STANDARD PRACTICES FOR ACTUATOR MOUNTING TO PROCESS VALVES

Similar documents
ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

Fisher 377 Trip Valve

Norbro Series 40R Pneumatic Actuator Double Acting or Spring Return

Recognizing and understanding schematic symbols will enable you to comprehend a circuit s function.

Pneumatic Actuators. Crafted without compromise, to make your life easier. The Leader in Actuator Technology

1 Important Safety Procedures. Qualified maintenance personnel should read and follow these straightforward instructions.

DIAMOND Gear Company, LTD. an ERIKS Company. Installation, Maintenance, & Operation Manual Declutchable Worm Gear

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics

Tyco PremiAir Pneumatic Actuators

Rotary Actuators, NAMUR interface VDI/VDE 3845 & ISO 5211 (ATEX certified) Series ARP

SHIFT INTERLOCK SYSTEM SHIFT INTERLOCK SYSTEM

BETTIS CONVERSION INSTRUCTIONS TO CONVERT HD SERIES ACTUATORS TO HD-M3, HD-SR-M3 HD-M3HW OR HD-SR-M3HW SERIES PNEUMATIC ACTUATORS

Electro-Pneumatic Bus Door Control Mechanism

A descriptive definition of valve actuators

Example. Fluid Power. Circuits

Valv-Powr Series VPVL Stainless Steel Model D Double-Acting and Spring-Return Rack-and-Pinion Compact Pneumatic Actuators

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

BULLETIN OCTOBER DeZURIK ROTARY DIAPHRAGM ACTUATORS

3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223

Powers Controls TH 192 S Single Temperature Room Thermostat

Model 43AP Pneumatic Controller, Style B

TS93 EMR T/PT/TDE. Surface applied door closer

SIMPLIFIED VALVE CIRCUIT GUIDE

POWERS Controls No. 4 Pneumatic Damper Actuator

P7100 PUMP INSTALLATION INSTRUCTIONS Diesel Care & Performance Inc

The Secret of Hydraulic Schematics. BTPHydraulics

THE 26-L BRAKE EQUIPMENT

Fisher 1061 Pneumatic Piston Rotary Actuator with Style F & G Mounting Adaptations

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

UM/ /2 or 5/3 Solenoid and air pilot actuated soft spool valves

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

PNEUMATIC CONTROLS Selection and Description

UNIT II Robots Drive Systems and End Effectors Part-A Questions

SIMPLIFIED VALVE CIRCUIT GUIDE

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

Procenter Delivery System* Troubleshooting Charts

MONO BLOCK DIRECTIONAL CONTROL VALVE TS1120TSLB

Installation Instructions K900 series Door Closer

Stainless Steel Single and Dual Circulation Kits

MP8000 Series Pneumatic Valve Actuators

*Rated to 207 Bar/3000 PSI with Aluminum Body. Catalog HY /US SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO.

PART 2 FORKLIFT HYDRAULIC SYSTEM

LINEAR MOTION CONTROL

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

4/2-Way Pneumatic Solenoid Valve

Single sub-base valve

Mono-Block II Installation & Operation Manual

Rexroth Hydraulic Pump A10VO Series User Manual

Pneumatic control for robotics and industrial automation Author: Naresh Raghavan

Fisher 377 Trip Valve

LINEAR ACTUATORS. Linear Actuators. Linear Actuators. Linear Actuators are Actuators that creates motion in a straight line, as contrasted

Series PVP Variable Volume Piston Pumps

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

Automatic Transmission Basics

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.

Why and How we Use Capacity Control

FILLING AND PURGING THE SYSTEM

HOW TO ORDER SAFETY PRODUCTS/SAFETY CONTROL SYSTEMS ELECTRICAL SAFETY CONTROLS

SMA Aluminum Cylinders

WILROY. Operation. Optional Diaphragm Rupture Detection HYDRAULICALLY ACTUATED DIAPHRAGM PUMP

Dive Rite 200 & 300 Bar Isolator Manifold Service Manual

Type Function Namur Port size Max. air flow Operating pressure Weight

Pneumatic actuators The Original! Technics of the top class.

PRESSURE REDUCING CONTROL VALVE

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits)

SELECTION, APPLICATION AND MAINTENANCE

OCTOPUS SELECTION & INSTALLATION GUIDE

TC 170 & TC 170 PD TRANSFER CASE

Installation Instructions

Electri-SAFE DataFlo Digital Electronic Positioner Installation, Operation and Maintenance Instructions

SITEMA PowerStroke. Technical Information TI-P12. 1 Function. 2 Applications. Mould Closing Devices series FSKP. Contents

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE AUTO 220 INTERNAL COMBUSTION ENGINES

*Rated to 207 Bar/3000 PSI with Aluminum Body. Denotes New Winner s Circle Product Line. Catalog HY /US

Quiz On Information Learned From Chapter 1

Model 5600 & 5600 Econominder

Instruction Manual. ThinkTop Basic Digital VDC PNP/NPN ESE00225EN

Signature and ISX CM870 Electronics

CPL SYSTEMS / GROENEVELD AUTOMATIC GREASING SYSTEM COMPLETE SYSTEM CHECK PNEUMATIC PUMP

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

Model No: VS SAFETY INSTRUCTIONS VS INTRODUCTION & APPLICATIONS VS CONTENTS. 2.1 Introduction. 2.

Fig 3. PLC Relay Output

MONO BLOCK DIRECTIONAL CONTROL VALVE TS

Bendix ABS for Trailers

Model 5600 & 5600 Econominder

#62192 Moroso Degree Wheel with Intake Center Line Calculator Instructions:

Q Series Piston Pumps Variable Displacement, Quiet Series for Industrial Applications

Char-Lynn Spool Valve Hydraulic Motors. Repair Information. W Series Geroler Motors

FILTRATION AMIAD PLASTIC FILTERS, SCREENS & DISCS

Industrial Hydraulic Remote Controlled Monitor

SOLENOID VALVES AND PNEUMATIC VALVES

Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

IMPORTANT DOCUMENTATION DO NOT DISCARD!

Fuel Injection Pump, Rotary ( )

Multi-talented. Valve and valve terminal series VG

IOM SERIES 820-E/P Electro-Pneumatic Positioner

PVM Piston Pumps Service Manual

UM/ /2 & 5/3 valves, solenoid and pilot actuated ISO , ISO size 1, 2, 3 & 4 Sub-base mounted

Transcription:

The standard operation of quarter-turn Process valves is: Clockwise (CW) rotation of the stem Closes the valve Counter-Clockwise (CCW) rotation of the stem Opens the valve Note: Point of reference is the top of the valve/actuator. This operation is reflected in the manual operation of all valves. When automating a ball valve the actuator must use this same operational direction. Double Acting (DA) The standard aero2 Double Acting actuator has the following operation: A 1/4-18NPT 4x10-32UNF Air supplied to the A manifold port pressurizes the cylinder between the two pistons and will drive them outward, causing the output shaft to turn counter clockwise (CCW). Air supplied to the manifold port pressurizes the outside of the two pistons and will drive them inward, causing the output shaft to turn clockwise (CW). STANDARD ROTATION (Top View Cutaway) OPEN CLOSE [A] A [] In the standard configuration the two pistons are arranged so that when they are pressurized through port A the output drive will rotate (CCW/Open) Air supplied to port will provide the reverse of this (CW/Close). 1

Spring Return (SR) The standard aero2 Spring Return actuator has the following operation: Springs are added to the outside of the two pistons to provide an actuation force when there is a loss of air pressure. Air supplied to the A manifold port pressurizes the cylinder between the two pistons and will drive them outward, causing the output shaft to turn counter clockwise (CCW/Open). At the same time this action will compress the springs. When air is removed from the pressurized port A the springs will drive the pistons inward to rotate the output drive in the clockwise (CW/Closed) direction. A 1/4-18NPT 4x10-32UNF STANDARD ROTATION (Top View Cutaway) OPEN CLOSE [A] [A] Effectively this action is referred to as Spring-to-Close or Fail Closed When a process valve is required to fail to the open position it becomes necessary to re-configure the actuator so that the piston will provide the reverse rotation from the standard arrangement. (See Reverse Rotation on aero2 Actuators on the following page) 2

Reverse Rotation on aero2 Actuators 1 1. 2. Standard Configuration Air Stroke pushes pistons outward which are engaged shaft) to rotate CCW-OPEN. Spring Stroke pushes pistons inward which are engaged shaft) to rotate CW-CLOSED. Remove End Caps 2 Rotate pistons and re-insert. Note: efore engaging the piston (gear rack) with the pinion, back rotate the pinion gear by one tooth for proper orientation. 1. 2. 3. Remove indicator cap and use the wrench flats to assist with the removal and replacement of pistons. Loosen travel stops to allow pistons to travel outside of body. Remove Pistons: A low (3psi) pressure applied to port A will help expose the pistons for removal. Reverse Configuration 3 1. Air Stroke pushes pistons outward which are engaged shaft) to rotate CW-CLOSED. 2. Spring Stroke pushes pistons inward which are engaged shaft) to rotate CCW-OPEN. Reverse acting actuators are identified with the letter R At the end of the part number. Example: A2S-20-10R 3

Mounting the Actuator to a Process Valve Actuator Mounting Kit Process Valve Prior to mounting a Double Acting Actuator to a Process valve first determine the current valve position. If the Process Valve is Closed: Rotate the actuator to the full (Closed) clockwise (CW) position by: Remove the indicator cap and apply a wrench to the flats or Apply air pressure to the manifold port Check that the indicator shows the correct position when replacing it. If the Process Valve is Open: Rotate the actuator to the full (Open) counter clockwise (CCW) position by: Remove the indicator cap and apply a wrench to the flats or Apply air pressure to the manifold port A Check that the indicator shows the correct position when replacing it. Mount the actuator. Common practice is to mount the actuator so that the length of the cylinder housing is parallel to the process piping. As shown above. Prior to Mounting Spring Return Actuators Springs are used with pneumatic actuators to drive a Process valve to the desired position in the event of air lost. Which is sometimes called Fail Closed or Fail Open. The standard spring return actuator will fail to the close position (CW) when air is lost. When air pressure is applied to the manifold port A the actuator will rotate (CCW) to the open position. The valve is to be closed before mounting in the standard configuration. In the reverse spring return actuator, the valve is to be set in the open position to achieve the desired fail to open arrangement. (Reverse Rotation on aero2 Actuators is shown on the previous page) 4

Pneumatic actuators will use a solenoid operated valve to provide an electrical signal that initiates operation. This is known as a pilot valve. The standard pilot used by SVF is a NAMUR-style valve that mounts directly to the actuator air inlet manifold. Application Terms Energize When an electrical signal is applied to the solenoid of the pilot valve De-Energize When an electrical signal is removed from the solenoid of the pilot valve Process valves (SVF ball valves) are used in a variety of control applications. Users will often specify the operation of a valve using the following types of statements: Energize to close- When electrical signal is applied the Process valve will Close Energize to open- When electrical signal is applied the Process valve will Open These statements also infer that when the pilot valve is de-energized the process valve will rotate to the other/opposite position. Installing SVF (Double Acting) When the pilot valve is arranged as shown here (Red Manual override button on top) air pressure will be directed to manifold port A when the solenoid is energized. (Process Valve Opens)_Energize To Open (CCW) When De-Energized the air will be directed to manifold port (Process Valve Closes) _De-Energize To Close (CW) So for this Double Acting valve/actuator arrangement the operation is Energize to Open To Reverse this operation (Configure for Energize to Close) the pilot is removed and rotated 180 degrees so that: When the solenoid is energized. Pressure is now applied to manifold port (Process Valve Closes) _Energize To Close (CW) When De-Energized the air will be directed to manifold port A (Process Valve Opens) _De-Energize To Open (CCW) (See next page for proper orientation of pilot valve) 5

Pilot valve Arrangement according to its desired Energize position. Rotate 180 O Rotate 180 O Energize to Close (CW) Energize to Open (CCW) Installing SVF (Spring Return) When the pilot valve is arranged as shown here (Red Manual override button UP) air pressure will be directed to manifold port A when the solenoid is energized. (Process Valve Opens) _Energize to Open (CCW) When De-Energized the air pressure will be exhausted and the springs will drive the Process valve CW (Process Valve Closes) _De-Energize to Close (CW) So for this Spring Return valve/actuator arrangement the operation is Energize to Open <Fail Closed> To Reverse this operation DO Not Rotate the. Instead the Spring Return Actuator must be Reversed or reconfigured for Fail Open. See Reverse Rotation instructions above. For a Reverse Rotation Spring Return Actuator: When the solenoid is energized. The air pressure will be directed to manifold port A (Process Valve Closes) _Energize to Close (CW) When De-Energized the air pressure will be exhausted and the springs will drive the Process valve CCW (Process Valve Opens) _De-Energize to Open Position Indication The final step in the assembly is to check that the position indicator is reading correctly. The Yellow indicator on the lack/yellow cap should be: Parallel to the Process pipeline when the valve is Open Perpendicular to the Process pipeline when the valve is Closed 6