: Voltage output of Signal Generator (also called the Source voltage or Applied

Cell Phone Vibration Experiment

Understanding Power Impedance Supply for Optimum Decoupling

MATERIALS. Multisim screen shots sent to TA.

Manufacturing Equipment Modeling

Lab 4 - Data Acquisition

Chapter 9: Controller design

UNIVERSITY OF WATERLOO ELECTRICAL & COMPUTER ENGINEERING DEPARTMENT ME269 ELECTROMECHANICAL DEVICES AND POWER PROCESSING.

MATLAB Control System Toolbox Root Locus Design GUI

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

Microcontroller-based experiments for a control systems course in electrical engineering technology

AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS

TEACHING AUTOMATIC CONTROL IN NON-SPECIALIST ENGINEERING SCHOOLS

Op-Amp Simulation EE/CS 5720/6720. Read Chapter 5 in Johns & Martin before you begin this assignment.

Experiment #11: LRC Circuit (Power Amplifier, Voltage Sensor)

Inwall Room Temperature Unit

Current Loop Tuning Procedure. Servo Drive Current Loop Tuning Procedure (intended for Analog input PWM output servo drives) General Procedure AN-015

Current and Temperature Ratings

Oscilloscope, Function Generator, and Voltage Division

Industrial Steam System Process Control Schemes

dspace DSP DS-1104 based State Observer Design for Position Control of DC Servo Motor

AC : MATHEMATICAL MODELING AND SIMULATION US- ING LABVIEW AND LABVIEW MATHSCRIPT

Exercise 10: Basic LabVIEW Programming

Experiment 3: Magnetic Fields of a Bar Magnet and Helmholtz Coil

ABB i-bus KNX Fan Coil Controller FC/S 1.1

Experiment 5. Strain Gage Measurements

Experiment 3: Magnetic Fields of a Bar Magnet and Helmholtz Coil

Introduction to LabVIEW for Control Design & Simulation Ricardo Dunia (NI), Eric Dean (NI), and Dr. Thomas Edgar (UT)

Indiana State Core Curriculum Standards updated 2009 Algebra I

Implementing PID Temperature Control Using LabVIEW. Abstract. Introduction

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Technical Guide No High Performance Drives -- speed and torque regulation

Electrical Resonance

See Horenstein 4.3 and 4.4

Understanding Poles and Zeros

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

ELECTRICAL ENGINEERING

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

SERVO CONTROL SYSTEMS 1: DC Servomechanisms

A1000 Cheat Sheet (Open Loop Vector)

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

HEAT HEAT COOL HEAT PUMP COOL

EE 402 RECITATION #13 REPORT

Fundamentals of HVAC Control Systems

Vi, fi input. Vphi output VCO. Vosc, fosc. voltage-controlled oscillator

Degree programme in Automation Engineering

Drivetech, Inc. Innovations in Motor Control, Drives, and Power Electronics

AN105. Introduction: The Nature of VCRs. Resistance Properties of FETs

Lab E1: Introduction to Circuits

EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

VCO Phase noise. Characterizing Phase Noise

Controller Design using the Maple Professional Math Toolbox for LabVIEW

Step Response of RC Circuits

EECE 460 : Control System Design

Lab #9: AC Steady State Analysis

INTERACTIVE LEARNING MODULES FOR PID CONTROL

Experiment 6 ~ Joule Heating of a Resistor

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

DCMS DC MOTOR SYSTEM User Manual

Pulse Width Modulation (PWM) LED Dimmer Circuit. Using a 555 Timer Chip

HIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER

Case study: how to use cutoff conditions in a FRA frequency scan?

Control System Definition

Algebra 1 Course Information

Annex: VISIR Remote Laboratory

Dr. Yeffry Handoko Putra, S.T., M.T

Design of a TL431-Based Controller for a Flyback Converter

G(s) = Y (s)/u(s) In this representation, the output is always the Transfer function times the input. Y (s) = G(s)U(s).

Experiment 4: Sensor Bridge Circuits (tbc 1/11/2007, revised 2/20/2007, 2/28/2007) I. Introduction. From Voltage Dividers to Wheatstone Bridges

Impedance 50 (75 connectors via adapters)

Frequency Response of Filters

Input and Output Capacitor Selection

FREQUENCY RESPONSE ANALYZERS

LabVIEW Day 1 Basics. Vern Lindberg. 1 The Look of LabVIEW

Cod. Documento: RT a Title: Fimer Plant Controller Description. Rev. Data Redatto Approvato S.Sidoti A.

Dash 18X / Dash 18 Data Acquisition Recorder

Power supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E

Evaluation copy. Build a Temperature Sensor. Project PROJECT DESIGN REQUIREMENTS

BJT Characteristics and Amplifiers

VCO K 0 /S K 0 is tho slope of the oscillator frequency to voltage characteristic in rads per sec. per volt.

School of Engineering Department of Electrical and Computer Engineering

ECE 3510 Final given: Spring 11

Algebra I Credit Recovery

RLC Series Resonance

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

[F/T] [5] [KHz] [AMP] [3] [V] 4 ) To set DC offset to -2.5V press the following keys [OFS] [+/-] [2] [.] [5] [V]

Best Practices for Controller Tuning

TwinCAT NC Configuration

EE 1202 Experiment #4 Capacitors, Inductors, and Transient Circuits

Chapter 11 Current Programmed Control

Application Note #49 RF Amplifier Output Voltage, Current, Power, and Impedance Relationship

Transcription:

Quanser NI-ELVIS Trainer (QNET) Series: QNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT) Student Manual

Table of Contents 1. Laboratory Objectives...1 2. References...1 3. Pre-Lab Assignments...1 3.1. Pre-Lab Assignment #1: Open-Loop Transfer Function...1 3.2. Pre-Lab Assignment #2: Closed-Loop Transfer Function...3 3.3. Pre-Lab Assignment #3: Controller Design...6 3.4. Pre-Lab Assignment #4: Final Controller Design...8 3.4.1. Heating Control Loop...8 3.4.2. Blowing Control Loop...11 3.4.3. Final Temperature Control Laws...12 4. In-Lab Session...12 4.1. System Hardware Configuration...12 4.2. Experimental Procedure...13 Document Number: 578 Revision: 01 Page: i

1. Laboratory Objectives The objective of this experiment is to design a temperature closed-loop controller that meets required specifications. The system should track and/or regulate the desired chamber temperature with minimum peak time and overshoot. A pre-requisite to this laboratory is to have successfully completed the system identification experiment described in Reference [3]. This laboratory is consistent with the system nomenclature used in Reference [3]. Regarding Gray Boxes: Gray boxes present in the instructor manual are not intended for the students as they provide solutions to the pre-lab assignments and contain typical experimental results from the laboratory procedure. 2. References [1] NI-ELVIS User Manual. [2] QNET-HVACT User Manual. [3] QNET Experiment #05: HVAC System Identification. 3. Pre-Lab Assignments This section must be performed before you go to the laboratory session. 3.1. Pre-Lab Assignment #1: Open-Loop Transfer Function In a first approach and in the present laboratory, the HVACT system is assumed to be a Single-Input-Single-Output (SISO) plant. This is motivated by the fact that both heating and blowing processes have first-order transfer functions, G h and G b respectively, with similar system parameters. While the controlled output is always the chamber temperature T c, the controlled input is either the heater or the blower voltage (but not both simultaneously) depending on whether the chamber needs to heated up or cooled down. Such a switching mechanism results in a "decoupling" between the the two inputs. The remaining HVAC input voltage is "disabled" Document Number: 578 Revision: 01 Page: 1

and set to zero. Therefore, the HVAC open-loop chamber transfer function, G c (s), from input voltage to chamber temperature difference can be defined such as: T G c ( s ) = c ( s ) K ss_c = [1] V ( ) c s τ c s + 1 where the model variables are defined in Table 1, below. Symbol Description Unit V c Chamber Command Voltage V K ss_c Chamber Open-Loop Steady-State Gain ºC/V τ c Chamber Open-Loop Time Constant s s Laplace Operator rad/s Table 1 HVAC SISO Model Nomenclature As described in Reference [3], it is reminded that the temperature difference, T c,isthe difference between the actual chamber temperature, T c, and the assumed-constant ambient temperature, T a. The first-order transfer function parameters of Equation [1] can be calculated as the average values of the model identified in Reference [3]. This is shown below: 1 K ss_c = + 2 K 1 ss_h 2 K ss_b and τ 1 = + c 2 τ 1 h 2 τ b [2] 1. From the system estimates obtained in Reference [3], obtain a numerical expression for the chamber open-loop steady-state gain K ss_c and time constant τ c, as defined in Equation [2]. Document Number: 578 Revision: 01 Page: 2

Evaluating K ss_c, as defined in Equation [2], leads to:. [s1] Evaluating τ c, as defined in Equation [2], results to:. [s2] 2. What is the type of the system? What can you infer about the resulting steady-state error? As defined in Equation [1], the system does not have any pole at the origin of the s- plane. Therefore, it is of type zero. It results that the open-loop system has a steadystate error to a step input and cannot follow a ramp. 3.2. Pre-Lab Assignment #2: Closed-Loop Transfer Function The purpose of the laboratory is to design a controller that allows us to command the chamber temperature to a desired level with no steady-state error. Therefore, a Proportional-plus-Integral (PI) control scheme is first chosen. This results in a temperature closed-loop diagram similar to the one illustrated in Figure 1, below. Figure 1 Temperature PI Control Loop Document Number: 578 Revision: 01 Page: 3

The PI control law implemented in the block diagram of Figure 1 can be formulated as follows: V c ( t ) = K p T c_e ( t) + K i T c_e ( t) dt [3] where the temperature error, T c_e, can be expressed as shown underneath: T c_e ( t ) = ( T c_r ( t ) T c ( t ) = T c_r ( t ) T c ( t )) [4] The corresponding control loop gains and variables are enumerated in Table 2, below. Symbol Description Unit K p Proportional Gain V/ºC K i Integral Gain V/s/ºC T c_r Reference Chamber Temperature (i.e. Setpoint) ºC T c_e Chamber Temperature Error ºC Table 2 PI Control Loop Nomenclature The sign of the command voltage V c, as calculated in Equation [3], can then be used to implement the switching strategy between the plant two possible inputs, that is to say V h and V b. Specifically, the sign of V c determines whether the chamber needs to heated up (i.e. V h is controlled by the PI loop and V b is set to zero) or cooled down (i.e. V h is set to zero and V b is controlled by the PI loop). Such a switching strategy is formulated by Equation [5] below: V h ( t ) = { V c ( t ) 0 ( t ) V c 0 V c ( t ) < 0 and V b ( t ) = { 0 0 ( t ) V c V c ( t ) V c ( t ) < 0 [5] 1. The resulting closed-loop transfer function, T CL (s), of the PI control system is defined in the Laplace domain as follows: T c ( s ) T CL ( s ) = [6] T c_r ( s ) Using the control block diagram [1] and/or Equation [3], derive the expression of T CL (s) as a function of the system parameters (K ss_c and τ c ) and the PI controller gains (K p and K i ). Document Number: 578 Revision: 01 Page: 4

The resulting closed-loop transfer function can be expressed as: [s3] 2. T CL (s) should be a second-order system whose denominator can be expressed under the following standard form: s 2 2 + 2 ζω n s + ω n where s is the Laplace operator, ζ the damping ratio, and ω n frequency. [7] the undamped natural Derive expressions for the proportional and integral gains, K p and K i, as functions of the system parameters, the damping ratio ζ, and natural frequency ω n. Identifying the coefficients of the two quadratic polynomials of Equations [s3] and [7] and solving for K p and K i results for the proportional gain to: [s4] and for the integral gain to: [s5] 3. For such quadratic systems, it is reminded from classic control theory that the response peak time, t p, can be expressed as: π t p = 1 ζ 2 [8] ω n Likewise the response Percent Overshoot (PO) can be formulated as: Document Number: 578 Revision: 01 Page: 5

PO = 100 e π ζ 1 ζ 2 [9] Derive expressions for the proportional and integral gains, K p and K i, as functions of the system parameters, the damping ratio ζ, and the time to first peak, t p. Solving Equation [8] for ω n, substituting the obtained expression into Equations [s4] and [s5], and rearranging result for the proportional gain to be such as: [s6] and for the integral gain to be expressed by: [s7] 3.3. Pre-Lab Assignment #3: Controller Design 1. Additionally to exhibiting no steady-state error to a step input, the temperature closedloop response is desired to achieve the following design specifications in terms of peak time, t p, and damping ratio, ζ: t p = 20.0 [ s ] and ζ = 0.56 [10] Calculate the proportional and integral gains, K p and K i, required to satisfy the design requirements stated in Equation [10]. Document Number: 578 Revision: 01 Page: 6

Evaluating Equation [s6] for the design requirements expressed in Equation [10] and with the system parameters found in Equations [s1] and [s2] leads to the following value for K p : [s8]. Likewise evaluating Equation [s7] for the design requirements expressed in Equation [10] and with the system parameters found in Equations [s1] and [s2] leads to the following value for K i : [s9]. 2. What is the desired Percent Overshoot (PO)? The desired ζ, as defined in Equation [10], results in the following Percent Overshoot (PO):. [s10] 3. Finally the designed PI control loop will operate around the following operating temperature level, T c_op : T c_op = 32.0 [ degc ] [11] If the chamber temperature setpoint variation, T c_r, is a square wave of 2-degree- Celsius amplitude around T c_op, to what values do you expect the temperature to overshoot to? Document Number: 578 Revision: 01 Page: 7

With a square wave setpoint variation, T c_r, of 2 degrees Celsius, the peak-to-peak signal is 4 degrees. It is reminded that the overshoot is applied to the peak-to-peak value and added to the reference signal. Therefore, the temperature response overshoot, T c_peak, can be expressed for a positive (i.e. rising) step input as follows: where represents the absolute value function. [s11] Evaluating the expression above, the positive overshoot value T c_peak is expected to be such as: [s12] 3.4. Pre-Lab Assignment #4: Final Controller Design The temperature Proportional-plus-Integral (PI) control scheme previously developed and illustrated in Figure 1, above, is improved in this section to better suit the characteristics of each of the heating and cooling processes, both composing the HVAC system. Therefore although based on the same standard PI loop, two slightly different control schemes are designed hereafter in order to better accommodate the physical particularities of each process. As previously defined in Equation [5], it is reminded that the switching logic between the heating and cooling control loops is still determined by the sign of V c. 3.4.1. Heating Control Loop For a more effective heating control loop, the basic PI scheme shown in Figure 1, above, is complemented with a feed-forward action, an offset voltage, and an integrator anti-windup element, as illustrated by the block diagram shown in Figure 2, below. Document Number: 578 Revision: 01 Page: 8

Figure 2 Heating Control Loop: Active Iff V c 0 It is reminded that the heating control loop effectively commands the heater input voltage, V h, and is only active if and only if V c is positive. The basic chamber command voltage V c is calculated accordingly to the PI control law formulated in Equation [3]. Also during the heating process, the blower input voltage remains constant and set to zero, as expressed below: V b ( t ) = 0 [12] where t is the continuous time. The complete control law for heating, as depicted by the block diagram of Figure 2 above, can be expressed as: V h ( t ) = V c ( t ) + V h_ff ( t ) + V h_off [13] where V h_off is the heater offset voltage and V h_ff is the heater feed-forward voltage as defined by: V h_ff ( t ) = K ff_h ( T c_r ( t ) T a ) [14] with T a the ambient temperature outside of the chamber, T c_r the desired chamber temperature, and K ff_h the heater feed-forward gain. Feed-forward action is necessary to bring and maintain the chamber temperature to the desired level. It compensates for the standard air cooling in the chamber due to natural heat Document Number: 578 Revision: 01 Page: 9

dissipation. The PI control system compensates for small variations (e.g. disturbances) from that operating point. 1. Using the definition of the heater steady-state gain K ss_h, characterize the heater voltage feed-forward gain K ff_h, as defined in Equation [14]. Hint: It is reminded that in the steady-state V h_ff is the voltage required to maintain T c at the desired level T c_r. The heater feed-forward gain can be expressed by: [s13] 2. From the parameters of the heating transfer function G h (s) estimated in Reference [3], calculate the numerical value of K ff_h? Evaluating Equation [s13] with the heater steady-state gain, K ss_h, estimated in Reference [3] and shown in Equation [s18] of Reference [3] leads to: [s14] The heater constant offset voltage, V h_off, is included in Equation [13] in order to compensate for the halogen lamp deadband. The actuator behaviour, resulting from such a deadband compensation will be more linear around small input voltages. V h_off has been estimated in Reference [3] as the upper limit of the heating actuator deadzone. The anti-windup element in the feedback loop stops the integral action when the actuator saturates to prevent large overshoots in the response. The HVAC heater saturates at V h_max. When this limit is reached, the surplus voltage is multiplied by the gain K a and the result is removed from the integrator input. The anti-windup element is implemented using a deadzone nonlinearity with a slope of K a, as shown in Figure 2. Document Number: 578 Revision: 01 Page: 10

3.4.2. Blowing Control Loop Likewise for a more effective blowing control loop, the basic PI scheme shown in Figure 1, above, is complemented with a constant offset voltage used for actuator deadband compensation and an anti-windup scheme. The resulting control scheme is illustrated by the block diagram shown in Figure 3, below. Figure 3 Blowing Control Loop: Active Iff V c < 0 It is reminded that the blowing (or cooling) control loop effectively commands the blower input voltage, V b, and is only active if and only if V c is negative. The basic chamber command voltage V c is calculated accordingly to the PI control law formulated in Equation [3]. Also during the cooling process, the heater input voltage remains constant and set to zero, as expressed below: V h ( t ) = 0 [15] where t is the continuous time. The complete control law for blowing, as depicted by the block diagram of Figure 3 above, can be expressed as: V b ( t ) = V c ( t ) + V b_off [16] where represents the absolute value function and V b_off is the blower offset voltage. Since V c is negative during blowing, the absolute value is required to send a positive command voltage to the blower (i.e. fan). Document Number: 578 Revision: 01 Page: 11

The blower constant offset voltage, V b_off, is included in Equation [16] in order to compensate for the fan deadband. V b_off has been estimated in Reference [3] as the upper limit of the fan deadzone. The blower saturates at V b_max. Similarly to the heating control loop, the integrator is "turned off" when V b_max is reached to prevent large overshoots that can result from the integrator charging up too much. The same deadzone nonlinearity slope K a is used. 3.4.3. Final Temperature Control Laws To summarize and reformulate the previous design considerations, the two actuator input voltages are completely defined below by Equations [17] and [18]. Using Equations [13] and [15], the heater input voltage is calculated as defined below: V c ( t ) + V h_ff ( t ) + V h_off 0 V c ( t ) V h ( t ) = { 0 V c ( t ) < 0 [17] Likewise using Equations [14] and [16], the blower input voltage is determined as follows: 0 0 V c ( t ) V b ( t ) = { [18] V c ( t) + V b_off V c ( t ) < 0 4. In-Lab Session 4.1. System Hardware Configuration This in-lab session is performed using the NI-ELVIS system equipped with a QNET- HVACT board and the Quanser Virtual Instrument (VI) controller file QNET_HVAC_Lab_06_PI_Control.vi. Please refer to Reference [2] for the setup and wiring information required to carry out the present control laboratory. Reference [2] also provides the specifications and a description of the main components composing your system. Before beginning the lab session, ensure the system is configured as follows: QNET HVACT module is connected to the ELVIS. ELVIS Communication Switch is set to BYPASS. DC power supply is connected to the QNET HVAC Trainer module. Document Number: 578 Revision: 01 Page: 12

The 4 LEDs +B, +15V, -15V, +5V on the QNET module should be ON. 4.2. Experimental Procedure Please follow the steps described below: Step 1. Read through Section 4.1 and go through the setup guide in Reference [2]. Step 2. Open the VI controller file QNET_HVAC_Lab_06_PI_Control.vi. You should obtain a front panel similar to the one shown in Figure 4, below. The default sampling rate for the implemented digital controller is 250 Hz. However, you can adjust it to your system's computing power. Please refer to Reference [2] for a complete system's description. The chamber temperature, directly sensed by the thermistor, is plotted on a chart (in red) as well as displayed in a Numeric Indicator located in the Chamber Temperature front panel box. The values are in degrees Celsius. Figure 4 Front Panel Used for the QNET-HVACT Temperature Control Laboratory Step 3. The vertical toggle switch in the Setpoint Type box allows you to choose Document Number: 578 Revision: 01 Page: 13

between a Square Wave or a Constant type of reference temperature, T c_r. Ensure that it is set to the Square Wave position. The temperature setpoint is also plotted on the front panel chart (in blue). Use the Numeric Controls of the Setpoint Properties box to set the chamber operating temperature, T c_op,to32 C(asexpressedinEquation [11]), the square wave Amplitude to -2 C, and Period to 150 seconds. Specifically the setpoint properties parameters are expressed in Table 3, below. Signal Type T c_op [ C] Amplitude [ C] Period [s] Square Wave 32.0-2.0 150.0 Table 3 Temperature Setpoint Parameters Step 4. When you first open the QNET_HVAC_Lab_06_PI_Control.vi controller file, the default controller gains are not yet tuned. An example of "untuned" controller parameters is provided in Table 4, below. K p K i K ff_h T a Ka V h_off [V/ C] [V/s/ C] [V/ C] [ C] [ C/V] [V] [V] 3.50 1.50 0.00 22.5 0.0 0.0 0.0 Table 4 "Untuned" Controller Parameters V b_off Run the LabVIEW VI (Ctrl+R) to start the controller. Ensure the initially green START push button is pressed and shown as a red STOP button to activate the controller. This button can be used to pause the controller execution. With the control action active, the chamber temperature should now go up and down to roughly track the desired square wave setpoint. You should obtain an "untuned" temperature response similar to the one depicted in Figure 4, above. After a few periods, you can stop the VI by pressing the red EXIT button on the front panel. Step 5. Using the Numeric Controls of the Controller Gains box, you should enter the system controller gains, namely K p,k i and K ff_h, that you have calculated in the prelab section. Also enter the ambient temperature (T a, in C) present outside of the HVAC chamber. Set the value of K a to 0.0 C/V, which effectively turns off the integral anti-windup element in the feedback system. Finally the deadband compensation parameters, V h_off and V b_off, should also be properly set to the values that you estimated in Reference [3]. Do so by using the Numeric Controls of the Deadband Compensation box on the front panel. Summarize your final tuned controller parameters by filling up Table 5 as shown below. Document Number: 578 Revision: 01 Page: 14

K p K i K ff_h T a Ka V h_off V b_off [V/ C] [V/s/ C] [V/ C] [ C] [ C/V] [V] [V] 0.57 0.37 0.07 22.5 0.5 0.8 12.6 Table 5 Tuned Controller Parameters Step 6. Start the controller by running the LabVIEW VI (Ctrl+R) in order to try your calculated gains on the actual system. The software applies square wave temperature setpoints to the closed-loop control system and plots both setpoint and actual chamber temperature over a 350-second time range. Observe the way the system switches between the two actuators (i.e. lamp and fan) in order for the chamber temperature to track the desired square wave setpoint around the operating level T c_op. Step 7. Let the system run until you have plotted on the chart the temperature response to 2 heating steps and to 2 cooling steps (at least the overshoot and peak time part of it). Step 8. Make a screen capture of the obtained step response plot and join a printout to your report. Document Number: 578 Revision: 01 Page: 15

Figure 5, below, illustrates typical experimental results from the designed closedloop system by showing the actual temperature response tracking a desired square wave setpoint. The anti-windup element is not being used in this closed-loop response. Figure 5 Desired And Actual Temperature Signals not using Integrator Anti-windup Step 9. Does the closed-loop system track the desired square wave setpoint accurately? Is there any steady-state error? Comment on the symmetry (or lack of) of the temperature response between heating and blowing steps. Explain. The system tracks the desired temperature square wave with considerable steadystate error, which is chiefly due to the integrator charging up too much and causing overshoot and the various nonlinearities of the system not accounted for in the model. As expected, the system has an asymmetrical response: heating behaves differently than cooling (i.e. blowing). Although assumed otherwise in the controller gain calculations, a different process/plant is at play in each case. Document Number: 578 Revision: 01 Page: 16

Step 10. Set the value of K a to 0.2 C/V, which corresponds to slope of the integral antiwindup deadzone to 0.2 C/V, and keep the same values for the other control parameters entered in Table 5. Start the controller by running the LabVIEW VI (Ctrl+R) in order to try your calculated gains on the actual system using the antiwindup element. Observe the effects on the response of having an anti-windup element. Then, adjust K a to improve the response and enter the tuned parameter in Table 5, above. Step 11. Let the system run until you have plotted on the chart the temperature response to 2 heating steps and to 2 cooling steps (at least the overshoot and peak time part of it). Step 12. Make a screen capture of the obtained step response plot and join a printout to your report. Figure 6, below, illustrates typical experimental results from the designed closedloop system using the anti-windup element by showing the actual temperature response tracking a desired square wave setpoint. Figure 6 Desired And Actual Temperature Signals using Integrator Anti-windup Step 13. You should now measure and determine your system performance from the Document Number: 578 Revision: 01 Page: 17

actual response plot, as displayed on the VI Front Panel. Do so by using the Graph Palette located on top of the Chart top left corner. Fill up Table 6 as shown below. You should have plotted two iterations of both step types, i.e. heating and blowing. First measure the corresponding Percent Overshoot, PO, and peak time, t p,forall4 step responses as specified in Table 6. T c_peak is the overshoot value. Then take the average of PO and t p over the 2 iterations of each step type. Finally, combine and average the results of both step types. What are your final values for PO and t p? Step Type Iteration # T c_peak [ºC] PO [%] t p [s] Heating 1 34.05 1.25 12.5 2 34.05 1.25 12.5 Average: X 1.25 0.0 Blowing 1 30.15 3.75 18.5 2 30.15 3.75 20.0 Average: X 3.75 0.0 Average Values: X 2.50 0.0 Table 6 Step Response Actual Performance Step 14. Do the measured Percent Overshoot and peak time meet the required specifications? Explain your observations. As measured and calculated in Table 6 above, the measured peak time is globally about 15.9 seconds on average and the Percent Overshoot is approximately to 2.5%. Therefore the t p of the actual system is close to the desired value in [10] and the resulting PO of the device is considerably less than the required value specified in [s10], primarily due to the integrator anti-windup mechanism. Consequently, the required design specifications are met. Step 15. If the design requirements defined by Equation [10] are still not satisfied, you should manually fine tune the controller parameters of Table 5 until the response performance improves to the desired level. Include in your laboratory report your final tuning parameters, experimental plots and results, as well as the measured system performance criteria satisfying the specifications. Step 16. Once all your experimental results are obtained, shut off the PROTOTYPING POWER BOARD switch and the SYSTEM POWER switch at the back of the ELVIS unit. Unplug the module AC cord. Then, stop the VI by pressing the red EXIT button. Document Number: 578 Revision: 01 Page: 18