CA SERIES CONDENSING UNITS INSTALLATION AND OPERATION MANUAL. AAON Coil Products MANUFACTURED IN THE U.S.A

Similar documents
Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

LOBOY 16 AIR CONDITIONERS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

SECTION AIR CONDITIONING UNIT

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

, User s Manual

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS

Why and How we Use Capacity Control

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

REMOTE AIR-COOLED CONDENSERS. Installation and Maintenance Data. Models Bulletin H-IM-73A June 2000 Part Number

MAC-120HE-01 Air-Cooled Chiller

COMPRESSOR REPLACEMENT PROCEDURE

Oil and Coolant Circulating Heating System. Model - OCSM

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Evaluate, Clean, and Tune Guidance

T-Series Air Conditioner T62 Model

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

NSN

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

HVAC-02, Air Conditioning Troubleshooting and Repair

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.

Refrigeration System Installation & Operation Manual

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t.

10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS

Utility Distribution Systems

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Low Profile Unit Cooler

Heat Pump Water Heater IOM Manual

WE-350 Series ¼ Turn Electric Actuator

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

SECTION MORTUARY REFRIGERATORS

First irst Co. Products

DESIGN STANDARDS SECTION

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

SECTION HEAT PUMPS

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402

Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

SL280UHV SERIES GAS FURNACE WARNING

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS

CDS TROUBLESHOOTING SECTION I. VACUUM Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING

Chilled Water HVAC Systems

STATEMENT OF WORK FOR MAINTENANCE OF AIR CONDITIONERS

Air Conditioner B B

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Panel Mounted Air Conditioners by Dantherm, Inc.

Genesis Air Conditioner

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Installation Instructions

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

User s Information/Installation Instructions

REMOTE RACK SYSTEM OWNERS MANUAL INSTALLATION OPERATIONS - MAINTENANCE

WINDOW ROOM AIR CONDITIONER

OWNER S GUIDE OPERATION & INSTALLATION

E2 Series Electric Furnaces

A. Section includes air conditioning units, controls and control panels.

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

SWIMMING POOL HEAT PUMP

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL. Rev. F 2015 Pentair Equipment Protection P/N

INSTALLATION INSTRUCTION

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL. Rev. F 2016 Pentair Equipment Protection P/N

CARING FOR YOUR WATER HEATER

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL

USER S MANUAL HSC-24A

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL. Rev. S 2014 Pentair Equipment Protection P/N

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

AE R6 December Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE R6

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

Split System Heat Pump Product Data

Trouble Shooting. Pump

Central Air Conditioner

T-SERIES Air Conditioner. T53 Model INSTRUCTION MANUAL. Rev. F 2013 Pentair Equipment Protection P/N

Portable Air Conditioner

Transcription:

AAON Coil Products CA SERIES CONDENSING UNITS INSTALLATION AND OPERATION MANUAL MANUFACTURED IN THE U.S.A! WARNING Scroll compressors will be damaged by operation with the wrong rotation. THE LOW PRESSURE SWITCH HAS BEEN DISCONNECTED AFTER TESTING AT THE FACTORY. The wiring must be reconnected and proper rotation determined at the time of start-up by a qualified service technician using suction and discharge pressures gauges. Any alteration should only be made at the unit power connection. 1

AAON Coil Products SECTION TABLE OF CONTENTS PAGE NUMBER INSTALLATION 3 General Location Service Clearance Setting the Unit Electrical Thermostat REFRIGERANT PIPING General 4 Interconnecting Piping CHECKOUT PROCEDURE 6 Cooling Compressor Checkout Procedure 7 SERVICE, TROUBLE SHOOTING & MAINTENANCE 8 General Instructions Coil Information! CAUTION Installation and service must be performed by a qualified installer or service agency.! IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC's and HCFC's) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance. Owner should pay particular attention to the words: NOTE, CAUTION AND WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert owner that personal injury and/or equipment damage may result if installation procedure is not handled properly. It is the intent of AAON Coil Products, Inc. to provide accurate and current specification information. However, in the interest of product improvement, AAON Coil Products, Inc. reserves the right to change pricing, specifications and/or design of it's products without notice, obligation or liability. P84510-A (ACP 27230) 1999 AAON Coil Products, Inc., all rights reserved throughout the world. 2

INSTALLATION AAON Coil Products 'CA' Series units are designed for fast easy installation GENERAL All CA condensing units have lifting areas at the underside of the equipment to allow moving and placement without physical damage. Arrange spreader bars, blocking or other lifting devices to prevent any damage to the coils or cabinet of the condensing unit. These condensing units may be placed on a roof or at ground level since they are designed for exposure to weather. When roof mounted, a steel frame must be provided that will support the unit above the roof itself. When installed at ground level, a substantial base must be provided that will not settle. LOCATION Airflow to and from the condensing unit must not be restricted. Obstruction to air flow will result in decreased performance and efficiency. The installation position must provide at least 3 feet of side clearance for proper air flow into the coils. When units are mounted adjacent to each other the clearance required between them would be 6 feet. Condensing units should not be installed in an enclosure or pit that is deeper than the height of the unit. When a recessed installation is used the side clearance requirement is doubled to 6 feet for the inlet air. The CA 02 through CA 05 model sizes have a horizontal airflow pattern. The discharge air side of one unit should not be aligned with the intake of another. The discharge air should be faced away from the adjacent building or structure. The CA 08 through CA 25 models have a vertical air discharge. There must be no obstruction above the equipment that may deflect this air back to the inlet of the condensing unit. Do not place the unit under an overhang. Condensing unit operation can also be affected by wind. It is good practice to position the unit so its length is parallel with the prevailing wind. SERVICE CLEARANCE One end of the CA condensing unit contains the access door that must be accessible for periodic service. This area contains the compressor, controls, safety devices, refrigerant service and shut-off valves.! IMPORTANT Three phase Scroll Compressors are directional and start-up must be performed by a qualified service technician using suction and discharge gauges. 3 It is recommended that a minimum of 4 feet be left free at this end of the unit for proper and easier servicing. SETTING THE UNIT If cables or chains are used to hoist the unit, care should be taken to prevent damage to the cabinet. Hoist unit to a point directly above the pad, and lower unit into the proper place. Unit may also be positioned with a forktruck. Remove the harness used in hoisting. Make sure the unit is properly seated and level. ELECTRICAL Check the unit data plate to make sure it agrees with the power supply. Connect power to the unit according to the wiring diagram provided with the unit. The power and control wiring may be brought in through the holes provided at one corner of the unit. Protect the branch circuit in accordance with code requirements. If the control wires are to run inside the same conduit, use 600 volt wire or as required by applicable codes. The unit must be electrically grounded in accordance with the National Electric Code, ANSI / NFPA No. 70-1984 when installed if an external source is utilized, in Canada use current C.S.A. Standard C22.1 Canadian Electric Code Part 1. Power wiring is to the unit terminal block or compressor contactor. All wiring beyond this point has been done by the manufacturer. Connect the control wiring and apply power to the unit. CHECK FOR PROPER ROTATION BY START- ING UNIT ONLY AFTER CONNECTING PRESSURE GAUGES TO SUCTION AND DISCHARGE. THE WILL BE DESTROYED IF RUN IN THE WRONG DIRECTION. NOTE: All units are factory wired for 230, 380, 415, 460 or 575 volt. THERMOSTAT Low voltage room thermostat should be located on an inside wall 4 to 5 feet above the floor where it will not be subjected to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with thermostat for general installation procedure.! WARNING Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.

REFRIGERANT PIPING GENERAL All refrigeration systems are factory assembled, including a holding charge of R-22, and tested. On 13-25 ton units the refrigerant system includes dual condenser coils providing two stage cooling. These systems are provided with liquid line filter driers and fully hermetic compressors. Compressors are equipped with a positive pressure forced lubrication system and crankcase heater. The air cooled condenser coil(s) is constructed of copper tubes with aluminum fins (copper fins optional), the air is pulled through with steel propeller fans. All CA Condensing units have factory furnished liquid and suction line shutoff valves. The pipe sizes must be selected to meet the actual installation conditions and not simply based on the connection sizes at the evaporator and/or condensing unit. The refrigeration section of these appliances has been listed by E.T.L. as meeting the applicable provisions of UL 1995, CAN/CSA C22.2, No. 236-Second Edition. NOTE: Crankcase Heater Operation The 8 through 25 ton sizes are equipped with a crankcase heater, which should be energized at least 24 hours prior to setting the thermostat for cooling operation with the compressor. This section is not intended to provide all the information required by the designer or installer of the refrigerant piping between the condensing units and the low side components. The appropriate sections of the ASHRAE Guide and the ASME standards should be used for final information. The piping between the condenser and low side must assure: minimum pressure drop continuous oil return prevention of liquid refrigerant slugging or carryover.! IMPORTANT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC's and HCFC's) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance. once piped, the interconnecting piping and air handler MUST BE evacuated to 50 microns or less; leak checked and charged with R22 refrigerant. open the shut off valves. run unit, check rotation of compressors using refrigerant gauges. check super heat and subcooling; subcooling should be 10-13 F, evaporator superheat should be 10-15 F. Also check the compressor discharge line superheat. It should be at least 60 F. make sure airhandler thermal expansion valve bulb is mounted with good thermal contact on the correct suction line on a horizontal section, close to the evaporator in the 4 or 8 o'clock position and insulated. the suction line should be insulated for its entire length. SUCTION LINE The suction line pipe size should be selected to have a maximum pressure drop of 3 PSI for the equivalent length of piping that is used. This corresponds to approximately 2 F with R22. Any vertical suction risers should be checked to confirm that oil will be returned to the compressor. (Use the following tables for pipe sizing information). All suction lines must be pitched in the direction of flow and supported to maintain their position. Acceptable system design and installation will include consideration as follows: Interconnecting Piping Summary piping from the condensing unit to the indoor air handler is the responsibility of the installing contractor. only clean "ACR" tubing should be used. condensing units are provided with in-line shutoff valves on both the liquid and suction lines. These should remained closed until the system is ready for start-up. piping should conform to generally accepted practices and codes. care must be taken not to cross the circuits on multiple circuit systems. Fully insulated piping must be used between the evaporator and the condensing unit. A suction accumulator is not included as part of the CA condensing unit and must be field furnished and installed if required by job conditions. R22 SUCTION LINE CAPACITY Pressure Loss = 3 PSI (2 F) at 40 F saturated suction LINE SIZE - inches MAX. TONS / 5/8" 1.1 7/8" 2.9 1 1/8" 5.8 1 3/8" 10.1 1 5/8" 16.0 NOTE: Pressure loss, PSI/100 feet of equivalent line length due to line friction. (Corresponding change in R22 saturation temperature.) 4

LIQUID LINE The liquid line pipe size should be selected to have a maximum pressure drop of 6 PSI which corresponds to approximately 2 F with R22. The CA condensing units have a built in filter drier. The units do not include a liquid line solenoid valve and this must be field furnished and installed if required by job conditions. (OPTIONAL) HOT GAS LINE The hot gas bypass option is a system that maintains evaporator pressure at or above a minimum value. This will prevent the coil from freezing and also keep the velocity of the refrigerant gas sufficiently high for proper oil return to the compressor when the cooling is at light load conditions. Pressure drop in the hot gas line is normally designed not to exceed the equivalent of a 2 F change in saturation temperature. The recommended sizing table below is based on a 1 F change in saturation temperature. Hot gas bypass lines must be insulated to minimize heat loss and condensation of gas inside the piping and to prevent injury from high temperature surfaces. R22 LIQUID LINE CAPACITY Pressure Loss = 3 PSI (1 F) at 100 F liquid MINIMUM TONS CAPACITY To Carry Oil Up a Suction Riser at 40 F saturated suction LINE SIZE - inches FITTING LOSSES In Equivalent Feet of Straight Copper Tubing Line Size - in. 90 Std. 90 LongRad Min. TONS / 3/4" 0.8 7/8" 1.1 1 1/8" 1.8 1 3/8" 2.9 1 5/8" 4.0 2 1/8" 7.2 90 Street 45 Std. 45 Street 180 Std. 1/2" 1.4 0.9 2.3 0.7 1.1 2.3 5/8" 1.6 1.0 2.5 0.8 1.3 2.5 7/8" 2.0 1.4 3.2 0.9 1.6 3.2 1 1/8" 2.6 1.7 4.1 1.3 2.1 4.1 1 3/8" 3.3 2.3 5.6 1.7 3.0 5.6 1 5/8" 4.0 2.6 6.3 2.1 3.4 6.3 2 1/8" 5.0 3.3 8.2 2.6 4.5 8.2 NOTE: The equivalent feet for a piping system must include the equivalent length of straight tubing for all the fittings, as well as, any valves that are added to the system. LINE SIZE - inches MAX. TONS / 1/2" 3.6 5/8" 6.7 7/8" 18.2 NOTE: Pressure loss, PSI/100 feet of equivalent line length due to line friction. (Corresponding change in R22 saturation temperature.) R22 HOT GAS BYPASS LINE CAPACITY Pressure Loss = 3 PSI (1 F) at 40 F saturated suction LINE SIZE - inches TONS / 1/2" 0.85 5/8" 1.6 7/8" 4.2 1 1/8" 8.5 1 3/8" 14.8 NOTE: Pressure loss, PSI/100 feet of equivalent line length due to line friction. (Corresponding change in R22 saturation temperature.) 5 WEIGHT OF REFRIGERANT 22 In Type L Copper Tubing (Pounds / 100 Feet) Line Size - in. LIQUID AT 100 F SUCTION AT 40 F 3/8" 4.3.065 1/2" 7.9.120 5/8" 12.7.195 7/8" 26.4.405 1 1/8" 45.0.690 1 3/8" 68.6 1.05 1 5/8" - - - 1.49 2 1/8" - - - 2.58 WIRING DIAGRAMS A complete set of unit wiring diagrams is provided and located inside the control compartment door. HEATING SYSTEMS (optional as part of indoor air handler) When heat is called for, the cooling section is inoperable except for the indoor blower motor. Actual heating is accomplished by an indoor air handling unit with heating capabilities.

CHECK OUT PROCEDURES CAUTION: Before leaving installation, a complete operating cycle should be observed to see that all components are functioning properly. COOLING 1. Main Power Switch(es) is / are on and power is to the unit. 2. Put the thermostat in cooling mode and place the "fan" switch to on. Check to see if air handler blower is running in the correct direction and at the nameplate amperage. 3. TURN COOLING ON - Check to see that the compressor is operating. Check the amperage draw and compare to the nameplate (check amperage at the load side of the compressor contactor). SYSTEM OFF TROUBLE COOLING PACKAGE POSSIBLE CAUSE 1. Check power at line side of contactor(s). 2. Thermostat not set for cooling. 3. High pressure control tripped. 4. Low pressure switch open (loss of charge). 5. Low pressure switch open (clogged filters). CONDENSER FAN WILL NOT RUN EVAPORATOR BLOWER WILL NOT RUN SHORT CYCLES FAN MOTOR RUNS HOT AND CUTS OUT WILL NOT START BLOWER DOES NOT DELIVER AIR 1. Overload thermal protector open in motor. 2. Motor run capacitor open or shorted. 3. Fan or shaft stuck. 1. Overload thermal protector open in motor. 2. Relay not closing. 3. Capacitor shorted or open (PSC motors only). 4. Stuck shaft or blower wheel. 1. Check for low refrigeration charge. 2. Compressor overload opening. 3. Ambient temperature too low. 4. Thermostat in supply air stream. 5. Filters dirty or air flow restricted. 6. Evaporator blower not running. 1. Line voltage too high. 1. Line voltage too low. 2. Limit switches are open. 3. Overload or pressure control tripped. 1. Blower running backwards (3 phase only). 2. Dirty filters. 3. Duct obstruction. 6

CHECKOUT PROCEDURE CONTROL PANEL NOT SET FOR COOLING POWER TO UNIT CHECK UNIT FUSES AND WINDING THERMOSTAT NOT CALLING FOR COOLING LO PRESSURE SWITCH OPEN NO POWER TO CONTACTOR HI PRESSURE SWITCH OPEN NO POWER TO UNIT CHECK CIRCUIT BREAKER AT POWER DISTRIBUTION PANEL LOW AMBIENT LOCKOUT OPEN (TEMPERATURE OUTSIDE BELOW 55 DEG.) TRANSFORMER OPEN BROKEN OR LOOSE CONTROL WON'T RUN NO 24 VOLT POWER TO HOLDING COIL CONTACTOR OPEN POWER TO HOLDING COIL HOLDING COIL BURNED OUT REPLACE CONTACTOR POWER TO CONTACTOR ALL 3 LEGS HUMS STUCK GROUNDED WINDING MOTOR WINDING OPEN REVERSE LEADS REPLACE RUNS DOESN'T RUN REPLACE CONTACTOR CLOSED DOESN'T HUM POWER TO ALL 3 LEGS MOTOR WINDING OPEN INTERNAL OVERLOAD OPEN REPLACE IF DOME IS HOT, IT MAY BE LOCKED OUT ON INTERNAL OVERLOAD. WAIT FOR RESET, IT COULD TAKE AS LONG AS 2 HOURS. CHECKOUT PROCEDURE NO POWER TO BROKEN LEADS REPLACE LEADS LOW AIR (CONDENSER) HIGH HEAD PRESSURE OVERCHARGE OF REFRIGERANT AIR IN SYSTEM DIRTY CONDENSER COIL RUNS OR CYCLES (Poor Cooling) LOW HEAD HIGH SUCTION PRESSURE DEFECTIVE VALVES REPLACE LOW AIR (EVAPORATOR) CHECK FILTERS, OR DIRTY EVAPORATOR COIL OR LOOSE BELT LOW SUCTION PRESSURE LOW REFRIGERANT CHARGE RESTRICTED FEEDER TUBE BAD EXPANSION VALVE POWER ELEMENT 7

SERVICING, TROUBLE SHOOTING AND MAINTENANCE In the event the unit cannot be made to function correctly, it is strongly recommended that only servicemen who are well qualified and experienced in heating and air conditioning be permitted to service the systems. GENERAL LUBRICATING INSTRUCTIONS All original condensing unit motors and fan bearings REQUIRE NO LUBRICATION. COIL INFORMATION The condenser coil(s) MUST BE KEPT CLEAN. This will reduce electrical use, maintain capacity and reduce stress on the unit. Before attempting to clean the coils; set thermostat to the "OFF" position; turn the electrical power to the unit to the "OFF" position at the disconnect switch. The condenser coil can be thoroughly cleaned by washing from the inside out with water and a coil cleaner and can be brushed on the outside by a broom. If coil is extremely dirty with clogged fins, a serviceman who specializes in coil cleaning should be called. DO NOT BEND OR DAMAGE FINS. If the unit has been off for over an hour, restore power to the unit and wait two hours before turning the thermostat on. The inside (evaporator) coil can be inspected at the air handler by removing the filters and observing the cleanliness of the coil from the filter side. If dirty, have an experienced serviceman clean by washing from the blower side toward the filter side. AIR HANDLER - FILTER INFORMATION Install new filters with size indicated on the filters or as indicated by installation instructions before running the air handler. Be sure filters are installed in the correct direction with respect to the air flow. FILTERS SHOULD BE CHECKED EVERY 30 DAYS AND RE- PLACED OR CLEANED AS NECESSARY. Do not permit the unit to be operated unless the filters are in place. Operation of the unit without filters will result in a clogged evaporator coil - a very expensive service job to correct. AIR HANDLER - BLOWER INFORMATION CLEAN BLOWER WHEELS are necessary to reduce electrical use, maintain capacity and reduce stress on the unit. To inspect and clean the blower; set thermostat to the "OFF" position; turn the electrical power to the unit to the "OFF" position at the disconnect switch. Clean the assembly, check the bearings for looseness, inspect the belt condition and tightness, check screws for tightness, rotate blower wheel while listening close to each bearing and with a finger on the bearing to check for noise or roughness in the bearing, which indicates a failing bearing. Replace blower deck, turn on the power to the unit, if the unit has been off over on hour do not turn the thermostat on for two or more hours after turning on disconnect. OBSTRUCTION TO AIR FLOW Supply and return air grilles must be kept clear so air can be freely drawn into and discharged from the system. AAON Coil Products CA COOLING UNITS INSTALLATION AND OPERATION MANUAL AAON Coil Products, Inc. 203 Gum Springs Road Longview, Texas U.S.A 75602 ph: 903-236-4403 fax: 903-236-4463 P84510 (Rev A) 11-98 (ACP 27230) 8