Comparison of tripping characteristics for miniature circuit-breakers

Similar documents
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF19 and EF45

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

System pro M compact Miniature Circuit Breaker S 200/S 200 M

Three-phase monitoring relay CM-PFE

Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA

MCB Tripping Characteristics. MCB s Knowhow ABB STOTZ KONTAKT ABB STOTZ KONTAKT

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Manual motor starter MS116

Technical data. RCBO s DS 261 / DS 271 Residual current operated circuit breakers with integral overcurrent protection

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

Application Switchgear for industrial and commercial applications. U e V AC 230/ (per pole)

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Type: DILM32 10(24V50HZ) Article No.:

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Type: DILM9 10(24VDC) Article No.:

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Manual Motor Starter MS 116 up to 16 A Technical Data

Type: DILM50(230V50HZ,240V60HZ) Article No.:

6 ELECTRICAL PARAMETERS

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

Catalog. Modular DIN rail components Installation contactors

Analog signal converters CC-E I/I Current / current isolators

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Power transformers. Special transformers Railway

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

SELECTION OF FINAL CIRCUIT PROTECTION

Technical catalogue. Modular DIN rail components Installation contactors

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

R.C.C.B. s two-pole LEXIC

Technicaldata General

ZS25 Screw Clamp Terminal Blocks Feed-through

Pluggable interface relays CR-P Pcb relays

Technical Redline ED.03

ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Transformers. Special transformers Reactors products

Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC C0201

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data.

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

The complete range of consumer switchboards and switchgear

5SV Residual Current Protective Devices

UFES Active protection for switchgear

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

SURGE PROTECTIVE DEVICES

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Tmax MCCBs. Molded case circuit breakers. Tmax

MNS is Switchgear System Technical Overview

Circuit Breakers. NRC Series. NRC Series

Bimetallic Overload Relay Specifications

Series 8146/5-V37 and Series 8150/5-V37

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER A, SERIES BCF0 AND BCF6

How can a charging station for electric vehicles be set up simply and safely?

Low Voltage Products. Switches Automatic Transfer Switches

Plug and Socket Devices CES 63 A Series 8579

Electrical Shore Connections / Cold Ironing

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

Thermistor motor protection

NEC Class 2 Power Circuits and Power Supplies

ABB i-bus KNX Switch Actuators SA/S Product Information

Protection from Short-circuit

ABB solutions for photovoltaics Protection and other modular devices

Medium voltage products. Fuses

ESB and EN installation contactors Application handbook

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Thermal-Magnetic Circuit Breaker M1-..

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date:

Unified requirements for systems with voltages above 1 kv up to 15 kv

Part 1 System Modeling & Studies for Existing Systems

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

ABB i-bus KNX Switch Actuators SA/S Product Information

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.

Motor Protection Voltage Unbalance and Single-Phasing

Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES

Residual Current Circuit Breaker

PSR The compact range Description

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

40 Series - Miniature PCB/Plug-in relays A. Features

CUSTOMER CLASS FILE. ABB STOTZ-KONTAKT GmbH _0_000

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

White paper. ABB solutions for switching and protection of low speed wind turbines

Easy Multifunctional Safe

1587/1577. Insulation Multimeters. Technical Data. Two powerful tools in one.

GS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks

SAFETY MANUAL SIL RELAY MODULE

Transcription:

Comparison of tripping characteristics for miniature circuit-breakers The requirements for Protection for safety Protection against overcurrent are specified in IEC 03--3. Miniature circuit-breakers are used to protect cables in installations. They should disconnect automatically as soon as the combination of the current rise and duration causes the cable or a component to heat up excessively. Tripping Ausl sezeit time Seconds Sekunden Minutes Minuten 0 I I II =.3.3 x x Il n II =.5.5 x Il n = R = 30ß 30 C C R 0 0 = Tripping Grenzkennlinie curve aus from dem 0 0 0 0 0 0. 0. 0. 0. 0.0 0.0 B C D 0.0 0.0.5 3 5 0 Multiple Vielfaches of des the Bemessungsstromes rated current 0 30 Miniature circuit-breaker are used for: overload protection and short circuit protection in electrical circuits as well as protection against electric shock by automatic disconnection. The disconnection is performed by two different releases. The instantaneous tripping by electro-magnetic release provides protection against short circuits. This is only dependent on current. The thermal bi-metal release is used for protection against overload. It trips by temperature rise, in other words both current and time. When selecting miniature circuit-breakers for short-circuit protection in accordance with IEC 03--3, the permissible let-through value I x t for extremely short disconnection times (<0.s) is contrasted with the Joulean heat impulse of the current k x S of the cable in order to verify whether sufficient protection is guaranteed in the event of a short circuit. The desire for the best protection, which requires miniature circuit-breakers to be highly sensitive, has to be reconciled with the different operating characteristics of the loads to be protected. Load current peaks must be permitted to pass unhindered, yet at the same time a disconnection must be ensured in the event of relatively low, but continuous, overloads. Various tripping characteristics are therefore available for circuit-breakers depending on the type of component or equipment to be protected: B, C and D for overcurrent protection of cables in accordance with IEC/EN 0898- K for the protecting motors and transformers and simultaneous overcurrent protection of cables with overload tripping based on IEC/EN 097- Z for control circuits with high impedances, voltage converter circuits and semicable protection and simultaneous overcurrent protection of cables with overload tripping based on IEC/EN 097- The combination of tripping curves of the electro-magnetic release and the thermal bi-metal release result in an overall tripping curve for overload protection. This curve referred to the individual tripping characteristic represents the time/ current behavior of a miniature circuit-breaker.

Protection against short-circuits Figure shows typical let-through or I t values of overcurrent circuit-breakers. In the case of S0-B miniature circuit-breaker, this causes the letthrough energy to be limited to approx. 0,000 A s if a prospective short-circuit current i K = ka occurs. This value is far less than 9,700 A, meaning PVC-insulated Cu cables with a crosssection of.5 mm can be protected in the event of a short-circuit. Let-through I t / A s 0 5 8 3 0 8 B, C In = 50, 3 A 3, 0 A 0, 5 A A 0, 3 A A Cu cable, PVC-insulated mm.5.5.0 0.75 Max. permitted I t values A s 8,00 9,700 3,00 7,00 3 0 3 0 8 0 3 3 Prospective short-circuit current I K /A gl fuse Circuit-breaker Fig. Let.-through energy I t Overload protection in accordance with IEC 03--3 For protection against overload, the protective device must be selected based on the current carrying capacity I z of the cable: I b I n I z () I.5 x I z () 0 years t I b = Design current of a circuit I n = Rated current of the protective device I z = Current carrying capacity of the cable in accordance with IEC/HD 03-5-5 I = Current ensuring effective operation in the conventional time of the protective device Area of complete heat dissipation with continuous current I z Permissible operating temperature 70 C (PVC) Area of limited heat dissipation in the event of overload I.5 x I z h 3 Area without heat dissipation for a maximum short circuit duration of 5s I t = constant, permissible short circuit temperature 0 C 5 sec 0. sec 3 With a disconnection time of < 0.s, the I t of the miniature circuit-breaker must be less than k S of the cable (k = material value in accordance with IEC /HD 03--3; S = cable cross section in mm ) I z.5 I z 0 I z 00 I z I I,5 I 0 I 00 I Fig. Load limit curve for PVC-insulated cables I I z CDC0000D00

IEC 03--3 In individual cases, conditions () and () may not guarantee complete protection in accordance with the rules as aforesaid may not assure protection in certain cases, for example where sustained overcurrents less than I occur. In such cases, consideration should be given to selecting a cable with a larger cross-section area. The general aim is to use the selected characteristic to protect a cable in accordance with its load capacity limit as shown in figure. Tripping time Seconds Sekunden Minutes Minuten 0 0 0 0 0 0 0 0 I =.05 x l n I n I I = =.. x x l n I n J= R = 00ß C C(K, Z) I =.3 x l n I n I I = =.5.5 x x l n I n J= R = 3030ß C C(B, C, D) = Tripping Grenzkennlinie curve from aus dem 0. 0. Protection against overload Furthermore, protection devices with I values close to the rated current I n can increase the effectiveness of overload protection significantly. Please refer in these cases to K- or Z-characteristic with I =, x I n. 0. 0. 0.0 0.0 0.0 Z B C 0.0.5 3 5 8 0 K D 0 30 Multiple of the rated current Temperature of PVC-insulated cables at overload Load Cable temperature*.0 x I n 70 C. x I n 8 C.5 x I n C Service life of PVC-insulated cables according to the Arrhenius equation Cable temperature Service life 70 C 0.0 years 90 C.5 years 00 C.0 year * 90 % of the temperature value is reached from operating temperature after 5 minutes. CDC0000D00 3

Comparison of tripping characteristics Z and B V DC control circuits In order to achieve the best possible protection of sensitive devices, such as contacts or prefabricated cables of sensors/limit switches, the instantaneous tripping must clear even low shortcircuit currents within milliseconds. The maximum cable lengths in relation to loop resistance must not be exceeded. Taking account of various parameters, the maximum cable lengths could be as follows:.5 mm, two-wire, Cu: MCB B max. 0 m MCB Z max. 7 m MCB Z max. 8 m Due to the low instantaneous tripping current, the maximum cable lengths can be realized by using the Z characteristic. Tripping time Sekunden Seconds Minutes Minuten 0 0 0 0 0 0 0 0 I =.05 x x l n I I n =. x l n I J n R J = 0 0ß C C (Z) R I =.3.3 x x l n I I n =.5.5 x l n I J n R J = R 30 30ß C C (B) = Grenzkennlinie Tripping curve from aus dem Note With direct current, the tripping values of the electromagnetic releases are increased by a factor of.5. 0. 0. Protection against overload As stated before it is obvious that tripping characteristic Z provides better protection during operation and is easier to choose when planning. 0. 0. 0.0 0.0 0.0 Z B 0.0.5 3 5 8 0 5 0 30 Vielfaches Multiple of des the Bemessungsstromes rated current Temperature of PVC-insulated cables at overload Load Cable temperature*.0 x I n 70 C. x I n 8 C.5 x I n C Service life of PVC-insulated cables using the Arrhenius equation Cable temperature Service life 70 C 0.0 years 90 C.5 years 00 C.0 year * 90 % of the temperature value is reached from operating temperature after 5 minutes. CDC0000D00

Comparison of tripping characteristics C and K K solves the conflict of service continuity in the event of peak currents and rapid disconnection in the event of a short-circuit. 0 0 0 I =.05 x l n I n I =. x li n n = 0ß C C (K) I =.3 x l n I n I =.5 x li n J R = 30ß C C (C) In circuits where inrush currents or starting current peaks can occur due to motors, chargers, welding transformers, etc., tripping characteristic K has proven to be successful for more than 70 years. Current peaks of up to 0 I n do not lead to unintentional disconnection. Tripping characteristic C only withstands current peaks of up to 5 I n. Note With direct current, the tripping values of the electromagnetic releases are increased by a factor of.5. Tripping Ausl sez time eit Sekunden Seconds Minutes Minuten 0 0 0 0 0 = Tripping Grenzkennlinie curve from aus dem 0. 0. Protection against overload As stated before it is obvious that tripping characteristic K provides better protection during operation and is easier to choose. 0. 0. 0.0 0.0 0.0 C 0.0.5 3 5 8 0 Multiple of the rated current K 0 30 Temperature of PVC-insulated cables at overload Load Cable temperature*.0 x I n 70 C. x I n 8 C.5 x I n C Service life of PVC-insulated cables using the Arrhenius equation Cable temperature Service life 70 C 0.0 years 90 C.5 years 00 C.0 year * 90 % of the temperature value is reached from operating temperature after 5 minutes. CDC0000D00 5

Comparison of tripping characteristics K and D K solves the conflict of service continuity in the event of peak currents and rapid switch off in the event of a short circuit. 0 0 0 I =.05 x x l n I n I =. x l n I n = 0 0ß C C (K) II =.3 x x l n I I n =.5 x x l n I J n R = = 30 30ß C C (D) Tripping characteristic K trips at the latest at I n in <0. seconds. By contrast, tripping characteristic D disconnect the device at 0 I n in <0. seconds, which could be a disadvantage both with regard to the loop resistance and for cable protection in the range from 0-0 x I n. Example: A socket is protected with a D miniature circuit-breaker. A minimum short-circuit current 30 A must be ensured in order to comply with the disconnection condition of 0. s for protection against electric shock. Note With direct current, the tripping values of the electromagnetic releases are increased by a factor of.5. Tripping time Sekunden Seconds Minutes Minuten 0 0 0 0 0 0. 0. = Grenzkennlinie Tripping curve from aus dem kalten cold state Zustand Protection against overload As stated before it is obvious that tripping characteristic K provides better protection during operation and is easier to choose. 0. 0. 0.0 0.0 0.0 0.0.5 3 5 80 K D 0 30 Multiple of the rated current Temperature of PVC-insulated cables at overload Load Cable temperature*.0 x I n 70 C. x I n 8 C.5 x I n C Service life of PVC-insulated cables according to the Arrhenius equation Cable temperature Service life 70 C 0.0 years 90 C.5 years 00 C.0 year * 90 % of the temperature value is reached from operating temperature after 5 minutes. CDC0000D00 CDC0000D00

Tripping characteristics B, C, D, Z, K Tripping characteristics B, C, D Tripping characteristics K, Z in accordance with IEC/EN 0898- in accordance with IEC/EN 097- Constructional requirements for MCBs for Constructional requirements for MCBs. household installations and similar purposes. I II I =.3 x li n I I x I n JR= 30ß C x I I n =.5 x l n = C I =.05 x l n I I I =. x l n JJR = 0ß C R = C = Tripping Grenzkennlinie curve from aus dem = Tripping Grenzkennlinie curve from aus dem B C D Z K.5 3 5 0 0 30.5 3 5 8 0 0 30 Compared with tripping characteristics B, C and D, K and Z provide better protection during operation and is easier to choose. Assignment B, C and D for overcurrent protection of cables in accordance with IEC/EN 0898- K for protecting windings in motors and transformers and simultaneous overcurrent protection of cables Z for control circuits with high impedances, voltage converter circuits and semiconductor protection and simultaneous overcurrent protection of cables CDC0000D00 7

Other criteria when selecting miniature circuit breakers In order to protect a circuit optimally, additional considerations and constraints must be considered when selecting the miniature circuit-breakers. Deviating ambient temperature For installations of miniature circuit-breakers at other temperatures than the reference value, derating factors have to be considered. The rated value of the current of a miniature circuit-breaker refers to a reference ambient temperature of 30 C for miniature circuit-breakers with the characteristics B, C and D and 0 C for miniature circuit-breakers with the characteristics K and Z. If the ambient temperature is higher, the maximum operating currents are reduced by approx. % per +0 C temperature difference. For precise calculations and extremely high or low ambient temperatures, reference tables must be consulted. Influence of adjacent devices If several miniature circuit-breakers are installed directly side by side with high load on all poles, a correction factor has to be applied to the rated current (see table). If distance pieces are used, the factor is not to be considered. No. of adjacent devices Factor F, 3 0.9, 5 0.8 0.75 Tripping characteristics Acc. to Tripping characteristics Rated current Thermal release ) Electromagnetic release ).5 I n Currents: I n conventional non-tripping current I conventional tripping current I IEC/EN 0898- B to 3 A.3 I n > h Tripping time Range of instantaneous tripping Tripping time 5 I n 0.... 5 s (I n 3 A)/0.... 30 s (I n > 3 A).5 I n 0 I n 0.... s (I n 3 A)/0.... 8 s (I n > 3 A).5 I n 0 I n > 0. s. I n I n > 0. s. I n < h 3) 5 I n < 0. s 3 I n 0.... 5 s (I n 3 A)/0.... 90 s (I n > 3 A) C 0.5 to 3 A.3 I n > h < h 3) 0 I n < 0. s D 0.5 to 3 A.3 I n > h < h 3) 0 I n < 0. s IEC/EN 097- K 0.5 to 3 A.05 I n > h < h 3) I n < 0. s Z 0.5 to 3 A.05 I n > h < h 3) 3 I n < 0. s ) The thermal releases are calibrated to a nominal reference ambient temperature; for B, C, D the reference value is 30 C, for K and Z the reference value is 0 C. In the case of higher ambient temperatures, the current values fall by approx. % for each 0 K temperature rise. ) The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/0 Hz. The thermal release operates independent of frequency. 3) As from operating temperature (after I > h) 8 CDC0000D00

Miniature circuit breakers for cable and equipment protection and their fields of application Fields of application S 00 S 00 P S 0 S 800 S 700 S 00 S 00 M S 00 U/UP S 500 HV S 750 (DR) SMISSLINE S 00 UDC S 800 PV WT 3 S 80 UC Industrial networks 90 V AC S 0 S 800 000 V AC S 500 HV Motor protection, transformer S 00-K S 00 P-K S 0-K S 800-K S 700-K S 00 M-K S 00 M-K S 80 UC-K S 800-D WT 3 S 00 M-D S 750 DR-K UPS 50 V DC to Photovoltaics 00 V DC S 80 UC S 800 UC S 00 M-UC C S 800 PV Semicable pro- Control S 00-Z S 00 P-Z S 00 M-UC Z tection circuits S 00 M-Z V DC Selectivity S 700 S 750 (DR) Isolating function in accordance S 00 S 00 P S 0 S 800 S 700 S 00 with IEC 03-5-537 S 00 M S 750 (DR) S 00 M USA, Canada 80 V AC S 00 UP 89 0 V AC S 00 U 0 V DC S 00 UDC USA, Canada 00 V AC S 0 077 80 V AC S 00 M S 00 P 0 V DC S 00 M S 00 P 500 V DC S 80 UC Marine classifications S 00 S 00 P S 800 S 700 (GL) S 00 M GL LRS S 00 M BV DNV Rated switching 000 max. 5,000 max. 0,000 max. 50,000 5,000,000 capacity I cn /A 0 000 0 000 (30/00 V AC) I n /A 3 0.5... 3 3 5 00 3 As a selective group or upstream MCB CDC0000D00 9

Contact ABB STOTZ-KONTAKT GmbH PO Box 0 80 900 Heidelberg, Germany Phone: +9 (0) 7 0 0 Fax: +9 (0) 7 0 3 5 E-mail: info.desto@de.abb.com www.abb.de/stotzkontakt Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Brochure number CDC 00 00 D00 (0.3-pdf) Copyright 03 ABB All rights reserved