BS03 AMTECH INDUSTRY CO.,LTD. Fixed Gas Detector Operation Manual ISO9001:2008

Similar documents
RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

RAEGuard EC FGM-13XX

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Online Infrared Flue Gas Analyzer Gasboard 3000

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

600-GD & 600-GDL 600 SERIES GAS DETECTOR

BEP FD-2 CONTOUR MATRIX FUME DETECTOR

IN-OUT Thermometer with Cable Free Sensor and Clock

LUCCI AIRFUSION QUEST II CEILING FAN

GREISINGER electronic GmbH

Instruction Manual. T3111 T3111L T3111P T3111Ex

OPL BASIC. Dosing System for Professional Laundry machines. Contents

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Digital Keypad Use s Manual

Combustible Gas Transmitter RK-05

Doc.No. NDP 192U-02. Electric Pump Controller CE-124P. Instruction Manual

GSM Alarm System User Manual

Telefon (+45) Telefax (+45) Installation and operating manual

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

Installation & User Instructions

AIR CONDITIONER INSTALLATION MANUAL

Munchkin Heat Exchanger Maintenance

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

SELECTION, APPLICATION AND MAINTENANCE

EX-5175-EC Sensor/Transmitter Manual

Temperature & Humidity SMS Alert Controller

INSTALLATION AND OPERATION MANUAL

Application Requirement

SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

ATL Fuel Level Sender Probes

Digital inductive conductivity transmitter

User s Manual Before using the inverter, you need to read and save the safety instructions.

Portable Air Conditioner

Drayton Digistat +2RF/+3RF

Non-invasive CLAMP-ON ultrasonic flowmeter for liquids

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1

Duct Humidity Transmitter

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

No. : EX##-OMF0004 OPERATION MANUAL. SI unit EX12#-SMB1

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

COLOR TFT LCD MONITOR. User Manual

Operating Manual Remote Cost Control Monitor

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

Intelligent GSM Auto-dial Alarm System User s Manual

New GSM Alarm System. User s Manual. Profile For a better understanding of this product, please read this user manual thoroughly before using it.

BTH360-S Bluetooth Stereo Headset Specifications & User's Guide

OCSM Series. High Resolution Digital Crane Scale. User Guide

2M IR Mini Dome Quick Installation Guide

Instruction manual for Firstline FCS12000CH

Elektromotoren und Gerätebau Barleben GmbH

GAS CYLINDER SAFETY. 2. GRADES OF GASES BOC have divided the gases that they supply into 3 grades.

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

ELECTRIC CENTRAL HEATING FLOW BOILER

TABLE OF CONTENT

LED Security Spotlight User Manual

User Manual Color video door phone

Home Security Alarm System

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

FIREDEX Conventional Fire Panels

TYPE 65UV CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output

PowerLogic Sub Meter Display (SMD and SMDOPN)

Microwave Meter. Instruction Manual

RS Stock No Instruction Manual RS-1340 Hot Wire Anemometer

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Energy savings

INFRARED QUARTZ WALL HEATER

12 Volt 30 Amp Digital Solar Charge Controller

T0118 T2118 T3118. Instruction Manual

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

24 Wide Screen LED Monitor with HDMI

COMBIMASS. Technical Data COMBIMASS eco-bio +

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Model: Manual DC: WIRELESS COLOR FORECAST STATION

Fire & Security DETECTORS

Combo heat press machine. Instruction

DSM155 Digital LED Light Meter User s Manual DSM155

=============================== WARNING

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

DAB+ / FM Tuner Model: TU-201

3 IN 1 BATHROOM HEATER

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL

Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter

FIRERAY 2000 Installation Guide

New XUY roller sensors

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Operation and Installation Manual

Digital Photo Picture Frame. Operation Manual

Operation Manual Magic Bowling. Warning Please read this manual carefully before using this machine

QLINK User Manual Stereo Audio Transmitter

REDWALL-V adjustment procedures guide

INFRARED REMOTE CONTROL HELICOPTER

VIDEO DOOR PHONE SYSTEM

GenStore Archive Cabinet

FAQ s on Siemens Magmeters

4-Port Pocket. USB KVM Switch with USB 2.0 Hub

Installation and Instructions Manual Model 4-20IQ Sensor Transmitters

Operation Manual For NDJ-8S Digital Rotary Viscometer

Ultrasonic Distance Meter. Operation Manual

User Guide. Heavy Duty Dissolved Oxygen Meter. Model

Transcription:

BS03 Fixed Gas Detector Operation Manual AMTECH INDUSTRY CO.,LTD ISO9001:2008

Safety Information Before using the device, please first carefully read and follow the following information to operate the device: Please don't use the defective detector. Before using, please check if there is crack or spare part missing. If yes, please contact the seller. In order to keep the accuracy, please calibrate it once before the first time using. Working voltage of the detector is DC18V to DC30V and recommended voltage is DC24V. The voltage exceeding DC30V will damage the detector. Before using, please make sure the housing is fixed. There should be no speedy gas flow on the installation place. Otherwise, it will influence the detection result. Please don't expose the device to the gas which concentration is exceeding the range. Otherwise, it will influence the accuracy and shorten the sensor life. Please don't paint the sensor parts or detector. Only sensor spare parts which are specified for BS03 are allowed to be used. It's suggested calibrate the sensor once every 6 months. In order to avoid damage human beings, please operate it when power off. Before opening the cover, make sure there is no mixture gas of combustible gas and air. Otherwise, it will possibly cause fire or explosion. Please avoid water or dust to come into the housing. Please Please don't expose the device to the environment which has electric shock, strong magnetic field or serious continuous mechanic shocking.

8. Normal problem and solution Problem Possible reason Solution Wrong wire It displays FAUL connection, wire Re-connect the wire broken, or sensor or replace the sensor damaged No response to the Sensor damaged Replace the sensor gas Circuit Fault Contact the seller Wrong connection Wire connection fault Check the connection to the controller Electric circuit fault Contact the seller When no using, please take out the battery from the remote controller. Installation must abide by the national and local regulations. It's forbidden to disassembly, adjust or repair the device without permission. All the operation inside the device must be carried by professional persons.

1. Brief introduction BS03 fixed gas detector, adopting high-quality catalytic gas sensor and SMD arts and crafts, has advantages of good reproducibility, disturbing-proof against temperature and humidity, long life-span and easy operation. The signal output is standard 4-20mA. It is widely used in refineries, chemical plant, LPG station, gas boiler, and Spray-Paints etc where gas leakage easily. follow the following steps to replace it: 2. Technical data Gas Range Resolution L-alarm H-alarm LEL 0-100%LEL 1%LEL 20%LEL 50%LEL LEL Vapor 0-100%LEL 1%LEL 20%LEL 50%LEL CO 0-1000PPM 1PPM 35PPM 200PPM H 2 S 0-100PPM 1PPM 10PPM 15PPM NH 3 0-100PPM 1PPM 25PPM 50PPM CL 2 0-20PPM 0.1PPM 5PPM 10PPM O 2 0-30%VOL 0.1%VOL 19.5%VOL 23.5%VOL SO 2 0-500PPM 1PPM 10PPM 50PPM CO2 0-6000PPM 1PPM 1500PPM 2000PPM Sensor type: Catalytic or electrochemical gas sensor Gas sampling: Natural diffusion Power supply: DC24V±25% Power consumption: 3W Working method: Continuous monitoring Error rate: ±5%F.S. Indication method: 4-digit LED light Condition display: 3 LED lights indicate fault alarm, L-alarm level alarm and H-alarm level Operation: Infrared remote control 7.1 Take off the calibration cover in counter-clockwise. 7.2 Pull out the decoration part downwards. 7.3 Screw off the jackscrew from the sensor protection cover. 7.4 Take off the protection cover in counter-clockwise. 7.5 Take out the old sensor. 7.6 Put the new sensor into the sensor cover. Note: Please put the new sensor into the correct fixing holes. It's forbidden to rotate the sensor. 7.7 Then install in turns protection cover, jackscrew, decoration part and calibration cover. The replacement is completed. 7.8 Electrify the detector and calibrate the detector.

figure on the screen is steady, press Confirm to remember this figure and calibrate it. It will go to effect after exiting from this mode. The screen displays F-3. The user can press Confirm to make the other setting or press Cancel to return to the normal status. Note: Zero calibration must be carried in the clean air. It's forbidden to calibrate zero when the target gas exists in the working place. 6.6Single point calibration 6.6.1 After using for some time, the result of the detection may be not so correct because of the sensor drift. Consider of the convenience of the user, the device is designed with the function of single point calibration. 6.6.2 Procedure: Put the device into the calibration gas with known concentration (Suggested inputting half of the detection range gas for 2-3 minutes). In normal status, press Setup four times and it displays F-4. Then press Confirm and it displays 50 (The pre-set calibration level). This figure can be changed by pressing + or -. And then press Confirm to remember this figure. Then it displays XXXX (The A/D of the present environment). When the figure on the screen is steady, press Confirm to remember this figure and calibrate it. It will go to effect after exiting from this mode. The screen displays F-4. The user can press Confirm to make the other setting or press Cancel to return to the normal status. Note: Please don't carry the above calibration when the detector is working or there is no calibration gas. 7. Sensor replacement In normal working environment, the life of catalytic sensor is 3 years and electrochemical sensor is 2 years. When the sensor life is overdue, the detection result may be not accurate. Please contact the seller for replacing the sensor. Before replacing the sensor, please first cut off the power supply and Response time: 30s (LEL) / 60s (toxic gas) Working temperature: -40 ~ 70 (LEL) / -20 ~ 50 (toxic) Working humidity: <93%RH Explosion-proof: Ex dⅡ CT6 Protection: IP55 Pressure Limit: 86-106kPa Signal output: 4~20mA 2 relay output Install screw thread: G3/4" Cable dimension: 1.5mm 2 3 Transmit distance: 1000m Dimensions and weight: l b h, mm 210 200 105 about 2100g 3. Construction illustration

No. Name No. Name 1 Calibration cap 9 Pipe connector 2 Decoration 10 Display screen 3 Lower cover 11 Wire connection hole 4 Upper cover 12 H-alarm LED 5 Wire connection hole 13 L-alarm LED 6 Pipe connector 14 Fault / Power LED 7 Remote receiver window 15 Ground nut 8 Fixing hole 4. Installation 4.1 Installation position 4.1.1 For petrol gas, oil gas and alcohol gas etc. which is heavier than the air, the position is 0.3m-0.6m higher than the ground. 4.1.2 For natural gas, CH4 etc which is lighter than the air, the position is 0.5m-2m higher than the gas source. Note: Gas density more than 0.97kg/CBM, then it's heavier. Gas density less than 0.97kg/CBM, then it's lighter. 4.1.3 The position should be far away from shocking, shattering, strong electromagnetic interference. Around the position, there should be at least 0.3m empty place. 4.1.4 The position should be within 1m around the possible gas leakage area, such as valve, pipe connection point, gas outlet place. Please try to install it nearer to the above places, but avoid influencing the working of the other equipments. Please avoid the environment of high temperature and humidity. Also please keep it from water swashing, oil and mechanical damage. Please also consider the convenience of maintenance and calibration. High concentration protection: FAUL; 3 LED are on (only for LEL) Low alarm: gas concentration; red low alarm LED on High alarm: gas concentration; red low and high alarm LED on Low alarm setting: F--1 High alarm setting: F--2 Zero calibration: F--3 Single point calibration: F--4 Factory setting: F--5 (Unavailable to the customers). 6.3 Low alarm setting In normal status, press Setup once and it displays F-1. Press Confirm, it displays 50 (The pre-set first level alarm). This figure can be adjusted by pressing + or -. After setting completed, press Confirm to save the result. The device exits to the normal status. The setting will affect. The screen displays F-2. The user can press Confirm to make the other setting or press Cancel to return to the normal status. 6.4 High alarm setting In normal status, press Setup twice and it displays F-2. Then press Confirm, it displays 20 (The pre-set first level alarm). This figure can be adjusted by pressing + or -. After setting completed, press Confirm to save the result. The device exits to the normal status. The setting will affect. The screen displays F-1. The user can press Confirm to make the other setting or press Cancel to return to the normal status. 6.5 Zero calibration After the detector work normally for more than 10 minutes, put the device into the clean air. (For O2 / N2 gas detector, the device should be put into pure N2 gas environment). In normal status, please press Setup three times, it displays F-3. Then press Confirm, it displays XXXX (The A/D of the present environment). When the

1000m. 5.5 After checking all the connection well, install the display PCB and the front cover. Make sure O-type circle is put on and connected with the cover tightly. 4.1.5 For large scale detection, we suggest install 1pc every 10-12 square meters, so as to get the best detection result. 4.2 Dimensions 6. Operation instruction 6.1 On the remote controller, there are totally fives buttons as follows: Setup, Confirm, Cancel, + and -. On the spot, it's forbidden to replace the batteries. Note: Setup, Confirm and Cancel are single-spring buttons. These buttons can only be springed once even if you press them continuously, and the interval between two springs should not be less than 1 second. + and - are continuous-spring buttons and can be springed by continuous pressing. Setting can only be affected after pressing Confirm. After setting, press Cancel to return to the normal mode. Effective setting can be kept till the next setup, even if without power. 6.2 Illustration of display: Normal: gas concentration Sensor fault: FAUL; yellow LED is on (only for LEL) 4.3 Installation methods Note: Fix the detector with sensor head downwards. According to the installation place, fix the detector onto the wall or gas pipes. Details as follows: Method 1: If there are transverse or vertical siphon with G3/4 Screw thread in installed places, please connect the two terminals of the detector to the gas pipes. Then connect and screw down the pipe screw thread nut and fix it tightly.

Method 2: If the user needs to install the detector on the wall, please choose an appropriate metope according to the detector dimensions. Then fix the detector by using 3 pieces of M6 70 bulge bolts in the corresponding installed orifice. Method 3: If there is 1" to 2 (diameter) pipe, the user can use 2 U-type bolts to fix the hanging plate on the pipe, and then fix the detector onto the plate. Or, the user can first fix the detector onto the plate and then fix the plate on the pipe. 5. Wire connection Note: Wire connection must be carried when power off. 5.1 Screw down the cover in counter-clockwise way. Then use a cross-type screw to screw down the 3 bolts and take off the display PCB. 5.2 Screw down the pipe connector in counter-clockwise way. Take out the explosion-proof pad. In turns, put 3-line wire to the internal of the enclosure through the pipe connector, compaction circle, air-proof closing plug and the wire connection hole. According to the explosion-proof requirement, please don't take out the explosion-proof closing plug from the unused wire connection holes. Please don't throw away any part inside the enclosure or the PCB. 5.3 All the wires should be connected to the terminals. The terminal instruction is as follows: Icon Name Function Specifications 24V Anode of power Power input DC24V±25% Cathode of DC24V±25% GND Power input power Iout Current output Current output 4~20mA H.S High alarm High alarm output Switch relay L.S Low alarm Low alarm output Switch relay 5.4 After the correct wire connection, take out the useless wire from the enclosure. Then tighten the compaction circle, rubber air-proof circle and wire. Explosion-proof soft tube can also be connected with the device directly. Note: The size of the wire between the controller and detector should be not less than 6mm, and the distance should be note more than