Repair of Spalling and Leaking Clay Brick Building Walls



Similar documents
Solving Persistent Moisture Problems and Moisture Damage

Basements are Changing. Basements Part of the Enclosure. Basements. Energy Efficient, Durable, Healthy. Below grade enclosure

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

Common Problems with Walls

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

EAST LYME HIGH SCHOOL

Renovating Your Basement

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls

Water Damage & Repair

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

Natatorium Building Enclosure Deterioration Due to Moisture Migration

Exterior Elevated Elements Inspection Guidelines

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

What you need to know about concrete block basement construction.

3 Masonry and Manufactured Stone (Interior and Exterior)

CONDENSATION IN REFRIDGERATED BUILDINGS

Water Management & Damage Prevention:

Building Condition Assessment: West Lexington Street Baltimore, Maryland

Structural Assessment Report

Preventing Ice Dams on Roofs

March 19, Ms. Jean McDonald CAP Management th Street, Suite 1010 Denver, Colorado 80202

Bituminous Sheet Flat Roofs: Their repair and maintenance

Before You Start an Energy Efficiency Retrofit The Building Envelope

COMMONLY USED RESIDENTIAL BUILDING CODES

Page & Turnbull imagining change in historic environments through design, research, and technology

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

Inspecting to a higher standard.

Asphalt Shingle Application Requirements

Excerpts from the Canadian National Building Code (NBC)

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

Basement Moisture Problems

Elevating Your House. Introduction CHAPTER 5

March 14, Installation of Bay, Bow and Garden Windows

ROOFS, SNOW AND ICE DAMS

Molds and mildew are fungi that grow

RDH Building Sciences Inc.

bout your HOUSE before you start Renovating Your Basement Moisture Problems

How To Repair A House

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

Facility Assessment for East Main Street, Huntley, IL

bout your house before you start Renovating Your Basement Moisture Problems

Basement & Foundation Damage

Building Condition Assessment: North Howard Street Baltimore, Maryland

Architectural Condition Survey

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver

Waterproofing and interior insulation for basements takes new twist in technology.

Additions and Alterations

Shingle Roofing: What s below the surface is important

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

PERFORMANCE GUIDELINES

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007

GYPSUM AREA SEPARATION FIREWALLS GA

Metropolitan Builders Association Masonry & Concrete Standard

Superform Products Ltd.

Low-slope reroofing guidelines

Self-Home Inspection Checklist

Post-insulation of cellar ceiling and cellar walls

Fiberglas, Exterior Wall Thermal Insulation

May 5, Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

Basement Insulation Systems

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

Melbourne balcony Assessments

Foundation. Foundation

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri

Certification: Building Plans Examiner. Exam ID: B3

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

R E S I D E N T I A L H O U S I N G

Integrating Healthy Housing Considerations into Weatherization Inspections. Jim LaRue

Engineers, Civil Structural Survey

Leaky Homes Financial Assistance Package (FAP) Repair plan example

Vision Home Inspection

Sample Drawing Package for One and Two Family Dwelling Applications

Chapter 3 Pre-Installation, Foundations and Piers

Signs of insulation problems In the winter. In the summer. conditioning system

Keeping the Heat In 6 Basement insulation

Residential Roofing Guide

Comment Form on Proposed Gut Rehabilitation Alternatives

The Ultimate Guide To Protecting Your House From Water In The Basement

Building Foundation and Structure

Module 3.7. Thermal bridging

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at Forest Drive, Annapolis, MD. Provided by: HurleyIR

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

Tiled Shower Pan Leaks - Investigation And Repair FAQ

Inspection Report. Condo Association. Property Address: 2222 W. Water St. Swamptown, IL. William Decker, IL Lic. #

about your house Before You Start Renovating Your Basement Moisture Problems Figure 1 Moisture problems to solve

Chapter 2 Basis of design and materials

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Transcription:

B etter buildings Repair of Spalling and Leaking Clay Brick Building Walls Overview A few years after being built in Waterloo in 1980, a condominium of three, six-storey buildings showed severe spalling of the clay brick building and site walls and leakage.there was significant masonry damage in three areas: below sloped roofs without eaves or gutters, at roof parapets and at enclosed, uninsulated balconies. Building professionals spent considerable time studying the deterioration of the bricks.the professionals gave conflicting explanations for the damage. It was not until the removal of drywall from the interior face of the exterior walls - after 10 years of recommendations, repairs and legal action - that the deterioration was accurately explained. By this time, there was extensive damage which had reduced the structural integrity of the buildings. after repairs The condominium owners made repairs to ensure a structurally sound building without leakage and falling brick fragments.the total cost of construction, including engineering, was about $1,500,000. Of the total, recladding and structural repair cost $1,125,000. Assessment Existing conditions The exterior clay brick TTW (through-the-wall) walls are load-bearing. Parging was applied to the back face of the bricks. Behind the brick walls there is batt insultation, a polyethelene vapour retarder and drywall fastened to steel studs.there are sloped roofs at the tops of some of the walls and flat roofs with brick parapets elsewhere.

Hambro joists support the 64-mm (2.5-in.) concrete floor slabs.the joists and edges of the floor slabs rest on the TTW walls.the ceiling drywall of the rooms is fastened to the bottom of the joists.the joist space is used as a return air plenum for the heating and cooling systems.the drywall at the exterior walls does not continue above the finished ceilings.the polyethylene vapour barrier is generally in place above the ceiling, but was not completely fastened. Several penthouse balconies, originally planned as exterior balconies, had single-glazed enclosures. The problem Visible deterioration included spalling of the brick faces on the facades and on landscaping walls and parapet walls at balconies and roofs. Damage to the walls below the sloped roofs, dubbed "wet walls", had gone so far that the bricks and parging-air barrier needed extensive repairs as well as measures to control water shedding. New siding covered existing brick After 10 years of inspections, examinations and legal proceedings, the interior drywall was removed from the exterior walls in five apartments. Spalling of the inside face of the bricks, which dislodged the parging, was found to be much more extensive than the exterior spalling. Leakage was occurring wherever the parging on the interior was damaged. Brick damage was significantly less on the "dry walls" that did not have sloped roofs shedding onto them, except at the corners where they met the wet walls.

Walls repaired under the penthouse roof (left arrow) and at the height of the balconies (right arrow) Causes of deterioration Bricks susceptible to freeze-thaw damage One cause suggested for the deterioration was that the bricks were excessively susceptible to freeze-thaw damage. However, examination of other buildings with similar wall construction did not find the same deterioration problems. Missing vapour retarder in plenum space The polyethylene vapour retarder did not always continue to the underside of the floor slabs above, exposing most of the parging on the back face of the brickwork to air in the plenum space.tests showed that condensation on the back face of the parging would not soak through in sufficient quantities to saturate the brickwork and cause freeze-thaw deterioration. In most of the locations examined, some of the vapour retarder and insulation had separated from the top track of the stud assembly. It was suggested that damage to the masonry could be prevented by making the vapour retarder continuous. However, the primary air barrier was the parging; where it was intact, it formed a reasonably good air barrier. Where the parging had separated from the brickwork, installation of an air barrier would be required to avoid air leakage and condensation. Modifications to the vapour retarder would not have a significant impact on the problem.

Roof water runoff The principal cause of the damage was water running off the sloped roofs onto the bricks. In rain or during a thaw there was visible staining of the brick work below each of the sloped roofs. The exterior brick damage generally correlated with these sites. The spalling of the interior faces of the brick and the dislodged parging matched the outline of the runoff patterns almost exactly. Damage and leakage were much more extensive on the upper floors than on the lower floors. In the runoff locations, where the parging was not intact, leakage into the building was most extensive. The consulting engineers concluded that the walls would perform adequately if the exterior face was undamaged, if the parging on the back face of the brick was intact and if water could not concentrate on the brick faces. If these conditions could not be met at a reasonable cost, the buildings would need an alternative exterior cladding. The Work Structural The structural integrity of the load-bearing walls had to be restored before installing the new, precoated, steel panel cladding.this involved removing vertical panels of brick in areas of deep spalling, shoring the slabs on the interior and installing new "columns" of brick designed to take over the vertical load-bearing function of the adjacent walls. Next to the new columns, and where sufficient brick integrity remained to act as a base, the spalled faces were removed and the bricks patched with a polymer-modified mortar to support the new air barrier.

Damaged brick Building envelope "Wet walls" Damage to the "wet walls" was so severe that they needed extensive repairs to the bricks and parging-air barrier along with measures to control water shedding. To replace the air barrier function of the detached parging, a trowel-on, cementitious air barrier material with a low vapour resistance was installed over the faces of the bricks on the walls to be clad. Temperature gradient and vapour pressure calculations showed that diffusion would not cause condensation on the inside face of the new air barrier. Sufficient insulation to move the dew point outside the air barrier layer was provided on the exterior side of the air barrier material. A free-draining insulation was applied to the exterior face of the air barrier. While the steel studs and bottom track were badly rusted--and occasionally disintegrated--the interior drywall was left in place, as deterioration was not expected to continue after it dried out. Localized water damage repairs were made to the interiors of the "wet walls". "Dry walls" Repairs were started at the top (sixth floor) and stopped when intact parging was found, usually at the third or fourth floor.the interior drywall was removed, starting from the corner of the wet wall until intact parging was found.the spalled interior faces of the bricks were repaired. Hollow-sounding parging was removed and replaced. Parging was installed on the back faces of all new bricks. The parging was continued around the corner onto the wet walls for a short distance to create an overlap with the exterior air barrier on the wet walls. While this connection was not perfect, the mortar joints in the brickwork helped to connect the two air barriers. Flashings were installed along the edges of the sloped roofs to prevent water from blowing off the sides of the sloped roofs onto the "dry walls." The interior finishes were then restored. Other repairs

Deteriorated roof-level parapet walls were rebuilt and all parapets counter-flashed to their full height on the roof side. New cap flashings were designed to shed water away from the brick. Sixth floor balcony enclosures were vented so they remain at exterior temperature. Some enclosures were replaced with watertight systems. Other balcony enclosures were removed and the floors waterproofed. Remedial measures for the landscape walls included lowering the soil level, installation of counter flashing, repair of brick and measures to prevent snow or soil accumulation at brick level. Results The structure has been restored and stabilized, and most owners now have leak-free units after almost 15 years of problems. However, they have had to accept a significant change to the appearance of their building. Some walls have leaked since the repairs. The leaks have been in areas that were not re-clad, insulated and provided with a new air barrier.when localized problems occur, deflectors are installed to redirect the water and a masonry sealer is applied to the brick. Because interior repairs were made only in leakage areas, there was limited disruption to the occupants and other living arrangements were not required. Improvements to the insulation levels and airtightness of the walls have meant some energy savings.the overall marketability of the units has improved. Financial considerations The final construction cost was about $1,500,000 (excluding Goods and Services Tax - GST), of which $1,125,000 was for recladding and structural repairs. The repair procedure was the lowest-cost approach presented. The project was funded entirely by unit owners through special assessments. The experience of this condominium shows the importance of establishing a contingency fund to pay for timely corrective measures. Despite a court judgment in their favour, the owners have not received any compensation for the construction costs. Contacts Owner representatives: Condominium board, technical committee and building superintendent Consultants: Consultants: Halsall Associates Ltd. rmarshall@halsall.com Contractors: Maxim Group General Contracting Ltd. If you have comments or would like to submit your project for publication, please contact: ldemigue@cmhc-schl.gc.ca.