WTT16... WTX16... Network Node.

Similar documents
OZW30. Central Unit SYNERGYR

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

Digital input modules

=============================== WARNING

Drayton Digistat +2RF/+3RF

PCS0100en Persy Control Services B.V. Netherlands

Heating Controller. Building Technologies HVAC Products

RUST ELECTRONICS LTD. Remote Switching Unit RCU-O4

QFP910. Water detector. Building Technologies. CE1N2732en Synco living

RRV934. Multi-controller. Synco living

User Manual for CH-PFC76810

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

StructureScan HD Module. Installation Guide ENGLISH

TYXIA. * _Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF channel

Draper Low Voltage, Remote Control, Serial and Network Wiring Guide

FOM-5A, 6A. Asynchronous Fiber Optic Modem

BroadBand PowerShield. User Manual

Installation and operating instructions: Radio dimmer Type: DALI DM ADVANCED LI

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Manual. Simrad StructureScan LSS-1 Sonar Module. English

HMI display Installation Guide

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

MINI MCR-SL-R-UI(-SP)

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Product and functional description

IN-OUT Thermometer with Cable Free Sensor and Clock

The Foundation User Manual LED Battery Slim Par Fixture (RGBA, DMX 7Ch/4CH)

Modular I/O System Analog and Digital Interface Modules

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Emergency lighting units EM powerled

TX OPEN RS232/485 module

Waveguide Access Point WGA631. Product Guide

Danfoss Link Mobile Phone Butler

Displayport Extender via 2 multimode fibers LC Duplex Connector Extends Displayport Link up to 200 meters

PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version ( )

WPR400 Wireless Portable Reader

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

HYDRUS ULTRASONIC METER

MOUNTING AND OPERATING INSTRUCTIONS

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

ABB Drives. User s Manual HTL Encoder Interface FEN-31

Duct Humidity Transmitter

Operating instructions for built-in electronic timers with Day and Week programms. Series 884

Wiring Instructions and Operating Manual 12 POINT ULTRABEAM REMOTE MONITORING SYSTEM

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: Data sheet GIOD.1 V_3.0

How To Use A Power Supply On A Powerline 2.2 (Ai)

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

HCR3.2/.. Chipcard reader HOTEL SOLUTION

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Antenna Splitter ASA 1. Instruction manual

2013 VTech Printed in China US

PRELIMINARY MANUAL STAGE COLOR 48. Preliminary User Guide. Official version will follow soon on: TABLE OF CONTENTS

Combi B Alarm box. Mounting instructions

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

MIC-WKT and MIC-WKT-IR

T0118 T2118 T3118. Instruction Manual

Infrarot-Bewegungsmelder IP44

PHOENIX CONTACT Features

Installation guide H A. HSI hardwired system interface

Business Audio System: Music & Messaging MP3 Player. by Grace Digital Audio. User Guide. Model No. GDI-USBM10

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

DALI RC BASIC SO. Control unit Operating instructions

Wireless Indoor/ Outdoor Thermometer

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

Redundancy Module QUINT-DIODE/40

HM-W536 Install Guide

Sense Components. Sense monitor. Antenna assembly. External mounting kit Current sensors. Download the Sense app. Go to sense.com/app.

MCR1900 Media Converter 19-Slot Chassis

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

Transmitter Actuator 230V wave UP 560. Operation

COMPALARM AP GENERAL MAIN FEATURES

Current Monitoring Kit QUICK START GUIDE

PRO370D 65A Mbus MID DIN rail three phase four wire energy meter. User manual Version 1.03

HP UPS R1500 Generation 3

Options for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface

QLINK User Manual Stereo Audio Transmitter

Current Monitoring Kit

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

Instruction Manual for Operating Panel 301 and 302

ST Series POWER SUPPLIES USER INSTRUCTIONS

Transmitter Speed. Instructions for use Betriebsanleitung Mode d emploi Instrucciones para el uso Istruzioni per l uso

HDTV Anywhere USER MANUAL / HDTV Anywhere ALL RIGHTS RESERVED MARMITEK

Perle Protocol Transparent Media Converter Modules

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

7 Lighting Technology

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

8-port 10/100Base-TX +2-port 100Base-FX Switch. User s Guide

ADM1TE 5/30A DIN rail single phase two wire energy meter

Product Information Fire alarm panel 8000 C

A good connection. International approvals.

LIEBERT VNSA Installation Sheet

Transcription:

Network Node WTT16... WTX16... The WT 16 network node is used to receive and handle the data transmitted by consumption meters of the Q AM system. In small plants, one network node suffices as a data collector. In larger plants, or when consumption data shall be read out from a remote location, an M-bus interface for connection to an OZW10 M-bus central unit or a gateway is required. The WTT16... network node is battery-powered, the mainspowered WTX16... version is available for special applications. Use The WT 16 network node is a component of the Q AM system. It has been designed for use in buildings to create a radio network for receiving and storing the data transmitted by the consumption meters installed in the building. Communication between several network nodes is via radio also so that no wiring is required. All measured values acquired by the consumption meters are continuously exchanged within the network, which means that every network node stores the current consumption values, the values read out at the end of the month, and the set day values of all metering devices on the network. Owing to this operating principle, all network data can be read out at any of the nodes, or a QUNDIS gateway for remote data transmission can be used with any of the nodes. CE1N2874en www.qundis.com

Functions eception and storage of the data transmitted by the consumption meters Automatic creation of a network with up to 12 WT 16 (with a maximum of 500 consumption meters) Passing on all relevant consumption values to all WT 16 on the network Communication via the QUNDIS gateway Communication with the OZW10 M-bus central unit Network node versions The WT 16 network node is a component of the Q AM system and has been designed for exclusive use with that system. It is available in a number of versions for different applications: Application Battery-powered Mains-powered Standard WTT16 WTX16 With S-232 interface for local data readout WTT16.232 WTX16.232 Network nodes with integrated gateway are used for the remote readout of Q AM networks. They are described in data sheet CE1J2878. Combinations All network nodes with integrated gateway can be used along with any other network node. The maximum number of 12 network nodes in one system must not be exceeded. The network nodes with gateway and integrated M-Bus master (WTX16.GSM and WTX16.IP) are able to read M-Bus meters according to EN13757-2/3 Technical design The network node consists of the following subassemblies: transceiver for Q AM network power supply: mains supply WTX16.. battery WTT16... memory for 500 meters backup battery M-Bus (Slave) S232 (optional) eceiver and transmitter are used for receiving consumption data and forwarding them to other network nodes of the network. The memory stores the consumption data. It is protected against temporary power drops (e.g. mains power failure or replacement of the main battery) by a backup battery. The network can be read locally via the M-Bus interface. The network nodes WT..16.232 have an additional S232 interface for readout purposes. WTT16.. nodes are battery-operated, while WTX16.. require a mains power supply AC 100V.. 230 V. Basic design Electronics section The network node consists of 2 major sections: The base and the housing with the electronics. It is thus possible to mount the base prior to commissioning, enabling the electrical installer to connect the WTX16 to the mains network. At the time of commissioning, the electronics section is snapped on and the electrical connections are made. The housing with the electronics is identical for all types of network nodes. It contains the network controls: 2/8

1 2 3 4 5 10 8 6 MODE ESET 7 DISPLAY 9 11 12 1. Connector for M-bus service connection 2. Connector for enhancements 3. Screw terminal for the fixed M-bus connection 4. Connector for power supply DC 3,6 V 5. Connector for backup battery Indication of mains supply 6. Operating mode button (red) 7. Button for switching the display (blue) 8. eset button (recessed) 9. Display 10. Connector (not for the user) 11. Firmware memory (covered up) 12. IrDA-Interface (optically) Wall-mounted section The wall-mounted section of the network nodes WTT16.. contains only the main battery. In variant WTT16.232 the S232 interface is fixed here. The wall-mounted section of the network nodes WTX16 and WTX16.232 contains the power pack and possibly an additional S232 interface. GND n.c. TS CTS x Tx 1 6 5 4 2 3 7 1. Mains connection L and N 2. Preinstalled mains cable (no flexible power cable!) 3. Extra insulation (shrink sleeve) 4. Connector for power supply DC 3,6 V 5. Screw terminal for the fixed M-bus connection 6. Connector for M-bus service connection 7. Indication of mains supply 3/8

Display The display of the WT 16 facilitates commissioning work and troubleshooting. In addition to the standard display that shows the operating mode of the WTT16, there are 5 different display levels from A to E that can be selected by the user. Display level - Current operating mode A WT 16 number (primary address) and alternate network number B Number of WT 16 on the network C Number of consumption meters on the network D E emaining capacity of the WTT16 s main battery in % Error code (3 groups) Operating modes There are different operating modes some of which can be selected by pressing the button on the network node; some are selected automatically, or from a connected PC via the ACT26 commissioning software. The selected operating mode appears on the display: Mode Display Explanation Idle-mode Delivery status. Switch to install mode by pressing the button MODE (>2 sec). Standard mode Extended standardmode 1) Installationsmode 2) Extended installationsmode 2) Protected installations mode 2)3) Search mode M M This is the normal operating mode of the data collectors: Telegrams from the metering devices can received, stored and handled further by the network. The receiver is always active to ensure fast communication. This mode is automatically activated in the case of mainspowered operation (WTX16...). It can also be started manually with the ACT26 service tool. In installation mode, the radio network will be built up automatically. Metering devices that transmit installation telegrams in this operating mode will be registered in the network. This mode is started by pressing the MODE button (>2sec). The extended Installation mode will register all metering devices that transmit either installation or data telegrams. This mode is useful if network is expanded later. Same as installation mode, except that connections are built up only by devices with the same network signature. This mode restores radio connection to lost or manually registered metering devices. This mode starts automatically. Extended search mode 2) Delete-mode 2)3) M This search run is used to restore the radio connection to lost or manually registered metering devices. Starting from version 2.2 this mode can also started manually by setting jumper 1 (in the plug field) and pressing the MODE button ( >2 sec.) Same as installation mode, except that all registered metering devices which are transmitting installation telegrams will be deleted. (meter replacement) 1) In battery powered network nodes this mode is terminated automatically after eight hours. 2) This mode is terminated automatically after eight hours. 3) Possibly only with the software ACT26 version 2.0 or higher 4/8

State of the system emote access Highspeedmode Bus-connection (from version 2.2) Display C M Explanation During remote access the symbol will be displayed. When all network nodes have switched on their receivers for fast data exchange, this will be displayed as two dots in the upper part of the LCD. If a connection to a bus is being built up, the number of the bus and the primary address of this bus will be briefly displayed. In the example, network node 03 is connected to M- BUS IrDA-master mode (from version 2.2) Add (from version 2.2) This mode is started by pressing the button MODE. (< 0,5 sec). It indicates readiness to connect additional IrDA devices (in IrDA Slave mode). This mode stops after 10 sec. If an unregistered IrDA-capable metering device (e.g. WHE467) is connected in IrDA master mode, it can be inserted into the network node by pressing the button DIS- PLAY while ADD is displayed. The last 4 digits of device number are indicated. (e.g. 20000123). The registration of the device takes place and search mode starts. Delete (from version 2.2) If an already registered IrDA-capable metering device is connected in IrDA-master mode it can be removed from the network node by pressing the button DISPLAY while DEL is displayed. The last 4 digits of device number are indicated (e.g. 20000123). The removal of the device takes place and if necessary search mode is stopped. Copy (from version 2.2) If a new network node (running in idle mode) is connected in IrDA-master mode, it is possible to make a copy of all network data into the new node by pressing the button DISPLAY while COPY is displayed. Copying lasts up to 20 minutes. At the end "StArt Prot" is displayed on LCD of the new network node for 1 hour. After mounting the new node the protected mode is also started by pressing the DISPLAY button. By this procedure the new network node is integrated in network and search mode is started automatically. Engineering notes Engineering For detailed engineering instructions, refer to the Engineering Manual CE1J2870. Commissioning the WTX.. For mains-powered WTX16... network nodes, the mains connections are to be made first at the selected mounting positions (typically on every second floor, mounting height 2 m), if required. 5/8

Wiring diagram S N L M1 M2 1... n S Switch L, N AC 230 V mains power supply M1, M2 M-Bus output 1... n optional interface(s) CAUTION: connect the mains cable to the power supply unit only!! 2 3 1 1 Mains connection L and N 2 Preinstalled mains cable (no flexible power cable!) 3 Extra insulation (shrink sleeve) Mains connection Connect the AC 230 V power supply line to the power pack of the WTX16 in the following order: emove the upper housing section of the WTX16 from the base. For that purpose, remove the 2 cable connections (power supply (4) and M- Bus (6)) between gateway and base. Then, use a suitable tool (screwdriver or similar) to slightly open one of the two lateral fixing levers so that upper housing section and base can be separated. Then, the top section of the WT 16 is to be fitted using 2 dowels and screws (spacing of dowels 184 mm with the WTX16...). Connection of the AC 230 V power line to the power pack of the WTX16... is to be made as follows: A 2-core mains cable (L and N) is already preinstalled at the mounting site. The power pack must be connected by qualified staff. The cores must be sheathed with the enclosed insulating sleeves to ensure compliance with safety class II. Then, the live (L) and neutral (N) conductors must be connected to terminal IN of the power pack. Mains voltage must be in the range from AC 100 to 240 V (50 / 60 Hz). There is no protective earth (PE) connection. Then, cable strain relief must be provided by fitting cable ties. Once the top section of the WT 16 is fitted, the housing with the electronics can be snapped on. Then, the power supply connector can be plugged into the electronics section and the WTT16 switched to installation mode by pressing the MODE button (red) for a few seconds. Then, additional network nodes or consumption meters of the Q AM system can automatically configure themselves to form a network. Ensure that the local regulations for radio transmission installations and electrical installations are complied with. Safety notes After opening the housing, certain parts of the device / system that become accessible carry dangerous voltage. Only qualified staff may interfere with such devices / systems. To ensure correct and safe operation, the product must be adequately shipped, stored, installed, operated and maintained Staff dealing with the product must be familiar with all potential hazards and maintenance measures in accordance with the instructions given in this document. Non-observance of these warning notes can lead to personal injury or damage to property! Ensure that the local regulations for radio transmission installations and electrical installations are complied with. 6/8

ESET In Germany: Pursuant to the "Verordnung über Allgemeine Bedingungen für die Elektrizitätsversorgung von Tarifkunden (AVBEltV)" of the Ministry of Economics, electrical installations behind the house s fused connection may only be erected, extended, changed and maintained by electrical installers that are registered with an electric utility. They must ensure that the general technical regulations and legal safety regulations are complied with. Commissioning the WTT.. 1 2 For safety reasons, the WTT16... is supplied without having the main battery connected. 1. Connector for power supply 2. Backup battery MODE DISPLAY Calculating the battery s life expectancy Battery replacement Depassivation Safety notes on lithium batteries After installation of the network node, connect the battery plug to the relevant connector (1). The display of the network node will show batt. Press the blue DISPLAY button once to start the life expectancy calculation for the new main battery. Caution: The main battery can be removed from the network node during operation and the plug can be connected again. In that case, the DISPLAY button may not be pressed as a confirmation. The result would be an erroneous display when showing the remaining capacity. First, remove the discharged main battery and insert the new one. Press the blue DISPLAY button once to start the life expectancy calculation for the new main battery. The backup battery MUST NOT be removed simultaneously. A fatal loss of data would happen. After storing the main battery for longer periods, especially at temperatures higher than 30 C, the battery might passivate. Under these circumstances it will not be able to deliver sufficient energy to the network node. If the network node detects a passivated battery a depassivation cycle is triggered. This is indicated by a flashing front LED. The procedure might take a few minutes. After depassivation the network node will start up automatically in IdLE mode. Long press of button MODE activates the installation mode of network node. Low temperatures at the battery may cause a similar behaviour in other modes too. The main battery used by the WTT16... requires careful treatment: Do not short-circuit or damage the battery Do not expose the battery to excessive heat eturn exhausted batteries to the supplier ead the enclosed safety instructions carefully M-Bus connection Any network node can be connected to the M-Bus temporarily (service connector) or continuously (screw terminal for the fixed M-bus connection). A plug for the screw terminal is included with every network node. Screw terminal for the fixed M-Bus connection max. 5 unit loads M-Bus service connection MODE ESET 7/8

150 250 100 31,8 9,7 Optical IrDA-interface Starting from version 2.2 each network node supports optical IrDa interface. This interface is always active and could be used for service with commissioning tools or for data exchange with others IrDA-able QUNDIS products. IrDA-master mode has to be started manually if network node it self should work as IrDA-master (e.g for data exchange with metering device). Technical data conformity to EMC directives Safety class IP32 Safety class 2 Electromagnetic compatibility immunity: EN 55 024/EN 301 489 emissions: EN 55 022/EN 300 220-1 Operating voltage WTT16... DC 3.6 V Lifetime of main battery > 5 years Operating voltage WTX16... AC 100..240 V, 50/60Hz ated frequency 868.3 MHz Transmitter power < 14 dbm Frequency of transmission <1% Perm. ambient temperature Transport and storage Operation Weight 20...+60 C (< 30 C recommended) 0...55 C 0.3 kg Dimensions WTX16... 55 2,5 184 200 250 60 250 150 WTT16... 55 2,5 9,7 160 25,3 200 205 150 55 250 250 Dimensions in mm The information provided in this Data Sheet only gives general descriptions and general technical features which, in the case of specific applications, may not necessarily apply, or which may change due to further development of the product. Technical features are binding only when expressly agreed upon at the time a contract is concluded. 8/8 2009 QUNDIS GmbH Subject to alteration