THE OPTIMISATION OF HEAT DISSIPATION FROM SERVER CABINETS INCREASING THE EFFICIENCY OF, OR REDUCING THE LOADING ON,

Similar documents
COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

White Paper Rack climate control in data centres

Elements of Energy Efficiency in Data Centre Cooling Architecture

DataCenter 2020: first results for energy-optimization at existing data centers

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

State of the Art Energy Efficient Data Centre Air Conditioning

APC APPLICATION NOTE #112

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Managing Data Centre Heat Issues

- White Paper - Data Centre Cooling. Best Practice

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

APC APPLICATION NOTE #92

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

Using CFD for optimal thermal management and cooling design in data centers

Benefits of Cold Aisle Containment During Cooling Failure

Virtual Data Centre Design A blueprint for success

Efficient and secure IT infrastructure Solutions for your data centre

Data Center Components Overview

Server Room Thermal Assessment

Airflow Simulation Solves Data Centre Cooling Problem

An Introduction to Cold Aisle Containment Systems in the Data Centre

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

SERVER ROOM CABINET INSTALLATION CONCEPTS

Thermal Optimisation in the Data Centre

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Environmental Data Center Management and Monitoring

EHDC. Cooling system for Data Center and server cabinets.

Data Center Power Consumption

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

Driving Data Center Efficiency Through the Adoption of Best Practices

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

The Different Types of Air Conditioning Equipment for IT Environments

Electric Coolant Pumps. Always at the Correct Temperature

Data centers have been cooled for many years by delivering

How To Improve Energy Efficiency Through Raising Inlet Temperatures

CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

RiMatrix S Make easy.

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

CRAC Precision climate control units for data centres

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

Data Centre Cooling Air Performance Metrics

How To Improve Energy Efficiency In A Data Center

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

V RICONDITION C OOLING SOLUTIONS. Next Generation Cold Corridor. Takes modular thinking in energy-efficient data centre design to a new level

Cabinets 101: Configuring A Network Or Server Cabinet

RACKMOUNT SOLUTIONS. 1/7/2013 AcoustiQuiet /UCoustic User Guide. The AcoustiQuiet /UCoustic User Guide provides useful

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Module 2.2. Heat transfer mechanisms

Technology Corporation

Data Center Equipment Power Trends

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

CoolTeg Plus Chilled Water (CW) version: AC-TCW

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Benefits of. Air Flow Management. Data Center

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Element D Services Heating, Ventilating, and Air Conditioning

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Measure Server delta- T using AUDIT- BUDDY

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

News in Data Center Cooling

Greening Commercial Data Centres

University of St Andrews. Energy Efficient Data Centre Cooling

Improving Rack Cooling Performance Using Airflow Management Blanking Panels

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

ASTACEA4 Inspect complex/central air conditioning systems

Using Portable Spot Air Conditioners in Industrial Applications

Data Center Cooling A guide from: Your partners in UPS Monitoring Systems

Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant

Data center upgrade proposal. (phase one)

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

imagine SOLAR AIR CONDITIONING MADE EASY

Choosing Close-Coupled IT Cooling Solutions

In Row Cooling Options for High Density IT Applications

JAWAHARLAL NEHRU UNIVERSITY

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

Improving Data Center Efficiency with Rack or Row Cooling Devices:

Mixing Valves. ARGUS Application Note: Mixing Valves

With the background of fulfilling public commitments for ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS

Enclosure and Airflow Management Solution

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Energy Performance Optimization of Server Room HVAC System

DATACENTER COLOCATION. Flexible, Secure and Connected

BRUNS-PAK Presents MARK S. EVANKO, Principal

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

WHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption

CANNON T4 MODULAR DATA CENTRE HALLS

Transcription:

Cold Aisle Containment THE OPTIMISATION OF HEAT DISSIPATION FROM SERVER CABINETS INCREASING THE EFFICIENCY OF, OR REDUCING THE LOADING ON, THE AIR-CONDITIONING SYSTEM IN THE COMPUTER CENTRE 1/11

Contents: 1. Introduction: Minimising losses, optimising cooling 2. Server cabinet installations in the computer centre: cold and warm aisles 2.1 Cold air coming from above 2.2 Cold air coming from below 3. Optimisation stage 1: Radial fans in the rear doors 4. Optimisation stage 2: Covering the cold aisle 5. Optimisation stage 3: Additionally closing the cold aisle front and rear 6. Optimisation stage 4: Water-cooled doors on the exit side of the servers 7. Optimisation stage 5: Water-cooled doors on the entry side of the servers 8. Optimisation stage 6: Closed cell with two AWHEs (LHX 20) at front and rear 9. Optimisation stage 7: Air-conditioning for safety only 10. Conclusion 11. Schroff company portrait and notes on the author 2/11

1. Introduction: Minimising losses, optimising cooling In recent years the power of servers in computer centres has increased dramatically, and the requirement for cooling has thus also risen. Today, computer centres are still cooled almost exclusively with air. Servers and other IT components are normally housed in server cabinets in such a way that cold air is sucked in through the front from the environment and warmed air is blown out to the rear. For this the cold air is provided by a central air-conditioning system. The loading on this air-conditioning must however be reduced by optimising the cooling in any of the following circumstances: where additional servers are later added to an existing server room. That is, when the number of installed servers comes to exceed that which the central air-conditioning system is capable of cooling; where a non-optimised server-room configuration requires a significant cooling of the space, such that a part of the cooling capacity of the air-conditioning is unnecessarily lost. 2. Server cabinet installations in the computer centre: Cold and warm aisles For pure air cooling, the maximum possible cooling per server cabinet is determined by the capacity of the surrounding space to supply sufficient cool air to the front of the cabinets and to extract the warm air at the rear of the cabinets from the space. Where server cabinets are arranged in aisles in which the rear of the cabinets of one row faces the fronts of the next row, the cabinets of the second row inevitably draw in directly a proportion of the warm air expelled from the first row. Arranging the cabinets into so-called 'warm' and 'cold' aisles, on the other hand, already optimises the air-conditioning of a computer centre. The suggestions set out below presuppose, however, that the cabinets themselves are already optimally arranged as regards the correct airflow. 2.1 Cold air coming from above In an arrangement with cold and warm aisles, the cold air can flow into the cold aisles by two different ways. The first: the cold air is supplied by the air-conditioner from above, and the warmed air is likewise sucked upwards or horizontally out of the space (not shown) by the air conditioner. 3/11

This is the preferred solution where, for example, no false floor is present. However, it gives rise to relatively large losses. The spatial proximity of the inlet and outlet of the air conditioner is a cause of 'short circuits', whereby a proportion of the cool air is promptly sucked out again with the warm air. What is more, some of the warmed air from the warm aisles is not extracted by the air conditioner but rather becomes mixed with the cool air entering from above, and is then drawn back into the server cabinets. 2.2 Cold air coming from below By introducing the cold air from below via a false floor into the cold aisle, some of these losses can be avoided. As with the previous arrangement, the warm air is removed from above by the air conditioner. 4/11

The air short-circuits between air inlet and extraction points do not occur here since the inlet (in the floor) and extraction points (ceiling) are sufficiently far apart to prevent them. In providing sufficient cold air to the topmost servers, however, again a proportion of the cold air invariably bypasses the servers altogether and is drawn upward to the extraction point. In such a configuration the cold airflow speed plays an important role. If this is too low, the uppermost servers in the cabinets do not receive sufficient cold air; the air temperature in the upper areas then becomes impermissibly high and hotspots occur. Where the airflow speed is too high, however, the cold air passes the lower servers too quickly and these receive too little cooling. The balancing point is further complicated by the fact that a mixing of warm and cold air occurs in the cold aisle and thus a temperature difference or zoning between the lower and upper cabinet areas. In certain circumstances this difference can be up to 5 K and effectively minimised only by measures for containing the cool air. 3. Optimisation stage 1: Radial fans in the rear doors To further improve cooling, the ordinary rear doors of server cabinets may be replaced with doors containing fans. These fans suck the warmed air from the cabinet and blow it directly to the extraction point of the air-conditioner. This approach is used primarily in server areas without a false floor, in order to keep air short circuits to a minimum. Losses are significantly reduced. A further benefit is that the air now flows uniformly throughout the entire height of the cabinet. The latter benefit is also obtained when the solution is used in conjunction with a false floor. It is quick and simple to swap standard doors for doors with fans, and this can even be done while the servers are operating. 5/11

4. Optimisation stage 2: Covering the cold aisle Where the cold air enters from a false floor, various possibilities exist to minimise losses from the cold aisle and to avoid the balancing act between too-high and too-low airflow speeds. The simplest solution is to fit a cover over the top of the cold aisle. By this means the airflow rate is reduced, for one thing, and for another it is ensured that most of the air fed into the cold aisle is in fact drawn into the server cabinets. The temperature zoning over the height of the cabinet is substantially reduced, which also increases the efficiency of the air conditioner. Nevertheless, losses continue to occur along the axis of the cold aisle (at the front and rear). 5. Optimisation stage 3: Additionally closing the cold aisle front and rear Here, in additionally to closing the cold aisle from above, it is sealed to front and rear (by means of a door or hatch). 6/11

The result is a cell with a form of forced air circulation: the cold air can only flow through the server cabinets. No losses occur. Temperature differences along the height of the server are effectively avoided by this means, thus optimising the energy demand on the air conditioner. 6. Optimisation stage 4: Water-cooled doors on the exit side of the servers The next improvement is made by replacing the doors on the exit side of the servers with doors containing either passive or active air-water heat exchangers (AWHE). The use of active or passive AWHEs in this position considerably reduces the load on the available air-conditioning system. In both cases, the warm air from the servers can be cooled prior to leaving the cabinet to a temperature lower than that of the cool air entering it. This characteristic can be useful in situations where the air-conditioning system has already reached the limit of its capacity, yet additional servers are to be installed. With doors fitted with active AWHEs a uniform distribution of air is obtained throughout the height of the cabinet. The fans of the active AWHEs suck the warm air from the rear section of the cabinet through the AWHE and blow it cooled into the server room. This provides a powerful support for the server's own fans. Where the doors are fitted with passive AWHEs, the air resistance of the heat exchanger must be exactly matched to the server fans to ensure that these are still capable of extracting the warm air. 7. Optimisation stage 5: Water-cooled doors on the entry side of the servers In this step, the doors on the entry side of the servers are replaced with doors containing either passive or active air-water heat exchangers (AWHE). Such an improvement can only be undertaken, however, if the design of the server units permits it. This is because, in order to be able to operate or monitor the servers from the front, they must be fed with cold air from the rear. In addition the patch cable and other important connections must be routed to the front in order 7/11

to avoid the need for hinges to the AWHE doors. The user is rewarded for these steps with further attractive benefits: No longer is a room air conditioner required. Only the chiller is required, for providing cold water for the AWHEs. By employing two-way valves in front of each AWHE, these only use as much water as is necessary to maintain the server temperature set by the user. The use of these two-way valves before each AWHE also allows the circulator pump to run very economically, maintaining a constant pressure with variable water volume. The not insignificant energy losses from cooling the server room and the false floor - building cooling - are dispensed with. On the contrary, since the room temperature will be significantly higher than that outside the building, a fraction of the heat is given to the outside environment through the wall of the building, thus also taking the load off the water cooler. An appreciable saving in energy costs is obtained, which can be further increased by the use of exclusively passive AWHEs. 8. Optimisation stage 6: Closed cell with two AWHEs (LHX 20), at front and rear Still more effective cooling is obtained by the use of two AWHEs, one to the left and one to the right, within the closed 'cold' cell at the end of the cabinet rows. The rear doors can further also be fitted with radial fans. In this arrangement, separate considerations must be made for installations with and without a false floor. In both cases, however, the efficiency of the server cooling will be greatly increased. 8/11

If a false floor is present, the admixing of additional cold air in this configuration gives many immediate advantages: The air temperature in the cold cell can be significantly lowered relative to that of the air entering from the false floor. The volume of air now delivered to the servers is increased. The surplus volume of cold air from the false floor can be made available for cooling other server cabinets. The server cabinets close to the AWHEs draw a greater proportion of their cold air from the AWHEs and less from the floor. This allows the centrally-positioned cabinets to draw more cold air from the floor. Distribution of the air circuit throughout the height of the server cabinets is much more uniform. Where no false floor is provided, the maximum cooling capacity of the AWHEs and the availability/supply of cold air to the individual server cabinets must be taken into account. Here also, a number of benefits are obtained: The server cabinets can be supplied with significantly colder air than could be provided by the air-conditioning system. The load on the air-conditioner can be substantially reduced. This design can be applied in rooms that otherwise would not be suitable as server spaces. Distribution of the air flow over the entire height of the server cabinets is considerably more uniform, helping to prevent the formation of hot spots. The temperature difference across the height of the cabinet is as good as eliminated. The result is higher energy efficiency for the system overall. 9/11

It is possible, by using the cooling doors described above with all the advantages stated for them, to extend the effectiveness of the cooling still further. 9. Optimisation stage 7: Air-conditioning for safety only In this final stage of improvement, all subsequently-installed server cabinets are grouped into closed units and cooled using AWHEs (LHX20). The result is a space-independent cooling design, and the advantages offered by water cooling can be exploited without limit. The inner temperature of the cabinet is matched exactly to the server requirements; the remaining infrastructure is not affected. This design allows existing computer centres whose air conditioning system is already so heavily loaded that the volume of cold air can be increased no further, but that have reserves for additional water cooling, to expand their server capacity. Existing server cabinets continue to be cooled via the central air conditioning. Where necessary an additional chiller must be provided for the AWHEs. Where a server room is not being retrofitted but rather designed from new, it will be possible to provide all of the cabinets with space-independent AWHE cooling (LHX 20) from the outset. Only those areas of the computer centre that require cooling will then be cooled; in normal operating conditions the power of the air conditioning can be reduced to a minimum level. The air conditioning system is required only to remove that fraction of the heat that is passed from the surfaces of the cabinets into the space, and also to provide a safety function. In the event that one of the AWHEs should fail, then the door, for example, of the affected cabinet would open automatically and the servers be supplied cold air from the air conditioner for a limited time. 10/11

10. Conclusion There are a variety of possibilities for making improvements to the heat dissipation in existing computer centres. These allow a reduction in the loading of an air conditioning system that is reaching its output limits while also allowing additional server cabinets to be installed. There is likewise potential for further optimisation on the IT side as the energy efficiency of individual devices (e.g. servers) is further improved. Many renowned manufacturers have thus joined open, non-profit-making organisations such as Green Grid and the Climate Savers Initiative. 11. Schroff company portrait and notes on the author Schroff, based in Straubenhardt, Germany, is a leading developer and manufacturer of electronics packaging systems for electronics, automation, information and communications technologies worldwide. The company's standard products range from cabinets for indoor and outdoor use, cases and subracks through power supply units and backplanes to microcomputer assembly systems including air conditioning. With this product platform as its basis, Schroff is able to realise customer-specific modifications quickly and at advantageous cost. Schroff's comprehensive integration service draws together its product and service competences to create a total solution with real customer benefit. Our products and services are the result of decades of focussing on the global interests of the electronics markets. Schroff has consistently built on its core competences such that today its expert knowledge in electronics packaging, thermal management and electromagnetic compatibility brings additional added-value to these fields. Adam Pawlowski, Dr-Ing., is a graduate of the aircraft engines department of the Politechnika Warszawska in Warsaw, specialising in combustion processes. During his time employed as an academic at Berlin's Technical University he completed his doctorate in the field of mechanical vibration principles. In the course of his professional development he worked for many years as a division head in the area of R&D climate-control technology for companies engaged in climatecontrol equipment for switchgear and in the automotive industry. Since August 2005 Dr Pawlowski has acted as product manager for climate-control equipment at Schroff GmbH. 11/11