High-Voltage Conventional Duct Detector D300A-HV. Installation Guide

Similar documents
Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

D287/D288/D292/D293A/D293E

E-PDD Duct Smoke Detector Installation Sheet

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES

DUCT SMOKE DETECTOR D4120

8900 EMR (WITH DETECTOR)

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

TS93 EMR T/PT/TDE. Surface applied door closer

D4120 Duct Smoke Detector D4S Sensor Component D4P120 Power Board Component

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

HM-W536 Install Guide

Smoke Detector PSD 2 & 4 Wire Units

INSTALLATION AND MAINTENANCE INSTRUCTIONS I R

DH100ACDCLWP Watertight Air Duct Smoke Detector with Extended Air Speed Range

Duct Humidity Transmitter

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions

OPL BASIC. Dosing System for Professional Laundry machines. Contents

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

SLIM LINE FUME HOOD MONITOR

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

12 Volt 30 Amp Digital Solar Charge Controller

TrueAlarm Fire Alarm Systems

HMI display Installation Guide

LIEBERT VNSA Installation Sheet

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

FIREDEX Conventional Fire Panels

DLP-PU/E Instruction Manual

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

T7079A,B Solid State Remote Temperature Controllers

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

Advantium 2 Plus Alarm

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

Smoke Detectors Ordering Information DS230 DS230 Series Heat Detectors DS230F DS233F Peripheral Accessories EOL200 TP280 Bases Features

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

SECTION DETECTION AND ALARM

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

rpsa FIRE PROTECTION ENGINEERS

Reliance DuraStar ORDINARY LOCATION INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS

PIEZOMETER AIRFLOW MEASURING RING

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

Technical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

, User s Manual

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

Fire & Security DETECTORS

EDD-600 FLOW TOTALIZER RATE INDICATOR OPERATION MANUAL. P.O. Box Odessa, Texas USA.

Control Panel. D9412GV4/D7412GV4 v2.03. en UL Installation Instructions

Y7230A CO 2 Alarm System

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

AC-115 Compact Networked Single Door Controller. Installation and User Manual

INSTALLATION INSTRUCTIONS

Water Leak Detection System

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

Telefon (+45) Telefax (+45) Installation and operating manual

UV100A Ultraviolet Air Treatment System

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

D9412GV3/D7412GV3. Approved Applications Compliance Guide. Control Panels

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

MOUNTING AND OPERATING INSTRUCTIONS

2-WAY WIRELESS SUPERVISED PHOTOELECTRIC SMOKE DETECTOR. Model: EL-4703 INSTALLATION INSTRUCTIONS

Holder/Release Devices with Integral Door Closers DORMA EMF/ EMR

Fire Fighter Phone System Installation Instructions

G670 Intermittent Pilot Ignition Controls

Cooktop Low-Profile Ventilation Hoods

DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual

OPERATING INSTRUCTIONS

Adjustment functions for both span and shift have been incorporated

MCR1900 Media Converter 19-Slot Chassis

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual


EMF/EMR. Holder/Release Devices with Integral Door Closers

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1

FIRERAY 2000 Installation Guide

Mounting Plate / Screwdriver. Alignment Stickers Screws / Desiccant Bag / Double-sided Tape / Rubber Seal Plug / Rubber Washer

650W Single Output Power Supply

FAAST. Fire Alarm Aspiration Sensing Technology

PowerLogic Sub Meter Display (SMD and SMDOPN)

FCC COMPLIANCE STATEMENT FOR AMERICAN USERS

VAQ. Built-in V-series Miniature Basic Switch for Compatibility with Business and Consumer Equipment. Pushbutton Switch (Cylindrical 10.5-dia.

WD-AMX Water Detection Controllers

Electronic Control Devices The European Product Catalogue 2007

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

MIC-WKT and MIC-WKT-IR

Fire Control Panels. Remote Annunciator Panels. UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features. Introduction

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Class 2 transformer (TBT) Low Tension Conform to EN A LED turns ON when the current exceeds 1 A at the 14V output connector

Repeaters and Mimics Data Sheet

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

tidesmarine Smart Seal Temperature Alarm System Generation II Installation Instructions Starboard side cable

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

Transcription:

High-Voltage Conventional Duct Detector D300A-HV en Installation Guide

High-Voltage Conventional Duct Detector Table of Contents en 3 Table of Contents 1 Notice 4 2 Overview 4 3 Mounting 4 3.1 Preparing the Duct 4 3.2 Verifying Air Flow and Direction 5 3.3 Assembling the Intake Sampling Tubes 6 3.4 Mounting the Intake Sampling Tubes 6 3.5 Mounting the Detector 6 3.6 Verifying the Air Sampling 6 4 Wiring 6 4.1 Testing 8 4.2 Replacing the Detector Head 8 5 Specifications 8 Bosch Security Systems, Inc. Installation Guide F.01U.035.635 5.0 2011.09

4 en Notice High-Voltage Conventional Duct Detector 1 Notice Use these instructions when installing the D300A-HV High-Voltage Conventional Duct Detector in a system controlled by a fire alarm control panel (FACP). Install, test, and maintain the D300A-HV according to these instructions, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ). NOTICE! Failure to follow these instructions can cause the device to not properly operate. Bosch is not responsible for improperly installed, tested, or maintained devices. NFPA 72 requires a complete, system-wide Functional Test be performed after making modifications, repairs, upgrades, or adjustments to the system s components, hardware, wiring, programming, software, or firmware. The D300A-HV is not intended for open area protection. Refer to the NFPA 90A and NFPA72E, for general and additional duct smoke detector operation and installation. DANGER! Follow the procedures in these instructions to avoid personal injury and/or damage to the equipment. 2 Overview 3 Mounting The D300A-HV High-Voltage Conventional Duct Detector Housing unit is an accessory device complete with a photoelectric smoke detector head used in HVAC duct works. It can be powered by 24 VAC, 24 VDC, or 230 VAC and is intendend for high-voltage applications. Air sampling is accomplished by two tubes that protrude into the duct. An exhaust tube of one standard length is supplied in the installation kit with the duct detector housing unit. Once the duct width is determined, the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths and cut to size to fit the duct. The air samples are collected by positive pressure to the detector head. Output terminals are provided for remote accessories such as remote status indicators (LEDs), reset keyswitches, and push buttons. CAUTION! To prevent false alarms, do not mount the D300A-HV Duct Detectors in areas: of extreme high or low temperatures, where high humidity exists, where duct air might contain gases or excess dust. Refer to NFPA 90A, NFPA 72E, and NFPA 101. Also refer to Section 5.0 Specifications. 3.1 Preparing the Duct When preparing the duct, refer to Figure 3.1 on page 5. 1. Remove the paper backing from the mounting template included in the Installation Kit. 2. Attach the template to the duct at the desired location. 3. Using the template as a guide, drill four mounting holes (3/32 in. [2.38 mm] diameter) for the duct mounting screws (four #12 x ½ in. [1.27 cm] sheet metal screws packaged in installation kit). 4. Drill or punch holes for the sampling tubes in the air duct (1.375 in. [3.49 cm]) 5. Clean all holes. F.01U.035.635 5.0 2011.09 Installation Guide Bosch Security Systems, Inc.

High-Voltage Conventional Duct Detector Mounting en 5 3.2 Verifying Air Flow and Direction Use the D300A-HV in ducts with air velocities between 300 ft to 4000 ft (91 m to 1219 m) per minute. Verify the air velocity by checking the duct installation specifications, or by using an Alnor Model 6000P (or equivalent) velocity meter. Refer to Figure 3.2 on page 5 for sampling tube orientation to air flow direction. Figure 3.1 Mount the Duct Housing 1 - Six duct widths (minimum) from any 7 - Exhaust tube bend or other obstruction 2 - Air duct 8 - Set screws (2) 3 - Template 9 - Intake sampling tube connectors (2) 4 - Stopper 10 - Duct mounting screws (2) 5 - Air flow for this illustration 11 - Top of the D300A-HV Housing 6 - Intake sampling tube 1 Figure 3.2 Intake Sampling Tube Orientation 1 - Insert stopper at this end of the 5 - Exhaust tube (2) intake sampling tube. 2 - Air flow 6 - Air holes (6) 3 - Intake sampling tube (2) 7 - Set screws (4) 4 - Duct width* 8 - Tops of the D300A-HV Housings * Support the intake sampling tube where the duct width is greater than 3 ft (91 cm). Bosch Security Systems, Inc. Installation Guide F.01U.035.635 5.0 2011.09

6 en Wiring High-Voltage Conventional Duct Detector 3.3 Assembling the Intake Sampling Tubes The intake sampling tube is a piece of steel piping with a series of holes drilled along its entire length. Ensure the holes face into the airflow. Exhaust tubes are pieces of steel piping approximately 7.5 in. (19 cm) long. The sampling tubes come in the standard lengths shown in the table. You need to cut them to fit in the duct. Model Number Sampling tube length FAA-325-2.5 2.5 ft (76 cm) FAA-325-5 5 ft (152.5 cm) FAA-325-10 10 ft (305 cm) Table 3.1 Intake Sampling Tube Standard Lengths 1. Prepare the intake sampling tubes by cutting them to the desired lengths. 2. Insert the stopper, included in the Installation Kit, into the end of the intake sampling tube. 3.4 Mounting the Intake Sampling Tubes The intake sampling tube connectors are equipped with set screws that allow you to mount the tubes only in the directions shown in Figure 3.2 on page 5. Consider the airflow direction when orienting the intake sampling tubes. 1. Insert the intake sampling tubes and exhaust tubes into the connectors. 2. Align the set screws to the set screw holes in the tubes and tighten. Refer to Figure 3.1 on page 5 for mounting details. 3.5 Mounting the Detector 1. Position the detector and intake sampling tube assembly in the desired location. 2. Using four duct mounting screws (four #12 x ½ in. [1.27 cm] sheet metal screws included in the installation kit), attach the D300A-HV on the duct. 3.6 Verifying the Air Sampling 4 Wiring Use a Dwyer Model 4000 Differential Pressure Gauge or its equivalent to verify the correct air sampling. Ensure the pressure differential between the input sampling tube and exhaust tube is greater than 0.01 in. (0.3 mm) and less than 1.2 in. (3.1 cm) of water. Refer to Figure 3.2 on page 5 for the intake sampling tube orientation to air flow direction. NOTICE! Ensure that power is removed from all wiring before routing. Observe polarity. Wiring must conform to applicable local codes, ordinances, and regulations covering this type of device. Wire the detectors according to the engineering drawing for that particular job requirement. For D300A-HV wiring details, refer to Figures 4.1 on page 7. Terminals are suitable for up to 14 AWG (1.8 mm) wire. CAUTION! Do not use looped wire under Terminals. Run break wire to provide supervision of connections. F.01U.035.635 5.0 2011.09 Installation Guide Bosch Security Systems, Inc.

High-Voltage Conventional Duct Detector Wiring en 7 To wire the D300A-HV: 1. De-energize the power source. 2. Wire all connections according to the engineering drawings. 3. Verify the system wiring. 4. Energize the detector. Figure 4.1 Wiring the D300A Terminals 1 - Switche Power connections upon 5 - Alarm contacts 1 A at 24 VDC reset(connect items 2 or 3, not both) 2-230 VAC 60 Hz input at 0.1 A 6 - Trouble contacts 10 A at 115 VAC* maximum 3-24 VAC/VDC 60 Hz input at 0.1 A 7 - Remote accessories maximum (detector only). Up to 1.9 A for auxiliary outputs. 4 - Alarm contacts 10 A at 115 VAC * Trouble contacts are shown in non-energized condition. Trouble contacts monitor power connected and head removed. 2 2 1 14 15 14 15 12 12 11 11 3 Figure 4.2 Wiring the D300A to an FACP 1 - UL Listed FACp 3 - EOL Device 2 - D300A-HV Detector Bosch Security Systems, Inc. Installation Guide F.01U.035.635 5.0 2011.09

8 en Specifications High-Voltage Conventional Duct Detector Black (-) 1 18 3 2 17 3 19 Red (+) 16 Black (-) 1 20 4 16 Red (+) Figure 4.3 Remote Access Memory 1-1.2 kω, 1 W current-limiting resistor 3 - Key or push button Test/Reset switch (4 A at 24 VDC) 2 - Red "ALARM LED" (15 ma at 24 VDC) 4 - Green Pilot LED (15 ma at 24 VDC) 4.1 Testing The D300A-HV photoelectric detector has a built-in sensitivity window verification feature. If the detector is within its calibrated sensitivity range, the detector LEDs flash green in standby or normal operation. If the detector drifts outside its sensitivity range, the LEDs flash red to indicate an out of sensitivity condition. Bosch D1000 Calibrated Smoke Detector Tester may also be used to check sensitivity. 4.2 Replacing the Detector Head If the detector head supplied with the D300A-HV must be replaced, only replace the existing head with a D282A-DH Replacement Photoelectric Smoke Detector Head. 1. Remove the four screws holding the detector s cover. 2. Remove the existing detector head by twisting it counterclockwise. 3. Insert the D282A-DH and turn it clockwise. 4. Replace the detector s cover and tighten the screws. 5 Specifications Standby Current 20 ma at 24 VAC 13 ma at 24 VDC 8 ma at 230 VAC Alarm Current 95 ma at 24 VAC 60 ma at 24 VDC 15 ma at 230 VAC Alarm Relay Contact Rating 10 A maximum at 250 VAC resistive Trouble Relay Contact Rating 10 A maximum at 250 VAC resistive Sensitivity Range (Factory Set) 1.5%/ft to ~2.75%/ft (4.8%/m to ~ 8.7%/m) Differential Pressure 0.01 in. (0.25 mm) - 1 in. (3 cm) of water Air Velocity 300 ft/min to 4000 ft/min (91 m/min to 1219 m/ min) Ambient Temperature +32 F to +120 F (0 C to +49 C ) F.01U.035.635 5.0 2011.09 Installation Guide Bosch Security Systems, Inc.

High-Voltage Conventional Duct Detector Specifications en 9 Humidity Intake Sampling Tubes Replacement Detector Head 10% RH to 85% RH (non-condensing) FAA-325-2.5: 2.5 ft (0.8m) FAA-325-5: 5.0 ft (1.5m) FAA-325-10: 10 ft (3m) D282A-DH Replacement Photoelectric Smoke Detector Head Bosch Security Systems, Inc. Installation Guide F.01U.035.635 5.0 2011.09

10 en Specifications High-Voltage Conventional Duct Detector F.01U.035.635 5.0 2011.09 Installation Guide Bosch Security Systems, Inc.

Bosch Security Systems, Inc. 130 Perinton Parkway NY 14450 Fairport USA www.boschsecurity.us Bosch Security Systems, Inc., 2011